This solicitation package describes an upcoming Invitation for Bid for an upgrade emergency power project at a Veterans Affairs medical center. The project scope involves upgrading emergency power in Building 138 and has a projected value between $5 million and $10 million. The solicitation will be issued by the Northern Indiana HealthCare System, VA Medical Center Network Contracting Office 10. The NAICS code is 238210 and business size standard is $16.5 million. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses, who must be registered and verified in VIP and SAM databases. The SDVOSB must perform a minimum of 15% of construction work. The performance period is 600 calendar days from notice to proceed. Bonds will be required. A site visit will be scheduled upon solicitation release on or about August 14, 2020, with bids due approximately 30 days later.
View the file
Other files
Show 40 more
Latest 50 of 61 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPGRADE EMERGENCY POWER IN BUILDING 138
VAMC, MARION, IN PROJECT: 610-16-104
01-01-18
26 51 00 - 1
SECTION 26 51 00
INTERIOR LIGHTING
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies the furnishing, installat ion, and connection of the interior lighting systems. The terms “lighting fixture,”
“fixture,” and “luminaire” are used interchangeably .
1.2 RELATED WORK
A. Section 01 74 19, CONSTRUCTION WASTE MANAGEMENT: Disposal of lamps.
B. Section 02 41 00, DEMOLITION: Removal and dispos al of lamps and ballasts.
C. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS: Requirement for seismic restraint for n onstructural components.
D. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL IN STALLATIONS:
Requirements that apply to all sections of Division 26.
E. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER C ONDUCTORS AND CABLES:
Low-voltage conductors.
F. Section 26 05 26, GROUNDING AND BONDING FOR ELEC TRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.
G. Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Pa ragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIR EMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Shop Drawings:
a. Submit the following information for each type o f lighting fixture designated on the LIGHTING FIXTURE SCHEDULE , arranged in order of lighting fixture designation.
b. Material and construction details, include infor mation on housing and optics system.
01-01-18
26 51 00 - 2
c. Physical dimensions and description.
d. Wiring schematic and connection diagram.
e. Installation details.
f. Energy efficiency data.
g. Photometric data based on laboratory tests compl ying with IES
Lighting Measurements testing and calculation guide s.
h. For LED lighting fixtures, submit US DOE LED Lig hting Facts label, and IES L70 rated life.
2. Manuals:
a. Submit, simultaneously with the shop drawings, c omplete maintenance and operating manuals, including techni cal data sheets, wiring diagrams, and information for orderi ng replacement parts.
b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated mainte nance and operating manuals two weeks prior to the final insp ection.
3. Certifications: Two weeks prior to final inspect ion, submit the following.
a. Certification by the Contractor that the interio r lighting systems have been properly installed and tested.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specif ication to the extent referenced. Publications are referenced in t he text by designation only.
B. American Society for Testing and Materials (ASTM ):
C635/C635M REV A-13.....Manufacture, Performance, a nd Testing of Metal
Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
C. Environmental Protection Agency (EPA):
40 CFR 261..............Identification and Listing of Hazardous Waste
D. Federal Communications Commission (FCC):
CFR Title 47, Part 15...Radio Frequency Devices
CFR Title 47, Part 18...Industrial, Scientific, and Medical Equipment
E. Illuminating Engineering Society of North Americ a (IESNA):
LM-79-08................Electrical and Photometric Measurements of
Solid-State Lighting Products
01-01-18
26 51 00 - 3
LM-80-15................Measuring Lumen Maintenance of LED Light
Sources
LM-82-12................Characterization of LED Lig ht Engines and LED
