Bid RFI 08 Attachment B AE18665 Preliminary Design Package Rev C.pdf

PDF 1 MB Posted

Attached to
Z1DA--Renovate Audiology 515-23-101
Solicitation number
36C25025B0019
Issued by

About this file

This document is a preliminary design package for an air handling unit (AHU-1) for a Veterans Affairs Medical Center renovation project. The package includes detailed mechanical engineering specifications for a custom air handling system with two primary fans: a supply air fan and a return air fan. Key technical specifications include:

Supply Air Fan: 6,500 CFM capacity, 16-inch size, with a total static pressure of 8.20 inches of water, powered by a 15 hp motor operating at 3,721 RPM. Return Air Fan: 6,335 CFM capacity, 20-inch size, with a total static pressure of 2.30 inches of water, powered by a 5 hp motor operating at 1,702 RPM. The system includes heating and cooling coils with specific performance parameters: a heating coil with 24.6 MBH capacity and a cooling coil with 189.7 MBH total heat load. The design incorporates aluminum fin materials, copper seamless tubes, and stainless steel casings, with pneumatic testing specified for the components.

View the file

Other files

File Type Posted
Award email notice - 515-23-101.pdf PDF
07.13_10-AF701 - FINISH AND SIGNAGE PLAN AND SCHEDULES.pdf PDF
07.7_10-AE112 - FIRST FLOOR ENLARGED PLANS AND ELEVATIONS.pdf PDF
07.6_10-AE111 - FIRST FLOOR ENLARGED PLANS AND ELEVATIONS.pdf PDF
36C25025B0019 0004.docx DOCX document
223500 DOMESTIC WATER HEAT EXCHANGERS.pdf PDF
07.15_10-AQ731 - EQUIPMENT PLANS.pdf PDF
Addendum 001 Summary.pdf PDF
081113 HOLLOW METAL DOORS AND FRAMES.pdf PDF
07.5_10-AE101 - FIRST FLOOR PLAN.pdf PDF
083400 SLIDING DOOR OPENING ASSEMBLIES.pdf PDF
13.12_M502 - MECHANICAL DETAILS.pdf PDF
107326 CANOPY COVERINGS V2.pdf PDF
00.2_GI002 - WALL TYPES.pdf PDF
36C25025B0019 0003.docx DOCX document
36C25025B0019 0002.docx DOCX document
Bid RFI 08 Attachment A 13 12 M502 - MECHANICAL DETAILS.pdf PDF
Wage Determination - MI20240079 - 4-4-25 - Calhoun MI.pdf PDF
Bid RFI 03 Attachment Install ADA Compliant Access Building 10 Hand Rail System.pdf PDF
S04 - Pre Bid Site Visit Attendance Log - 515-23-101 Signed.pdf PDF
36C25025B0019 0001.docx DOCX document
S04 - Pre-Bid Site Visit Agenda - 515-23-101.pdf PDF
36C25025B0019_1.docx DOCX document
S02 J-A Pelco - 515-23-101.pdf PDF
S02 J-A Hirsch - 515-23-101.pdf PDF
S02 J-A Simplex 515-23-101.pdf PDF
S02 Contractor EMR Certification Form - 515-23-101.docx DOCX document
S02 Drawings - 515-23-101 - BID DOCS 100.pdf PDF
S02 ATTACHMENT VAAR 852.219-75 LIMITATIONS OF SUBCONTRACTING CERT - 515-23-101.docx DOCX document
S02 J-A Kaba - 515-23-101.pdf PDF
S02 J-A ALC DDC - 515-23-101.pdf PDF
S02 RFI Form - 515-23-101.doc DOC document
S02 515-23-101 - BID DOCS 100 - Specifications - 3-27-25.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P18665 Rev. C

Version 2022.7.5

Project 18665-1 6,500 CFM

AHU-1

APD

Components (in w.c.)

