Canandaigua VAMC Boiler Plant - Final RBM Survey.pdf
PDF 3 MB Posted
- Attached to
- Z1DA--528A5-20-502 BOILER REPLACEMENT PROJECT
- Solicitation number
- 36C24224R0032
About this file
This document is a Regulated Building Materials Survey Report for the Canandaigua VA Medical Center Boiler Plant Replacement project, VA Project No. 528A5-20-502. The report details the findings of asbestos, lead, and PCB sampling conducted as part of this renovation project. Key findings include the identification of asbestos-containing materials (ACMs) in boiler insulation, pipe insulation, window glazing, pipe sealant, and other building materials. Estimated quantities of the identified ACMs are provided. The report also summarizes limited lead paint and PCB sampling results. Conclusions and recommendations regarding proper abatement and disposal of the identified regulated materials are included. This information will be relevant for the construction contractor executing the boiler replacement work at the facility.
The related federal contract opportunity is a solicitation for the Boiler Replacement Project at the Canandaigua VAMC, Solicitation #36C24224R0032. This is a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside, with a proposal due date of June 28, 2024. The scope includes replacing the boiler plant at the medical center. Three previous similar contracts within the past 10 years must be provided for evaluation.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
p
REGULATED BUILDING MATERIALS
SURVEY REPORT
Building 12 - Boiler Plant
A/E Services to Design Boiler Replacement VA Project No. 528A5-20-502 Canandaigua VA Medical Center 400 Fort Hill Avenue Canandaigua , New York 14424
Mabbett Project No. R2021068.000
March 8, 2022
Prepared For:
Encorus Group 23 Mechanic Street Springville, NY 14141
Mabbett & Associates, Inc. www.mabbett.com 105 Central Street, Suite 4100 Stoneham, MA 02180-1260 T. 781-275-6050 F: 781-954-5155 Massachusetts | Virginia | Rhode Island | New York
© 2022, Mabbett & Associates, Inc.
REGULATED BUILDING MATERIALS SURVEY REPORT
Design Boiler Replacement | Canandaigua VAMC
© 2022, Mabbett & Associates, Inc. Page i March 8, 2022 Project No..R2021068.000 Canandaigua VAMC Boiler Plant - Final
ACKNOWLEDGEMENT
This Regulated Building Materials Survey Report has been prepared by Mabbett & Associates, Inc. (Mabbett®) for the A/E Services to Design Boiler Replacement at the Canandaigua Veterans Affairs Medical Center located in Canandaigua , New York, VA Project No. 528A5-20-502. The information presented herein is based on the facts and information conveyed to or received by Mabbett during the preparation of this report. If any of the information provided to Mabbett that was used in preparing this report is incorrect, incomplete, or subject to change, Mabbett would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to Mabbett as of the date of this report and considered applicable to this report.
The attached Regulated Building Materials Survey Report was prepared by Mr. Kevin M. Donovan, Senior Environmental, Health & Safety Specialist of Mabbett & Associates, Inc.
This report has been reviewed and approved by:
Michael F. Delaney Director, Building Sciences Group
MFD:KMD/rsg
© 2022, Mabbett & Associates, Inc. Page ii March 8, 2022 Project No..R2021.068.000 Canandaigua VAMC Boiler Plant - Final
TABLE OF CONTENTS
SECTION PAGE
1.0 INTRODUCTION
2.0 ASBESTOS SURVEY
2.1 Sampling Methodology
2.2 Analytical Methodology
2.3 Materials with Trace Amounts of Asbestos
2.4 Summary of Asbestos Containing Materials Findings
3.0 LEAD CONTAINING PAINT SURVEY
4.0 BUILDING MATERIAL PCB SAMPLING
5.0 CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos
5.2 Lead Containing Paint
5.3 PCB Containing Material
6.0 LIMITATIONS
TABLES
Table 1 – Summary of ACM Table 2 – Summary of Lead Paint Chip Analytical Results Table 3 – Summary of PCB Analytical Results
FIGURES
RBM-1 – Asbestos Sampling Location Plan RBM-2 – Lead and PCB Sampling Location Plan
APPENDICES
Appendix A – Summary of Asbestos Sampling Results Appendix B – PLM & TEM Laboratory Reports and Chains of Custody Appendix C – Lead Paint Chip Laboratory Report and Chain of Custody Appendix D – PCB Laboratory Report and Chain of Custody Appendix E – Mabbett & Associates, Inc. Report Dated November 16, 2010
© 2022, Mabbett & Associates, Inc. Page 1 March 8, 2022
1.0 INTRODUCTION
Mabbett and Associates, Inc. (Mabbett®) performed a survey for Regulated Building Materials (RBM) as part of the Renovation of the Boiler Plant project at the Canandaigua Veterans Affairs Medical Center (VAMC) located in Canandaigua , New York, VA Project No. 528A5-20-502. Site survey work was performed on January 18, 2022, by appropriately credentialed regulated building materials inspector, and consisted of the following activities:
A review of the existing facility regulated building material reports and renovation history;
An Asbestos Containing Material (ACM) survey of suspect materials (Analysis by Polarized Light Microscopy
[PLM] and Transmission Electron Microscopy [TEM]);
Limited Lead Containing Paint (LCP) sampling (Analysis by atomic absorption [AA]); and Limited sampling of building materials for PCBs (Polychlorinated Biphenyl) (Extraction Method EPA 3540C).
© 2022, Mabbett & Associates, Inc. Page 2 March 8, 2022
2.0 ASBESTOS SURVEY
A visual screening inspection was conducted by a New York State licensed asbestos inspector to identify locations of suspect ACM and conceptualize the sampling program. Only areas that were accessible during the field work phase were inspected, with reasonable efforts made during the initial field survey work to access areas as necessary to complete the asbestos survey and sampling program.
