233700 OUTLETS AND INLETS seismic.pdf

PDF 10 KB Posted

Attached to
Z1DA--Upgrade Emergency Power 138 610-16-104
Solicitation number
36C25020B0081
Issued by

About this file

This document contains a solicitation for upgrade emergency power at a Veterans Affairs medical center building and specifications for air outlets and inlets to be installed as part of the project. The solicitation seeks bids for upgrading emergency power in Building 138 at the VA Medical Center in Marion, Indiana, with a project magnitude between $5 million and $10 million. The NAICS code is 238210 and the business size standard is $16.5 million. The set-aside is for a Service-Disabled Veteran-Owned Small Business, which must perform a minimum of 15% of the construction work. The specifications provide requirements for air diffusers, registers, grilles and related components to be installed as part of the HVAC system. Materials, performance testing, supply and return outlets, wire mesh grilles and installation procedures are specified. The bid due date will be approximately 30 days after the solicitation is posted on August 14, 2020 to beta.sam.gov. The contract duration shall not exceed 600 calendar days from notice to proceed.

View the file

Other files

File Type Posted
36C25020B0081 0014.docx DOCX document
36C25020B0081 0013.docx DOCX document
EP001S.pdf PDF
36C25020B0081 0012.docx DOCX document
261313 MEDIUM-VOLTAGE CIRCUIT BREAKER SWITCHGEAR seismic.pdf PDF
RFIs - Responses and Answers 20210323.pdf PDF
230541 NOISE AND VIBRATION CONTROL seismic.pdf PDF
231000 FACILITY FUEL SYSTEMS seismic.pdf PDF
211313 Wet-Pipe Sprinkler Systems seismic.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part6.pdf PDF
260533 Raceway and Boxes seismic.pdf PDF
Revised Bid Schedule.rtf RTF text file
238200 Convection Heating and Cooling Units seismic.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part3.pdf PDF
232113 Hydronic Piping seismic.pdf PDF
238100 DECENTRALIZED UNITARY HVAC EQUIPMENT.pdf PDF
263623 Automatic Transfer Switches seismic.pdf PDF
233100 HVAC DUCTS AND CASINGS seismic.pdf PDF
232300 REFRIGERANT PIPING seismic.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part2.pdf PDF
230511 COMMON WORK RESULTS FOR HVAC seismic.pdf PDF
232111 BOILER PLANT PIPING SYSTEMS seismic.pdf PDF
092216 NON-STRUCTURAL METAL FRAMING 2.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part4.pdf PDF
261313 Appendix_Concrete Pad for Metering Cabinet.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part5.pdf PDF
000110 Table of Contents seismic.pdf PDF
265100 Interior Lighting seismic.pdf PDF
238413 Self-Contained Steam Humidifiers.pdf PDF
232213 Steam and Condensate Heating Piping seismic.pdf PDF
262313 Generator Paralleling Cont seismic.pdf PDF
262200 Low Voltage Transformers seismic.pdf PDF
610-16-104 Upgrade Emergency Power Addendum Drawings 2021 0402 sealed_Part1.pdf PDF
36C25020B0081 0011.docx DOCX document
074000 Siding Panels seismic.pdf PDF
36C25020B0081 0010.docx DOCX document
36C25020B0081 0009.docx DOCX document
36C25020B0081 0008.docx DOCX document
36C25020B0081 0007.docx DOCX document
36C25020B0081 0006.docx DOCX document
EP201 - POWER - MV SWITCHGEAR ELEVATION.pdf PDF
36C25020B0081 0005.docx DOCX document
EE601 - EMCS - RISER DIAGRAM.pdf PDF
RFI Responses.docx DOCX document
194EP-100 - ELECTRICAL POWER PLAN.pdf PDF
Card Reader Specification 281300.pdf PDF
610-16-104 addendum 04 all drawings 20201201.pdf PDF
610-16-104 Fires Safety CD review and responses 20201201.pdf PDF
Tax Exemption - Indiana (FTW).pdf PDF
36C25020B0081 0004.docx DOCX document
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UPGRADE EMERGENCY POWER IN BUILDING 138

VAMC, MARION, IN PROJECT: 610-16-104

02-01-20

23 37 00 - 1

SECTION 23 37 00

AIR OUTLETS AND INLETS

PART 1 - GENERAL

1.1 DESCRIPTION

A. Air Outlets and Inlets: Diffusers, Registers, an d Grilles.

1.2 RELATED WORK

A. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, a nd SAMPLES.

B. Section 08 90 00, LOUVERS and VENTS.

C. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL

COMPONENTS.

D. Section 23 05 11, COMMON WORK RESULTS FOR HVAC a nd STEAM GENERATION.

E. Section 23 05 41, NOISE and VIBRATION CONTROL FO R HVAC PIPING and

EQUIPMENT.

