About this file

36C25219B0056 0003 S06 - FA100 - FIRE ALARM - MODIFICATIONS FOR SPRINKLER SYSTEM INTERFACE.pdf

View the file

Other files

File Type Posted
36C25219C0222-000.docx DOCX document
36C25219B0056-0005000.docx DOCX document
36C25219B0056-0004002.pdf PDF
36C25219B0056-0004000.docx DOCX document
36C25219B0056-0004001.pdf PDF
36C25219B0056-0003007.pdf PDF
36C25219B0056-0003008.pdf PDF
36C25219B0056-0003003.pdf PDF
36C25219B0056-0003004.pdf PDF
36C25219B0056-0003005.pdf PDF
36C25219B0056-0003020.pdf PDF
36C25219B0056-0003015.pdf PDF
36C25219B0056-0003013.pdf PDF
36C25219B0056-0003014.pdf PDF
36C25219B0056-0003019.pdf PDF
36C25219B0056-0003006.pdf PDF
36C25219B0056-0003012.pdf PDF
36C25219B0056-0003017.pdf PDF
36C25219B0056-0003016.pdf PDF
36C25219B0056-0003011.pdf PDF
36C25219B0056-0003009.pdf PDF
36C25219B0056-0003010.pdf PDF
36C25219B0056-0003018.pdf PDF
36C25219B0056-0003002.pdf PDF
36C25219B0056-0003000.docx DOCX document
36C25219B0056-0002001.pdf PDF
36C25219B0056-0002000.docx DOCX document
36C25219B0056-0002002.pdf PDF
36C25219B0056-0001000.docx DOCX document
36C25219B0056-001.docx DOCX document
36C25219B0056-002.pdf PDF
36C25219B0056-005.pdf PDF
36C25219B0056-004.pdf PDF
36C25219B0056-003.pdf PDF
36C25219B0056-006.pdf PDF
36C25219B0056-000.docx DOCX document
36C25219B0056-000.docx DOCX document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WING A WING B WING C WING D

FACP

VS

AIM

VS PIV EAST - 005-007

PIV WEST - 005-008

VS

AIM

VS PIV - 005-047

PIV - 005-048

AIM

AIM

VS

PS

AIM

PS FLOW (SYS-A DRY)

OS&Y (SYS-A DRY)

VS

FLOW (SYS-A WET)

BACK-FLOW OS&Y's

OS&Y (SYS-A WET)

WF

VS

AIM

AIM

WF FLOW (SYS-B WET)

VS BACK-FLOW OS&Y's

AIM

AIM

VS

PS

AIM

PS FLOW (SYS-C DRY)

OS&Y (SYS-C DRY)

VS

LOW AIR (SYS-C DRY)

BACK-FLOW OS&Y's

OS&Y (SYS-C WET)

VS

AIM

WF FLOW (SYS-D WET)

VS BACK-FLOW OS&Y's

006-007

006-008

005-044

005-045

NEW

NEW

NEW

005-005

005-006

005-009

005-010

005-011

005-012

LOW AIR (SYS-A DRY)

005-029

005-043

FATCFATC

135°FT/RC

SAOM

AIM

AOM

AOM

AOM

135°FT/RC

S

AOM

AIM

AOM

AOM

AOM

135°FT/RC

S

AOM

AIM

AOM

AOM

FA200

FA200

FA200

FA200

FA200

FA200

FA200

FA200

AOM

135°FT/RC

S

135°FT/RC

S

135°FT/RC

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

CLEMENT J. ZABLOCKI VAMC

#6 o n e e i g h t h i n c h o n e f o o t t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number 695-16-112

FIRE SPRINKLER ENGINEER

RTM CONSULTANTS, INC

6640 Parkdale Place, Suite J, Indianapolis, IN 46254

PHONE: (317) 329-7700

905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204

317.800.6388 WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

CLEMENT J. ZABLOCKI VA MEDICAL CENTER

MILWAUKEE, WISCONSIN

C :\U se rs

\k al le n\

D oc um en ts \1

4.

.0

Bl dg .S pr in kl er

R ep la ce m en t 6

-1 6-

2_ ka lle n_ ka lle n.

rv t

FA100

FDCMC

FIRE ALARM - MODIFICATIONS FOR SPRINKLER

SYSTEM INTERFACE AND ELEVATOR CONTROL

- BASEMENT FLOOR PLAN 0

14.1020.06BUILDING 6 FIRE

SPRINKLER REPLACEMENT

SCALE: 1/16" = 1'-0"FA100

1 FIRE ALARM - SPRINKLER SYSTEM INTERFACE POINT LOCATIONS - BASEMENT FLOOR 0

N

1. EXISTING FIRE ALARM SYSTEM CONTROL PANEL AND SYSTEM CABINETS.

RE-PROGRAM EXISTING POINTS TO MATCH NEW DESCRIPTIONS AND SEQUENCE OF

OPERATIONS, ADD NEW FIRE ALARM POINTS TO PROGRAMMING AS INDICATED.