Prior to the execution of this survey, existing building plans for the project locations were examined and VA engineering personnel interviewed to discern the age and condition of existing materials, as well as the renovation history of the area being surveyed. Due to inclement weather at the time of the survey, the roof was not inspected and no samples collected. Roofing materials should be assumed to contain asbestos until sampled and determined to be non-ACM.
2.1 Sampling Methodology
Site inspection work was performed on January 18, 2022 by New York State licensed asbestos inspector Mr. Kevin M. Donovan (#09-07125). Bulk asbestos samples were collected using EPA National Emissions Standards for Hazardous Air Pollutants (NESHAP), 40 CFR Part 763, and Asbestos Hazard Emergency Response Act (AHERA) protocols. The inspection was limited to areas that may be impacted by the proposed renovation project. Bulk suspect ACM sampling was generally conducted according to the following sampling protocol:
Friable surfacing material:
• At least three bulk samples shall be collected from each homogeneous area that is 1,000 ft2 or less.
• At least five bulk samples shall be collected from each homogeneous area that is greater than
1,000 ft2 but less than or equal to 5,000 ft2.
• At least seven bulk samples shall be collected from each homogeneous area that is greater than
5,000 ft2.
Thermal system insulation:
• At least three bulk samples shall be collected from each homogeneous area of thermal system insulation.
• At least one bulk sample shall be collected from each homogeneous area of patched area of thermal system insulation.
• Sufficient samples shall be collected from elbows and fittings to determine if they contain ACM.
• Bulk samples shall not be collected from any homogeneous area where the state licensed asbestos inspector determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACM.
Miscellaneous material:
• At least two bulk sample shall be collected from each homogeneous area that is less than
100 ft2.
• At least three bulk samples shall be collected from each homogeneous area that is greater than
100 ft2.
Areas that were inaccessible, or where the survey was limited to visual observation only, are identified below:
Within walls Within fire doors Enclosed pipe/duct chases
© 2022, Mabbett & Associates, Inc. Page 3 March 8, 2022
Inside mechanical equipment/ductwork Inside the boilers Above fixed drywall or plaster ceilings Electrical equipment
2.2 Analytical Methodology
The collected bulk samples were submitted under chain of custody (COC) procedures to Scientific Analytical Institute (SAI) of Greensboro, North Carolina for PLM and TEM analysis as required by the New York State Environmental Laboratory Approval Program (ELAP). PLM analysis of friable materials was performed using NYS ELAP Method 198.1. Samples of Non-Friable Organically Bound (NOB) materials were analyzed by PLM (NYS ELAP Method 198.6) subsequent to matrix reduction. NOB samples that were identified as non-ACM by PLM methods were re-analyzed by TEM (NYS ELAP Method 198.4) for confirmation purposes. SAI is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program
(NVLAP).
Bulk sample results from this inspection are summarized in Table 1, Summary of Asbestos Sampling Results. The EPA, Occupational Safety and Health Administration (OSHA), and Part 56 of Title 12 of the Official Compilation of Codes, Rules and Regulations of the State of New York (12 NYCRR Part 56) defines any material that contains greater than one percent (>1%) asbestos as being an ACM. As such, the analytical laboratory identified bulk samples as positive for asbestos that met the regulatory criteria of greater than one percent (>1%) asbestos.
Laboratory reports and COC documentation are provided in Appendix A of this report.
2.3 Materials with Trace Amounts of Asbestos
Where laboratory analysis identified trace amounts of asbestos, that is, materials with less than 1% asbestos, the material sampled has generally not been listed as ACM in this report. This determination is consistent with New York State and US EPA definitions of ACM. Federal OSHA regulations may require additional evaluation of materials containing trace amounts of asbestos prior to activities which could cause release of fibers into the air.
Evaluations of materials with trace amounts of asbestos and of the fiber release potential of work practices have not been addressed in this report.
2.4 Summary of Asbestos Containing Materials Findings
Mabbett also collected eighteen (18)) samples of materials that were previously sampled in the Mabbett report dated November 16, 2010, attached as Appendix E, to confirm previous results. Mabbett also identified ten (10) additional areas of homogenous materials and collected thirty (30) representative bulk ACM samples. Asbestos sampling locations and results are identified on Figures RBM-1 and RBM-2. Forty-eight (48) samples collected were analyzed by PLM and TEM (friable and NOB). The laboratory-reported analytical data, including available historical data utilized for this survey, indicated that six (6) of the materials sampled as part of this survey contained 1% or greater of asbestos and are classified as ACM. Previously identified pipe insulation, pipe fitting insulation, boiler insulation, breeching insulation, tank insulation, window glazing, pipe sealant, sheet flooring and associated adhesive and roof drain materials were determined to be ACM or PACM. Estimated quantities of materials identified as ACM and PACM are presented in Table 1 below:
© 2022, Mabbett & Associates, Inc. Page 4 March 8, 2022
Table 1 Summary of ACM
Design Boiler Replacement Canandaigua VA Medical Center
Location Description of Material
Percent and Type of Asbestos
Estimated Quantity Amount Units
Lower Level - East of Boiler #2 Black Sink Coat 1.2% Chrysotile 1 Each Lower Level - Boilers #1, 2 & 3 Boiler Insulation 18.2 % Chrysotile * 2,600 Square Feet
Lower Level - Boiler Room South High Pressure Steam Pipe Insulation
<1% Chrysotile & 28.6% Amosite * 25 Linear Feet
Lower Level - Boiler Room East Pipe Sealant 6% Chrysotile * 1 Square Foot Upper and Lower Levels - Boiler Room
Interior and Exterior Window Glazing 3% Chrysotile 2,000 Linear Feet
Upper Level - Office and Adjacent Tan, Brown & Green Sheet Flooring and Adhesive
8.5% Chrysotile * 180 Square Feet
Upper Level - Boiler Room Roof Drain Mastic 4.5% Chrysotile * 10 Square Feet
Upper and Lower Levels - Boiler Room
4" to 12" Pipe Insulation PACM * 250 Linear Feet
Boilers #1, 2 & 3 36" Breeching Insulation PACM * 96 Linear Feet
Upper Level - Boiler Room 4' Tank Insulation PACM * 100 Square Feet Lower Level - Boiler Room 5' Tank Insulation PACM * 190 Square Feet Lower Level - Boiler Room 6' Tank Insulation PACM * 282 Square Feet Notes:
* = Previously Identified ACM & PACM PACM = Presumed Asbestos Containing Material
© 2022, Mabbett & Associates, Inc. Page 5 March 8, 2022
3.0 LEAD CONTAINING PAINT SURVEY
The limited LCP survey included the collection of paint chips from painted surfaces and systems in the areas surveyed that may be impacted by the planned renovation. Eight-teen (18) samples of different homogenous areas of paint were collected during this survey. Paint chip samples were submitted under standard COC procedures to SAI. Analysis was conducted using AA EPA method SW846-3050B/6010C/700B.