Entrance Loss (Damper) 0.15 Shelf Mixing 0.50

Heating Coils 0.03 Cooling Coils 0.36

Dispersion Grid Humidifier 0.01

Plenum Fan

Exit Loss (Damper) 0.15

Filters 2" Pre & High Efficiency Filter 0.75 High Efficiency Filter 0.50

Filter Loading 1.75 Sub Total Internal Static Pressure [ ISP ] 4.20

Summation of Statics Internal Static Pressure [ ISP ] 4.20

Estimated Negative External Static Pressure [ ESP ]

Estimated Positive External Static Pressure [ ESP ] 4.00

Total Static Pressure [ TSP ] 8.20

Supply Air Fan

STATIC PRESSURE CALCULATION

Performance Quantity 1

Volume (CFM) 6,500 Total External SP (in. wg) 8.3

Operating Power (hp) 12.54 Required Power (hp) 12.54

Fan RPM 3721 Max Fan RPM 3,900

Oper. Frequency (Hz) 64 Elevation (ft) 0

Start-up Temp.(F) 70 Operating Temp.(F) 70

Fan Configuration Size 16

Arrangement 4 Class III

Rotation CW Qty 1 Rotation CCW Qty 0

Orientation Horizontal

Equipment Weights Fan (LMD)(lb) 95

Motor/Drive (lb) 253 Accessories (lb) 10

Misc Fan Data Fan Energy Index (FEI) 1.21

Outlet Velocity (ft/min) 3,125 Static Efficiency (%) 68

Tip Speed (ft/min) 16,075 Thrust Weight (%) 44.7

Thrust Force (lb) 160 Corner Weight A (lb) 107 Corner Weight B (lb) 107 Corner Weight C (lb) 72 Corner Weight D (lb) 72

Motor and Drives Motor Included

Size (hp) 15

RPM 3500

Enclosure TEFC V/C/P 208/60/3

Frame Size 254T Max Frame Size 256

Location Centered

Model: 16-APH-4-100-III-150 Plenum Fan Operating Performance

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 96 97 91 92 89 85 83 82 94 83 42

Outlet 94 95 93 96 96 93 90 87 100 89 58 LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5 ft- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 5 ft

12/17/2024Printed Date:

18665Job:

SupplyMark:

16-APH-4-100-III-150Model:

Generated by: slawrence@airenterprises.comCAPS 4.46.969 Page 1 of 3 L:\Files\18600s\18665\Engineering\18665.gfcj

Version 2022.7.5

Project 18665-1 6,335 CFM

AHU-1

APD

Components (in w.c.)

Entrance Loss (Damper) 0.15

Plenum Fan

Exit Loss (Damper) 0.15

Filters

Filter Loading Sub Total Internal Static Pressure [ ISP ] 0.30

Summation of Statics Internal Static Pressure [ ISP ] 0.30

Estimated Negative External Static Pressure [ ESP ]

Estimated Positive External Static Pressure [ ESP ] 2.00

Total Static Pressure [ TSP ] 2.30

STATIC PRESSURE CALCULATION

Return Air Fan

Performance Quantity 1

Volume (CFM) 6,336 Total External SP (in. wg) 2.3

Operating Power (hp) 3.57 Required Power (hp) 4.01

Fan RPM 1702 Max Fan RPM 2,706

Oper. Frequency (Hz) 58 Elevation (ft) 0

Start-up Temp.(F) 70 Operating Temp.(F) 70

Fan Configuration Size 20

Arrangement 4 Class II

Rotation CW Qty 1 Rotation CCW Qty 0

Orientation Horizontal

Equipment Weights Fan (LMD)(lb) 113

Motor/Drive (lb) 84 Accessories (lb) 19

Misc Fan Data Fan Energy Index (FEI) 1.31

Outlet Velocity (ft/min) 2,077 Static Efficiency (%) 64

Tip Speed (ft/min) 8,914 Thrust Weight (%) 30.1

Thrust Force (lb) 65 Corner Weight A (lb) 55 Corner Weight B (lb) 55 Corner Weight C (lb) 53 Corner Weight D (lb) 53

Motor and Drives Motor Included

Size (hp) 5

RPM 1770

Enclosure TEFC V/C/P 208/60/3

Frame Size 184T Max Frame Size 256

Location Centered

Model: 20-APH-4-100-II-50 Plenum Fan Operating Performance

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 82 77 87 80 75 74 69 65 83 72 20 Outlet 82 83 90 86 84 82 76 71 89 78 27

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5 ft- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 5 ft

06/26/2024Printed Date:

18665Job:

ReturnMark:

20-APH-4-100-II-50Model:

Generated by: slawrence@airenterprises.comCAPS 4.44.1078 Page 4 of 6 L:\Files\18600s\18665\Engineering\18665.gfcj

12/17/2024Date:

Job Name: AE18665

System ID: Heating

Total Weight

Totals: 78

LBS.Model No.

