AIM
PSAIM
FLOW - 006-007
LOW AIR - 006-008
PS
AIM
PS
AIM
AIM VS
AIM VS PIV - 005-047
PIV - 005-048PS
FLOW - 005-044
LOW AIR - 005-045
FACPFATCFATC
AIM
PSAIM
FLOW - 005-029
LOW AIR - 005-043
PS
VS
AIM
VS PIV EAST - 005-007
PIV WEST - 005-008
AIM
AIM
VS
PS
AIM
PS FLOW (SYS-A DRY)
OS&Y (SYS-A DRY)
VS
FLOW (SYS-A WET)
BACK-FLOW OS&Y's
OS&Y (SYS-A WET)
WF
VS
005-005
005-006
005-009
005-010
005-011
005-012
LOW AIR (SYS-A DRY)
135°FT/RC
SAOM
AIM
AOM
AOM
AOM
135°FT/RC
S
135°FT/RC
S
AOM
AIM
AOM
AOM
AOM
135°FT/RC
135°FT/RC
S
AOM
AIM
AOM
AOM
AOM
135°FT/RC
S
AIM
WF FLOW (SYS-D WET)
VS BACK-FLOW OS&Y's
006-007
006-008
VS
AIM
VS PIV - 005-047
PIV - 005-048
AIM
AIM
VS
PS
AIM
PS FLOW (SYS-C DRY)
OS&Y (SYS-C DRY)
VS
LOW AIR (SYS-C DRY)
BACK-FLOW OS&Y's
OS&Y (SYS-C WET)
VS
005-044
005-045
NEW
NEW
NEW
FACPFATCFATC
AIM
AIM
WF FLOW (SYS-B WET)
VS BACK-FLOW OS&Y's
005-029
005-043
VS
AIM
VS PIV EAST - 005-007
PIV WEST - 005-008
AIM
AIM
VS
PS
AIM
PS FLOW (SYS-A DRY)
OS&Y (SYS-A DRY)
VS
FLOW (SYS-A WET)
BACK-FLOW OS&Y's
OS&Y (SYS-A WET)
WF
VS
005-005
005-006
005-009
005-010
005-011
005-012
LOW AIR (SYS-A DRY)
AIM
VS
FLOW (SYS-C WET)
OS&Y (SYS-C WET)
WF NEW
NEW3
STAIR C1 - THIRD FLOOR
AIM
VS
FLOW (SYS-C WET)
OS&Y (SYS-C WET)
WF NEW
NEW3
STAIR C1 - SECOND FLOOR
AIM
VS
FLOW (SYS-C WET)
OS&Y (SYS-C WET)
WF NEW
NEW3
STAIR C1 -FIRST FLOOR
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CLEMENT J. ZABLOCKI VAMC
#6 o n e e i g h t h i n c h o n e f o o t t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
COR : MATTHEW OSGOOD 695-16-112
FIRE SPRINKLER ENGINEER
RTM CONSULTANTS, INC
6640 Parkdale Place, Suite J, Indianapolis, IN 46254
PHONE: (317) 329-7700
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
CLEMENT J. ZABLOCKI VA MEDICAL CENTER
MILWAUKEE, WISCONSIN
C :\U se rs
\k al le n\
D oc um en ts \1
4.
.0
Bl dg .S pr in kl er
R ep la ce m en t 6
-1 6-
2_ ka lle n_ ka lle n.
rv t
FA200
FDCMC
FIRE ALARM - MODIFICATIONS FOR SPRINKLER
SYSTEM INTERFACE AND ELEVATOR CONTROL
- BASEMENT FLOOR PLAN DETAILS
14.1020.06BUILDING 6 FIRE
SPRINKLER REPLACEMENT
SCALE: AS INDICATEDFA200
1 FIRE ALARM - INTERFACE POINT LOCATIONS
N
SCALE: 1/8" = 1'-0"FA200
4 FIRE ALARM CONTROL PANELS
1. EXISTING FIRE ALARM SYSTEM CONTROL PANEL AND SYSTEM CABINETS.
RE-PROGRAM EXISTING POINTS TO MATCH NEW DESCRIPTIONS AND SEQUENCE OF
OPERATIONS, ADD NEW FIRE ALARM POINTS TO PROGRAMMING AS INDICATED.
EXISTING SYSTEM IS CERBERUS MXL BASED. PROVIDE 100% ACCEPTANCE TESTING
OF ALL NEW AND MODIFIED POINTS AND 10% RE-ACCEPTANCE TESTING OF
REMAINDER OF FIRE ALARM SYSTEM IN ACCORDANCE WITH NFPA 72 REQUIREMENTS.
ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA
FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS.
2. REUSE EXISTING FIRE ALARM INTERFACE MODULE HARDWARE. CONNECT TO NEW
SPRINKLER EQUIPMENT AS INDICATED. CONNECT TO EXISTING FIRE ALARM SYSTEM.
ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA
FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS
3. PROVIDE AND INSTALL NEW FIRE ALARM INTERFACE MODULE HARDWARE. CONNECT
TO NEW SPRINKLER EQUIPMENT AS INDICATED. CONNECT TO EXISTING FIRE ALARM.
ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA
FIRE PROTECTION DESIGN MANUAL, AND OTHER APPLICABLE REQUIREMENTS.