The results of the limited LCP sampling are summarized in Table 2, with laboratory reports provided in Appendix C.
Table 2 Summary of Lead Paint Chip Analytical Results
Design Boiler Replacement Canandaigua VA Medical Center
Sample # Location Substrate and Component Color Result (mg/Kg)
Pb-01 Lower Level - SW Concrete Floor Gray 0.017 Pb-02 Lower Level - South Concrete Floor Gray <0.0038 Pb-03 Lower Level - Entry (SE) Metal Door Frame Brown <0.0064 Pb-04 Lower Level - SW Ceramic Floor Tile Red 0.034 Pb-05 Lower Level - SE Concrete Wall White 0.031 Pb-06 Lower Level - Boiler #2 (East) Metal Boiler Gray 0.02 Pb-07 Lower Level - Boiler #2 (East) Metal Column Gray 7.9 Pb-08 Lower Level - Boiler #3 (NW) Metal Gas Pipe Green 0.036 Pb-09 Lower Level - South wall Metal Column Gray 12 Pb-10 Lower Level - Boiler #3 (East) Concrete Block Wall Yellow 0.006 Pb-11 Lower Level - Outside Bathroom Metal Railing Yellow <0.0075 Pb-12 Lower Level - Bathroom (North) Ceramic Wall Tile Tan <0.0033 Pb-13 Lower Level - Bathroom (North) Plaster Wall Blue 0.0057 Pb-14 Upper Level - South Metal Tank Support Black 0.83 Pb-15 Upper Level - South Concrete Floor Gray 0.74 Pb-16 Upper Level - South Metal Railing Yellow 7 Pb-17 Upper Level - SW Brick wall White 0.034 Pb-18 Exterior - SW Ramp Stone Window Sill Tan 0.1
© 2022, Mabbett & Associates, Inc. Page 6 March 8, 2022
4.0 BUILDING MATERIAL PCB SAMPLING
As part of this regulated building materials survey, Mabbett conducted sampling of suspect building materials for PCB. Mabbett sampled three (3) homogenous areas of suspect PCB-containing materials and submitted them under standard COC procedures to Alpha Analytical of Westborough, Massachusetts. Analysis was conducted using EPA Method SW-846 8082A. A copy of the lab report detailing the findings of this sampling is provided in Appendix D. Results of this PCB sampling are summarized below in Table 3.
Table 3 Summary of PCB Analytical Results
Design Boiler Replacement Canandaigua VA Medical Center
Sample # Location Material Result (mg/Kg)
PCB-01 Lower Level - SE Interior Window Glazing 365 PCB-02 Lower Level - SE Interior Window Frame Filler 834 PCB-03 Exterior - at Ramp (SE) Exterior Window Frame Caulk 2.72
Notes: mg/kg = Parts Per Million (PPM)
© 2022, Mabbett & Associates, Inc. Page 7 March 8, 2022
5.0 CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos
Identified ACM must be abated and properly disposed of prior to disturbance by state licensed and properly trained contractors. All abatement must be performed in accordance with federal, state and local requirements.
Any suspect materials encountered during demolition or renovation activities that were not identified in this report as being non-ACM, should be assumed to be ACM unless sample results prove otherwise. Suspect ACM that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, should be assumed to contain asbestos if discovered during any demolition or renovation process or until otherwise verified.
5.2 Lead Containing Paint
The purpose of the limited LCP survey was to identify similar areas of LCP. During the on-site survey, representative samples of similar areas of interior building coatings were collected and analyzed for lead content.
The regulations addressing LCP in non-residential buildings are focused on occupational exposures involved with paint-disturbing activities and related waste-disposal activities.
Occupational exposure to lead during construction is regulated by OSHA regulation 29 CFR 1926.62 “Lead in Construction,” as well as other applicable state and local regulations. These regulations involve air monitoring to determine worker exposure levels when disturbing paint containing measurable levels of lead. This LCP survey cannot determine a safe level of lead for the purpose of paint-disturbing activities. However, this report is intended to provide guidance as to the location of LCP so it can be controlled, abated, or disposed of properly during this project’s construction related activities. Information gathered during this LCP survey should be used to determine where worker exposures to airborne lead may occur. Additionally, this information should also be used to assess the potential for exposure to workers, and for determining appropriate controls necessary to limit his or her health risks during this project.