HW-5.0AS-48.0 X 44.0-1-0.25

Qty.

In Face

CA-HW-100Dwg:

Coil Type:

Row:

Fin:

Circuit:

HW

1/4

Aluminum Star

Tube:

Fin Material:

Csg Material:

Connection:

Hdr Material:

0.625 inch X 0.025 inch Copper Seamless Tubes, Orificed Tubes , Belled

Standard Non-Ferrous, Brazed Joints

1-1/2" Leg with 304 Stainless Casings

TF:

5 / IN

FL

44.00

Thickness: 0.0075

- Pneumatic TestMisc:

INCH

IN.

1.5" Threaded, Red Brass, Extended 14 inches

UnspecifiedCoil Hand:

Performance

Pressure:

Airflow:

Standard Face Velocity:

Entering Dry Bulb Temp:

Leaving Dry Bulb Temp:

Sensible Heat Load:

Total Heat Load:

Outside Surface Fouling:

Losses

Air Pressure Drop:

Entering Temp:

Leaving Temp:

Flow Rate:

Tube Velocity:

Inside Surface Fouling:

Elevation:29.92 IN HG Sea Level

6,500.0 SCFM

443.2 FPM

51.5 °F

55.0 °F

24.6 MBH

24.6 MBH

0.0000 HRꞏFT²ꞏ°F/BTU

Water

180.0 °F

160.0 °F

3.00 GPM

0.3

0.0000 HRꞏFT²ꞏ°F/BTU

0.03 IN H2O 0.1 FT H2O

System Face Area: FT²14.7

Fluid Pressure Drop:

Comments:

V

FPS

Notes & Warnings:

51 Coil is outside of the scope of AHRI standard 410.

46 Total surface not used. Check rows calculated. Reduce fluid flow, rows, or fins per inch.

13 Pressure drop shown is based on belled tube ends.

Program Version: 3.6.0 Dll Ver: PriceDB Ver:1.2.20 27.7AE18665.afn

1-800-AEROFINwww.Aerofin.com 4621 Murray Place, Lynchburg, VA 24502 (434) 528-6242(Fax)

12/17/2024Date:

Job Name: AE18665

System ID: Cooling

Total Weight

Totals: 275

LBS.Model No.

W-12.0AS-48.0 X 44.0-4-0.333

Qty.

In Face

CA-W-100Dwg:

Coil Type:

Row:

Fin:

Circuit:

W

1/3

Aluminum Star

Tube:

Fin Material:

Csg Material:

Connection:

Hdr Material:

0.625 inch X 0.025 inch Copper Seamless Tubes , Belled

Standard Non-Ferrous, Brazed Joints

1-1/2" Leg with 304 Stainless Casings

TF:

12 / IN

FL

44.00

Thickness: 0.0075

- Pneumatic TestMisc:

INCH

IN.

2" Threaded, Red Brass, Extended 14 inches

UnspecifiedCoil Hand:

Performance

Pressure:

Airflow:

Standard Face Velocity:

Entering Dry Bulb Temp:

Leaving Dry Bulb Temp:

Sensible Heat Load:

Total Heat Load:

Outside Surface Fouling:

Losses

Air Pressure Drop:

Entering Wet Bulb Temp:

Leaving Wet Bulb Temp:

Entering Temp:

Leaving Temp:

Flow Rate:

Tube Velocity:

Inside Surface Fouling:

Elevation:29.92 IN HG Sea Level

6,500.0 SCFM

443.2 FPM

77.5 °F

63.8 °F

55.0 °F

53.9 °F

158.0 MBH

189.7 MBH

0.0000 HRꞏFT²ꞏ°F/BTU

Water

44.0 °F

56.7 °F

30.00 GPM

3.0

0.0000 HRꞏFT²ꞏ°F/BTU

0.36 IN H2O 5.1 FT H2O

System Face Area: FT²14.7

Fluid Pressure Drop:

Comments:

V

FPS

Notes & Warnings:

56 Rated in accordance with AHRI Standard 410.

13 Pressure drop shown is based on belled tube ends.

Program Version: 3.6.0 Dll Ver: PriceDB Ver:1.2.20 27.7AE18665.afn

1-800-AEROFINwww.Aerofin.com 4621 Murray Place, Lynchburg, VA 24502 (434) 528-6242(Fax)

P18665-1-01
18665 APD Calc