528A5-20-502 Boiler Replacement_Plans_Part 3.pdf

PDF 7 MB Posted

Attached to
Z1DA--528A5-20-502 BOILER REPLACEMENT PROJECT Federal contract opportunity
Solicitation number
36C24224R0032
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document is a solicitation (Solicitation Number: 36C24224R0032) for the Boiler Replacement Project at the Canandaigua VA Medical Center. The Department of Veterans Affairs is seeking a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) firm to perform this work. The project involves replacing existing boilers and associated equipment at the facility. Proposals are due by Friday, June 28, 2024 at the previously stated time. The evaluation criteria include details of three previous similar contracts performed within the past ten years. A site visit is scheduled for Thursday, June 6, 2024. This is an amendment to the original solicitation to correct errors and make additional changes.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--528A5-20-502 BOILER REPLACEMENT PROJECT, newest first.
File Type Posted
Canandaigua VAMC Boiler Plant - Final RBM Survey.pdf PDF
36C24224R0032 0009.docx DOCX document
852.219-75 VA Notice of Limitations on Subcontracting.docx DOCX document
36C24224R0032 0008.docx DOCX document
36C24224R0032 0007.docx DOCX document
36C24224R0032 0006.docx DOCX document
Attachment B.pdf PDF
Attachment A_VHA Boiler and Associated Plant Safety Device Testing Manual 8th Edition.pdf PDF
36C24224R0032 0005.docx DOCX document
Sensepoint XCD_IOM.pdf PDF
Copy of Pre-Bid RFI Questions_Encorus Response 2024-06-13.pdf PDF
Touchpoint Plus_Quick Start guide.pdf PDF
2024-06-13 Question 1 Attachments.pdf PDF
36C24224R0032 0004.docx DOCX document
touchpoint-plus-user-guide-man0996_v1_0216.pdf PDF
36C24224R0032 0003.docx DOCX document
Site Visit Sign In Sheet.pdf PDF
528A5-20-502 Boiler Replacement_Plans_Part 1.pdf PDF
528A5-20-502 Boiler Replacement_Specifications REV1.pdf PDF
S02 - Past Performance Questionnaire - Exhibit B.docx DOCX document
528A5-20-502_SOW R1_Boiler Plant Replacement.pdf PDF
528A5-20-502 Boiler Replacement_Plans_Part 2.pdf PDF
36C24224R0032 0002.docx DOCX document
36C24224R0032 0001.docx DOCX document
S02 - Past Performance Questionnaire.docx DOCX document
852.219-78 VA Notice of Limitations on Subcontracting.docx DOCX document
20-502 Bid Specifications.pdf PDF
528A5-20-502 DESIGN BOLIER REPLACEMENT SET.pdf PDF
S02 - Contractor Projects Form.docx DOCX document
36C24224R0032.docx DOCX document
013200 Construction Documentation.pdf PDF
P07 Wage Determination.pdf PDF
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL NOTES AND LEGENDS 100% STAMPED FINAL

DESIGN

FULLY SPRINKLERED

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

2023-06-23 E-001

BLDG 12

528A5-20-502

JFF CJR

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

HIGH-VOLTAGE OIL CIRCUIT BREAKER

HIGH-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

FUSIBLE LINK

GENERATOR, POWERG

CAPACITOR

METER

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT

CIRCUIT INTERRUPTER

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SINGLE

RECEPTACLE, SINGLE WITH SWITCHS

RECEPTACLE, SPECIAL PURPOSE

S RECEPTACLE, SWITCHED DUPLEX

ELECTRICAL SYMBOLS - POWER PLAN

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

TRANSFORMER, PLANT

BRANCH CIRCUIT HOMERUN. LINES INDICATE

NUMBER OF CIRCUITS, NEUTRAL, AND SWITCH LEG

CONDUCTORS. ONE SEPARATE GREEN

GROUNDING CONDUCTOR SHALL BE PROVIDED

FOR EACH HOMERUN; NOT SHOWN

JB PULL BOX/JUNCTION BOX

WIREWAY

RIGID CONDUIT LINE = RC

DUCT BANK

POWER DUCT = P

BUSWAY

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

CONDUIT TERMINATED 6" [152mm] AFF

IN STANDARD BOX FOR EXTENSION TO

EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING

(FLUSH W/FINISHED FLOOR) FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

VARIABLE FREQUENCY DRIVE

VFD

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE

3 = THREE-WAY

P = WITH PILOT LIGHT

WP= WEATHER PROOF

LOWER CASE = FIXTURE CONTROLLED

ELECTRICAL SYMBOLS - LIGHTING PLAN

LIGHT FIXTURE, CEILING MOUNTED, LETTER INDICATES TYPE.

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN

GENERAL ELECTRICAL NOTES

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE

ARCHITECTURAL REFLECTED CEILING PLAN.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH

CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH

WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

D. COORDINATE ALL SHUTDOWNS AND INTERRUPTIONS OF SERVICE WITH THE COR IN ACCORDANCE WITH

THE SPECIFICATION REQUIREMENTS.

E. ALL CONDUIT TO BE LABELED AT EACH END TO IDENTIFY TERMINATION LOCATIONS.

F. ALL SPARE CONDUIT SHALL CONTAIN A PULL STRING TO FACILITATE FUTURE USE.

G. THE CONTRACTOR IS TO PROVIDE EXCAVATION/TRENCHING PLANS TO THE VA COR FOR APPROVAL

PRIOR TO STARTING ANY EXCAVATION OR TRENCHING WORK.

H. CONTRACTOR TO LABEL ALL EQUIPMENT, CONDUIT, JUNCTION BOXES, PULL BOXES, ETC IN

ACCORDANCE WITH VA COR PROVIDED DIRECTION..

