Canandaigua VAMC Boiler Plant - Final RBM Survey.pdf

PDF 3 MB Posted

Attached to
Z1DA--528A5-20-502 BOILER REPLACEMENT PROJECT
Solicitation number
36C24224R0032
Issued by

About this file

This document is a Regulated Building Materials Survey Report for the Canandaigua VA Medical Center Boiler Plant Replacement project, VA Project No. 528A5-20-502. The report details the findings of asbestos, lead, and PCB sampling conducted as part of this renovation project. Key findings include the identification of asbestos-containing materials (ACMs) in boiler insulation, pipe insulation, window glazing, pipe sealant, and other building materials. Estimated quantities of the identified ACMs are provided. The report also summarizes limited lead paint and PCB sampling results. Conclusions and recommendations regarding proper abatement and disposal of the identified regulated materials are included. This information will be relevant for the construction contractor executing the boiler replacement work at the facility.

The related federal contract opportunity is a solicitation for the Boiler Replacement Project at the Canandaigua VAMC, Solicitation #36C24224R0032. This is a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside, with a proposal due date of June 28, 2024. The scope includes replacing the boiler plant at the medical center. Three previous similar contracts within the past 10 years must be provided for evaluation.

View the file

Other files

File Type Posted
36C24224R0032 0009.docx DOCX document
36C24224R0032 0008.docx DOCX document
852.219-75 VA Notice of Limitations on Subcontracting.docx DOCX document
36C24224R0032 0007.docx DOCX document
36C24224R0032 0006.docx DOCX document
Attachment A_VHA Boiler and Associated Plant Safety Device Testing Manual 8th Edition.pdf PDF
Attachment B.pdf PDF
36C24224R0032 0005.docx DOCX document
Touchpoint Plus_Quick Start guide.pdf PDF
36C24224R0032 0004.docx DOCX document
Copy of Pre-Bid RFI Questions_Encorus Response 2024-06-13.pdf PDF
touchpoint-plus-user-guide-man0996_v1_0216.pdf PDF
2024-06-13 Question 1 Attachments.pdf PDF
Sensepoint XCD_IOM.pdf PDF
36C24224R0032 0003.docx DOCX document
Site Visit Sign In Sheet.pdf PDF
528A5-20-502 Boiler Replacement_Plans_Part 3.pdf PDF
528A5-20-502 Boiler Replacement_Plans_Part 2.pdf PDF
36C24224R0032 0002.docx DOCX document
528A5-20-502 Boiler Replacement_Plans_Part 1.pdf PDF
528A5-20-502 Boiler Replacement_Specifications REV1.pdf PDF
S02 - Past Performance Questionnaire - Exhibit B.docx DOCX document
528A5-20-502_SOW R1_Boiler Plant Replacement.pdf PDF
36C24224R0032 0001.docx DOCX document
S02 - Past Performance Questionnaire.docx DOCX document
P07 Wage Determination.pdf PDF
S02 - Contractor Projects Form.docx DOCX document
013200 Construction Documentation.pdf PDF
528A5-20-502 DESIGN BOLIER REPLACEMENT SET.pdf PDF
852.219-78 VA Notice of Limitations on Subcontracting.docx DOCX document
36C24224R0032.docx DOCX document
20-502 Bid Specifications.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

p

REGULATED BUILDING MATERIALS

SURVEY REPORT

Building 12 - Boiler Plant

A/E Services to Design Boiler Replacement VA Project No. 528A5-20-502 Canandaigua VA Medical Center 400 Fort Hill Avenue Canandaigua , New York 14424

Mabbett Project No. R2021068.000

March 8, 2022

Prepared For:

Encorus Group 23 Mechanic Street Springville, NY 14141

Mabbett & Associates, Inc. www.mabbett.com 105 Central Street, Suite 4100 Stoneham, MA 02180-1260 T. 781-275-6050 F: 781-954-5155 Massachusetts | Virginia | Rhode Island | New York

© 2022, Mabbett & Associates, Inc.

REGULATED BUILDING MATERIALS SURVEY REPORT

Design Boiler Replacement | Canandaigua VAMC

© 2022, Mabbett & Associates, Inc. Page i March 8, 2022 Project No..R2021068.000 Canandaigua VAMC Boiler Plant - Final

ACKNOWLEDGEMENT

This Regulated Building Materials Survey Report has been prepared by Mabbett & Associates, Inc. (Mabbett®) for the A/E Services to Design Boiler Replacement at the Canandaigua Veterans Affairs Medical Center located in Canandaigua , New York, VA Project No. 528A5-20-502. The information presented herein is based on the facts and information conveyed to or received by Mabbett during the preparation of this report. If any of the information provided to Mabbett that was used in preparing this report is incorrect, incomplete, or subject to change, Mabbett would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to Mabbett as of the date of this report and considered applicable to this report.

The attached Regulated Building Materials Survey Report was prepared by Mr. Kevin M. Donovan, Senior Environmental, Health & Safety Specialist of Mabbett & Associates, Inc.

This report has been reviewed and approved by:

Michael F. Delaney Director, Building Sciences Group

MFD:KMD/rsg

© 2022, Mabbett & Associates, Inc. Page ii March 8, 2022 Project No..R2021.068.000 Canandaigua VAMC Boiler Plant - Final

TABLE OF CONTENTS

SECTION PAGE

1.0 INTRODUCTION

2.0 ASBESTOS SURVEY

2.1 Sampling Methodology

2.2 Analytical Methodology

2.3 Materials with Trace Amounts of Asbestos

2.4 Summary of Asbestos Containing Materials Findings

3.0 LEAD CONTAINING PAINT SURVEY

4.0 BUILDING MATERIAL PCB SAMPLING

5.0 CONCLUSIONS AND RECOMMENDATIONS

5.1 Asbestos

5.2 Lead Containing Paint

5.3 PCB Containing Material

6.0 LIMITATIONS

TABLES

Table 1 – Summary of ACM Table 2 – Summary of Lead Paint Chip Analytical Results Table 3 – Summary of PCB Analytical Results