EXISTING SYSTEM IS CERBERUS MXL BASED. PROVIDE 100% ACCEPTANCE TESTING

OF ALL NEW AND MODIFIED POINTS AND 10% RE-ACCEPTANCE TESTING OF

REMAINDER OF FIRE ALARM SYSTEM IN ACCORDANCE WITH NFPA 72 REQUIREMENTS.

ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA

FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS.

2. REUSE EXISTING FIRE ALARM INTERFACE MODULE HARDWARE. CONNECT TO NEW

SPRINKLER EQUIPMENT AS INDICATED. CONNECT TO EXISTING FIRE ALARM SYSTEM.

ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA

FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS

3. PROVIDE AND INSTALL NEW FIRE ALARM INTERFACE MODULE HARDWARE. CONNECT

TO NEW SPRINKLER EQUIPMENT AS INDICATED. CONNECT TO EXISTING FIRE ALARM.

ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA

FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS.

4. EXISTING HARDWARE AND ADDRESS INFORMATION BASED ON LABELS AT DEVICES

AND HAVE NOT BEEN VERIFIED IN FACP PROGRAMMING. DEVICES HAVE NOT BEEN

TESTED TO ENSURE FUNCTIONALITY OR CORRECT PROGRAMMING.

5. PROVIDE AND INSTALL NEW ADDRESSABLE SMOKE AND HEAT DETECTORS. INSTALL

HEAT DETECTOR WITHIN 2' OF SPRINKLER HEAD IN ELEVATOR MACHINE ROOM.

CONNECT TO EXISTING FIRE ALARM. ACTIVATE ELEVATOR EMERGENCY OPERATION

AND SHUNT TRIP SEQUENCE ON ACTIVATION. ALL WORK TO BE IN ACCORDANCE WITH

REQUIREMENTS OF NFPA 72, N.E.C., THE VA FIRE PROTECTION DESIGN MANUAL, ANSI

A17.1, AND OTHER APPLICABLE REQUIREMENTS.

6. PROVIDE AND INSTALL NEW ADDRESSABLE OUTPUT MODULES FOR ELEVATOR

RECALL FUNCTIONS, CONNECT TO ELEVATOR CONTROL TO EXTENT POSSIBLE WITH

CURRENT ELEVATOR EQUIPMENT. PROVIDE, INSTALL, PROGRAM, AND TEST FIRE

ALARM DEVICES FOR FUTURE USE. CONNECT TO EXISTING FIRE ALARM CIRCUIT. ALL

WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA FIRE

PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER APPLICABLE REQUIREMENTS.

PROGRAM FIRE ALARM SYSTEM TO ACTIVATE APPLICABLE MODULE UPON ACTIVATION

OF EXISTING ELEVATOR LOBBY SMOKE DETECTORS.

7. PROVIDE AND INSTALL NEW ADDRESSABLE OUTPUT MODULES FOR ACTIVATION OF

ELEVATOR POWER SHUNT TRIP AND NEW ADDRESSABLE INPUT MODULE FOR

SUPERVISION OF ACTIVATION VOLTAGE, CONNECT TO ELEVATOR CONTROL POWER

TO EXTENT POSSIBLE WITH CURRENT ELEVATOR EQUIPMENT. INSTALL, PROGRAM,

AND TEST FIRE ALARM DEVICES FOR FUTURE USE. CONNECT TO EXISTING FIRE

ALARM CIRCUIT. ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72,

N.E.C., THE VA FIRE PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER

APPLICABLE REQUIREMENTS.

8. PROVIDE AND INSTALL NEW ADDRESSABLE SMOKE AND HEAT DETECTORS IN TOP OF

ELEVATOR SHAFT WHERE SPRINKLER HEAD IS INSTALLED. INSTALL HEAT DETECTOR

WITHIN 2' OF SPRINKLER HEAD. ACTIVATE ELEVATOR EMERGENCY OPERATION AND

SHUNT TRIP SEQUENCE ON ACTIVATION. CONNECT TO EXISTING FIRE ALARM CIRCUIT.

ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA

FIRE PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER APPLICABLE

REQUIREMENTS.

# FIRE ALARM SYSTEM PLAN NOTES:

DEVICE LEGEND

SYMBOL DESCRIPTION NOTES

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

SMOKE DETECTOR

HEAT DETECTOR FT### = FIXED TEMPERATURE ### DEGREE,

RR=RATE OF RISE, RC=RATE COMPENSATION

ADDRESSABLE OUTPUT CONTROL

MODULE

ADDRESSABLE INPUT MONITOR

MODULE

FLOW DETECTOR/SWITCH

PRESSURE SWITCH

VALVE SUPERVISORY SWITCH

FACP

FATC

S

AOM

AIM

WF

PS

VS

00 16' 32' BID DOCUMENTS

COR : MATTHEW OSGOOD

5/20/2019

ACCOMPANYING 36C25219B0056 0003