I. REFER TO GC101 THROUGH GC103, GC601 FOR PHASING DETAILS.

J. ALL MATERIALS TO BE PURCHASED IN ACCORDANCE WITH THE BUY AMERICAN ACT.

GENERAL ELECTRICAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC, SHOWN ON

PLANS TO BE REMOVED, COMPLETELY REMOVE CONDUIT AND WIRING TO THE SOURCE (OVER CURRENT

PROTECTIVE DEVICE, DISCONNECT, ETC).

B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE.

COMPLETELY REMOVE ALL ABANDONED WIRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH

RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

PHOTOCELLPC

ELECTRICAL DUCTBANK

X# FEEDER ID

X# = SEE FEEDER SCHEDULE E-601

LIGHT FIXTURE, WALL MOUNTED, LETTER INDICATES TYPE.

A

K KEY INTERLOCKED SWITCH

M MANHOLE

UNDERGROUND ELECTRICUE

GENERAL LINETYPES

EXISTING DUCT BANK

EXTENTS OF DETAIL

DEMOLITION

UNDERGROUND FUEL LINEFOS

ABANDON DUCT BANK

SAW CUT CONCRETE

WATER LINEW

STORM LINESD

FIREWATER LINEFW

SANITARY SEWER LINESS

GAS LINEG

FENCE LINE

ABANDON UNDERGROUND ELECTRICAUE

GROUND LINE

* PROTECTIVE RELAY (* INDICATES ANSI FUNCTION

NUMBER AND NUMBER INDICATES QUANTITY)

25 - SYNCHRONIZING OR SYNCHRONISM- CHECK

DEVICE

50 - INSTANTANEOUS OVERCURRENT

51 - AC INVERSE TIME OVERCURRENT RELAY

52 - AC CIRCUIT BREAKER

67 - AC DIRECTIONAL OVER CURRENT RELAY

87 - DIFFERENTIAL PROTECTIVE RELAY

SUFFIXES INDICATING ZONE OF PROTECTION

B - BUS G - GROUND L - LINE

N - NEUTRAL T - TRANSFORMER U - UNIT

SPARE CONDUIT

FILLED CONDUIT

CURRENT TRANSFORMER

FO FIBER OPTIC

A

GFCI

PORT, TELEPHONE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK/TABLE F-FLUSH FL-FLUSH

G-GROUND H-HIDDEN M-MULLION O-OUTDOOR

P-PEDESTAL RK-RACK R-ROOF REC-RECESSED

S-SURFACE W-WALL

T=TECHNOLOGY

P-PHONE FX-FAX/FACSIMILE

T2-SECONDARY TECHNOLOGY

X-LEGEND REF

M T

T2 X

PORT, DATA; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING O-OUTDOOR

FL-FLOOR W-WALL D-DESK/TABLE

T=TECHNOLOGY/TYPE

IP-INTERNET PROTOCOL (RJ45)

T2-SECONDARY TECHNOLOGY

X-LEGEND REFERENCE

E-EXISTING

M T

T2 X

DEMOLITIONX X X X

GND

CONDUIT SYMBOLS

CONDUIT UP

CONDUIT DOWN

VERTICAL RISER

DEMOLITION/ / / / / / / / / / / /

M

A

V

W

WH

W W

RC

DB

P

B B

O.C.B.

CU ELECTRICAL COPPER

TELECOMMUNICATION SYMBOLS

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

S-SURFACE C-CEILING W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

Z-BUZZER EP-EXPLOSION PROTECTED HORN LOUD SPEAKER

IP-NETWORK LOUD SPEAKER E-EXISTING

M T E

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

S-SURFACE C-CEILING W-WALL D-DESK

T=TECHNOLOGY/TYPE

M-MASTER S-SLAVE E-EXISTING

VIDEO CAMERA; LETTER INDICATES AS FOLLOWS:

M=MOUNT

S-SURFACE C-CEILING W-WALL R-ROOF CM-CORNER

T/T2=TECHNOLOGY/TYPE

WP, WEATHER RESISTANT 720-HD 720P 1080-HD1080P

PTZ-PAN/TILT/ZOOM CLR-COLOR, E-EXISTING EX-EXPLOSION PROOF

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

S-STRIKE E-EXISTING

E T

T

M

E T M

T2 X T M

E

M

TE

CENTRAL PROCESSING UNIT; LETTER INDICATES AS FOLLOWS:

E-EXISTING

CARD READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

W-WALL

T/T2=TECHNOLOGY/TYPE

P-PROXIMITY E-EXISTING

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

W-WALL D-DESK

T/T2=TECHNOLOGY/TYPE

X-REQUEST TO EXIST ESB-BOILER PLANT EMERGENCY STOP

E-EXISTING

LIGHT FIXTURE, LETTER INDICATES TYPE

LIGHT FIXTURE, CEILING MOUNTED, LETTER INDICATES TYPE

LIGHT FIXTURE, CEILING MOUNTED EMERGENCY, LETTER INDICATES TYPE

A

A

A

LIGHT FIXTURE, CEILING MOUNTED, LETTER INDICATES TYPE

A

A

LIGHT FIXTURE, CEILING MOUNTED EMERGENCY, LETTER INDICATES TYPE

T

M RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

R-RACK

T=TECHNOLOGY/TYPE

D-DIGITAL

INSTRUMENTATION SYMBOLS

W CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

P-PEDESTAL R-RACK S-SURFACE W-WALL

M-MULLION

GAS

E

GAS DETECTION SYSTEM CONTROL PANEL

E = EXISTING

GAS DETECTOR; LETTER INDICATES AS FOLLOWS:

T = TYPE

CO = CARBON MONOXIDE

GAS = COMBUSTIBLE GAS

T

GENERAL SYMBOLS

DEMOLISH/REMOVE

ROOM NAME AND NUMBERC2

CORRIDOR

PHASE CALLOUT#

6/23/2023

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text X

LOWER LEVEL

781' - 0"

F

65"-70" SCADA BOARD

POWER AND DATA

OUTLET (BEHIND

VIDEO BOARD)

/1 EI101

UPPER LEVEL

792' - 0"

VA ROOM NAME PLATE

DUPLEX OUTLET

1'

6"

5'

0"

INTERCOM

4'

0"

LOWER LEVEL

781' - 0"

G F E

/1 E-401

REFRIGERATOR

DUPLEX GFCI

(BEHIND

REFRIGERATOR)

DUPLEX GFCI DUPLEX GFCI INTERCOM

PANEL

BOILER

EMERGENCY

STOP

PULL STATION

ELECTRONIC

SECURITY LOCK

4'

0"

1'

1/

4"

1'

1/

4"

1'

3/

4"

DUPLEX GFCI

LOWER LEVEL

781' - 0"

GFE

55"-60" OVERHEAD SCADA BOARDS.

PROVIDE WITH ARTICULATING TV

WALL MOUNT

SCADA SYSTEM

EQUIPMENT RACK AND

SECURITY RACK

POWER AND

DATA OUTLET

(BEHIND SCADA

BOARDS)

POWER AND

DATA OUTLET

(BEHIND SCADA

BOARDS)

EXISTING GENERATOR

ANNUNCIATOR PANEL

/1 E-401

QUADRUPLEX

OUTLET

2 POINT

DATA OUTLET

GAS DETECTOR

DUPLEX OUTLET DUPLEX OUTLET

QUADRUPLEX

OUTLET

QUADRUPLEX

OUTLET

INTERCOM

1'

6"

4'

0"

6'

0"

8 POINT

DATA OUTLET

QUADRUPLEX

OUTLET

QUADRUPLEX OUTLET

(IN WALL)

8 POINT DATA OUTLET

8 POINT DATA

OUTLET

QUADRUPLEX

OUTLET

8 POINT DATA

OUTLET

8 POINT DATA

OUTLET

PIT LEVEL

764' - 7"

4.4

HYDRAULIC

LIFT FUSED

DISCONNECT

/1 EP104

(LOCATE WITHIN

LINE OF SIGHT OF LIFT)

4'

1/

4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23 E-201

ELECTRICAL ELEVATIONS

BLDG 12

JFF DGA

FULLY SPRINKLERED

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

SCALE: 1/2" = 1'-0"3

ELEVATION OUTSIDE CONTROL ROOM A105

SCALE: 1/2" = 1'-0"1

CONTROL ROOM SOUTH WALL ELEVATION

SCALE: 1/2" = 1'-0"2

CONTROL ROOM NORTH WALL ELEVATION

SCALE: 1/2" = 1'-0"4

ELECTRICAL ELEVATION STORAGE A001 - LOOKING WEST

EXISTING LIGHT SWITCH

TO REMAIN

Revisions: Date: 6/23/2023

GFCI GFCI GFCI COGFCI

H H

F

J

G F C I

GFCI

G F

C I

G F

C I

GFE

SCADA SYSTEM

EQUIPMENT RACK

CONDUIT STUB-UPS

VA WORKSTATION

VA WORKSTATION ENGINEERING WORKSTATION

SCADA PRINTEROPERATOR WORKSTATION ENGINEERING PRINTER

SECURITY EQUIPMENT RACK

OPERATORS WORKSTATION

CONTROL ROOM

A105

EXISTING NETWORK EQUIPMENT RACK

EXISTING GENERATOR

ANNUNCIATOR PANEL

W

IP

E

W

IP

W

IP

/1 EI101

E-201

SYSTEM OVERVIEW SCREENS

GAS DETECTOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23 E-401

ELECTRICAL ENLARGED PLAN

BLDG 12

JFF DGA

FULLY SPRINKLERED

SCALE: 1/2" = 1'-0"1

ELECTRICAL ENLARGED PLAN - CONTROL ROOM

N

KEYPLAN

B12

B11

PARKING

N

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. OPERATORS' WORKSTATIONS TO BE PROVIDED BY CONTRACTOR. OPERATORS'

WORKSTATIONS SHALL BE PROVIDED WITH SCADA CLIENT, DAILY AND MONTHLY

REPORTING CLIENT, MAINTENANCE TRACKING SOFTWARE PACKAGES, AND

ACCESS TO CAMERA FEEDS WITHIN THE BOILER PLANT.

3. SYSTEM OVERVIEW SCREENS WITHIN THE CONTROL ROOM SHELL BE

CONTROLLABLE BY THE OPERATORS' WORKSTATIONS TO DISPLAY ANY SCREEN

THAT IS A PART OF THE SCADA SYSTEM. SYSTEM OVERVIEW SCREENS TO BE

PROVIDED BY CONTRACTOR.

4. ENGINEERING WORK STATIONS TO BE PROVIDED BY CONTRACTOR. ENGINEERING

WORKSTATIONS SHELL BE PROVIDED WITH SOFTWARE NECESSARY TO MAKE

MODIFICATION TO ALL PLCS, SCADA SCREENS, SERVERS, ETC. THAT FORM A

PART OF THE BOILER MONITORING AND CONTROL SYSTEMS, AND HAVE SYSTEMS

LOCATED WITHIN THE BOILER PLANT.