FIGURES

RBM-1 – Asbestos Sampling Location Plan RBM-2 – Lead and PCB Sampling Location Plan

APPENDICES

Appendix A – Summary of Asbestos Sampling Results Appendix B – PLM & TEM Laboratory Reports and Chains of Custody Appendix C – Lead Paint Chip Laboratory Report and Chain of Custody Appendix D – PCB Laboratory Report and Chain of Custody Appendix E – Mabbett & Associates, Inc. Report Dated November 16, 2010

© 2022, Mabbett & Associates, Inc. Page 1 March 8, 2022

1.0 INTRODUCTION

Mabbett and Associates, Inc. (Mabbett®) performed a survey for Regulated Building Materials (RBM) as part of the Renovation of the Boiler Plant project at the Canandaigua Veterans Affairs Medical Center (VAMC) located in Canandaigua , New York, VA Project No. 528A5-20-502. Site survey work was performed on January 18, 2022, by appropriately credentialed regulated building materials inspector, and consisted of the following activities:

A review of the existing facility regulated building material reports and renovation history;

An Asbestos Containing Material (ACM) survey of suspect materials (Analysis by Polarized Light Microscopy

[PLM] and Transmission Electron Microscopy [TEM]);

Limited Lead Containing Paint (LCP) sampling (Analysis by atomic absorption [AA]); and Limited sampling of building materials for PCBs (Polychlorinated Biphenyl) (Extraction Method EPA 3540C).

© 2022, Mabbett & Associates, Inc. Page 2 March 8, 2022

2.0 ASBESTOS SURVEY

A visual screening inspection was conducted by a New York State licensed asbestos inspector to identify locations of suspect ACM and conceptualize the sampling program. Only areas that were accessible during the field work phase were inspected, with reasonable efforts made during the initial field survey work to access areas as necessary to complete the asbestos survey and sampling program.

Prior to the execution of this survey, existing building plans for the project locations were examined and VA engineering personnel interviewed to discern the age and condition of existing materials, as well as the renovation history of the area being surveyed. Due to inclement weather at the time of the survey, the roof was not inspected and no samples collected. Roofing materials should be assumed to contain asbestos until sampled and determined to be non-ACM.

2.1 Sampling Methodology

Site inspection work was performed on January 18, 2022 by New York State licensed asbestos inspector Mr. Kevin M. Donovan (#09-07125). Bulk asbestos samples were collected using EPA National Emissions Standards for Hazardous Air Pollutants (NESHAP), 40 CFR Part 763, and Asbestos Hazard Emergency Response Act (AHERA) protocols. The inspection was limited to areas that may be impacted by the proposed renovation project. Bulk suspect ACM sampling was generally conducted according to the following sampling protocol:

Friable surfacing material:

• At least three bulk samples shall be collected from each homogeneous area that is 1,000 ft2 or less.

• At least five bulk samples shall be collected from each homogeneous area that is greater than

1,000 ft2 but less than or equal to 5,000 ft2.

• At least seven bulk samples shall be collected from each homogeneous area that is greater than

5,000 ft2.

Thermal system insulation:

• At least three bulk samples shall be collected from each homogeneous area of thermal system insulation.

• At least one bulk sample shall be collected from each homogeneous area of patched area of thermal system insulation.

• Sufficient samples shall be collected from elbows and fittings to determine if they contain ACM.

• Bulk samples shall not be collected from any homogeneous area where the state licensed asbestos inspector determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACM.

Miscellaneous material:

• At least two bulk sample shall be collected from each homogeneous area that is less than

100 ft2.

• At least three bulk samples shall be collected from each homogeneous area that is greater than

100 ft2.

Areas that were inaccessible, or where the survey was limited to visual observation only, are identified below:

Within walls Within fire doors Enclosed pipe/duct chases

© 2022, Mabbett & Associates, Inc. Page 3 March 8, 2022

Inside mechanical equipment/ductwork Inside the boilers Above fixed drywall or plaster ceilings Electrical equipment

2.2 Analytical Methodology

The collected bulk samples were submitted under chain of custody (COC) procedures to Scientific Analytical Institute (SAI) of Greensboro, North Carolina for PLM and TEM analysis as required by the New York State Environmental Laboratory Approval Program (ELAP). PLM analysis of friable materials was performed using NYS ELAP Method 198.1. Samples of Non-Friable Organically Bound (NOB) materials were analyzed by PLM (NYS ELAP Method 198.6) subsequent to matrix reduction. NOB samples that were identified as non-ACM by PLM methods were re-analyzed by TEM (NYS ELAP Method 198.4) for confirmation purposes. SAI is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program

(NVLAP).

Bulk sample results from this inspection are summarized in Table 1, Summary of Asbestos Sampling Results. The EPA, Occupational Safety and Health Administration (OSHA), and Part 56 of Title 12 of the Official Compilation of Codes, Rules and Regulations of the State of New York (12 NYCRR Part 56) defines any material that contains greater than one percent (>1%) asbestos as being an ACM. As such, the analytical laboratory identified bulk samples as positive for asbestos that met the regulatory criteria of greater than one percent (>1%) asbestos.

Laboratory reports and COC documentation are provided in Appendix A of this report.

2.3 Materials with Trace Amounts of Asbestos

Where laboratory analysis identified trace amounts of asbestos, that is, materials with less than 1% asbestos, the material sampled has generally not been listed as ACM in this report. This determination is consistent with New York State and US EPA definitions of ACM. Federal OSHA regulations may require additional evaluation of materials containing trace amounts of asbestos prior to activities which could cause release of fibers into the air.

Evaluations of materials with trace amounts of asbestos and of the fiber release potential of work practices have not been addressed in this report.