A concentration of lead greater than or equal to 0.5 mg/Kg percent by weight or 1.0 mg/cm2 exceeds EPA and HUD residential standards is considered an indicator of risk. Representative samples of LCP waste to be generated during building renovation, or following demolition but prior to disposal, should be collected and analyzed using toxicity characteristic leaching procedure (TCLP) in accordance with 40 CFR Part 261. Management and disposal of lead containing waste must be done in accordance with all applicable local, state, and federal regulations.
OSHA regulations may require certain procedures for any paint that contains lead, even if it is below these levels.
All LCP identified, regardless of the lead content, should either be sampled and analyzed by TCLP and then handled/disposed of accordingly, or segregated from other large-scale debris and then managed as hazardous waste in accordance with federal, state, and local hazardous waste disposal regulations.
5.3 PCB Containing Material
The suspect PCB caulking material sampling results determined window glazing and caulking materials contain PCBs above regulatory levels. Materials containing ≥ 50 ppm PCB are considered a TSCA regulated PCB Bulk Product Waste. These materials are required to be removed and managed at an appropriate waste management facility. Surrounding media can either be assumed to be PCB impacted at ≥ 1 ppm and therefore PCB Remediation Waste or would need to be evaluated to determine actual PCB content. If adjoining building materials are determined to be PCB Remediation Waste, they can be removed or managed in place. Depending upon approach taken, EPA approval may be required.
© 2022, Mabbett & Associates, Inc. Page 8 March 8, 2022
6.0 LIMITATIONS
This survey report is the result of a diligent and thorough inspection for regulated building materials of the designated areas and materials that may be impacted by the renovation project. Inaccessible areas were not included in this survey. Although a comprehensive inspection was performed, Mabbett does not claim to have identified all hazardous materials that could be present in the facility (for example, materials potentially located within the inaccessible areas). Mabbett has conducted this assessment with reasonable care and has performed this project in accordance with generally accepted industry standards. There can be no assurances, and Mabbett makes no assurances, that the information, research, and technology used to prepare this report may not change in the future, thus affecting the results reported herein.
© 2022, Mabbett & Associates, Inc. FIGURES March 8, 2022 Project No. R20210068.000 Canandaigua VAMC Boiler Plant - Final
FIGURES
DN
DN
UP
NO ACM EXPECTED
IN THIS AREA
NO ACM EXPECTED
IN THIS AREA
AA-1 AA-1
AA-1
AA-1
AA-1
AA-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ASBESTOS SAMPLE LOCATIONS RBM SURVEY
DESIGN BOILER REPLACEMENT -
CANANDAIGUA VAMC
400 FORT HILL AVENUE
CANANDAIGUA, NY 14424
FEBRUARY 2022
RBM-1
BLDG 12
528A5-20-502
MFD ECG
B12
B11
PARKING
N
B12
B11
PARKING
N
SCALE: 1/8" = 1'-0"
LOWER LEVEL PLAN1 SCALE: 1/8" = 1'-0"
UPPER LEVEL PLAN2
02A*
02A**
02A
02A
LEGEND
APPROXIMATE ASBESTOS SAMPLE LOCATION
NO ASBESTOS DETECTED (NAD)
SAMPLE POSITIVE FOR ASBESTOS <1%
SAMPLE POSITIVE FOR ASBESTOS >1%.
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA. 02180
T. 781-275-6050
GENERAL SURVEY NOTES
1. DRAWINGS DO NOT CLAIM TO IDENTIFY ALL THE ASBESTOS CONTAINING MATERIAL
(ACM) PRESENT IN THE BUILDING AND SHOULD NOT BE THE SOLE BASIS FOR
IDENTIFYING ACM FOR FUTURE RENOVATION OR DEMOLITION PROJECTS, ABATEMENT
SPECIFICATIONS, ETC. MABBETTS'S SURVEY WAS PERFORMED WITH LIMITATIONS
INHERENT TO NON-DESTRUCTIVE VISUAL INSPECTIONS. ANY SUSPECT MATERIAL
ENCOUNTERED DURING RENOVATION/DEMOLITION THAT IS NOT IDENTIFIED AS BEING
NON-ACM SHOULD BE ASSUMED TO BE ACM UNLESS SAMPLE RESULTS PROVE
OTHERWISE.
2. BASE PLAN OBTAINED FROM DRAWING H-101 HAZARDOUS ABATEMENT PLAN OF
PROJECT 528A5-20-502, PREPARED BY ENCORUS GROUP, INC.
3. SURVEY COMPLETED ON 18 JANUARY 2022 BY MABBETT & ASSOCIATES, INC.
DN
UP
NO ACM EXPECTED
IN THIS AREA
NO ACM EXPECTED
IN THIS AREA
AA-1 AA-1
AA-1
AA-1
AA-1
AA-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
LEAD & PCBs SAMPLE LOCATIONS RBM SURVEY DESIGN BOILER REPLACEMENT -
CANANDAIGUA VAMC
400 FORT HILL AVENUE
CANANDAIGUA, NY 14424
FEBRUARY 2022
RBM-2
BLDG 12
528A5-20-502
MFD ECG
GENERAL SURVEY NOTES
1. DRAWINGS DO NOT CLAIM TO IDENTIFY ALL THE LEAD AND PCB CONTAINING MATERIAL
PRESENT IN THE BUILDING AND SHOULD NOT BE THE SOLE BASIS FOR IDENTIFYING
ACM FOR FUTURE RENOVATION OR DEMOLITION PROJECTS, ABATEMENT
SPECIFICATIONS, ETC. MABBETTS'S SURVEY WAS PERFORMED WITH LIMITATIONS
INHERENT TO NON-DESTRUCTIVE VISUAL INSPECTIONS. ANY SUSPECT MATERIAL
ENCOUNTERED DURING RENOVATION/DEMOLITION THAT IS NOT IDENTIFIED AS BEING
NON-ACM SHOULD BE ASSUMED TO BE ACM UNLESS SAMPLE RESULTS PROVE
OTHERWISE.