Lamps for Electrical and Photometric Properties as a Function of Temperature
F. Institute of Electrical and Electronic Engineers (IEEE):
C62.41-91(R1995)........Surge Voltages in Low Volta ge AC Power Circuits
G. International Code Council (ICC):
IBC-15..................International Building Code
H. National Electrical Manufacturer's Association ( NEMA):
C78.376-14..............Chromaticity of Fluorescent Lamps
C82.1-04(R2015).........Lamp Ballasts – Line Freque ncy Fluorescent Lamp
Ballasts
C82.2-02(R2016).........Method of Measurement of Fl uorescent Lamp
Ballasts
C82.4-17................Lamp Ballasts - Ballasts fo r High-Intensity
Discharge and Low-Pressure Sodium (LPS) Lamps
(Multiple-Supply Type)
C82.11-17...............Lamp Ballasts - High Freque ncy Fluorescent Lamp
Ballasts
LL 9-11.................Dimming of T8 Fluorescent L ighting Systems
SSL 1-16................Electronic Drivers for LED Devices, Arrays, or
Systems
I. National Fire Protection Association (NFPA):
70-20...................National Electrical Code (N EC)
101-18..................Life Safety Code
J. Underwriters Laboratories, Inc. (UL):
496-17..................Lampholders
542-05..................Fluorescent Lamp Starters
844-12..................Luminaires for Use in Hazar dous (Classified)
Locations
924-16..................Emergency Lighting and Powe r Equipment
935-01..................Fluorescent-Lamp Ballasts
1029-94.................High-Intensity-Discharge La mp Ballasts
1029A-06................Ignitors and Related Auxili aries for HID Lamp
Ballasts
1598-08.................Luminaires
1574-04.................Track Lighting Systems
01-01-18
26 51 00 - 4
2108-15.................Low-Voltage Lighting System s
8750-15.................Light Emitting Diode (LED) Light Sources for
Use in Lighting Products
PART 2 - PRODUCTS
2.1 LIGHTING FIXTURES
A. Shall be in accordance with NFPA, UL, as shown o n drawings, and as specified.
B. Sheet Metal:
1. Shall be formed to prevent warping and sagging. Housing, trim and lens frame shall be true, straight (unless intentio nally curved), and parallel to each other as designed.
2. Wireways and fittings shall be free of burrs and sharp edges, and shall accommodate internal and branch circuit wirin g without damage to the wiring.
3. When installed, any exposed fixture housing surf ace, trim frame, door frame, and lens frame shall be free of light l eaks.
4. Hinged door frames shall operate smoothly withou t binding. Latches shall function easily by finger action without the use of tools.
C. Recessed fixtures mounted in an insulated ceilin g shall be listed for use in insulated ceilings.
D. Mechanical Safety: Lighting fixture closures (le ns doors, trim frame, hinged housings, etc.) shall be retained in a secur e manner by captive screws, chains, aircraft cable, captive hinges, or fasteners such that they cannot be accidentally dislodged during normal operation or routine maintenance.
E. Metal Finishes:
1. The manufacturer shall apply standard finish (un less otherwise specified) over a corrosion-resistant primer, after cleaning to free the metal surfaces of rust, grease, dirt and other deposits. Edges of pre-finished sheet metal exposed during forming, stamping or shearing processes shall be finished in a similar c orrosion resistant manner to match the adjacent surface(s). Fixture finish shall be free of stains or evidence of rusting, bli stering, or flaking, and shall be applied after fabrication.
2. Interior light reflecting finishes shall be whit e with not less than
85 percent reflectances, except where otherwise sho wn on the drawing.
3. Exterior finishes shall be as shown on the drawi ngs.
01-01-18
26 51 00 - 5
F. Lighting fixtures shall have a specific means fo r grounding metallic wireways and housings to an equipment grounding con ductor.
G. Lighting fixtures in hazardous areas shall be su itable for installation in Class and Division areas as defined in NFPA 70.
2.2 LED EXIT LIGHT FIXTURES
A. Exit light fixtures shall meet applicable requir ements of NFPA and UL.
B. Housing and door shall be die-cast aluminum.
C. For general purpose exit light fixtures, door fr ame shall be hinged, with latch. For vandal-resistant exit light fixtur es, door frame shall be secured with tamper-resistant screws.