2.4 Summary of Asbestos Containing Materials Findings

Mabbett also collected eighteen (18)) samples of materials that were previously sampled in the Mabbett report dated November 16, 2010, attached as Appendix E, to confirm previous results. Mabbett also identified ten (10) additional areas of homogenous materials and collected thirty (30) representative bulk ACM samples. Asbestos sampling locations and results are identified on Figures RBM-1 and RBM-2. Forty-eight (48) samples collected were analyzed by PLM and TEM (friable and NOB). The laboratory-reported analytical data, including available historical data utilized for this survey, indicated that six (6) of the materials sampled as part of this survey contained 1% or greater of asbestos and are classified as ACM. Previously identified pipe insulation, pipe fitting insulation, boiler insulation, breeching insulation, tank insulation, window glazing, pipe sealant, sheet flooring and associated adhesive and roof drain materials were determined to be ACM or PACM. Estimated quantities of materials identified as ACM and PACM are presented in Table 1 below:

© 2022, Mabbett & Associates, Inc. Page 4 March 8, 2022

Table 1 Summary of ACM

Design Boiler Replacement Canandaigua VA Medical Center

Location Description of Material

Percent and Type of Asbestos

Estimated Quantity Amount Units

Lower Level - East of Boiler #2 Black Sink Coat 1.2% Chrysotile 1 Each Lower Level - Boilers #1, 2 & 3 Boiler Insulation 18.2 % Chrysotile * 2,600 Square Feet

Lower Level - Boiler Room South High Pressure Steam Pipe Insulation

<1% Chrysotile & 28.6% Amosite * 25 Linear Feet

Lower Level - Boiler Room East Pipe Sealant 6% Chrysotile * 1 Square Foot Upper and Lower Levels - Boiler Room

Interior and Exterior Window Glazing 3% Chrysotile 2,000 Linear Feet

Upper Level - Office and Adjacent Tan, Brown & Green Sheet Flooring and Adhesive

8.5% Chrysotile * 180 Square Feet

Upper Level - Boiler Room Roof Drain Mastic 4.5% Chrysotile * 10 Square Feet

Upper and Lower Levels - Boiler Room

4" to 12" Pipe Insulation PACM * 250 Linear Feet

Boilers #1, 2 & 3 36" Breeching Insulation PACM * 96 Linear Feet

Upper Level - Boiler Room 4' Tank Insulation PACM * 100 Square Feet Lower Level - Boiler Room 5' Tank Insulation PACM * 190 Square Feet Lower Level - Boiler Room 6' Tank Insulation PACM * 282 Square Feet Notes:

* = Previously Identified ACM & PACM PACM = Presumed Asbestos Containing Material

© 2022, Mabbett & Associates, Inc. Page 5 March 8, 2022

3.0 LEAD CONTAINING PAINT SURVEY

The limited LCP survey included the collection of paint chips from painted surfaces and systems in the areas surveyed that may be impacted by the planned renovation. Eight-teen (18) samples of different homogenous areas of paint were collected during this survey. Paint chip samples were submitted under standard COC procedures to SAI. Analysis was conducted using AA EPA method SW846-3050B/6010C/700B.

The results of the limited LCP sampling are summarized in Table 2, with laboratory reports provided in Appendix C.

Table 2 Summary of Lead Paint Chip Analytical Results

Design Boiler Replacement Canandaigua VA Medical Center

Sample # Location Substrate and Component Color Result (mg/Kg)

Pb-01 Lower Level - SW Concrete Floor Gray 0.017 Pb-02 Lower Level - South Concrete Floor Gray <0.0038 Pb-03 Lower Level - Entry (SE) Metal Door Frame Brown <0.0064 Pb-04 Lower Level - SW Ceramic Floor Tile Red 0.034 Pb-05 Lower Level - SE Concrete Wall White 0.031 Pb-06 Lower Level - Boiler #2 (East) Metal Boiler Gray 0.02 Pb-07 Lower Level - Boiler #2 (East) Metal Column Gray 7.9 Pb-08 Lower Level - Boiler #3 (NW) Metal Gas Pipe Green 0.036 Pb-09 Lower Level - South wall Metal Column Gray 12 Pb-10 Lower Level - Boiler #3 (East) Concrete Block Wall Yellow 0.006 Pb-11 Lower Level - Outside Bathroom Metal Railing Yellow <0.0075 Pb-12 Lower Level - Bathroom (North) Ceramic Wall Tile Tan <0.0033 Pb-13 Lower Level - Bathroom (North) Plaster Wall Blue 0.0057 Pb-14 Upper Level - South Metal Tank Support Black 0.83 Pb-15 Upper Level - South Concrete Floor Gray 0.74 Pb-16 Upper Level - South Metal Railing Yellow 7 Pb-17 Upper Level - SW Brick wall White 0.034 Pb-18 Exterior - SW Ramp Stone Window Sill Tan 0.1

© 2022, Mabbett & Associates, Inc. Page 6 March 8, 2022

4.0 BUILDING MATERIAL PCB SAMPLING

As part of this regulated building materials survey, Mabbett conducted sampling of suspect building materials for PCB. Mabbett sampled three (3) homogenous areas of suspect PCB-containing materials and submitted them under standard COC procedures to Alpha Analytical of Westborough, Massachusetts. Analysis was conducted using EPA Method SW-846 8082A. A copy of the lab report detailing the findings of this sampling is provided in Appendix D. Results of this PCB sampling are summarized below in Table 3.

Table 3 Summary of PCB Analytical Results

Design Boiler Replacement Canandaigua VA Medical Center

Sample # Location Material Result (mg/Kg)

PCB-01 Lower Level - SE Interior Window Glazing 365 PCB-02 Lower Level - SE Interior Window Frame Filler 834 PCB-03 Exterior - at Ramp (SE) Exterior Window Frame Caulk 2.72

Notes: mg/kg = Parts Per Million (PPM)

© 2022, Mabbett & Associates, Inc. Page 7 March 8, 2022

5.0 CONCLUSIONS AND RECOMMENDATIONS

5.1 Asbestos

Identified ACM must be abated and properly disposed of prior to disturbance by state licensed and properly trained contractors. All abatement must be performed in accordance with federal, state and local requirements.

Any suspect materials encountered during demolition or renovation activities that were not identified in this report as being non-ACM, should be assumed to be ACM unless sample results prove otherwise. Suspect ACM that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, should be assumed to contain asbestos if discovered during any demolition or renovation process or until otherwise verified.