5. VA WORKSTATIONS TO BE SUPPLIED BY THE VA. VA TO SUPPLY VA

WORKSTATIONS WITH REQUIRED SOFTWARE PACKAGES.

6. SEE SPECIFICATION 23 09 11 SECTION 2.5 FOR FOR SPECIFIC INFORMATION

REGARDING WORKSTATION REQUIREMENTS FOR THOSE SERVING THE BOILER

PLANT OPERATIONS.

UP

UP

UP

DN

DN

GFCI

G F

C I

G F

C I

GFCI

GFCIGFCI

G F

C I

GFCI

G F

C I

GFCI

G F

C I

T

GFCI GFCI

G F

C I

G F

C I

GFCI

GFCI

G F

C I

G F

C I

GFCI

C P

C P

M

M

C P

M

M

M

M

M

M M

M

M

M

M

C P

M

M

M

M

M M

M

M

M M

M

ATS

MM

M

M

M

M

J

J

J

J

J

MC

P

MM

MLKJHGFEDCBA

7.1

CONDUIT TO EXISTING METAL

STORAGE BUILDING AND DIESEL

TANK BUILDING TO BE REMOVED

EXISTING 208V GENERATOR

TO BE REMOVED

EXISTING ATS

TO BE REMOVED

UNDER MAIN CB

CHASE TO REMAIN

X

X

XXX

X X

X X

XX

X

XX

X

XX X

X

X

X

X X

X X

X

X

X

X

X

X

X

X

BLDG 13

PNLB

EXISTING DAY TANK/FUEL

PUMP TO BE REMOVED

480V

SWGR-ATS

MASTER BOILER

CTRL PNL

AIR COMPRESSOR AC-1

TO BE REMOVED AND

SAVED FOR REUSE

AC-2

AC-2 DISCONNECT

CHEMICAL PUMPS 1 & 2

CHEMICAL PUMP CONTROLLERS 1 & 2

FWP (FEED

WATER PUMP)

PANEL LP1

PANEL P

UNUSED DISC

PANEL M DISC

SUPPLY PUMP 1

SUPPLY PUMP 2

CONDENSATE TRANSFER

PUMP 1 DISC

CONDENSATE TRANSFER

PUMP 2 DISC

XX

CONDENSATE

TRANSFER PUMPS

XX XXX

FWP

CONTROLLER

X

PANEL M

X X X

TELEPHONE

PANEL LP-2

X X

PNL LP-2-1

X

X

X

X

XX

X

X

X

CFP-1

CFP-2

X X

DEDICATED

CIRCUIT FOR A/C

PANEL 1A

BUILDING 12

METER/CT CABINET

BLDG 12 PANEL

HWH-1

BOILER EMERGENCY STOPCCTV

MONITORS

GAS MONITORING

PANEL

PP3-5

PP3-2

GENERATOR

ANNUNCITOR PANEL

BOILER

EMERGENCY

STOP

NEW BOILER

EMERGENCY STOP

BOILER

EMERGENCY STOP

NEW BOILER STOP

PP-3

PULLBOX

4.4

X

REMOVE

TRANSFORMER T12.1

AND SAVE FOR

REINSTALLATION

X XXXX X

X X

EF-4 DISC

X

X

SUMP

PUMP-2 CP

SAH-1 DISC

EUH-1 DISC

SAF-1 DISC

SUMP

PUMP-1 CP

X X X

X

XXX

PP-5

BOILER 2 CTRL PNL

BOILER 1 CTRL PNL

BOILER 3 CTRL PNL

SEE DWG MD101

FOR ADDITIONAL INFORMATION

XMFR T12.2

XMFR T12.3

EF-6

PP-2

PP-1

DP-1

DP-2

DP-3

VFC'S

EF-4

STRT

SAF-2

DISC.

SAF-3

DISC.

EUH-3

DISC.

SAH-2

DISC.

HVAC CONDUIT

STUB-UP AREA

SUMP

PUMP-2

EUH-2

DISC.

GD-3

GD-3

DISC.

GD-3A

GD-3A

DISC.

EF-8

EF-8 DISC.

FIRE PUMP

COMPRESSOR

DISC

UNIT HEATER

UH-1

FXAC

M.O.D.

EF-8 DAMPER

JOCKEY PUMP

CONTROLLER

FIRE PUMP CONTROLLER/

POWER TRANSFER SWITCH

HVAC CONDUIT

STUB-UP AREA

FWP-5 FWP-4

SUPPLY PUMPS

DISC.

EF-7 DISC.

EF-7

DIESEL PUMP

DISC.

GENERATOR TO BE

RELOCATED.SEE EP101

FOR NEW LOCATION

GD-2, 2A

DISC.

GD-2, 2A

GD-1, 1A

DISC.

GD-1, 1A

VACUUM

CONDENSATE

PUMP

DIESEL TANK MONITOR

FUEL OIL PUMPS

FUEL OIL TANK MONITOR

XXX

FIRE AND

JOCKEY PUMPS

BOILER

EMERGENCY STOP

RELOCATE EXISTING

DISCONNECT SWITCH TO

ALLOW INSTALLATION OF

NEW DOORWAY

SUMP PUMPS. INTERRUPTION

OF SUMP PUMPS MUST BE

COORDINATED WITH VA COR.

IN NO CASE SHALL SUMP

PUMPS BE LEFT OFF AND

UNMONITORED.

SUMP PUMPS. INTERRUPTION

OF SUMP PUMPS MUST BE

COORDINATED WITH VA COR.

IN NO CASE SHALL SUMP

PUMPS BE LEFT OFF AND

UNMONITORED.

