Asbestos Inspection Report.pdf
PDF 235 KB Posted
- Attached to
- Y1AZ--Renovate Bldg. 15, 2nd Floor
- Solicitation number
- 36C24625B0007
About this file
This is an asbestos re-inspection report for Building 15 at the Charles George VA Medical Center in Asheville, North Carolina, conducted by Affinity Environmental Consulting in December 2024. The report identifies seven homogeneous areas containing asbestos-containing materials (ACM) throughout the building, including floor tiles and mastic, thermal system insulation (TSI) pipe runs and fittings, tar/gravel roofing materials, joint compound on sheetrock walls, and black moisture barrier.
The report includes detailed floor plans showing the locations of ACM and notes that while the building was renovated in the mid-1990s with some TSI removal, not all ACM was removed. Specific findings include 3 broken tiles in Room SP002, 10,000 SF of white/tan floor tile and mastic throughout various areas (with some areas abated in 2012), and 12,000 SF of roofing materials. The report indicates that most floor tiles and mastics should be assumed to contain asbestos unless tested when carpet is removed. A positive composite sample of drywall joint compound (<1% Chrysotile) was found on the 2nd floor in Room 212, and the report recommends bulk sampling of individual walls prior to any disturbance.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Homogenous
Area
Asbestos-Containing
Material Location Description
Current
Condition
Potential for
Disturbance
Estimated
Quantity
A15-004
Weston
Off White 12" x 12" Floor
Tile & Mastic
Basement Storage Rooms on West Side of Building
MISC - NF
Localized
Damage
LPD 1,500 SF
A15-005
Weston
White/Tan 12" x 12" Floor
Tile & Mastic (Mastic Only
In Some Areas)
Basement Hallway, 1st
Floor Various Areas, &
2nd Floor Throughout
MISC - NF G LPD 10,000 SF
A15-011
Weston TSI Pipe Runs
Inside Wall & Ceiling
Chases TSI - F Unknown LPD Unknown
A15-012
Weston TSI Pipe Fittings
Inside Wall & Ceiling
Chases TSI - F Unknown LPD Unknown
A15-015
Weston
Tar/Gravel Roofing, Shingles, Flashings, & Roof MISC - NF G LPD 12,000 SF
D-15-01 Joint Compound on
Sheetrock Walls
Throughout Original Walls of Building 15 MISC-F G PD Throughout
W-01 Black Moisture Barrier
Throughout Perimeter
Walls of Building Between
Plaster & Exterior Wall
MISC - NF Hidden LPD Throughout
O&M - Drywall & Joint Compound
Positive Composite Sample < 1% Chrysotile from 2nd Floor at Room 212. All Other
Samples were None Detected. Recommend
Bulk Sample Individual Walls Prior to
Disturbance.
All visible Pipe Fittings are fiberglass-
Assumed ACM
Assumed ACM Until Tested
Sampled 10/15/19
Note: Building Was Renovated in Mid 1990's. Visible TSI was probably removed at that time. Not All ACM was removed. Floor Tiles & Mastics should be assumed ACM unless tested when carpet is to be removed. The exception being the non-asbestos mastic under HA A15-004.
ASBESTOS RE-INSEPCTION
3 Broken Tiles in Room SP002
(PPE Storage)
Majority is under carpet. 1st Floor Under
Carpet In Various Areas. Rooms 208 and
209 abated January 2012 (Some mastic remains in concrete pores in these rooms).
Has been removed from All 3rd Floor as of 12/5/2022.
All visible Pipe Runs are fiberglass-
Assumed ACM
BUILDING 15
Comments/Reccomendations
CHARLES GEORGE VAMC
ASHEVILLE, NORTH CAROLINA
SURF = Surfacing F= Friable SF = Square Feet G = Good LPD = Low Potential for Disturbance
MISC = Miscellaneous Material NF = Non-friable LF = Linear Feet D = Damaged PD = Potential for Disturbance
TSI = Thermal System Insulation CF = Cubic Feet SD = Significantly Damaged PSD = Potential of Significant Disturbance
NOTE : Quantities Listed are for inspection purposes only. Quantities should be field verified for all other uses.
AEC Project #24251
December 2024