5.2 Lead Containing Paint

The purpose of the limited LCP survey was to identify similar areas of LCP. During the on-site survey, representative samples of similar areas of interior building coatings were collected and analyzed for lead content.

The regulations addressing LCP in non-residential buildings are focused on occupational exposures involved with paint-disturbing activities and related waste-disposal activities.

Occupational exposure to lead during construction is regulated by OSHA regulation 29 CFR 1926.62 “Lead in Construction,” as well as other applicable state and local regulations. These regulations involve air monitoring to determine worker exposure levels when disturbing paint containing measurable levels of lead. This LCP survey cannot determine a safe level of lead for the purpose of paint-disturbing activities. However, this report is intended to provide guidance as to the location of LCP so it can be controlled, abated, or disposed of properly during this project’s construction related activities. Information gathered during this LCP survey should be used to determine where worker exposures to airborne lead may occur. Additionally, this information should also be used to assess the potential for exposure to workers, and for determining appropriate controls necessary to limit his or her health risks during this project.

A concentration of lead greater than or equal to 0.5 mg/Kg percent by weight or 1.0 mg/cm2 exceeds EPA and HUD residential standards is considered an indicator of risk. Representative samples of LCP waste to be generated during building renovation, or following demolition but prior to disposal, should be collected and analyzed using toxicity characteristic leaching procedure (TCLP) in accordance with 40 CFR Part 261. Management and disposal of lead containing waste must be done in accordance with all applicable local, state, and federal regulations.

OSHA regulations may require certain procedures for any paint that contains lead, even if it is below these levels.

All LCP identified, regardless of the lead content, should either be sampled and analyzed by TCLP and then handled/disposed of accordingly, or segregated from other large-scale debris and then managed as hazardous waste in accordance with federal, state, and local hazardous waste disposal regulations.

5.3 PCB Containing Material

The suspect PCB caulking material sampling results determined window glazing and caulking materials contain PCBs above regulatory levels. Materials containing ≥ 50 ppm PCB are considered a TSCA regulated PCB Bulk Product Waste. These materials are required to be removed and managed at an appropriate waste management facility. Surrounding media can either be assumed to be PCB impacted at ≥ 1 ppm and therefore PCB Remediation Waste or would need to be evaluated to determine actual PCB content. If adjoining building materials are determined to be PCB Remediation Waste, they can be removed or managed in place. Depending upon approach taken, EPA approval may be required.

© 2022, Mabbett & Associates, Inc. Page 8 March 8, 2022

6.0 LIMITATIONS

This survey report is the result of a diligent and thorough inspection for regulated building materials of the designated areas and materials that may be impacted by the renovation project. Inaccessible areas were not included in this survey. Although a comprehensive inspection was performed, Mabbett does not claim to have identified all hazardous materials that could be present in the facility (for example, materials potentially located within the inaccessible areas). Mabbett has conducted this assessment with reasonable care and has performed this project in accordance with generally accepted industry standards. There can be no assurances, and Mabbett makes no assurances, that the information, research, and technology used to prepare this report may not change in the future, thus affecting the results reported herein.

© 2022, Mabbett & Associates, Inc. FIGURES March 8, 2022 Project No. R20210068.000 Canandaigua VAMC Boiler Plant - Final

FIGURES

DN

DN

UP

NO ACM EXPECTED

IN THIS AREA

NO ACM EXPECTED

IN THIS AREA

AA-1 AA-1

AA-1

AA-1

AA-1

AA-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ASBESTOS SAMPLE LOCATIONS RBM SURVEY

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

FEBRUARY 2022

RBM-1

BLDG 12

528A5-20-502

MFD ECG

B12

B11

PARKING

N

B12

B11

PARKING

N

SCALE: 1/8" = 1'-0"

LOWER LEVEL PLAN1 SCALE: 1/8" = 1'-0"

UPPER LEVEL PLAN2

02A*

02A**

02A

02A

LEGEND

APPROXIMATE ASBESTOS SAMPLE LOCATION

NO ASBESTOS DETECTED (NAD)

SAMPLE POSITIVE FOR ASBESTOS <1%

SAMPLE POSITIVE FOR ASBESTOS >1%.

Scientists I Engineers I Program Managers

Mabbett & Associates, Inc.

105 Central Street Stoneham, MA. 02180

T. 781-275-6050

GENERAL SURVEY NOTES

1. DRAWINGS DO NOT CLAIM TO IDENTIFY ALL THE ASBESTOS CONTAINING MATERIAL

(ACM) PRESENT IN THE BUILDING AND SHOULD NOT BE THE SOLE BASIS FOR

IDENTIFYING ACM FOR FUTURE RENOVATION OR DEMOLITION PROJECTS, ABATEMENT

SPECIFICATIONS, ETC. MABBETTS'S SURVEY WAS PERFORMED WITH LIMITATIONS

INHERENT TO NON-DESTRUCTIVE VISUAL INSPECTIONS. ANY SUSPECT MATERIAL

ENCOUNTERED DURING RENOVATION/DEMOLITION THAT IS NOT IDENTIFIED AS BEING

NON-ACM SHOULD BE ASSUMED TO BE ACM UNLESS SAMPLE RESULTS PROVE

OTHERWISE.

2. BASE PLAN OBTAINED FROM DRAWING H-101 HAZARDOUS ABATEMENT PLAN OF

PROJECT 528A5-20-502, PREPARED BY ENCORUS GROUP, INC.

