EE601 - EMCS - RISER DIAGRAM.pdf
PDF 288 KB Posted
- Attached to
- Z1DA--Upgrade Emergency Power 138 610-16-104
- Solicitation number
- 36C25020B0081
About this file
This document package includes an EMCS riser diagram and details for a federal solicitation to upgrade emergency power in Building 138 at the Marion VA Medical Center.
The solicitation will be for upgrading emergency power in Building 138 of the Marion VA Medical Center in Marion, Indiana. It is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses, with a minimum of 15% of construction work required to be performed by the prime contractor. The project magnitude is between $5 million and $10 million under NAICS code 238210. The successful offeror must demonstrate no more than three serious or one repeat/willful OSHA or EPA violations and an EMR of 1.0 or less. The duration shall not exceed 600 calendar days from NTP. Performance and payment bonds will be required.
The riser diagram shows the existing and proposed EMCS and electrical infrastructure to support the emergency power upgrades. It details cabling, conduits, equipment, generators, automatic transfer switches, meters and enclosures to integrate the new systems.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EMCS SERVER
KEYBOARD/MONITOR/MOUSE
1500VA UPS
BUILDING 175
M
GEN
GEN-175
BUILDING 185
BUILDING 124
M
IDE
ATS-124
M
EEDP
ATS-124
M
PRI. ATS
ATS-175
M
PRI. ATS
ATS-175
M
PRI. ATS
ATS-175
M
PRI. ATS
ATS-175
M
PRI. ATS
ATS-175
M
PRI. ATS
M
PRI. ATS
M
PRI. ATS
M
GEN
GEN-175
M
GEN
GEN-175ATS-175 ATS-175 ATS-175
M
LS ATS
M
CR ATS
M
EQ ATS
ATS-185 ATS-185 ATS-185
BUILDING 127
M
PRI. ATS
ATS-127
BUILDING 16
M
EMDP
ATS-16
M
15, 16, 17
ATS-16
BUILDING 76
M
PRI. ATS
ATS-124
M
GEN
GEN-76
EM CS
SYSTEM
SERVER
FIBER
ETHERNET
SW ITCH
LIU
SERVER CABINET
DUPLEX FIBER JUM PERS AS REQUIRED
BUILDING 138
M M M
ATS-138 ATS-138 ATS-138
BUILDING 174
M
ATS-174
M EDIUM VOLTAGE STANDBY GENERATORS
M M
FUTURE
GEN 2
GEN
GEN 1
GEN
LIU
LIU
LIU
LIU
LIU
LIU
LIU
LIU
2" C.
2" C.
2" C. 2" C.
1" C.
1" C.
1" C.
1" C.
1" C.
1" C.
1" C.
1" C.
8 2
3 1
3 3
3 3
3 3 3 3
33333
19 LIU
19 LIUSIGNALS 02A 20
1. OM 4 DUPLEX MULTIMODE FIBER JUMPER FROM LIU
TO MEDIA CONVERTER.
2. CAT 6 CABLE.
3. RS-485 CABLE TO REM OTE CONNECTIVITY UNIT OR
GENERATOR CONTROLLER. SERIAL CONNECTION
FROM M ETER TO M ETER VIA M ODBUS IS AN
ACCEPTABLE TOPOLOGY AS W ELL (IN LIEU OF
HOMERUNS TO REM OTE CONNECTIVITY UNIT).
4. 7-#12 (3-BLK, 3-W HT, 1-GRD.) TO CT LEADS. LOCATE
CT'S ON MAIN GENERATOR FEED/LOAD SIDE OF ATS.
5. 5-#12 (3-BLK, 1-W HT, 1-GRD.) TO VOLTAGE TAP.
6. 6-#12 (3-RED, 3-W HT) FOR ATS I/O (ON EM , ON
NORM AL, START GENERATOR).
7. 4-#14 (2-RED, 2-W HT) FOR ATS I/O (EM SOURCE AVAIL.,
NORM AL SOURCE AVAIL.)
8. 120V-20A EM ERGENCY POW ER CIRCUIT. SEE
ENLARGED ROOM PLANS SHEET FOR MORE
INFORMATION.