4. EXISTING HARDWARE AND ADDRESS INFORMATION BASED ON LABELS AT DEVICES
AND HAVE NOT BEEN VERIFIED IN FACP PROGRAMMING. DEVICES HAVE NOT BEEN
TESTED TO ENSURE FUNCTIONALITY OR CORRECT PROGRAMMING.
5. PROVIDE AND INSTALL NEW ADDRESSABLE SMOKE AND HEAT DETECTORS. INSTALL
HEAT DETECTOR WITHIN 2' OF SPRINKLER HEAD IN ELEVATOR MACHINE ROOM.
CONNECT TO EXISTING FIRE ALARM. ACTIVATE ELEVATOR EMERGENCY OPERATION
AND SHUNT TRIP SEQUENCE ON ACTIVATION. ALL WORK TO BE IN ACCORDANCE WITH
REQUIREMENTS OF NFPA 72, N.E.C., THE VA FIRE PROTECTION DESIGN MANUAL, ANSI
A17.1, AND OTHER APPLICABLE REQUIREMENTS.
6. PROVIDE AND INSTALL NEW ADDRESSABLE OUTPUT MODULES FOR ELEVATOR
RECALL FUNCTIONS, CONNECT TO ELEVATOR CONTROL TO EXTENT POSSIBLE WITH
CURRENT ELEVATOR EQUIPMENT. PROVIDE, INSTALL, PROGRAM, AND TEST FIRE
ALARM DEVICES FOR FUTURE USE. CONNECT TO EXISTING FIRE ALARM CIRCUIT. ALL
WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA FIRE
PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER APPLICABLE REQUIREMENTS.
PROGRAM FIRE ALARM SYSTEM TO ACTIVATE APPLICABLE MODULE UPON ACTIVATION
OF EXISTING ELEVATOR LOBBY SMOKE DETECTORS.
7. PROVIDE AND INSTALL NEW ADDRESSABLE OUTPUT MODULES FOR ACTIVATION OF
ELEVATOR POWER SHUNT TRIP AND NEW ADDRESSABLE INPUT MODULE FOR
SUPERVISION OF ACTIVATION VOLTAGE, CONNECT TO ELEVATOR CONTROL POWER
TO EXTENT POSSIBLE WITH CURRENT ELEVATOR EQUIPMENT. INSTALL, PROGRAM,
AND TEST FIRE ALARM DEVICES FOR FUTURE USE. CONNECT TO EXISTING FIRE
ALARM CIRCUIT. ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72,
N.E.C., THE VA FIRE PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER
APPLICABLE REQUIREMENTS.
8. PROVIDE AND INSTALL NEW ADDRESSABLE SMOKE AND HEAT DETECTORS IN TOP OF
ELEVATOR SHAFT WHERE SPRINKLER HEAD IS INSTALLED. INSTALL HEAT DETECTOR
WITHIN 2' OF SPRINKLER HEAD. ACTIVATE ELEVATOR EMERGENCY OPERATION AND
SHUNT TRIP SEQUENCE ON ACTIVATION. CONNECT TO EXISTING FIRE ALARM CIRCUIT.
ALL WORK TO BE IN ACCORDANCE WITH REQUIREMENTS OF NFPA 72, N.E.C., THE VA
FIRE PROTECTION DESIGN MANUAL, ANSI A17.1, AND OTHER APPLICABLE
REQUIREMENTS.
# FIRE ALARM SYSTEM PLAN NOTES:
DEVICE LEGEND
SYMBOL DESCRIPTION NOTES
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
SMOKE DETECTOR
HEAT DETECTOR FT### = FIXED TEMPERATURE ### DEGREE,
RR=RATE OF RISE, RC=RATE COMPENSATION
ADDRESSABLE OUTPUT CONTROL
MODULE
ADDRESSABLE INPUT MONITOR
MODULE
FLOW DETECTOR/SWITCH
PRESSURE SWITCH
VALVE SUPERVISORY SWITCH
FACP
FATC
S
AOM
AIM
WF
PS
VS
SCALE: 1/8" = 1'-0"FA200
2 ELEVATOR C2 MECH ROOM
SCALE: 1/8" = 1'-0"FA200
1 ELEVATOR A MECH ROOM
SCALE: 1/8" = 1'-0"FA200
3 ELEVATOR C1 MECH ROOM
EXISTING FIRE ALARM SPRINKLER INTERFACE POINT LOCATIONS AND ADDRESSES
NEW FIRE ALARM SPRINKLER INTERFACE POINT LOCATIONS AND ADDRESSES
SCALE: 1/8" = 1'-0"FA200
5 A WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
6 B WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
7 C WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
8 D WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
4 FIRE ALARM CONTROL PANELS
SCALE: 1/8" = 1'-0"FA200
9 A WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
10 B WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
11 C WING FIRE SPRINKLER RISER
SCALE: 1/8" = 1'-0"FA200
8 D WING FIRE SPRINKLER RISER
NEW FIRE ALARM ELEVATOR INTERFACE POINTS
00 8' 16' 00 8' 16' 00 8' 16' 00 8' 16' 00 8' 16'
00 8' 16'00 8' 16'00 8' 16'00 8' 16'00 8' 16'
00 8' 16' 00 8' 16' 00 8' 16'
BID DOCUMENTS
5/20/2019
ELEVATOR C HAS BE RECENTLY UPGRADED
REUSE EXISTING FIRE ALARM DEVICES
ACCOMPANYING 36C25219B0056 0003