3. SURVEY COMPLETED ON 18 JANUARY 2022 BY MABBETT & ASSOCIATES, INC.

DN

UP

NO ACM EXPECTED

IN THIS AREA

NO ACM EXPECTED

IN THIS AREA

AA-1 AA-1

AA-1

AA-1

AA-1

AA-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

LEAD & PCBs SAMPLE LOCATIONS RBM SURVEY DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

FEBRUARY 2022

RBM-2

BLDG 12

528A5-20-502

MFD ECG

GENERAL SURVEY NOTES

1. DRAWINGS DO NOT CLAIM TO IDENTIFY ALL THE LEAD AND PCB CONTAINING MATERIAL

PRESENT IN THE BUILDING AND SHOULD NOT BE THE SOLE BASIS FOR IDENTIFYING

ACM FOR FUTURE RENOVATION OR DEMOLITION PROJECTS, ABATEMENT

SPECIFICATIONS, ETC. MABBETTS'S SURVEY WAS PERFORMED WITH LIMITATIONS

INHERENT TO NON-DESTRUCTIVE VISUAL INSPECTIONS. ANY SUSPECT MATERIAL

ENCOUNTERED DURING RENOVATION/DEMOLITION THAT IS NOT IDENTIFIED AS BEING

NON-ACM SHOULD BE ASSUMED TO BE ACM UNLESS SAMPLE RESULTS PROVE

OTHERWISE.

2. BASE PLAN OBTAINED FROM DRAWING H-101 HAZARDOUS ABATEMENT PLAN OF

PROJECT 528A5-20-502, PREPARED BY ENCORUS GROUP, INC.

3. SURVEY COMPLETED ON 18 JANUARY 2022 BY MABBETT & ASSOCIATES, INC.

B12

B11

PARKING

N

B12

B11

PARKING

N

SCALE: 1/8" = 1'-0"

LOWER LEVEL PLAN1 SCALE: 1/8" = 1'-0"

UPPER LEVEL PLAN2

Pb-01

LEGEND

APPROXIMATE LEAD SAMPLE LOCATION

APPROXIMATE PCBs SAMPLE LOCATION

Scientists I Engineers I Program Managers

Mabbett & Associates, Inc.

105 Central Street Stoneham, MA. 02180

T. 781-275-6050

PCB-01

© 2022, Mabbett & Associates, Inc. APPENDIX A March 8, 2020 Project No. R20210068.000

APPENDIX A

Summary of Asbestos Sampling Results

© 2022, Mabbett & Associates, Inc. Appendix A Page 1 of 2 March 8, 2020

Appendix A

Summary of Asbestos Sampling Results Design Boiler Replacement

Canandaigua VA Medical Center

Sample No. Sample Location Description of Material

Percent and Type of Asbestos (by PLM &

TEM Analysis)

01A Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 01B Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 01C Lower Level - Bathroom 4" Ceramic Wall Tile (Grout) NAD (PLM) 02A Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 02B Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 02C Lower Level - Bathroom 4" Ceramic Wall Tile (Adhesive) NAD (PLM) & NAD (TEM) 03A Lower Level - SW 6" Red Ceramic Floor Tile (Grout) NAD (PLM) 03B Lower Level - Boiler #3 (W) 6" Red Ceramic Floor Tile (Grout) NAD (PLM) 03C Lower Level - Boiler #2 6" Red Ceramic Floor Tile (Grout) NAD (PLM)

04A Lower Level - SW 6" Red Ceramic Floor Tile (Adhesive)

NAD (PLM) & <1%

Chrysotile (TEM)

04B Lower Level - Boiler #3 (W) 6" Red Ceramic Floor Tile (Adhesive)

NAD (PLM) & <1%

Chrysotile (TEM)

04C Lower Level - Boiler #2 6" Red Ceramic Floor Tile (Adhesive)

NAD (PLM) & <1%

Chrysotile (TEM)

05A Lower Level - Bathroom (NE) Joint Compound NAD (PLM) 05B Lower Level - Office (NE) Joint Compound NAD (PLM) 05C Upper Level - Office (South) Joint Compound NAD (PLM) 06A Exterior - At Ramp (SE) Brick Mortar NAD (PLM) 06B Exterior - SE Corner Brick Mortar NAD (PLM) 06C Exterior - SW Corner Brick Mortar NAD (PLM) 07A Lower Level - SE Area Red Fire Stop NAD (PLM) & NAD (TEM)

07B Lower Level - SE Area Red Fire Stop NAD (PLM) & <1% Chrysotile (TEM)

07C Lower Level - SE Area Red Fire Stop NAD (PLM) & NAD (TEM) 08A Lower Level -Boiler #2 (East) Black Sink Coat 1.2% Chrysotile (PLM) 08B Lower Level -Boiler #2 (East) Black Sink Coat 1.2% Chrysotile (PLM)

08C Lower Level -Boiler #2 (East) Black Sink Coat 0.2% Chrysotile (PLM) & <1% Chrysotile (TEM)

9 Upper Level - Generator Room Spray-on Fire Proofing NAD (PLM)

10 Lower Level - Boiler Room (SE) Interior Window Glazing NAD (PLM) & 3% Chrysotile (TEM)

11 Exterior - (SE) Light Gray Expansion Caulk NAD (PLM) & NAD (TEM) 12 Exterior - (SE) Fibrous Expansion Material NAD (PLM)

© 2022, Mabbett & Associates, Inc. Appendix A Page 2 of 2 March 8, 2020

Appendix A Summary of Asbestos Sampling Results

Design Boiler Replacement Canandaigua VA Medical Center

Sample No. Sample Location Description of Material

Percent and Type of Asbestos (by PLM &

TEM Analysis)

13 Exterior - (SE) Light Gray Window Caulk NAD (PLM) & NAD (TEM) 14 Lower level - Bathroom Gypsum Wallboard NAD (PLM) 15 Lower level - Bathroom Wall Plaster (Base Coat) NAD (PLM) 16 Lower level - Bathroom Wall Plaster (Finish Coat) NAD (PLM) 17 Lower level - Bathroom 2' x 2' White Ceiling Tile (Smooth) NAD (PLM) 18 Upper Level - Office (South) 2' x 2' White Ceiling Tile (Fissured) NAD (PLM) 19 Lower Level - (NE) Interior Expansion Caulk NAD (PLM) & NAD (TEM) 20 Lower level - Bathroom 12" x 12" Blue Floor Tile NAD (PLM) & NAD (TEM) 21 Lower level - Bathroom 12" x 12" Blue Floor Tile Mastic NAD (PLM) & NAD (TEM) 22 Upper Level - Office (South) Cove Base Mastic NAD (PLM) & NAD (TEM) 24 Exterior - SW Area Door Caulk NAD (PLM) & NAD (TEM) 25 Exterior - SW Area Window Glazing 4% Chrysotile (PLM) 26 Exterior - SW Area Dark Gray Window Caulk NAD (PLM) & NAD (TEM) 27 Lower Level - Boiler Room (NW) Plaster Sealant NAD (PLM)