9. PROVIDE STRIP HEATER IN METER ENCLOSURE
(W HERE OUTDOORS).
10. NEW DIGITAL METER FOR EMCS
MONITORING/CONTROL. PROVIDE UPS W ITHIN
ENCLOSURE.
11. NEW FIBER TERM INATION PANEL (LIU).
12. OM 4 6 STRAND M ULTIM ODE FIBER FEEDER FROM LIU
IN BUILDING 175 PROVIDING CONNECTIVITY TO EM CS
SERVER/MEDIA CONVERTER/ETHERNET SW ITCH.
PROVIDE #14 AW G INSULATED TRACER W IRE W ITH
ALL UNDERGROUND FIBER OPTIC CABLES. LABEL
"TRACER" AT ALL ACCESSIBLE PULLBOXES.
13. PROVIDE ADDITIONAL M ETER(S) IN SAM E ENCLOSURE
W HERE MULTIPLE ATS(S) ARE IN CLOSE PROXIMITY.
14. NEW VA STANDARD DATA OUTLET TO NEAREST
SIGNALS CLOSET IN BLDG. 13E APPROXIMATELY 300'
AW AY. VA TO PROVIDE NETW ORK CONNECTION.
15. REMOTE CONNECTIVITY UNIT.
16. UTILIZE OSP RATED CABLE.
17. 8-#14 (4-RED, 2-W HT) FOR ATS I/O (BYPASS TO
NORM AL BYPASS TO EM. AUTOM ATIC SECTION
CONNECTED).
18. 4-#14 (2-RED, 4-W HT) FOR ATS I/O (TEST W ITHOUT
TRANSFER).
A. ALL CABLING SHALL BE IN CONDUIT, 0.75"C. M IN.
B. PROVIDE NAM EPLATES PER SPECIFICATIONS.
C. COORDINATE ALL W ORK W ITH EM CS
MANUFACTURER.
D. REFER TO SINGLE-LINE DIAGRAM S/FLOOR PLANS FOR
MORE INFORM ATION.
E. REFER TO SPECIFICATION SECTION 26 36 24 ENERGY
MONITORING AND CONTROL SYSTEM (EM CS) AND
PROVIDE ALL REQUIRED LABOR AND M ATERIAL FOR A
COMPLETE AND OPERATIONAL SYSTEM.
F. ALL SOFTW ARE M UST BE LISTED AS APPROVED BY VA
OIT ON THE VA TECHNICAL REFERENCE MODEL (TRM).
G . CONTRACTOR SHALL PROVIDE TEMPORARY POW ER
FOR EM CS VENDOR TO UPGRADE EACH EXISTING
ATS. COMPLETE W ORK IN NO LONGER THAN AN
EIGHT HOUR SHUTDOW N FOR EACH ATS. PROVIDE
TEM PORARY ATS TO BYPASS EXISTING ATS.
TEM PORARY ATS SHALL BE SIZED TO M ATCH LINE
SIDE FEEDER OVERCURRENT PROTECTIVE DEVICE AT
A MINIM UM . SPLICE NORM AL AND EMERGENCY LINE
SIDE AND LOAD SIDE FEEDS IN EXISTING ATS AND
ROUTE TO TEMPORARY ATS. BLANKET OFF ALL LIVE
CONDUCTORS. PROVIDE TEM PORARY START CIRCUIT
TO TEM PORARY ATS. COORDINATE ALL
W ORK/OUTAGES W ITH EM CS VENDOR. W HEN EM CS
W ORK ON EXISTING ATS IS COMPLETE, RECONNECT
EXISTING ATS AND EQUIPM ENT.
DETAIL NOTES GENERAL NOTES
TYPICAL GENERATOR
HOUSING/METERING
GEN
1.25"C.
M
1.25" C.
ATS
M
TYPICAL ELECTRIC
SECONDARY ATS/METER
ROOM LOCATIONS
1.25" C.
ATS
M
TYPICAL ELECTRIC
PRIM ARY ATS/M ETER
ROOM LOCATION
GW M C 1
10 13 8 15
1 11 12
9 10
RCU
LIU
19. PROVIDE M ULTI-PORT GIGABIT M EDIA CONVERTER IN
EM CS SERVER RACK. TRANSITIONS NETW ORK S3290
SERIES W ITH SFP M ODULE, FIBER AND COPPER
JUMPERS, AND POW ER SUPPLY. PROVIDE RACK
MOUNT KIT.