2. BASE PLAN OBTAINED FROM DRAWING H-101 HAZARDOUS ABATEMENT PLAN OF
PROJECT 528A5-20-502, PREPARED BY ENCORUS GROUP, INC.
3. SURVEY COMPLETED ON 18 JANUARY 2022 BY MABBETT & ASSOCIATES, INC.
B12
B11
PARKING
N
B12
B11
PARKING
N
SCALE: 1/8" = 1'-0"
LOWER LEVEL PLAN1 SCALE: 1/8" = 1'-0"
UPPER LEVEL PLAN2
Pb-01
LEGEND
APPROXIMATE LEAD SAMPLE LOCATION
APPROXIMATE PCBs SAMPLE LOCATION
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA. 02180
T. 781-275-6050
PCB-01
© 2022, Mabbett & Associates, Inc. APPENDIX A March 8, 2020 Project No. R20210068.000
APPENDIX A
Summary of Asbestos Sampling Results
© 2022, Mabbett & Associates, Inc. Appendix A Page 1 of 2 March 8, 2020
Appendix A
Summary of Asbestos Sampling Results Design Boiler Replacement
Canandaigua VA Medical Center
Sample No. Sample Location Description of Material
Percent and Type of Asbestos (by PLM &
TEM Analysis)
01A Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 01B Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 01C Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 02A Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 02B Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 02C Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 03A Lower Level - SW 6" Red Ceramic Floor Tile (Grout) NAD (PLM) 03B Lower Level - Boiler #3 (W) 6" Red Ceramic Floor Tile (Grout) NAD (PLM) 03C Lower Level - Boiler #2 6" Red Ceramic Floor Tile (Grout) NAD (PLM)
04A Lower Level - SW 6" Red Ceramic Floor Tile (Adhesive)
NAD (PLM) & <1%
Chrysotile (TEM)
04B Lower Level - Boiler #3 (W) 6" Red Ceramic Floor Tile (Adhesive)
NAD (PLM) & <1%
Chrysotile (TEM)
04C Lower Level - Boiler #2 6" Red Ceramic Floor Tile (Adhesive)
NAD (PLM) & <1%
Chrysotile (TEM)
05A Lower Level - Bathroom (NE) Joint Compound NAD (PLM) 05B Lower Level - Office (NE) Joint Compound NAD (PLM) 05C Upper Level - Office (South) Joint Compound NAD (PLM) 06A Exterior - At Ramp (SE) Brick Mortar NAD (PLM) 06B Exterior - SE Corner Brick Mortar NAD (PLM) 06C Exterior - SW Corner Brick Mortar NAD (PLM) 07A Lower Level - SE Area Red Fire Stop NAD (PLM) & NAD (TEM)
07B Lower Level - SE Area Red Fire Stop NAD (PLM) & <1% Chrysotile (TEM)
07C Lower Level - SE Area Red Fire Stop NAD (PLM) & NAD (TEM) 08A Lower Level -Boiler #2 (East) Black Sink Coat 1.2% Chrysotile (PLM) 08B Lower Level -Boiler #2 (East) Black Sink Coat 1.2% Chrysotile (PLM)
08C Lower Level -Boiler #2 (East) Black Sink Coat 0.2% Chrysotile (PLM) & <1% Chrysotile (TEM)
9 Upper Level - Generator Room Spray-on Fire Proofing NAD (PLM)
10 Lower Level - Boiler Room (SE) Interior Window Glazing NAD (PLM) & 3% Chrysotile (TEM)
11 Exterior - (SE) Light Gray Expansion Caulk NAD (PLM) & NAD (TEM) 12 Exterior - (SE) Fibrous Expansion Material NAD (PLM)
© 2022, Mabbett & Associates, Inc. Appendix A Page 2 of 2 March 8, 2020
Appendix A Summary of Asbestos Sampling Results
Design Boiler Replacement Canandaigua VA Medical Center
Sample No. Sample Location Description of Material
Percent and Type of Asbestos (by PLM &
TEM Analysis)
13 Exterior - (SE) Light Gray Window Caulk NAD (PLM) & NAD (TEM) 14 Lower level - Bathroom Gypsum Wallboard NAD (PLM) 15 Lower level - Bathroom Wall Plaster (Base Coat) NAD (PLM) 16 Lower level - Bathroom Wall Plaster (Finish Coat) NAD (PLM) 17 Lower level - Bathroom 2' x 2' White Ceiling Tile (Smooth) NAD (PLM) 18 Upper Level - Office (South) 2' x 2' White Ceiling Tile (Fissured) NAD (PLM) 19 Lower Level - (NE) Interior Expansion Caulk NAD (PLM) & NAD (TEM) 20 Lower level - Bathroom 12" x 12" Blue Floor Tile NAD (PLM) & NAD (TEM) 21 Lower level - Bathroom 12" x 12" Blue Floor Tile Mastic NAD (PLM) & NAD (TEM) 22 Upper Level - Office (South) Cove Base Mastic NAD (PLM) & NAD (TEM) 24 Exterior - SW Area Door Caulk NAD (PLM) & NAD (TEM) 25 Exterior - SW Area Window Glazing 4% Chrysotile (PLM) 26 Exterior - SW Area Dark Gray Window Caulk NAD (PLM) & NAD (TEM) 27 Lower Level - Boiler Room (NW) Plaster Sealant NAD (PLM)
28A Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 28B Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 28C Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 29A Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM) 29B Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM) 29C Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM)
Notes:
NAD = No Asbestos Detected PLM = Polarized Light Microscopy Analysis TEM = Transmission Electron Microscopy Analysis
© 2022, Mabbett & Associates, Inc. APPENDIX B March 8, 2022
APPENDIX B
PLM and TEM Laboratory Reports and Chains of Custody
71984284Lab Order ID:
Canadaigua VAMC Boiler PlantProject:
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected 01A
4" ceramic wall tile (grout)-lower level bathroom