28A Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 28B Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 28C Upper Level - North White Fiberglass End Sealant NAD (PLM) & NAD (TEM) 29A Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM) 29B Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM) 29C Lower Level - Tool Room Generator Exhaust Insulation NAD (PLM)

Notes:

NAD = No Asbestos Detected PLM = Polarized Light Microscopy Analysis TEM = Transmission Electron Microscopy Analysis

© 2022, Mabbett & Associates, Inc. APPENDIX B March 8, 2022

APPENDIX B

PLM and TEM Laboratory Reports and Chains of Custody

71984284Lab Order ID:

Canadaigua VAMC Boiler PlantProject:

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected 01A

4" ceramic wall tile (grout)-lower level bathroom

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_1

Other100.0

None Detected 01B

4" ceramic wall tile (grout)-lower level bathroom

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_2

Other100.0

None Detected 01C

4" ceramic wall tile (grout)-lower level bathroom

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_3

Other100.0

None Detected 02A

4" ceramic wall tile (adhesive)

- lower level bathroom

198.6 (NOB): Inconclusive - No asbestos detected

Cream Non Fibrous Homogeneous

Ashed, Crushed71984284PNY_4

Other100.0

None Detected 02B

4" ceramic wall tile (adhesive)

- lower level bathroom

198.6 (NOB): Inconclusive - No asbestos detected

Cream Non Fibrous Homogeneous

Ashed, Crushed71984284PNY_5

Other100.0

None Detected 02C

4" ceramic wall tile (adhesive)

- lower level bathroom

198.6 (NOB): Inconclusive - No asbestos detected

Cream Non Fibrous Homogeneous

Ashed, Crushed71984284PNY_6

Other100.0

None Detected 03A

6" red ceramic floor tile (grout) - lower level, (SW)

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_7

Other100.0

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Yanelis Delgado (49)

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected 03B

6" red ceramic floor tile (grout) - lower level, boiler #3 (W)

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_8

Other100.0

None Detected 03C

6" red ceramic floor tile (grout) - lower level, boiler #2

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_9

Other100.0

None Detected 04A

6" red ceramic floor tile (adhesive) - lower level, SW

198.6 (NOB): Inconclusive - No asbestos detected

Yellow Non Fibrous Homogeneous

Dissolved71984284PNY_10

Other100.0

None Detected 04B

6" red ceramic floor tile (adhesive) - lower level, boiler #3 (West)

198.6 (NOB): Inconclusive - No asbestos detected

Yellow Non Fibrous Homogeneous

Dissolved71984284PNY_11

Other100.0

None Detected 04C

6" red ceramic floor tile (adhesive) - lower level, boiler #32

198.6 (NOB): Inconclusive - No asbestos detected

Yellow Non Fibrous Homogeneous

Dissolved71984284PNY_12

Other100.0

None Detected 05A

Joint compound- lower level-bathroom (NE)

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_13

Other100.0

None Detected 05B

Joint compound- lower level-office (NE)

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_14

Other100.0

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected 05C

Joint compound- lower level-office (South)

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_15

Other100.0

None Detected 06A

Brick mortar- exterior- at ramp

(SE)

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_16

Other100.0

None Detected 06B

Brick mortar- exterior- at ramp SE corner

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_17

Other100.0

None Detected 06C

Brick mortar- exterior- at ramp SW corner

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_18

Other100.0

None Detected 07A

Red fire stop- lower level- SE area

198.6 (NOB): Inconclusive - No asbestos detected

Pink Non Fibrous Homogeneous

Ashed71984284PNY_19

Other100.0

None Detected 07B

Red fire stop- lower level- SE area

198.6 (NOB): Inconclusive - No asbestos detected

Pink Non Fibrous Homogeneous

Ashed71984284PNY_20

Other100.0

None Detected 07C

Red fire stop- lower level- SE area

198.6 (NOB): Inconclusive - No asbestos detected

Pink Non Fibrous Homogeneous

Ashed71984284PNY_21

Other100.0

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

08A Black sink coat- lower level-boiler #2 (East)

198.6 (NOB): Total asbestos 1.2

Black Non Fibrous Homogeneous

Dissolved71984284PNY_22

1.2% Chrysotile Other98.8%

08B Black sink coat- lower level-boiler #2 (East)

198.6 (NOB): Total asbestos 1.2

Black Non Fibrous Homogeneous

Dissolved71984284PNY_23

1.2% Chrysotile Other98.8%

08C Black sink coat- lower level-boiler #2 (East)

198.6 (NOB): Inconclusive-trace Chrysotile

Black Non Fibrous Homogeneous

Dissolved71984284PNY_24

0.2% Chrysotile Other99.8%

None Detected

Spray-on fire proofing- upper level- generator room

198.1

Cream Fibrous Homogeneous

Teased71984284PNY_25

80.0% Cellulose Other20.0%

Interior window glazing-lower level boiler room (SE)

198.1

Gray Non Fibrous Homogeneous

Crushed71984284PNY_26

3.0% Chrysotile Other97.0%

Light grey expansion caulk-exterior (SE)

198.6 (NOB): Inconclusive-trace Chrysotile

Gray Non Fibrous Homogeneous

Crushed71984284PNY_27

0.1% Chrysotile Other99.9%

None Detected

Fiborous expansion material-exterior (SE)

198.1

Gray, Black Non Fibrous Heterogeneous

Ashed71984284PNY_28

10.0% Cellulose Other90.0%

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected

Light grey window caulk-exterior (SE)

198.6 (NOB): Inconclusive - No asbestos detected

Gray Non Fibrous Homogeneous

Ashed71984284PNY_29

Other100.0

None Detected

Gypsum wallboard- lower level- bathroom

198.1

Grayish Non Fibrous Homogeneous

Crushed71984284PNY_30

10.0% Cellulose Other90.0%

None Detected

Wall plaster (base coat)- lower level- bathroom

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_31

Other100.0

None Detected

Wall plaster (finish coat)-lower level- bathroom

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_32

Other100.0

None Detected

2x2 white ceiling tile (smooth)