XX

12 6

4 8

1 412

X

XX

X

X

XX

X

MP1-4

PB7 PB6

LSB #4

LSB #5

SP2SP1

RR-1 DISC 2

RR-1

RR-1 DISC 1

CP-5

B12 DISC

X

EXISTING

CONCRETE PADCF-1

HWH-1 DISC

PP3-29

PDMP-4

X1X4X2X4X4X1

UH-1 DISC

REMOVE ALL

LIGHTING,

OUTLETS, ETC IN

THESE SPACES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

ED101

ELECTRICAL DEMOLITION POWER

PLAN - LOWER LEVEL BLDG 12

JFF MAW

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"1

ELECTRICAL DEMOLITION POWER PLAN - LOWER LEVEL

N

KEYPLAN

B12

B11

PARKING

N

GENERAL NOTES

1. SEE E-001 FOE E-SERIES NOTES AND LEGENDS.

2. SEE ED601 FOR DEMO ONE-LINE DIAGRAM

3. SEE MECHANICAL DRAWING MD101 FOR ADDITIONAL INFORMATION

4. THIS IS A PHASED PROJECT. SEE PHASING PLAN FOR ADDITONAL INFORMATION.

5. PROTECT BUILDING GROUNDING CONDUCTOR(S) FROM DAMAGE DURING SLAB

DEMOLITION.

6. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

1/2" 1/4"

KEYED NOTES

1 CUT CONDUIT STUB-UPS FLUSH WITH FLOOR SLAB, AND CAP.

2 CONDUIT TO BE PROTECTED DURING SLAB DEMOLITION.

3 CONDUIT FED FROM MP-2 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

4 CONDUIT FED FROM CP-1 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

5 CONDUIT FED FROM SWITCHGEAR CUT BACK TO EDGE OF SLAB DEMOLITION AND

CAP. REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

6 CONDUITS FED FROM DP 3 PROTECT DURING SLAB DEMOLITION,CONDUITS FED

FROM MP-4, AND, MP-3 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP. REFER

TO DRAWING SD101 FOR ADDITIONAL DETAILS.

7 CONDUITS FED FROM MP-1, AND, MP-3 CUT BACK TO EDGE OF SLAB DEMOLITION

AND CAP. REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

8 CONDUIT FED FROM FED FROM DP-1 PROTECT DURING SLAB DEMOLITION.

CONDUIT FED FROM MP-1 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

9 CONDUITS FED FROM MP-3, AND MP-5 CUT BACK TO EDGE OF SLAB DEMOLITION

AND CAP. REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

10 CONDUIT FED FROM CP-2 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

11 CONDUIT FED FROM CP-3 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

12 CONDUIT FED FROM MP-4 CUT BACK TO EDGE OF SLAB DEMOLITION AND CAP.

REFER TO DRAWING SD101 FOR ADDITIONAL DETAILS.

13 ALL STUB ENDED CONDUIT AND WIRE TO BE REMOVED BACK TO SURFACE.

M

H

H

H

M

M

M

M M

F A T C

JHGFEDCBA

SAH-1

EUH-1

SAF-1

EF-4

CONDUIT EXTENDS

DOWN TO DISCONNECT

SWITCH BELOW, (TYP OF 2)

EUH-2

EUH-3

SAF-3SAF-2

CONDUIT EXTENDS

DOWN TO DISCONNECT

SWITCH BELOW,

(TYP OF 5)

X

X

SP1/SP2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

ED102

ELECTRICAL DEMOLITION POWER

PLAN - UPPER LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"1

ELECTRICAL DEMOLITION POWER PLAN - UPPER LEVEL

KEYPLAN

B12

B11

PARKING

N

N

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. THIS IS A PHASED PROJECT. SEE PHASING PLAN FOR ADDITONAL INFORMATION.

3. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

4. REMOVE ALL CABLE AND CONDUIT ASSOCIATED WITH ROOFTOP PACUS. SEE

MECHANICAL DEMOLITION DRAWINGS REMOVAL OF ROOFTOP UNITS.

