Bid RFI 08 Attachment B AE18665 Preliminary Design Package Rev C.pdf
PDF 1 MB Posted
- Attached to
- Z1DA--Renovate Audiology 515-23-101
- Solicitation number
- 36C25025B0019
About this file
This document is a preliminary design package for an air handling unit (AHU-1) for a Veterans Affairs Medical Center renovation project. The package includes detailed mechanical engineering specifications for a custom air handling system with two primary fans: a supply air fan and a return air fan. Key technical specifications include:
Supply Air Fan: 6,500 CFM capacity, 16-inch size, with a total static pressure of 8.20 inches of water, powered by a 15 hp motor operating at 3,721 RPM. Return Air Fan: 6,335 CFM capacity, 20-inch size, with a total static pressure of 2.30 inches of water, powered by a 5 hp motor operating at 1,702 RPM. The system includes heating and cooling coils with specific performance parameters: a heating coil with 24.6 MBH capacity and a cooling coil with 189.7 MBH total heat load. The design incorporates aluminum fin materials, copper seamless tubes, and stainless steel casings, with pneumatic testing specified for the components.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P18665 Rev. C
Version 2022.7.5
Project 18665-1 6,500 CFM
AHU-1
APD
Components (in w.c.)
Entrance Loss (Damper) 0.15 Shelf Mixing 0.50
Heating Coils 0.03 Cooling Coils 0.36
Dispersion Grid Humidifier 0.01
Plenum Fan
Exit Loss (Damper) 0.15
Filters 2" Pre & High Efficiency Filter 0.75 High Efficiency Filter 0.50
Filter Loading 1.75 Sub Total Internal Static Pressure [ ISP ] 4.20
Summation of Statics Internal Static Pressure [ ISP ] 4.20
Estimated Negative External Static Pressure [ ESP ]
Estimated Positive External Static Pressure [ ESP ] 4.00
Total Static Pressure [ TSP ] 8.20
Supply Air Fan
STATIC PRESSURE CALCULATION
Performance Quantity 1
Volume (CFM) 6,500 Total External SP (in. wg) 8.3
Operating Power (hp) 12.54 Required Power (hp) 12.54
Fan RPM 3721 Max Fan RPM 3,900
Oper. Frequency (Hz) 64 Elevation (ft) 0
Start-up Temp.(F) 70 Operating Temp.(F) 70
Fan Configuration Size 16
Arrangement 4 Class III
Rotation CW Qty 1 Rotation CCW Qty 0
Orientation Horizontal
Equipment Weights Fan (LMD)(lb) 95
Motor/Drive (lb) 253 Accessories (lb) 10
Misc Fan Data Fan Energy Index (FEI) 1.21
Outlet Velocity (ft/min) 3,125 Static Efficiency (%) 68
Tip Speed (ft/min) 16,075 Thrust Weight (%) 44.7
Thrust Force (lb) 160 Corner Weight A (lb) 107 Corner Weight B (lb) 107 Corner Weight C (lb) 72 Corner Weight D (lb) 72
Motor and Drives Motor Included
Size (hp) 15
RPM 3500
Enclosure TEFC V/C/P 208/60/3
Frame Size 254T Max Frame Size 256
Location Centered
Model: 16-APH-4-100-III-150 Plenum Fan Operating Performance
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 96 97 91 92 89 85 83 82 94 83 42
Outlet 94 95 93 96 96 93 90 87 100 89 58 LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5 ft- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 5 ft
12/17/2024Printed Date:
18665Job:
SupplyMark:
16-APH-4-100-III-150Model:
Generated by: slawrence@airenterprises.comCAPS 4.46.969 Page 1 of 3 L:\Files\18600s\18665\Engineering\18665.gfcj
Version 2022.7.5
Project 18665-1 6,335 CFM
AHU-1
APD
Components (in w.c.)
Entrance Loss (Damper) 0.15
Plenum Fan
Exit Loss (Damper) 0.15
Filters
Filter Loading Sub Total Internal Static Pressure [ ISP ] 0.30
Summation of Statics Internal Static Pressure [ ISP ] 0.30
Estimated Negative External Static Pressure [ ESP ]
Estimated Positive External Static Pressure [ ESP ] 2.00
Total Static Pressure [ TSP ] 2.30
STATIC PRESSURE CALCULATION
Return Air Fan
Performance Quantity 1
Volume (CFM) 6,336 Total External SP (in. wg) 2.3
Operating Power (hp) 3.57 Required Power (hp) 4.01
Fan RPM 1702 Max Fan RPM 2,706
Oper. Frequency (Hz) 58 Elevation (ft) 0
Start-up Temp.(F) 70 Operating Temp.(F) 70
Fan Configuration Size 20
Arrangement 4 Class II
Rotation CW Qty 1 Rotation CCW Qty 0
Orientation Horizontal
Equipment Weights Fan (LMD)(lb) 113
Motor/Drive (lb) 84 Accessories (lb) 19
Misc Fan Data Fan Energy Index (FEI) 1.31
Outlet Velocity (ft/min) 2,077 Static Efficiency (%) 64
Tip Speed (ft/min) 8,914 Thrust Weight (%) 30.1
Thrust Force (lb) 65 Corner Weight A (lb) 55 Corner Weight B (lb) 55 Corner Weight C (lb) 53 Corner Weight D (lb) 53
Motor and Drives Motor Included
Size (hp) 5
RPM 1770
Enclosure TEFC V/C/P 208/60/3
Frame Size 184T Max Frame Size 256
Location Centered
Model: 20-APH-4-100-II-50 Plenum Fan Operating Performance
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 82 77 87 80 75 74 69 65 83 72 20 Outlet 82 83 90 86 84 82 76 71 89 78 27
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5 ft- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 5 ft
06/26/2024Printed Date:
18665Job:
ReturnMark:
20-APH-4-100-II-50Model:
Generated by: slawrence@airenterprises.comCAPS 4.44.1078 Page 4 of 6 L:\Files\18600s\18665\Engineering\18665.gfcj
12/17/2024Date:
Job Name: AE18665
System ID: Heating
Total Weight
Totals: 78
LBS.Model No.
