This solicitation package describes an upcoming federal contract opportunity to upgrade emergency power systems at a Veterans Affairs medical center building in Marion, Indiana. The project involves replacing emergency power systems in Building 138 and has a budget between $5 million to $10 million. The solicitation will be a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses, with a requirement to perform a minimum of 15% of construction work. Interested contractors must be registered and verified in the Vendor Information Pages and SAM databases. The performance period is expected to last 600 calendar days from notice to proceed. The solicitation and drawings will be posted on August 14, 2020 on sam.gov, with bids due approximately 30 days later.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPGRADE EMERGENCY POWER IN BUILDING 138
VAMC, MARION, IN PROJECT: 610-16-104
03-01-20
23 82 00 - 1
SECTION 23 82 00
CONVECTION HEATING AND COOLING UNITS
PART 1 - GENERAL
1.1 DESCRIPTION
This section specifies unit heaters.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, a nd SAMPLES
C. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS: Seismic restraints for equipment.
D. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General mechanical requirements and items, which are common to more th an one section of
Division 23.
E. Section 23 05 41, NOISE and VIBRATION CONTROL FO R HVAC PIPING and
EQUIPMENT: Noise requirements.
F. Section 23 05 93, TESTING, ADJUSTING, and BALANC ING FOR HVAC: Flow rates adjusting and balancing.
G. Section 23 31 00, HVAC DUCTS and CASINGS: Ducts and flexible connectors.
1.3 QUALITY ASSURANCE
Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK
RESULTS FOR HVAC. Provide guarantee in accordance w ith FAR clause
52.246-21
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, and SAMPLES.
B. Manufacturer's Literature and Data:
1. Unit heaters.
C. Certificates:
1. Compliance with Article, QUALITY ASSURANCE.
2. Compliance with specified standards.
D. Operation and Maintenance Manuals: Submit in acc ordance with Article, INSTRUCTIONS, in Section 01 00 00, GENERAL REQUIREM ENTS.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of thi s specification to the extent referenced. The publications are referenced in the text by the basic designation only.
03-01-20
23 82 00 - 2
B. National Fire Protection Association (NFPA):
90A-2018................Standard for the Installati on of Air
Conditioning and Ventilating Systems
70-2017.................National Electrical Code
C. Underwriters Laboratories, Inc. (UL):
1995-2015...............Heating and Cooling Equipme nt
PART 2 - PRODUCTS
2.1 UNIT HEATERS
A. General: Vertical discharge type for electric he ating medium.
B. Casing: Steel sheet, phosphatized to resist rust and finished in baked enamel. Provide hanger supports.
C. Fan: Propeller type, direct driven by manufactur er's standard electric motor. Provide resilient mounting.
D. Electric Units: UL listed, factory wired to term inal strips for field connection of power and control wiring.
1. Heating elements: Nickel chromium alloy resistan ce wire embedded in a magnesium oxide insulating refractory and sealed in corrosion resisting metallic sheath with fins. Three phase he aters shall have balanced phases.
2. Thermal cutout: Manual reset type, which disconn ects elements, and motor in the event normal operating temperatures ar e exceeded.
3. Magnetic contactor: Factory installed with low v oltage relay for remote pilot duty thermostat operation.
E. Controls: Provide field installed remote wall mo unted line voltage electric space thermostats for each unit, where sho wn.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Work shall be installed as shown and according t o the manufacturer’s diagrams and recommendations.
B. Handle and install units in accordance with manu facturer's written instructions.
C. Support units rigidly so they always remain stat ionary. Cross-bracing or other means of stiffening shall be provided as n ecessary. Method of support shall be such that distortion and malfuncti on of units cannot occur.
3.2 OPERATIONAL TEST
Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
03-01-20
23 82 00 - 3
- - - E N D - - -