- lower level- bathroom

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_33

10.0% Cellulose Other90.0%

None Detected

2x2 white ceiling tile (finish)-upper level- office (South)

198.1

Gray Fibrous Homogeneous

Ashed71984284PNY_34

60.0% 10.0%

Mineral Wool Fiber Glass

Other30.0%

None Detected

Interior expansion caulk-lower level- NE

198.6 (NOB): Inconclusive - No asbestos detected

Grayish Non Fibrous Heterogeneous

Ashed71984284PNY_35

Other100.0

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected

12x12 blue floor tile- lower level bathroom

198.6 (NOB): Inconclusive - No asbestos detected

Blue Non Fibrous Homogeneous

Dissolved71984284PNY_36

Other100.0

None Detected

12x12 blue floor tile-mastic-lower level bathroom

198.6 (NOB): Inconclusive - No asbestos detected

Yellow Non Fibrous Homogeneous

Dissolved71984284PNY_37

Other100.0

None Detected

Cove base mastic- upper level office (South)

198.6 (NOB): Inconclusive - No asbestos detected

Cream Non Fibrous Homogeneous

Ashed71984284PNY_38

Other100.0

None Detected

198.6 (NOB): Inconclusive - No asbestos detected

Cream Non Fibrous Homogeneous

Ashed71984284PNY_39

Other100.0

None Detected 24 Door caulk- exterior- SW area

198.6 (NOB): Inconclusive - No asbestos detected

Gray Non Fibrous Homogeneous

Ashed71984284PNY_40

Other100.0

Window glazing- exterior- SEarea

198.1

White Non Fibrous Homogeneous

Crushed71984284PNY_41

4.0% Chrysotile Other96.0%

None Detected

Dark gray window caulk-exterior SW area

198.6 (NOB): Inconclusive - No asbestos detected

Gray Non Fibrous Homogeneous

Ashed71984284PNY_42

Other100.0

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

1/31/2022Date Received:

2/2/2022Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Bulk Asbestos Analysis By Polarized Light Microscopy:

NY ELAP Methods 198.1, 198.6 and Transmission Electron Microscopy:

NY ELAP Method 198.4

Michael DelaneyAttn:

71984284_PNAnalysis ID:

Customer: Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

None Detected

Plaster sealant- lower level boiler room (NW)

198.1

Gray Non Fibrous Heterogeneous

Crushed71984284PNY_43

Other100.0

None Detected 28A

White fiberglass and sealant-upper level- North

198.6 (NOB): Inconclusive - No asbestos detected

White Non Fibrous Homogeneous

Ashed71984284PNY_44

Other100.0

None Detected 28B

White fiberglass and sealant-upper level- North

198.6 (NOB): Inconclusive - No asbestos detected

White Non Fibrous Homogeneous

Ashed71984284PNY_45

Other100.0

None Detected 28C

White fiberglass and sealant-upper level- North

198.6 (NOB): Inconclusive - No asbestos detected

White Non Fibrous Homogeneous

Ashed71984284PNY_46

Other100.0

None Detected 29A

Generator exhaust insulation-lower level, tool room

198.1

Cream Non Fibrous Heterogeneous

Dissolved71984284PNY_47

10.0% Cellulose Other90.0%

None Detected 29B

Generator exhaust insulation-lower level, tool room

198.1

Cream Non Fibrous Heterogeneous

Dissolved71984284PNY_48

10.0% Cellulose Other90.0%

None Detected 29C

Generator exhaust insulation-lower level, tool room

198.1

Cream Non Fibrous Heterogeneous

Dissolved71984284PNY_49

10.0% Cellulose Other90.0%

Disclaimer: Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. ELAP method 198.1 derived results are applicable to friable bulk materials only. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP, AIHA, NY ELAP or any other agency of the U.S. government. NY ELAP LAB ID: 11922.

Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical institute participates in the AIHA IHPAT program. IHPAT Laboratory ID: 173190. Analytical uncertainty available upon request.

Approved SignatoryAnalyst

/QPi Scientific Analytical Institute 4604 DundasiJr~ Greensboro, NC 27407

Phone: 336~292~3888 Fax: 336.292.331.3 www.sailab.com lab@sailab.com

Contact:

OJ.-i~O EmaH'gj:

L.ab Use Only Lab. Order ID: J l ~ Cfi:J.o 65"

· Client Code: . ----',---'----'-

Asbestos Test :Types . PLM EPA 600/R-93/116 (PLM) jg] Positive stop • PLM Point Count 400 (PT4) • PLM Point Coun:t 1000 (PTM) .· • .

PCM NIOSH 7400~A Rules (PCM) • Billin2/Invoice Information Turn Around Times B Rules (PCB) 0 TWA(PTA)• Company:

Contact:

Address:

PO Number:

Project Name/Number:

· Sample ID#

OIA.

. J l/ I' (...QV""v,,i~ ~

90 Min. D I 48 Hours D cc

• . TEM AHERA (AHE)

3 Hours D I 72 Hours · .6a' TEM Level II (LII) • 6 Hours D I 96Hours D TEM NIOSH 7402 (TNI) • 12 Hours O I 120 Hours D · TEM Bulk Qualitative (TBL) • 24 Houi:s D I 144+H<mrs D TEM Bulk Chatfield (TBS)•. tJ

TEM Bulk Quantitative (TBQ)

TEMWipeASTM D6480-05 · • TEMMicrovac ASTM D5.755-02 · • . }:'EMWater EPA 100.2 (TWl) • .:.Ccftlie2:::: ·; }'r 'j'. C •-•• .. : :~.'-z.c ~.--C~:::'c-'. -·---~ Ad

"" - t OJve,vd L

Total# of Samples

D~'t~/Time Received by I Date/time

A(;C./9el~t)ted r.;r' J.. w.