D. Finish shall be satin or fine-grain brushed alum inum.
E. There shall be no radioactive material used in t he fixtures.
F. Fixtures:
1. Inscription panels shall be cast or stamped alum inum a minimum of
2.25 mm (0.090 inch) thick, stenciled with 150 mm ( 6 inch) high letters, baked with red color stable plastic or fib erglass. Lamps shall be luminous Light Emitting Diodes (LED) mount ed in center of letters on red color stable plastic or fiberglass.
2. Double-Faced Fixtures: Provide double-faced fixt ures where required or as shown on drawings.
3. Directional Arrows: Provide directional arrows a s part of the inscription panel where required or as shown on dra wings.
Directional arrows shall be the "chevron-type" of s imilar size and width as the letters and meet the requirements of N FPA 101.
G. Voltage: Multi-voltage (120 – 277V).
2.3 LED LIGHT FIXTURES
A. General:
1. LED light fixtures shall be in accordance with I ES, NFPA, UL, as shown on the drawings, and as specified.
2. LED light fixtures shall be Reduction of Hazardo us Substances
(RoHS)-compliant.
3. LED drivers shall include the following features unless otherwise indicated:
a. Minimum efficiency: 85% at full load.
b. Minimum Operating Ambient Temperature: -20˚ C. ( -4˚ F.)
c. Input Voltage: 120 - 277V (±10%) at 60 Hz.
d. Integral short circuit, open circuit, and overlo ad protection.
e. Power Factor: ≥ 0.95.
01-01-18
26 51 00 - 6
f. Total Harmonic Distortion: ≤ 20%.
g. Comply with FCC 47 CFR Part 15.
4. LED modules shall include the following features unless otherwise indicated:
a. Comply with IES LM-79 and LM-80 requirements.
b. Minimum CRI 80 and color temperature 3000˚ K unl ess otherwise specified in LIGHTING FIXTURE SCHEDULE.
c. Minimum Rated Life: 50,000 hours per IES L70.
d. Light output lumens as indicated in the LIGHTING FIXTURE
SCHEDULE.
5. LED light fixtures shall have at least a 5 year limited manufacturer’s warranty covering drivers, modules, and integral control devices from defects in material and workma nship.
B. LED Downlights:
1. Housing, LED driver, and LED module shall be pro ducts of the same manufacturer.
C. LED Troffers:
1. LED drivers, modules, and reflector shall be acc essible, serviceable, and replaceable from below the ceiling .
2. Housing, LED driver, and LED module shall be pro ducts of the same manufacturer.
3. LED light fixtures shall be DesignLights Consort ium (DLC) qualified.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installation shall be in accordance with the NEC , manufacturer's instructions, and as shown on the drawings or speci fied.
B. Align, mount, and level the lighting fixtures un iformly.
C. Wall-mounted fixtures shall be attached to the s tuds in the walls, or to a 20 gauge metal backing plate that is attached to the studs in the walls. Lighting fixtures shall not be attached dir ectly to gypsum board.
D. Lighting Fixture Supports:
1. Shall provide support for all of the fixtures. S upports may be anchored to channels of the ceiling construction, t o the structural slab or to structural members within a partition, o r above a suspended ceiling.
2. Shall maintain the fixture positions after clean ing and relamping.
01-01-18
26 51 00 - 7
3. Shall support the lighting fixtures without caus ing the ceiling or partition to deflect.
4. Hardware for recessed lighting fixtures:
a. All fixture mounting devices connecting fixtures to the ceiling system or building structure shall have a capacity for a horizontal force of 100 percent of the fixture weig ht and a vertical force of 400 percent of the fixture weight .
b. Mounting devices shall clamp the fixture to the ceiling system structure (main grid runners or fixture framing cro ss runners) at four points in such a manner as to resist spreading of these supporting members. Each support point device shall utilize a screw or approved hardware to "lock" the fixture ho using to the ceiling system, restraining the fixture from moveme nt in any direction relative to the ceiling. The screw (size No. 10 minimum) or approved hardware shall pass through th e ceiling member (T-bar, channel or spline), or it may extend over the inside of the flange of the channel (or spline) tha t faces away from the fixture, in a manner that prevents any fix ture movement.
c. In addition to the above, the following is requi red for fixtures exceeding 9 kg (20 pounds) in weight.