HW-5.0AS-48.0 X 44.0-1-0.25
Qty.
In Face
CA-HW-100Dwg:
Coil Type:
Row:
Fin:
Circuit:
HW
1/4
Aluminum Star
Tube:
Fin Material:
Csg Material:
Connection:
Hdr Material:
0.625 inch X 0.025 inch Copper Seamless Tubes, Orificed Tubes , Belled
Standard Non-Ferrous, Brazed Joints
1-1/2" Leg with 304 Stainless Casings
TF:
5 / IN
FL
44.00
Thickness: 0.0075
- Pneumatic TestMisc:
INCH
IN.
1.5" Threaded, Red Brass, Extended 14 inches
UnspecifiedCoil Hand:
Performance
Pressure:
Airflow:
Standard Face Velocity:
Entering Dry Bulb Temp:
Leaving Dry Bulb Temp:
Sensible Heat Load:
Total Heat Load:
Outside Surface Fouling:
Losses
Air Pressure Drop:
Entering Temp:
Leaving Temp:
Flow Rate:
Tube Velocity:
Inside Surface Fouling:
Elevation:29.92 IN HG Sea Level
6,500.0 SCFM
443.2 FPM
51.5 °F
55.0 °F
24.6 MBH
24.6 MBH
0.0000 HRꞏFT²ꞏ°F/BTU
Water
180.0 °F
160.0 °F
3.00 GPM
0.3
0.0000 HRꞏFT²ꞏ°F/BTU
0.03 IN H2O 0.1 FT H2O
System Face Area: FT²14.7
Fluid Pressure Drop:
Comments:
V
FPS
Notes & Warnings:
51 Coil is outside of the scope of AHRI standard 410.
46 Total surface not used. Check rows calculated. Reduce fluid flow, rows, or fins per inch.
13 Pressure drop shown is based on belled tube ends.
Program Version: 3.6.0 Dll Ver: PriceDB Ver:1.2.20 27.7AE18665.afn
1-800-AEROFINwww.Aerofin.com 4621 Murray Place, Lynchburg, VA 24502 (434) 528-6242(Fax)
12/17/2024Date:
Job Name: AE18665
System ID: Cooling
Total Weight
Totals: 275
LBS.Model No.
W-12.0AS-48.0 X 44.0-4-0.333
Qty.
In Face
CA-W-100Dwg:
Coil Type:
Row:
Fin:
Circuit:
W
1/3
Aluminum Star
Tube:
Fin Material:
Csg Material:
Connection:
Hdr Material:
0.625 inch X 0.025 inch Copper Seamless Tubes , Belled
Standard Non-Ferrous, Brazed Joints
1-1/2" Leg with 304 Stainless Casings
TF:
12 / IN
FL
44.00
Thickness: 0.0075
- Pneumatic TestMisc:
INCH
IN.
2" Threaded, Red Brass, Extended 14 inches
UnspecifiedCoil Hand:
Performance
Pressure:
Airflow:
Standard Face Velocity:
Entering Dry Bulb Temp:
Leaving Dry Bulb Temp:
Sensible Heat Load:
Total Heat Load:
Outside Surface Fouling:
Losses
Air Pressure Drop:
Entering Wet Bulb Temp:
Leaving Wet Bulb Temp:
Entering Temp:
Leaving Temp:
Flow Rate:
Tube Velocity:
Inside Surface Fouling:
Elevation:29.92 IN HG Sea Level
6,500.0 SCFM
443.2 FPM
77.5 °F
63.8 °F
55.0 °F
53.9 °F
158.0 MBH
189.7 MBH
0.0000 HRꞏFT²ꞏ°F/BTU
Water
44.0 °F
56.7 °F
30.00 GPM
3.0
0.0000 HRꞏFT²ꞏ°F/BTU
0.36 IN H2O 5.1 FT H2O
System Face Area: FT²14.7
Fluid Pressure Drop:
Comments:
V
FPS
Notes & Warnings:
56 Rated in accordance with AHRI Standard 410.
13 Pressure drop shown is based on belled tube ends.
Program Version: 3.6.0 Dll Ver: PriceDB Ver:1.2.20 27.7AE18665.afn
1-800-AEROFINwww.Aerofin.com 4621 Murray Place, Lynchburg, VA 24502 (434) 528-6242(Fax)
| P18665-1-01 |
| 18665 APD Calc |
| 18665 GH Fan Selections |
| 18665 Heating Coil |
| 18665 Cooling Coil |
File details come from the government source that posted it. Updated .