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_1
Other100.0
None Detected 01B
4" ceramic wall tile (grout)-lower level bathroom
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_2
Other100.0
None Detected 01C
4" ceramic wall tile (grout)-lower level bathroom
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_3
Other100.0
None Detected 02A
4" ceramic wall tile (adhesive)
- lower level bathroom
198.6 (NOB): Inconclusive - No asbestos detected
Cream Non Fibrous Homogeneous
Ashed, Crushed71984284PNY_4
Other100.0
None Detected 02B
4" ceramic wall tile (adhesive)
- lower level bathroom
198.6 (NOB): Inconclusive - No asbestos detected
Cream Non Fibrous Homogeneous
Ashed, Crushed71984284PNY_5
Other100.0
None Detected 02C
4" ceramic wall tile (adhesive)
- lower level bathroom
198.6 (NOB): Inconclusive - No asbestos detected
Cream Non Fibrous Homogeneous
Ashed, Crushed71984284PNY_6
Other100.0
None Detected 03A
6" red ceramic floor tile (grout) - lower level, (SW)
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_7
Other100.0
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Yanelis Delgado (49)
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected 03B
6" red ceramic floor tile (grout) - lower level, boiler #3 (W)
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_8
Other100.0
None Detected 03C
6" red ceramic floor tile (grout) - lower level, boiler #2
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_9
Other100.0
None Detected 04A
6" red ceramic floor tile (adhesive) - lower level, SW
198.6 (NOB): Inconclusive - No asbestos detected
Yellow Non Fibrous Homogeneous
Dissolved71984284PNY_10
Other100.0
None Detected 04B
6" red ceramic floor tile (adhesive) - lower level, boiler #3 (West)
198.6 (NOB): Inconclusive - No asbestos detected
Yellow Non Fibrous Homogeneous
Dissolved71984284PNY_11
Other100.0
None Detected 04C
6" red ceramic floor tile (adhesive) - lower level, boiler #32
198.6 (NOB): Inconclusive - No asbestos detected
Yellow Non Fibrous Homogeneous
Dissolved71984284PNY_12
Other100.0
None Detected 05A
Joint compound- lower level-bathroom (NE)
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_13
Other100.0
None Detected 05B
Joint compound- lower level-office (NE)
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_14
Other100.0
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected 05C
Joint compound- lower level-office (South)
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_15
Other100.0
None Detected 06A
Brick mortar- exterior- at ramp
(SE)
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_16
Other100.0
None Detected 06B
Brick mortar- exterior- at ramp SE corner
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_17
Other100.0
None Detected 06C
Brick mortar- exterior- at ramp SW corner
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_18
Other100.0
None Detected 07A
Red fire stop- lower level- SE area
198.6 (NOB): Inconclusive - No asbestos detected
Pink Non Fibrous Homogeneous
Ashed71984284PNY_19
Other100.0
None Detected 07B
Red fire stop- lower level- SE area
198.6 (NOB): Inconclusive - No asbestos detected
Pink Non Fibrous Homogeneous
Ashed71984284PNY_20
Other100.0
None Detected 07C
Red fire stop- lower level- SE area
198.6 (NOB): Inconclusive - No asbestos detected
Pink Non Fibrous Homogeneous
Ashed71984284PNY_21
Other100.0
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
08A Black sink coat- lower level-boiler #2 (East)
198.6 (NOB): Total asbestos 1.2
Black Non Fibrous Homogeneous
Dissolved71984284PNY_22
1.2% Chrysotile Other98.8%
08B Black sink coat- lower level-boiler #2 (East)
198.6 (NOB): Total asbestos 1.2
Black Non Fibrous Homogeneous
Dissolved71984284PNY_23
1.2% Chrysotile Other98.8%
08C Black sink coat- lower level-boiler #2 (East)
198.6 (NOB): Inconclusive-trace Chrysotile
Black Non Fibrous Homogeneous
Dissolved71984284PNY_24
0.2% Chrysotile Other99.8%
None Detected
Spray-on fire proofing- upper level- generator room
198.1
Cream Fibrous Homogeneous
Teased71984284PNY_25
80.0% Cellulose Other20.0%
Interior window glazing-lower level boiler room (SE)
198.1
Gray Non Fibrous Homogeneous
Crushed71984284PNY_26
3.0% Chrysotile Other97.0%
Light grey expansion caulk-exterior (SE)
198.6 (NOB): Inconclusive-trace Chrysotile
Gray Non Fibrous Homogeneous
Crushed71984284PNY_27
0.1% Chrysotile Other99.9%
None Detected
Fiborous expansion material-exterior (SE)
198.1
Gray, Black Non Fibrous Heterogeneous
Ashed71984284PNY_28
10.0% Cellulose Other90.0%
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected
Light grey window caulk-exterior (SE)
198.6 (NOB): Inconclusive - No asbestos detected
Gray Non Fibrous Homogeneous
Ashed71984284PNY_29
Other100.0
None Detected
Gypsum wallboard- lower level- bathroom
198.1