PANEL EM-GEN

EXSITING 4160V

GENERATOR AND

CONTROLS TO REMAIN

DEAERATOR TANK TO BE REMOVED, SEE

MECHANICAL DRAWINGS FOR ADDITIONAL

INFORMATION. COORDINATE ELECTRICAL

DISCONNECTION WITH MECHANICAL

DEMOLITION

4 4

4 4

A3 B3

A

B

N/L

3 3 a b a b

B A

B A B A

B A B A

B A B A

B A

DP-1-4

DP-1-3

DP-1-3

DP-1-3

DP-1-3

DP-1-8

DP-1-4

DP-1-8

DP-1-8

DP-1-7DP-1-7

DP-1-7

DP-1-7

DP-1-7

DP-1-7

DP-1-7

DP-1-5,a

DP-1-3

DP-1-3 DP-1-3

DP-1-3

DP-1-4

DP-1-4

DP-1-4

DP-1-6

DP-1-1 DP-1-2

DP-1-4

DP-1-3

DP-1-2

DP-1-5,b

DP-1-10

DP-1-7

DP-1-7

DP-1-5

DP-1-7

DP-1-10

DP-1-10

DP-1-10

DP-1-10

DP-1-8

DP-1-8

DP-1-4 DP-1-4

DP-1-6

DP-1-5,b

DP-1-5,a

DP-1-5,b

DP-1-5,a

DP-1-5,a

DP-1-1

DP-1-2

DP-1-4

DP-1-4

DP-1-4 DP-1-4

DP-1-4

DP-1-5,a

DP-1-5,a

DP-1-4

DP-1-4

DP-1-6 DP-1-6

DP-1-6

DP-1-6

DP-1-7

DP-1-6

DP-1-6

DP-1-6

DP-1-6

DP-1-4141 41

41 41

DP-1-5,b

DP-1-7

DP-1-5,a

DP-1-5,b

DP-1-5,bDP-1-5,a DP-1-5,b

DP-1-5,aDP-1-5,aDP-1-5,b

DP-1-5,a

DP-1-5,a

DP-1-5,b

DP-1-6

DP-1-6

DP-1-10

DP-1-8

DP-1-6DP-1-6

DP-1-6

DP-1-6

DP-1-6

DN

UP

UP

DN

DN

MLKJHGFEDCBA

7.1

X X X

X

XXX

X

X X

X

XX

X X

XXXXXX X

X X X X X X X X X X X X X X X

XXXX

X

XXXX

XXXXXXX

X

X X

X

X X

X

X X

X

XX XX

X X

X X

X

X

X

X X

X X

X

X X

X

X X

X X

X

XX

XX

X X

X

X X

X X X X X XX

X

X

X

XXX XXXX

X

X

X

X

XXX

X X X

XXX

XX

X

X

X X

X X

X

X

X X

4.4

XX XX

XXX

X X

XX

X

X

XXXX

XXXX

X

XX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

ED103

ELECTRICAL DEMOLITION LIGHTING

PLAN - LOWER LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

KEYPLAN

B12

B11

PARKING

N

N

SCALE: 1/8" = 1'-0"1

ELECTRICAL DEMOLITION LIGHTING PLAN - LOWER LEVEL

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. THIS IS A PHASED PROJECT. SEE PHASING PLAN FOR ADDITONAL INFORMATION.

3. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

KEYED NOTES

1 REMOVE REMAINING JUCTION BOX AND FIXTURES. PULL WIRES BACK TO PANEL

AND REMOVE CONDUIT.

2 MAINTAIN EXISTING CONDUIT AND CABLE TO RECONNECT TO NEW LIGHTING

FIXTURES. SEE EL101.

H

M

M

M

M M

N/L

N/L

N/L

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

N/L

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

DP-1-2-a

DP-1-2-b

MLKJHGFEDCBA

7.1

X

X

X

X

X

X

X

X

X X X

X

X

X

X

X

X

X

X

X

X

XX

XXX

X

XX

X

4.4

X X

X X

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

ED104

ELECTRICAL DEMOLITION LIGHTING

PLAN - UPPER LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

KEYPLAN

B12

B11

PARKING

N

N

SCALE: 1/8" = 1'-0"1

ELECTRICAL DEMOLITION LIGHTING PLAN - UPPER LEVEL

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. THIS IS A PHASED PROJECT. SEE PHASING PLAN FOR ADDITONAL INFORMATION.

3. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

X X

X

G F

C I

GFCI

T XX

X

X

X

X

X X

X

X

X

X

X

X

X

GFCI GFCI

G F

C I

G F

C I

GFCI

G F

C I

G F

C I

GFCI

MLKJHGFEDCBA

7.1

8 8

4.4

W 72

E

W 72

E

W 72

E

W I P E

X

X

X

X

W

W

W

TYP

W

HS

HS

HS

HS

HS

HS

HS

HS

HS

HS

HS

HS

X

X

X

X

HS

HS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

ED112

ELECTRICAL DEMOLITION SECURITY

PLAN - LOWER LEVEL BLDG 12

KRK CJR

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"1

ELECTRICAL SECURITY DEMOLITION PLAN - LOWER LEVEL

KEYPLAN

B12

B11

PARKING

N

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

N

KEYED NOTES

1 REMOVE EXISTING CAMERAS. UPDATE EXISTING SYSTEM TO ACCOMMODATE

REMOVAL. TURN CAMERAS OVER TO VA FOLLOWING REMOVAL

2 REMOVE EXISTING LOUDSPEAKER. TURN OVER TO VA FOLLOWING REMOVAL.

3 EXISTING CARD READERS TO BE REMOVED AND REPLACED WITH NEW DEVICES

COMPLIANT WITH VA REQUIREMENTS AND PROJECT SPECIFICATIONS.

4 REMOTE ALARM SPEAKER AND LIGHT. REMOVE ALONG WITH ALL CONDUIT AND

WIRE BACK TO SOURCE PANEL. RETURN SPEAKER AND LIGHTS TO VA FOLLOWING

REMOVAL.

RG&E CKT 251

4160V, 3Ø

EX 3#250 kcmil &

1#4/0 AWG

RG&E STATION 755

S&C, 15kV, 40kA

RG&E CKT 2901

4160V, 3Ø

MH-E-3

EX 3#250 kcmil & 1#4/0 AWG

EX 3#2/0 AWG & 1#4/0 AWGEX 3#2/0 AWG & 1#4/0 AWG

TO BLDG #10

MH-E-6

MV SWITCH SS-7

15kV, S&C, PMH-6, 600A

MV SWITCH SS-1A

15kV, S&C, PMH-10, 600A

MV SWITCH SS-1B

15kV, S&C, PMH-10, 600A

TO MH-E-7

MH-E-5 MH-E-4

TO BLDG

#11 & #16

TO BLDG #10

TO MH-E-2

TO MH-E-2

CO-GEN PLANT GENERATOR SWITCHGEAR

480V, 1600A, 3Ø, 4W, 60HZ BUSBARS

FULLY RATED FOR 65kA RMS SYM FAULT CURRENT

/800A

GENERATOR

DISCONNECT

25104

GENERATOR

DISCONNECT

290105

N.C.

PREPARED

SPACE

PREPARED

SPACE

TO PANEL DP-1

(ED602)

TO PANEL DP-2

(ED602)

600A 800A F101

LSIG

1200A 1600A F102

LSIG

1600A 1600A F103

800A 800A F104

1200A 1600A M101 N.C.