20. EXISTING SW ITCH. COORDINATE CONNECTION W ITH
OIT.
DETAIL NOTES CONT'D
DEDICATED EMCS FIBER OPTIC
CABLE, 6 STRAND, 62.5/125 mM
BLDG 175 TO BLDG 185
ZIP TIE OR CHAIN
SOURCE/DESTINATIONRED PHENOLIC NAM EPLATE
EVERY ACCESSIBLE FIBER OPTIC CABLE
A. IDENTIFY EACH FIBER OPTIC CABLE PASSING THROUGH EACH ELECTRIC PULLBOX W ITH A
LAM INATED PHENOLIC NAM EPLATE TAG SECURED TO CABLE W ITH PERMANENT STRAP
OR BAND. NAM EPLATES SHALL BE 0.125" THICK, RED W ITH W HITE CORE, LETTERING
SHALL BE 0.25" MINIM UM HEIGHT. TEXT SHALL BE PER DETAIL. SUBMIT SAMPLE DURING
SHOP DRAW ING REVIEW , COM PLETE AND ATTACHED TO SAM PLE OF FIBER OPTIC CABLE.
GENERAL NOTE
DETAIL NOTES
1. NEW SERVER GRADE CABINET INCLUDING
FRONT LOCKING PERFORATED DOORS,
REAR LOCKING PERFORATED DOORS,
TOP MOUNTED VENTILATION FANS.
2. 1RU HORIZONTAL W IRE M ANAGER.
3. RACK M OUNTED FIBER TERMINATION
PANEL W ITH COUPLER BULKHEARDS.
4. 24 PORT FIBER SW ITCH W ITH COPPER
1GB UPLINK PORTS W ITH OM4 GIGABIT
SFP FOR EACH UTILIZED PORT.
5. EM CS SW ITCH.
6. EM CS RACK M OUNTED SERVER.
7. RACK M OUNTED COMBINATION 17" LCD
MONITOR, KEYBOARD AND MOUSE IN 1RU
FLIP UP ASSEM BLY.
8. NEW 1500 VA UPS TO SERVE RACK
MOUNTED EQUIPM ENT. PROVIDE LAN
CONNECTION MODULE AND CONNECT TO
NEW LOCAL DATA DROP W ITH NETW ORK
MANAGEM ENT MODULE.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Services
Engineering and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Marion VA Marion, IN
UPGRADE EMERGENCY
POWER IN BUILDING 138
#610-16-104
PROJECT NO. 2018-05034 FULLY SPRINKLERED
CONSTRUCTION DOCUMENTS
C
B
IM
\M o d e l\
-0
-E le c tr ic a l C e n tr a l_ jh s lo n e .r v t
/2
/2
:3
:2
A
M
EE601
EMCS - RISER DIAGRAM
12/17/2019 MSG JHS
SCALE: NONE
EMCS RISER DIAGRAM
SCALE: NONE
EMCS NAMEPLATE DETAIL
SCALE: 1/8" = 1'-0"
NEW EMCS SERVER CABINET AND EQUIPMENT
MULTIPLE
DRAWING 52 OF 60Revisions: Date:
95% REVIEW 12/17/2019
Addendum 4 11/23/2020
Addendum 5 12/21/2020
ASCO MODEL
F940 (34, 36, OR 38) 0097XC
(TYP. 8)
ASCO
F940360097XC
NEW NEW NEW
ASCO
B940326049XC
ASCO
NEW
ASCO
E940380097XC
RUSS ELECTRIC
RMT 4000 3CE
ANTIQUATED
RUSS ELECTRIC
BYPASS
RUSS ELECTRIC
RTBDCT-1003CEF
RUSS ELECTRIC
RTBDCT-2253CEF
RUSS ELECTRIC
RTBDCT-4003CEF
| Sheets |
| EE601 - EMCS - RISER DIAGRAM |
| EP201 - POWER - MV SWITCHGEAR ELEVATION |
File details come from the government source that posted it. Updated .