F. Section 23 05 93, TESTING, ADJUSTING, and BALANC ING FOR HVAC.

1.3 QUALITY ASSURANCE

A. Refer to Article, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK

RESULTS FOR HVAC.

B. Fire Safety Code: Comply with NFPA 90A.

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, and SAMPLES.

B. Manufacturer's Literature and Data:

2. Registers, grilles and accessories.

C. Coordination Drawings: Refer to article, SUBMITT ALS, in Section 23 05

11, COMMON WORK RESULTS FOR HVAC.

1.5 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of thi s specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. Air Diffusion Council Test Code:

1062 GRD-2015...........Certification, Rating, and Test Manual 4 th

Edition

C. American Society of Civil Engineers (ASCE):

ASCE7-2017..............Minimum Design Loads for Bu ildings and Other

Structures

D. American Society for Testing and Materials (ASTM ):

02-01-20

23 37 00 - 2

A167-99 2009............Standard Specification for Stainless and

Heat-Resisting Chromium-Nickel Steel Plate, Sheet and Strip

B209- 2014..............Standard Specification for Aluminum and

Aluminum-Alloy Sheet and Plate

E. National Fire Protection Association (NFPA):

90A-2018................Standard for the Installati on of Air

Conditioning and Ventilating Systems

F. Underwriters Laboratories, Inc. (UL):

181-2013................UL Standard for Safety Fact ory-Made Air Ducts and Connectors

PART 2 - PRODUCTS

2.1 EQUIPMENT SUPPORTS

Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.

2.2 AIR OUTLETS AND INLETS

A. Materials:

1. Steel or aluminum. Provide manufacturer's standa rd gasket.

2. Exposed Fastenings: The same material as the res pective inlet or outlet. Fasteners for aluminum may be stainless ste el.

3. Contractor shall review all drawings and details and provide all devices with appropriate dimensions and trim for th e specific locations.

B. Performance Test Data: In accordance with Air Di ffusion Council Code

1062GRD. Refer to Section 23 05 41, NOISE and VIBRA TION CONTROL FOR

HVAC PIPING and EQUIPMENT for NC criteria.

C. Air Supply Outlets:

1. Supply Registers: Double deflection type with ho rizontal face bars and opposed blade damper with removable key operato r.

a. Margin: Flat, 30 mm (1-1/4 inches) wide.

b. Bar spacing: 20 mm (3/4 inch) maximum.

c. Finish: Off white baked enamel for ceiling mount ed units. Wall units shall have a prime coat for field painting, o r shall be extruded with manufacturer's standard finish.

2. Supply Grilles: Same as registers but without th e opposed blade damper.

D. Return and Exhaust Registers and Grilles: Provid e opposed blade damper without removable key operator for registers.

02-01-20

23 37 00 - 3

1. Finish: Off-white baked enamel for ceiling mount ed units. Wall units shall have a prime coat for field painting, or shal l be extruded aluminum with manufacturer's standard aluminum fini sh.

2. Standard Type: Fixed horizontal face bars set at 30 to 45 degrees, approximately 30 mm (1-1/4 inch) margin.

3. Perforated Face Type: To match supply units.

4. Grid Core Type: 13 mm by 13 mm (1/2 inch by 1/2 inch) core with 30 mm (1-1/4 inch) margin.

5. Linear Type: To match supply units.

6. Door Grilles: Are furnished with the doors.

7. Egg Crate Grilles: Aluminum or Painted Steel 1/2 by 1/2 by 1/2 inch grid providing 90% free area.

a. Heavy extruded aluminum frame shall have counter sunk screw mounting. Unless otherwise indicated, register bla des and frame shall have factory applied white finish.

b. Grille shall be suitable for duct or surface mou nting as indicated on drawings. All necessary appurtenances shall be provided to allow for mounting.

2.3 WIRE MESH GRILLE

A. Fabricate grille with 2 x 2 mesh 13 mm (1/2 inch ) galvanized steel or aluminum hardware cloth in a spot welded galvanized steel frame with approximately 40 mm (1-1/2 inch) margin.

B. Use grilles where shown in unfinished areas such as mechanical rooms.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with provisions of Section 23 05 11, COMM ON WORK RESULTS FOR

HVAC AND STEAM GENERATION, particularly regarding c oordination with other trades and work in existing buildings.

B. Protection and Cleaning: Protect equipment and m aterials against physical damage. Place equipment in first class ope rating condition, or return to source of supply for repair or replacemen t, as determined by the COR. Protect equipment during construction agai nst entry of foreign matter to the inside and clean both inside and outs ide before operation and painting.

- - - E N D - - -