Asbestos Bulk Sampling Report.pdf

PDF 604 KB Posted

Attached to
Y1AZ--Renovate Bldg. 15, 2nd Floor
Solicitation number
36C24625B0007
Issued by

About this file

This is a limited asbestos bulk sampling and XRF paint testing report dated January 30, 2021, conducted by Affinity Energy & Environmental Engineers for Building #15's 3rd Floor East Renovation Area at the Charles George VAMC in Asheville, NC.

The report details results from two types of testing: 1) Four bulk samples of tan/gray sprayed-on fireproofing from the concrete ceiling deck were analyzed using PLM techniques, with no asbestos detected in any samples. 2) XRF paint testing was conducted on plaster walls and ceilings in Room 300, Room 301 closet, and the main corridor, with all ten test locations showing lead content well below the federal regulatory level of 1.0 mg/cm². The testing was conducted prior to renovation work, with samples analyzed by SAI laboratory in Greensboro, NC. The report includes complete laboratory analysis data sheets showing detailed sample compositions, with the fireproofing samples consisting of 98% mineral wool and 2% other materials.

View the file

Other files

File Type Posted
36C24625B0007 Amendment 0011.pdf PDF
Block 14 Cont. - VAAR 852.222-71.pdf PDF
36C24625B0007 Amendment 0010.pdf PDF
Attachment IV - Drawings Set rev w Changes Summary.pdf PDF
Attachment III - Additional Questions and Responses rev.pdf PDF
Block 14 Continuation I.pdf PDF
Block 14 Continuation II.pdf PDF
Attachment I - Questions and Responses rev.pdf PDF
36C24625B0007 0009.docx DOCX document
Attachment II - Follow-On Questions and Responses rev.pdf PDF
36C24625B0007 Amendment 0008 - Renovate Bldg 15 2nd Floor.pdf PDF
Asbestos Abatement Report 12.06.2024.pdf PDF
36C24625B0007 0007.docx DOCX document
36C24625B0007 0006.pdf PDF
36C24625B0007 0005.docx DOCX document
Follow-On Questions.docx DOCX document
01 91 00 GENERAL COMMISSIONING REQUIREMENTS - REV 1.pdf PDF
Specifications - REV 4.pdf PDF
Dwgs C-AJ-0070 - Floor Infill Details.pdf PDF
VAMC Build 15 3rd FL ASB-LBP Report.pdf PDF
Drawings - REV 3.pdf PDF
SBA DSBS Profile Instructions.pdf PDF
Drawing Changes Identified REV 3.pdf PDF
Additional Questions and Responses.pdf PDF
36C24625B0007 0004.docx DOCX document
Map for Dumpster and Temp Power Hook Up.pdf PDF
Asbestos Inspection Report.pdf PDF
36C24625B0007 0003.docx DOCX document
RFI Questions and Responses - Renovate B15 2nd Floor 2.20.2025.pdf PDF
Site Visit Sign-in Sheets - B15.pdf PDF
36C24625B0007 0002.docx DOCX document
36C24625B0007 0001.docx DOCX document
Map of Hospital - Path to B15.pdf PDF
NC Wage Determination 1.03.2025.pdf PDF
Specifications - Final.pdf PDF
36C24625B0007_1.docx DOCX document
Bid Item Cost Breakdown.xlsx XLSX spreadsheet
SOW - 637-20-103.pdf PDF
Drawings - Final.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Affinity Energy & Environmental Engineers, PA P.O. Box 2261

Asheville, NC 28802

Tele: 828-393-8182

January 30, 2021

Mr. Michael Bruno

Charles George VAMC

1100 Tunnel Road

Asheville, NC 28805-2087

RE: Limited Asbestos Bulk Sampling & XRF Paint Testing

Building #15 – 3rd Floor East Renovation Area

Charles George VAMC - Asheville, North Carolina

Affinity Project #13031IN

Mr. Bruno:

On January 28th, 2021, Affinity performed limited bulk sampling of suspect asbestos-containing sprayed-on fireproofing located on the concrete ceiling deck of the 3rd Floor East Renovation Area of Building #15 located on the VAMC campus in Asheville, NC. The sampling was conducted prior to disturbance of the fireproofing.

The samples were sent VIA Fed-ex to SAI in Greensboro, NC to be analyzed for asbestos content using PLM techniques. Following are the results of the sampling.

Sample # Location Material Asbestos Content

FP-01-01 Building #15 - 3rd Floor East Tan/Gray Sprayed-on Fireproofing None Detected

FP-01-02 Building #15 - 3rd Floor East Tan/Gray Sprayed-on Fireproofing None Detected

FP-01-03 Building #15 - 3rd Floor East Tan/Gray Sprayed-on Fireproofing None Detected

FP-01-04 Building #15 - 3rd Floor East Tan/Gray Sprayed-on Fireproofing None Detected

No asbestos was detected in the fireproofing samples. Please find laboratory analysis data sheets attached.

