This document is a detailed architectural drawing showing wall type specifications for a renovation project at the Battle Creek VA Medical Center. The drawing provides comprehensive technical details for three primary wall types: Type A (Typical Partition), Type B (One-Sided Partition), and Type R (Rated Partition), with precise engineering specifications for each wall configuration. The technical drawings include specific measurements for cold-formed steel framing, gypsum board layers, insulation types (such as batt insulation), sound attenuation requirements, track and stud configurations, and structural connection details. The document includes section views illustrating floor, ceiling, and structural connections, with annotations for stud sizes, gauge, material strengths, and Underwriters Laboratories (UL) ratings. The drawing is part of bid documents for the VA Medical Center's Audiology renovation project, dated January 17, 2025, with a bid addendum issued on May 9, 2025.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTINUOUS SEALANT AT BOTH SIDES OF TRACK
SCHEDULED BASE
CONTINUOUS TRACK AND FASTENERS @ 16" O.C. MAX
FULL HEIGHT SOUND ATTENUATION BLANKET
(1) LAYER GYPSUM BOARD ON EACH SIDE
SCHEDULED CEILING
SECTION AT FLOOR
SECTION AT CEILING
TOP OF STRUCTURAL SLAB WITH SCHEDULED FLOOR FINISH
COLD FORMED STEEL FRAMING
SUBSTRATE [1] SUBSTRATE [2]MARK
3 1/2" BATTA1 COLD FORMED STEEL4 7/8"
TYPE A - TYPICAL PARTITION
(1) 5/8 GYPSUM BOARD
TYPE "X"
WALL THICKNESS CORE STRUCTURE
(1) 5/8 GYPSUM BOARD
TYPE "X"
INSULATION /
BATT
STUD SIZE RATING UL
3 5/8" -
6" BATTA2 COLD FORMED STEEL7 1/4" (1) 5/8 GYPSUM BOARD
TYPE "X"
(1) 5/8 GYPSUM BOARD
TYPE "X"
6" -
EXTEND WALL 6" PAST CEILING IF ONE OR
BOTH SIDES ARE ACT OTHERWISE
CONCLUDE AT CEILING HEIGHT
6"
EXTEND 3 1/2" BATT INSULATION 2'-0" MIN ON BOTH SIDES
ALTERNATE BRACING AT 48" O.C. MAX TO DECK ABOVE
A3
A4
> STC 50
> STC 55
UL4193 1/2" BATTCOLD FORMED STEEL5 1/2" (1) 5/8 GYPSUM BOARD
TYPE "X"
(2) 5/8 GYPSUM BOARD
TYPE "X"
3 5/8"
3 1/2" BATTCOLD FORMED STEEL6 3/4" (2) 5/8 GYPSUM BOARD
TYPE "X"
(3) 5/8 GYPSUM BOARD
TYPE "X"
3 5/8"
UL419
UL419
UL419
FIELD VERIFY DEPTH OF
STRUCTURE
APPROX LINE OF CEILING
SEE REFLECTED CEILING
PLAN FOR PROPOSED
CEILING HEIGHTS
UNDERSIDE OF
STRUCTURAL DECK
MECHANICAL
PENETRATION
ROUGH OPENING
DOOR
ROUGH
OPENING
WINDOW
ROUGH
OPENING
MECHANICAL
PENETRATION
ROUGH OPENING
TOP OF SLAB
H
H
H
H
H
H J J
JJ
S
S
S
S
S
S
J J
JJ
SPAN 4 TO 6 FT:
6" STUD, 20 GA
SPAN 6 TO 10 FT:
8" STUD, 16 GA
SPANS 10 TO 16 FT:
8" STUD, 14 GA
HEADER: SECTION H-H
TYPE A
JAMB: SECTION J-J SILL: SECTION S-S
TYPE B
C-STUD
CSJ, 50 KSI
TRACK STUD
CSJ, 50 KSI
TRACK STUD,
TSB, 33 KSI
SPANS: > 4 FEET
3 5/8" STUD
20 GA
JAMB STUD
(BEYOND)
#8 SCREWS @ 6"
O.C. MAX., TYP.
#8 SCREWS @ 6"
O.C. MAX., TYP.