LSI

BECKWITH

M3410A

PROTECTION:

27/59 81 O/U

ALARM:

60V 51N

52a-G101 52b-G101

TRIP-G101 -86G

TRIP-G101

TRIP-M101 -50BF

CT CT

GEN PT'S (3)

120V/69V480V

BUS PT'S (3)

120V/69V480V

800:5

800A 800A G101 N.0.

LINE PT'S (3)

120V/69V480V

1200:5

600A 800A G102B N.C.

DG-1

550.4KW,

480V, 3Ø, 60Hz

DIESEL GENERATOR

TVSS

ALLEN-BRADLEY PLC CONTROL

SYSTEM

24 VDC

BATTERY AND

CHARGER

120V 480V

CPT

TO SWITCHGEAR

LOADS/TRIP & CLOSE CKTS

P026 P027

SQUARE D

ION MTR

60A

XFMR T-12

4160V PRI

1000kVA OA

480/277V SEC

RECONNECT EXISTING PRIMARY

CABLES TO NEW SERVICE

TRANSFORMER.

UNDER OIL

LOAD LINE

SELECTOR SWITCH

#4/0 AWG

L.A. L.A.

BECKWITH

M3410A

PROTECTION:

27/59

ALARM:

60V

CT CT

TRIP M101

52a-M101 52b-M101

50N 51N /

1200:5

BASLER BE1

TRIP M101

TRIP G102B

TRIP G101

24V TO DG-1

3/0

SEL

REMOTE

I/O

MODULE

TX

RX

SEL

REMOTE

I/O

MODULE

TX

RX

CT CT

VAMC MAIN SWGR

1200A, 4160V, 3Ø, 4W, 58kA RMS MOMENTARY, 60HZ BUSBARS SQUARE D, METAL-CLAD, OUTDOOR SHELTERED ISLE SWGR

5252 52-A

NORMAL

52-B

EMERGENCY

300:5 300:5

52 52-1

200:5

52 52-2

240/120V-4160V

15kVA, CPT

STATION

POWER PANEL

240/120V-4160V

SEL 751

TRIP

50N 51N

ALARM

CT CT 200:5

SEL 751

ALARM

CT CT

SEL 751

TRIP

51N

CT CT

TRIP 52-A NORMAL

(51/51N)

SEL 751

TRIP

51N

CT CT

ALARM ALARM

TRIP 52-1 TRIP 52-2

TRIP

50N 51N

TRIP 52-B EMERGENCY

(51/51N)

BUS PT

EXISTING FIBER OPTIC CABLE

TRIP AB PLC (32) TRIP AB PLC (32)

N E

L

350A 400A

FIRE

PUMP

JOCKEY

PUMP

FIRE PUMP

CONTROLLER/POWER

TRANSFER SWITCH

JOCKEY PUMP

CONTROLLER

/350A

3#-1/0 AWG & 1-#2 GRD IN 4"

CND

3#-4/0 AWG & 1-#2

GRD IN 2" CND

EXISTING GENERATOR TO BE

RELOCATED. DISCONNECT WIRING

AT GENERATOR AND PREPARE TO

BE EXTENDED TO NEW GENERATOR

LOCATION.

EXISTING FIRE PUMP, FIRE PUMP

CONTROLLER, JOCKEY PUMP, AND

JOCKEY PUMP CONTROLLER TO BE

DISCONNECTED AND REMOVED.

TURN OVER TO VA FOLLOWING

REMOVAL. EXISTING WIRING FROM

FIRE PUMP CONTROLLER TO

TRANSFORMER T-12 AND

GENERATOR DG-1 TO BE

COMPLETELY REMOVED. CAP AND

SEAL CONDUIT AT BUILDING

ENTRANCE AND AT GENERATOR

PAD.

MODIFY EXISTING TRIP CIRCUITRY

TO REMOVE TRIP SIGNAL TO

BREAKER G102B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL DEMOLITION ONE-LINE

DIAGRAM

100% STAMPED FINAL

DESIGN

FULLY SPRINKLERED

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

2023-06-23

ED601

BLDG 12

528A5-20-502

JFF CJR

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

6/23/2023

AutoCAD SHX Text

EXCITER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DM

AutoCAD SHX Text

TTB

AutoCAD SHX Text

TTB

AutoCAD SHX Text

TTB

AutoCAD SHX Text 86G

AutoCAD SHX Text

TTB

AutoCAD SHX Text

TTB

AutoCAD SHX Text

TTB

AutoCAD SHX Text

DM

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text

ABC

AutoCAD SHX Text

AutoCAD SHX Text V

AutoCAD SHX Text

TTB

AutoCAD SHX Text

AS

AutoCAD SHX Text A

AutoCAD SHX Text

TTB

AutoCAD SHX Text

AS

AutoCAD SHX Text A

AutoCAD SHX Text

TTB

AutoCAD SHX Text

AS

AutoCAD SHX Text A

AutoCAD SHX Text

TTB

AutoCAD SHX Text

TTB

AutoCAD SHX Text

AS

AutoCAD SHX Text A

AutoCAD SHX Text

TTB

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

DISTRIBUTION DP-2

1200A, 480V, 3Ø, 4W, 60HZ BUSBARS

FULLY RATED FOR 65kA RMS SYM FAULT CURRENT

MLO

150A175A175A 125A125A125A

SAF-1

DISTRIBUTION DP-3

20A

SAF-2 SAF-3 EF-1 EF-2 EF-3 PACKAGED AC UNIT

PACU-1

4 TON

30A

225A

PACKAGED AC UNIT

PACU-2

3 TON

30A

AC-1

20kVA

35A15A

EF-4

225A, 480V, 3Ø, 3-W, 60Hz BUSBARS FULLY RATED FOR 65kA RMS SYM FAULT CURRENT

FROM CO-GEN PLANT

PARALLELING SWGR,

BREAKER F102

(ED601)