Grayish Non Fibrous Homogeneous
Crushed71984284PNY_30
10.0% Cellulose Other90.0%
None Detected
Wall plaster (base coat)- lower level- bathroom
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_31
Other100.0
None Detected
Wall plaster (finish coat)-lower level- bathroom
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_32
Other100.0
None Detected
2x2 white ceiling tile (smooth)
- lower level- bathroom
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_33
10.0% Cellulose Other90.0%
None Detected
2x2 white ceiling tile (finish)-upper level- office (South)
198.1
Gray Fibrous Homogeneous
Ashed71984284PNY_34
60.0% 10.0%
Mineral Wool Fiber Glass
Other30.0%
None Detected
Interior expansion caulk-lower level- NE
198.6 (NOB): Inconclusive - No asbestos detected
Grayish Non Fibrous Heterogeneous
Ashed71984284PNY_35
Other100.0
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected
12x12 blue floor tile- lower level bathroom
198.6 (NOB): Inconclusive - No asbestos detected
Blue Non Fibrous Homogeneous
Dissolved71984284PNY_36
Other100.0
None Detected
12x12 blue floor tile-mastic-lower level bathroom
198.6 (NOB): Inconclusive - No asbestos detected
Yellow Non Fibrous Homogeneous
Dissolved71984284PNY_37
Other100.0
None Detected
Cove base mastic- upper level office (South)
198.6 (NOB): Inconclusive - No asbestos detected
Cream Non Fibrous Homogeneous
Ashed71984284PNY_38
Other100.0
None Detected
198.6 (NOB): Inconclusive - No asbestos detected
Cream Non Fibrous Homogeneous
Ashed71984284PNY_39
Other100.0
None Detected 24 Door caulk- exterior- SW area
198.6 (NOB): Inconclusive - No asbestos detected
Gray Non Fibrous Homogeneous
Ashed71984284PNY_40
Other100.0
Window glazing- exterior- SEarea
198.1
White Non Fibrous Homogeneous
Crushed71984284PNY_41
4.0% Chrysotile Other96.0%
None Detected
Dark gray window caulk-exterior SW area
198.6 (NOB): Inconclusive - No asbestos detected
Gray Non Fibrous Homogeneous
Ashed71984284PNY_42
Other100.0
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
1/31/2022Date Received:
2/2/2022Date Reported:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Bulk Asbestos Analysis By Polarized Light Microscopy:
NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:
NY ELAP Method 198.4
Michael DelaneyAttn:
71984284_PNAnalysis ID:
Customer: Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
None Detected
Plaster sealant- lower level boiler room (NW)
198.1
Gray Non Fibrous Heterogeneous
Crushed71984284PNY_43
Other100.0
None Detected 28A
White fiberglass and sealant-upper level- North
198.6 (NOB): Inconclusive - No asbestos detected
White Non Fibrous Homogeneous
Ashed71984284PNY_44
Other100.0
None Detected 28B
White fiberglass and sealant-upper level- North
198.6 (NOB): Inconclusive - No asbestos detected
White Non Fibrous Homogeneous
Ashed71984284PNY_45
Other100.0
None Detected 28C
White fiberglass and sealant-upper level- North
198.6 (NOB): Inconclusive - No asbestos detected
White Non Fibrous Homogeneous
Ashed71984284PNY_46
Other100.0
None Detected 29A
Generator exhaust insulation-lower level, tool room
198.1
Cream Non Fibrous Heterogeneous
Dissolved71984284PNY_47
10.0% Cellulose Other90.0%
None Detected 29B
Generator exhaust insulation-lower level, tool room
198.1
Cream Non Fibrous Heterogeneous
Dissolved71984284PNY_48
10.0% Cellulose Other90.0%
None Detected 29C
Generator exhaust insulation-lower level, tool room
198.1
Cream Non Fibrous Heterogeneous
Dissolved71984284PNY_49
10.0% Cellulose Other90.0%
Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.
Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.
Approved SignatoryAnalyst
/QPi Scientific Analytical Institute 4604 DundasiJr~ Greensboro, NC 27407
Phone: 336~292~3888 Fax: 336.292.331.3 www.sailab.com lab@sailab.com
Contact:
OJ.-i~O EmaH'gj:
L.ab Use Only Lab. Order ID: J l ~ Cfi:J.o 65"
· Client Code: . ----',---'----'-
Asbestos Test :Types . PLM EPA 600/R-93/116 (PLM) jg] Positive stop • PLM Point Count 400 (PT4) • PLM Point Coun:t 1000 (PTM) .· • .
PCM NIOSH 7400~A Rules (PCM) • Billin2/Invoice Information Turn Around Times B Rules (PCB) 0 TWA(PTA)• Company:
Contact:
Address:
PO Number:
Project Name/Number:
· Sample ID#
OIA.
. J l/ I' (...QV""v,,i~ ~
90 Min. D I 48 Hours D cc
• . TEM AHERA (AHE)
3 Hours D I 72 Hours · .6a' TEM Level II (LII) • 6 Hours D I 96Hours D TEM NIOSH 7402 (TNI) • 12 Hours O I 120 Hours D · TEM Bulk Qualitative (TBL) • 24 Houi:s D I 144+H<mrs D TEM Bulk Chatfield (TBS)•. tJ
TEM Bulk Quantitative (TBQ)
TEMWipeASTM D6480-05 · • TEMMicrovac ASTM D5.755-02 · • . }:'EMWater EPA 100.2 (TWl) • .:.Ccftlie2:::: ·; }'r 'j'. C •-•• .. : :~.'-z.c ~.--C~:::'c-'. -·---~ Ad
"" - t OJve,vd L
Total# of Samples
D~'t~/Time Received by I Date/time
A(;C./9el~t)ted r.;r' J.. w.