[="']' ,,:~) ._ ~ '; ~.-·J'.~,:,,,-'. ·.4,'!f' JI 4l~.,;({~lf""t•J r.Jt::ffe~ .

lb:;i "a.if6J...r1·~1.il'~i.'l:J~u ~ .... ~

1J U) {f fl "1

Page_J_of ~, A-F-017 EXP: 12,1-13

(A, .J'·

Scientific Analytical Institute 4604 Dundas Dr. Greensboro, NC 27407

Phone: 336.292.3888 Fax: 336.292.3313 ' www.sailab~com lab@sailab.com

Lab Use Only .

Lab Order ID: ·1 \t,\lf;'3(o, Client Code: ------

IL-

n tx?v: ov,.l c:..,;..11!,:;:·1,rva-,, 1vvr-fJlr,v,-, 1.~v: , . .,.. 1}~ ·. I--

-..,... ~ JI~ " L,~-.-- /'I • " - ,,, . YJ,_ - -----'.-- . ..._/3 _- .__s __ ._ - -----~,..,, ~ ·--•~=..,...~-

Page ~o~

1/31/2022 Project: Canadaigua VAMC Boiler Plant

Lab Order ID: 71984284

Lab Notes

Description

Lab Sample ID

Sample ID

NY ELAP: 198.4

Asbestos LCL-UCL

(Wt. %)

Bulk Asbestos Analysis by Transmission Electron Microscopy

Date Received:

2/3/2022Date Reported:

Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

Customer:

Analysis ID: 71984284_TO

Attn: Michael Delaney

Acid Sol.

Organic

(Wt. %)(Wt. %) (Wt. %)

NY ELAP 11922

No Asbestos Detected79%18%

2A

71984284TOB_1

4" Ceramic wall tile (grout)-lower

No Asbestos Detected70.%6.8%

2B

71984284TOB_2

4" Ceramic wall tile (grout)-lower

No Asbestos Detected66%9.8%

2C

71984284TOB_3

4" Ceramic wall tile (grout)-lower

42%30.%

4A

71984284TOB_4

6" red ceramic foor tile (grout) 0.25% - 0.30%Chrysotile0.28 %

34%6.2%

4B

71984284TOB_5

6" red ceramic foor tile (grout) 0.54% - 0.66%Chrysotile0.60 %

31%16%

4C

71984284TOB_6

6" red ceramic foor tile (grout) 0.48% - 0.59%Chrysotile0.54 %

Daniel Schwartz (22)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Approved Signatory

Page 1 of 4tem_2.2.001

Analyst

Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government.

T-F-026 r17 2/29/2020

Lab Order ID: 71984284

Lab Notes

Description

Lab Sample ID

Sample ID

NY ELAP: 198.4

Asbestos LCL-UCL

(Wt. %)

Bulk Asbestos Analysis by Transmission Electron Microscopy

Date Received:

2/3/2022Date Reported:

Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

Customer:

Analysis ID: 71984284_TO

Attn: Michael Delaney

Acid Sol.

Organic

(Wt. %)(Wt. %) (Wt. %)

NY ELAP 11922

No Asbestos Detected30.%45%

7A

71984284TOB_7

Red fire stop- lower level

27%46%

7B

71984284TOB_8

Red fire stop- lower level 0.24% - 0.30%Chrysotile0.27 %

No Asbestos Detected35%45%

7C

71984284TOB_9

Red fire stop- lower level

28%70.%

8C

71984284TOB_21

Black sink coat - lower level 0.018% - 0.022%Chrysotile0.020 %

No Asbestos Detected29%45%

71984284TOB_22

Light gray expansion caulk - exterior

(SE)

No Asbestos Detected0.96%65%

71984284TOB_10

Light grey window caulk

Daniel Schwartz (22)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Approved Signatory

Page 2 of 4tem_2.2.001

Analyst

Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement

Lab Order ID: 71984284

Lab Notes

Description

Lab Sample ID

Sample ID

NY ELAP: 198.4

Asbestos LCL-UCL

(Wt. %)

Bulk Asbestos Analysis by Transmission Electron Microscopy

Date Received:

2/3/2022Date Reported:

Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

Customer:

Analysis ID: 71984284_TO

Attn: Michael Delaney

Acid Sol.

Organic

(Wt. %)(Wt. %) (Wt. %)

NY ELAP 11922

No Asbestos Detected38%29%

71984284TOB_11

Interior expansion caulk- lower level

No Asbestos Detected83%15%

71984284TOB_12

12 x12 Blue floor tile

No Asbestos Detected37%51%

71984284TOB_13

12 x12 Blue floor tile

No Asbestos Detected40.%33%

71984284TOB_14

Cove base mastic- upper

No Asbestos Detected28%62%

71984284TOB_15

Cove base mastic- upper

No Asbestos Detected7.7%81%

71984284TOB_16

Door caulk- exterior

Daniel Schwartz (22)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Approved Signatory

Page 3 of 4tem_2.2.001

Analyst

Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement

Lab Order ID: 71984284

Lab Notes

Description

Lab Sample ID

Sample ID

NY ELAP: 198.4

Asbestos LCL-UCL

(Wt. %)

Bulk Asbestos Analysis by Transmission Electron Microscopy

Date Received:

2/3/2022Date Reported:

Mabbett & Associates, Inc.

105 Central Street, Suite 4100 Stoneham, MA 02180

Customer:

Analysis ID: 71984284_TO

Attn: Michael Delaney

Acid Sol.

Organic

(Wt. %)(Wt. %) (Wt. %)

NY ELAP 11922

No Asbestos Detected10.%52%

71984284TOB_17

Dark grey widow caulk

No Asbestos Detected44%43%

28A

71984284TOB_18

White fiberglasss and sealant

No Asbestos Detected51%45%

28B

71984284TOB_19

White fiberglasss and sealant

No Asbestos Detected57%43%

28C

71984284TOB_20

White fiberglasss and sealant

Daniel Schwartz (22)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Approved Signatory

Page 4 of 4tem_2.2.001

Analyst

Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement

/QPi Scientific Analytical…

This is the start of the file's text. The full file is on GovTribe.