XRF paint testing was also conducted on the plaster ceiling in the Main Corridor of the 3rd Floor East

Renovation Area Following are the results of the XRF paint testing.

Index Time Color Substrate Component Location PbC mg/cm² Results

1 1/28/2021 14:19 WHITE PLASTER WALL 301 CLOSET 0.04 Negative

2 1/28/2021 14:20 WHITE PLASTER WALL 301 CLOSET 0.21 Negative

3 1/28/2021 14:20 WHITE PLASTER WALL 301 CLOSET 0.03 Negative

4 1/28/2021 14:21 WHITE PLASTER WALL 301 CLOSET 0.12 Negative

5 1/28/2021 14:22 WHITE PLASTER CEILING CORRIDOR AT 301 0.05 Negative

6 1/28/2021 14:22 WHITE PLASTER CEILING CORRIDOR AT 301 0.27 Negative

7 1/28/2021 14:22 WHITE PLASTER CEILING CORRIDOR AT 301 0.15 Negative

8 1/28/2021 14:23 WHITE PLASTER CEILING CORRIDOR AT 301 0.17 Negative

9 1/28/2021 14:25 WHITE PLASTER WALL ROOM 300 0 Negative

10 1/28/2021 14:25 WHITE PLASTER WALL ROOM 300 0 Negative

The plaster corridor ceiling does not contain lead in paint above the federal regulatory level of 1.0 mg/cm2.

Thank you for the opportunity to be of service. If you have any questions or require additional information, please do not hesitate to call.

Sincerely, Affinity Energy & Environmental Engineers, PA

Mike G. Cook, CIEC

NC Asbestos Inspector #12016

Attachment

Affinity Project #13031IN Limited Asbestos Bulk/XRF Paint Sampling Report

January 30, 2021 Building #15 – 3rd Floor East Renovation Area Charles George VAMC

Asheville, NC

LABORATORY ANALYSIS

DATA SHEETS

Bulk Asbestos Analysis By Polarized Light Microscopy

EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E

VAMC Building #15Project:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Mike CookAttn:Customer: Affinity Energy & Environmental Engineers PO Box 2261 Asheville, NC 28802

Analysis ID: 71958850_PLM

Date Reported: 1/29/2021

Date Received: 1/29/2021

Lab Order ID: 71958850

None Detected

FP-01-01

3rd Floor East Gray Fibrous Heterogeneous

Teased71958850PLM_1

Mineral Wool Other 98% 2%

None Detected

FP-01-02

3rd Floor East Gray Fibrous Heterogeneous

Teased71958850PLM_2

Mineral Wool Other 98% 2%

None Detected

FP-01-03

3rd Floor East Gray Fibrous Heterogeneous

Teased71958850PLM_3

Mineral Wool Other 98% 2%

None Detected

FP-01-04

3rd Floor East Gray Fibrous Heterogeneous

Teased71958850PLM_4

Mineral Wool Other 98% 2%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Jalen Moore (4)

P-F-002 r15 1/16/2021

•· Scientific Analytical Institute 4604· Dundas Dr. Greensboro; NC 27407

Phone: 336.292.3888 Fax: 336.292.3313 www.sailab.com lab@sailab.com

Company Co.ntact Information Company: Affinity Energy & Environmental Engineers, PA Contact: Mike Cook

Address: P.O. Box 2261 Phone 0: (828) 508-3812

Ashville. NC 28802 Fax0:

Email Iii: mcook@affen-v.com

.Billin2/Invoice Information Turn Around Times Company~ SAME 90 Min. • 48 Hours • - I - Contact: j Hours LJ IL. -ttours LJ

Address: 6 Hours •~ 96 Hours • 12 Hours ~ 120Hours D 24 Hours • l44+Hours 0

I PO Number:

. Project Name/Number: \feimc ~,~l~\., 1\= ls

Lab Use Only\\nV\(7~/) Lab Order [D: \,. v \:Jl) D\l _ Client Code: ______ _

PLM EPA 600/R-93/l 16 (PLM)

Positive stop • PLM Point Count 400 (PT4) 0 PLM Point Count 1000 (PTM) 0 PCM N!OSH 7400-A Rules (PCM) 0 B Rules (PCB) 0 TWA (PT A) 0

TEM AHERA (AHE) 0

u .:,1s1 L<:V<,J H \L-HJ LJ

TEM NIOSH 7402 (TN!) •

TEM Bulk Qualitative (TBL) • TEM Bulk Chatfield (TBS) • TEM Bulk Quantitative (TBQ). • TEM Wipe ASTM D6480-05 • TEM Microvac ASTM D5755-02 • TEM Water EPA 100.2 (TWI) • Other: •

. Satnple ID # Description/Location Volume/Area • Comments

:3rJ F

Total # of Samples_£

Dateffime Date/Time

Page -dm ~~.21L21

Affinity Project #13031IN
LABORATORY ANALYSIS
DATA SHEETS