[="']' ,,:~) ._ ~ '; ~.-·J'.~,:,,,-'. ·.4,'!f' JI 4l~.,;({~lf""t•J r.Jt::ffe~ .
lb:;i "a.if6J...r1·~1.il'~i.'l:J~u ~ .... ~
1J U) {f fl "1
Page_J_of ~, A-F-017 EXP: 12,1-13
(A, .J'·
Scientific Analytical Institute 4604 Dundas Dr. Greensboro, NC 27407
Phone: 336.292.3888 Fax: 336.292.3313 ' www.sailab~com lab@sailab.com
Lab Use Only .
Lab Order ID: ·1 \t,\lf;'3(o, Client Code: ------
IL-
n tx?v: ov,.l c:..,;..11!,:;:·1,rva-,, 1vvr-fJlr,v,-, 1.~v: , . .,.. 1}~ ·. I--
-..,... ~ JI~ " L,~-.-- /'I • " - ,,, . YJ,_ - -----'.-- . ..._/3 _- .__s __ ._ - -----~,..,, ~ ·--•~=..,...~-
Page ~o~
1/31/2022 Project: Canadaigua VAMC Boiler Plant
Lab Order ID: 71984284
Lab Notes
Description
Lab Sample ID
Sample ID
NY ELAP: 198.4
Asbestos LCL-UCL
(Wt. %)
Bulk Asbestos Analysis by Transmission Electron Microscopy
Date Received:
2/3/2022Date Reported:
Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
Customer:
Analysis ID: 71984284_TO
Attn: Michael Delaney
Acid Sol.
Organic
(Wt. %)(Wt. %) (Wt. %)
NY ELAP 11922
No Asbestos Detected79%18%
2A
71984284TOB_1
4" Ceramic wall tile (grout)-lower
No Asbestos Detected70.%6.8%
2B
71984284TOB_2
4" Ceramic wall tile (grout)-lower
No Asbestos Detected66%9.8%
2C
71984284TOB_3
4" Ceramic wall tile (grout)-lower
42%30.%
4A
71984284TOB_4
6" red ceramic foor tile (grout) 0.25% - 0.30%Chrysotile0.28 %
34%6.2%
4B
71984284TOB_5
6" red ceramic foor tile (grout) 0.54% - 0.66%Chrysotile0.60 %
31%16%
4C
71984284TOB_6
6" red ceramic foor tile (grout) 0.48% - 0.59%Chrysotile0.54 %
Daniel Schwartz (22)
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Approved Signatory
Page 1 of 4tem_2.2.001
Analyst
Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government.
T-F-026 r17 2/29/2020
Lab Order ID: 71984284
Lab Notes
Description
Lab Sample ID
Sample ID
NY ELAP: 198.4
Asbestos LCL-UCL
(Wt. %)
Bulk Asbestos Analysis by Transmission Electron Microscopy
Date Received:
2/3/2022Date Reported:
Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
Customer:
Analysis ID: 71984284_TO
Attn: Michael Delaney
Acid Sol.
Organic
(Wt. %)(Wt. %) (Wt. %)
NY ELAP 11922
No Asbestos Detected30.%45%
7A
71984284TOB_7
Red fire stop- lower level
27%46%
7B
71984284TOB_8
Red fire stop- lower level 0.24% - 0.30%Chrysotile0.27 %
No Asbestos Detected35%45%
7C
71984284TOB_9
Red fire stop- lower level
28%70.%
8C
71984284TOB_21
Black sink coat - lower level 0.018% - 0.022%Chrysotile0.020 %
No Asbestos Detected29%45%
71984284TOB_22
Light gray expansion caulk - exterior
(SE)
No Asbestos Detected0.96%65%
71984284TOB_10
Light grey window caulk
Daniel Schwartz (22)
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Approved Signatory
Page 2 of 4tem_2.2.001
Analyst
Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement
Lab Order ID: 71984284
Lab Notes
Description
Lab Sample ID
Sample ID
NY ELAP: 198.4
Asbestos LCL-UCL
(Wt. %)
Bulk Asbestos Analysis by Transmission Electron Microscopy
Date Received:
2/3/2022Date Reported:
Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
Customer:
Analysis ID: 71984284_TO
Attn: Michael Delaney
Acid Sol.
Organic
(Wt. %)(Wt. %) (Wt. %)
NY ELAP 11922
No Asbestos Detected38%29%
71984284TOB_11
Interior expansion caulk- lower level
No Asbestos Detected83%15%
71984284TOB_12
12 x12 Blue floor tile
No Asbestos Detected37%51%
71984284TOB_13
12 x12 Blue floor tile
No Asbestos Detected40.%33%
71984284TOB_14
Cove base mastic- upper
No Asbestos Detected28%62%
71984284TOB_15
Cove base mastic- upper
No Asbestos Detected7.7%81%
71984284TOB_16
Door caulk- exterior
Daniel Schwartz (22)
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Approved Signatory
Page 3 of 4tem_2.2.001
Analyst
Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement
Lab Order ID: 71984284
Lab Notes
Description
Lab Sample ID
Sample ID
NY ELAP: 198.4
Asbestos LCL-UCL
(Wt. %)
Bulk Asbestos Analysis by Transmission Electron Microscopy
Date Received:
2/3/2022Date Reported:
Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180
Customer:
Analysis ID: 71984284_TO
Attn: Michael Delaney
Acid Sol.
Organic
(Wt. %)(Wt. %) (Wt. %)
NY ELAP 11922
No Asbestos Detected10.%52%
71984284TOB_17
Dark grey widow caulk
No Asbestos Detected44%43%
28A
71984284TOB_18
White fiberglasss and sealant
No Asbestos Detected51%45%
28B
71984284TOB_19
White fiberglasss and sealant
No Asbestos Detected57%43%
28C
71984284TOB_20
White fiberglasss and sealant
Daniel Schwartz (22)
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Approved Signatory
Page 4 of 4tem_2.2.001
Analyst
Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement
/QPi Scientific Analytical…