TYPE A
TYPE B
TYPE A
TYPE B
CLIP ANGLE
ATTACHMENT TOP
AND BOTTOM
JAMB STUD
(BEYOND)
STUD PER PARTITION
SCHEDULE
SPAN 4 TO 6 FT:
6" STUD, 20 GA
SPAN 6 TO 10 FT:
8" STUD, 16 GA
SPANS 10 TO 16 FT:
8" STUD, 14 GA
SPANS: > 4 FEET
3 5/8" STUD
20 GA
DOUBLE C-STUDS
CSJ, 50 KSI
TRACK STUD CSJ, 50 KSI
TRACK STUD,
TSB, 33 KSI
#8 SCREWS @ 6"
O.C. MAX., TYP.
#8 SCREWS @ 6"
O.C. MAX., TYP.
CLIP ANGLE ATTACHMENT
TOP AND BOTTOM
STUD PER PARTITION
SCHEDULE
JAMB STUD
(BEYOND)
#12 - 14 FASTENERS
@ 24" O.C. MIN. EA. SIDE
TRACK STUD
TSB 33 KSI
(BELOW)
STUD PER PARTITION
SCHEDULE
STUD PER PARTITION
SCHEDULE
OPENING
OPENING
TRACK STUD TSB 33 KSI
(BELOW)
#12 - 14 FASTENERS
@ 24" O.C. MIN.
CLIP ANGLE
ATTACHMENT
(BEYOND)
CLIP ANGLE
ATTACHMENT
(BEYOND)
#12 - 14 FASTENERS
@ 24" O.C. MIN.
TRACK STUD TSB 33 KSI
(BELOW)
TRACK STUD TSB 33
KSI (BELOW)
C-STUD
CSJ, 50 KSI
C-STUD
CSJ, 50 KSI
TOP OF STRUCTURAL SLAB WITH SCHEDULED FLOOR FINISH
3 5/8" COLD FORMED STEEL FRAMING - CAN BE REDUCED
IF NOT IN PLUMBING WALLS
FULL HEIGHT SOUND ATTENUATION BLANKET
(1) LAYER GYPSUM BOARD
SECTION AT FLOOR
SUBSTRATE [1] SUBSTRATE [2]MARK
3 1/2" BATT B1 COLD FORMED STEEL4 1/4" -
WALL THICKNESS CORE STRUCTURE
(1) 5/8 GYPSUM BOARD
INSULATION /
BATT
STUD SIZE RATING UL
3 5/8" - -
TYPE B - ONE SIDED PARTITION
SCHEDULED CEILING SECTION AT CEILING
EXTEND 3 1/2" BATT INSULATION 2'-0" MIN
EXTEND WALL 6" PAST ACT CEILING
OTHERWISE CONCLUDE AT CEILING HEIGHT
6"
ALTERNATE BRACING AT 48" O.C. MAX TO DECK ABOVE
CONTINUOUS SEALANT AT BOTH SIDES OF TRACK
SCHEDULED BASE
CONTINUOUS TRACK AND FASTENERS @ 16" O.C. MAX
3 1/2" BATT B1 COLD FORMED STEEL4 1/4" - (1) VENEER PLASTER 3 5/8" - -
CONTINUOUS SEALANT AT BOTH SIDES OF RUNNER (TOP & BOTTOM)
SCHEDULED BASE
CONTINUOUS METAL "C" RUNNER AND FASTENERS @ 16" O.C. MIN.
FULL HEIGHT SOUND ATTENUATION BLANKET
(1) LAYER TYPE 'X' GYPSUM BOARD ON EACH SIDE
EXISTING STRUCTURE ABOVE
CONTINUOUS DEEP LEG DEFLECTION TRACK FOR 1/2" STRUCTURE
DEFLECTION.
SCHEDULED CEILING
SECTION AT FLOOR
SECTION AT CEILING
CONTINUOUS OR ACOUSTIC SEALANT IN ALL VOIDS ABOVE TRACK ON
BOTH SIDES OF PARTITION.
HOLD STUD 1/2" FROM TOP OF DEFLECTION TRACK, ATTACH GWB TO
STUDS ONLY AND ATTACH STUDS TO THE DEFLECTION TRACK.
TOP OF STRUCTURAL SLAB & SCHEDULED FLOOR FINISH
SECTION AT
STRUCTURE ABOVE
COLD FORMED STEEL FRAMING
FIRESTOP SEALANT AT EACH SIDE OF PARTITION
TYPE R - RATED PARTITION
SUBSTRATE [1] SUBSTRATE [2]MARK
3 1/2" MINERAL
FIBER.