1) Where fixtures mounted in ASTM Standard C635 "In termediate
Duty" and "Heavy Duty" ceilings and weigh between 9 kg and 25 kg (20 pounds and 56 pounds), provide two 12 gauge safety hangers hung slack between diagonal corners of the fixture and the building structure.
2) Where fixtures weigh over 25 kg (56 pounds), the y shall be independently supported from the building structure by approved hangers. Two-way angular bracing of hanger s shall be provided to prevent lateral motion.
d. Where ceiling cross runners are installed for su pport of lighting fixtures, they shall have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners.
5. Surface mounted lighting fixtures:
a. Fixtures shall be bolted against the ceiling ind ependent of the outlet box at four points spaced near the corners o f each unit.
The bolts (or stud-clips) shall be minimum 6 mm (1/ 4 inch) bolt, secured to main ceiling runners and/or secured to c ross runners.
01-01-18
26 51 00 - 8
Non-turning studs may be attached to the main ceili ng runners and cross runners with special non-friction clip device s designed for the purpose, provided they bolt through the runner, or are also secured to the building structure by 12 gauge safet y hangers.
Studs or bolts securing fixtures weighing in excess of 25 kg (56 pounds) shall be supported directly from the buildi ng structure.
b. Where ceiling cross runners are installed for su pport of lighting fixtures, they shall have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners.
c. Fixtures less than 6.8 kg (15 pounds) in weight and occupying less than 3715 sq cm (two square feet) of ceiling a rea may, when designed for the purpose, be supported directly fro m the outlet box when all the following conditions are met.
1) Screws attaching the fixture to the outlet box p ass through round holes (not key-hole slots) in the fixture bod y.
2) The outlet box is attached to a main ceiling run ner (or cross runner) with approved hardware.
3) The outlet box is supported vertically from the building structure.
d. Fixtures mounted in open construction shall be s ecured directly to the building structure with approved bolting and clamping devices.
6. Single or double pendant-mounted lighting fixtur es:
a. Each stem shall be supported by an approved outl et box mounted swivel joint and canopy which holds the stem captiv e and provides spring load (or approved equivalent) dampening of f ixture oscillations. Outlet box shall be supported vertica lly from the building structure.
7. Outlet boxes for support of lighting fixtures (w here permitted) shall be secured directly to the building structure with approved devices or supported vertically in a hung ceiling f rom the building structure with a nine gauge wire hanger, and be sec ured by an approved device to a main ceiling runner or cross r unner to prevent any horizontal movement relative to the ceiling.
E. Furnish and install the new lamps as specified f or all lighting fixtures installed under this project, and for all existing lighting fixtures reused under this project.
01-01-18
26 51 00 - 9
F. The electrical and ceiling trades shall coordina te to ascertain that approved lighting fixtures are furnished in the pro per sizes and installed with the proper devices (hangers, clips, trim frames, flanges, etc.), to match the ceiling system being i nstalled.
G. Bond lighting fixtures to the grounding system a s specified in Section
26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYST EMS.
H. At completion of project, replace all defective components of the lighting fixtures at no cost to the Government.
I. Dispose of lamps per requirements of Section 01 74 19, CONSTRUCTION
WASTE MANAGEMENT.
3.2 ACCEPTANCE CHECKS AND TESTS
A. Perform the following:
1. Visual Inspection:
a. Verify proper operation by operating the lightin g controls.
b. Visually inspect for damage to fixtures, lenses, reflectors, diffusers, and louvers. Clean fixtures, lenses, re flectors, diffusers, and louvers that have accumulated dust, dirt, or fingerprints during construction.
2. Electrical tests:
a. Exercise dimming components of the lighting fixt ures over full range of dimming capability by operating the contro l devices(s) in the presence of the COR. Observe for visually d etectable flicker over full dimming range, and replace defect ive components at no cost to the Government.
3.3 FOLLOW-UP VERIFICATION
A. Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that the lighting systems are in good operating condition and properly performing the int ended function.
---END---