R1 COLD FORMED STEEL4 7/8" (1) 5/8 GYPSUM BOARD
TYPE "X"
WALL THICKNESS CORE STRUCTURE
(1) 5/8 GYPSUM BOARD
TYPE "X"
INSULATION /
BATT
STUD SIZE RATING UL
3 5/8" SMOKE RESISTIVE UL U419
R2 COLD FORMED STEEL4 7/8" (1) 5/8 GYPSUM BOARD
TYPE "X"
(1) 5/8 GYPSUM BOARD
TYPE "X"
3 5/8" SMOKE BARRIER UL U419
R3 COLD FORMED STEEL4 7/8" (1) 5/8 GYPSUM BOARD
TYPE "X"
(1) 5/8 GYPSUM BOARD
TYPE "X"
3 5/8" 1-HOUR FIRE BARRIER UL U419
3 1/2" MINERAL
FIBER.
3 1/2" MINERAL
FIBER.
R4 COLD FORMED STEEL4 7/8" (1) 5/8 GYPSUM BOARD
TYPE "X"
(1) 5/8 GYPSUM BOARD
TYPE "X"
3 5/8" FULL HEIGHT - UNRATED -3 1/2" MINERAL
FIBER.
A. REFERENCE FLOOR PLANS AND PARTITION TYPES FOR ACTUAL FRAMING MEMBERS.
B. COORDINATE WITH MECHANICAL, ELECTRICAL, AND PLUMBING PLANS FOR OPENINGS THAT
ACCOMMODATE NEW MECHANICAL, ELECTRICAL, AND PLUMBING WORK.
C. ANCHOR GYPSUM BOARD WITH SCREWS AT 8" O.C. ON EDGES AT 12" O.C. IN FIELD PER UL DESIGN
NUMBERS LISTED.
D. LABEL ALL RATED PARTITIONS ABOVE CEILING WITH PLAQUE OR STENCILED SIGN READING: "(SMOKE BARRIER/ FIRE BARRIER/ SMOKE RESISTIVE) : SEAL AND PROTECT ALL OPENINGS". REFER TO PARTITION SCHEDULE ON THIS SHEET FOR RATING TYPE. SIGN SHALL BE PLACED ON BOTH SIDES OF PARTITIONS.
E. COORDINATE FRAMING WITH FIRE AND SMOKE DAMPERS AT PENETRATIONS IN RATED PARTITIONS.
F. PROVIDE CONTINUOUS FIRE RATED SEALANT AT THE PERIMETER OF ALL FIRE RATED WALLS AND
CHASES, INCLUDING THE TOP, BOTTOM, AND SIDE EDGES ON BOTH SIDES OF WALL.
G. ROUGH OPENING FRAMING CONFIGURATIONS DEPICTED ARE BASED ON COLD FORMED METAL STUD FRAMED WALL PARTITIONS AND ARE DIAGRAMMATIC IN NATURE, REFER TO ENLARGED DETAILS FOR
FURTHER CONTEXT
H. ALL COLD FORMED STEEL FRAMING IS 20 GAUGE OR HEAVIER.
I. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS
OCCURRING AT OPPOSITE FACE OF WALLS.
J. PROVIDE WALL REINFORCEMENT BETWEEN STUDS WHERE REQUIRED BY INSTALLATION OF MILLWORK
AND/OR WALL HUNG EQUIPMENT.
K. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL WALL STUD INSTALLATIONS EXCEEDING STUD
MANUFACTURER REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
L. REFER TO DIMENSION PLANS FOR AREAS THAT REQUIRE MOISTURE RESISTIVE GYPSUM.
M. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND
ATTENUATION BLANKETS.
N. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND
SEALED. FRAMING TO 1/2" +/- CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
O. SOUND ATTENUATION BATTS (SAB) ARE TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM
UNLESS NOTED OTHERWISE.
G E N E R A L P A R T I T I O N N O T E S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /B a tt le
C re e k V
A
R e n o v a te
A u d io lo g y B
/F
F E
B a tt le
C re e k
R e n o v a te A u d io lo g y
B rv t
/9
/2
:5
:0
P M
GI002
WALL TYPES
01/17/2025 SS CD
RENOVATE AUDIOLOGY 515-23-101
5500 Armstrong Rd, Battle Creek, MI
BID DOCUMENTS 100%
10 & 136
BATTLE CREEK
VA MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
1/4" = 1'-0"
FRAME WALL ROUGH OPENING DIAGRAM
3" = 1'-0"
HEAD JAMB & SILL CONFIGURATIONS - TYPICAL
BID DOCUMENTS 01/17/2025
1 BID ADDENDUM #1 05/09/2025