MLO

80A 80A 25A 225A

SAH-1

15A15A

SAH-2

20A 20A 20A 20A 20A 20A 20A

DUPLEX

SUMP PUMP

40A

HOT WATER

HEATER

20A

GD-1

20A

GD-2

20A

GD-3

DP-1

XFMR T12.1

480V PRI

112.5kVA

208/120V SEC

PANEL

PP-1

FROM CO-GEN PLANT

PARALLELING SWGR,

BREAKER F101

(ED601)

/400A

PANEL

PP-2

FEED-THROUGH

LUGS

CONNECTION

/// DM

200A

175A 150A100A

80A

80A

20A 20A

SPARE SPAREDUPLEX

SUMP PUMP

25A 70A

XFMR T12.2

480V PRI

112.5kVA

208/120V SEC

PANEL

PP-4

EXHAUST

FAN

EF-8

FIRE PUMP

ROOM

RECEPT.

20A 20A

20A

FIRE PUMP

ROOM

LIGHTING

UNIT

HEATER

UH-2

20A

UNIT

HEATER

UH-1

20A

EX ATS

ASCO 7000

W/ BYPASS

TO BLDG 16

EMERGENCY POWER

200kW/250kVA 208/120V

DETROIT DIESEL

694A, SKID MOUNTED

250A

N E

L / / / / /

/JUNCTION

BOX IN

EX BLDG

EX J-BOX

BLDG 12

EX CT CABINET

UTILIZED AS TAP BOX,

TO BE REMOVED

EX BUILDING 12 PANELBOARD

208/120V, 3Ø, 4W, 60HZ BUSBARS

400A 70A 100A

PANEL 1A PANEL P PANEL LT-1 EMERGENCY

GEN PANEL

(4160V GEN)

PANEL

LT-2

FUEL

PUMP

STATION

S. METAL

STORAGE

BUILDING

400A

PANEL M

20A

GD-3A

20A

GD-2A

20A

GD-1A

EXISTING ATS IN

BUILDING 13 TO

BE REMOVED.

TURN OVER TO

VA FOLLOWING

REMOVAL.

EXISTING

PANELBOARDS

TO BE REMOVED

EXISTING

METERING

EQUIPMENT TO

BE REMOVED

EXISTING

PANELBOARDS

TO BE REMOVED

EXISTING

ENCLOSED

CIRCUIT

BREAKER TO BE

REMOVED

EXISTING

TRANSFORMER

TO BE

RELOCATED.

EXISTING

GENERATOR AND

ASSOCIATED

EQUIPMENT TO

BE REMOVED

PANEL

INCINERATOR

(BUILDING 13)

225A

SEE MECHANICAL DRAWINGS

FOR EQUIPMENT REMOVAL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL DEMOLITION ONE-LINE

DIAGRAM

100% STAMPED FINAL

DESIGN

FULLY SPRINKLERED

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

2023-06-23

ED602

BLDG 12

528A5-20-502

JFF CJR

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

6/23/2023

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

FVNR

AutoCAD SHX Text 3/4

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text

CP

AutoCAD SHX Text

CP

AutoCAD SHX Text

CP

AutoCAD SHX Text 30A

AutoCAD SHX Text 30A

AutoCAD SHX Text 30A

AutoCAD SHX Text 60A

AutoCAD SHX Text 3/4

AutoCAD SHX Text 3/4

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text

VFC

AutoCAD SHX Text

VFC

AutoCAD SHX Text

VFC

AutoCAD SHX Text

VFC

AutoCAD SHX Text

VFC

AutoCAD SHX Text

VFC

AutoCAD SHX Text 30A

AutoCAD SHX Text 30A

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

FVNR

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

FVNR

AutoCAD SHX Text 24kW

AutoCAD SHX Text 60A

AutoCAD SHX Text H

AutoCAD SHX Text 1.5

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text 3/4

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text 1.5

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

FVNR

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

FVNR

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

CP

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

CP

AutoCAD SHX Text M

AutoCAD SHX Text .25

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text G

AutoCAD SHX Text 1.5

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text 3/4

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text 1.5

AutoCAD SHX Text M

AutoCAD SHX Text 30A

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

P

MLKJHGFEDCBA

7.1

4.4

H01

H01

H01

H01H01

H01 H01

H01 H01

H01H01

C01

C01 C01

C01 C01

C01 C01

UTILITY ROOM

A106

STAIRS

A111

CONTROL ROOM

A105

ELECTRICAL ROOM

A103

WORKSHOP

B101

BOILER ROOM

A102

MEN

A107

JANITOR

A109

WOMEN

A108

B02B02B02

C01

C01

E01

E01

E01

E01

A01

A01

G01 G01

G01 G01 G01

G01 G01

G01

C01

C01 C01 C01

C01C01

C01 C01

C01 C01

C01 C01

A01

B02 B02

E01

I01

9 TYP

I01

I01 a b a b

I01

I01 I01

I01

I01 I01

I01

I01

DP-4

DP-1

A01

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-5

DP-5

1 DP-5

DP-1

3 DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

9 DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-5

DP-5

DP-5

DP-1

DP-1

DP-1

STORAGE

A101

STAIRS

A002 c c c d d d d g g g e e e ee e e h

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

EL101

ELECTRICAL LIGHTING PLAN -

LOWER LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

KEYPLAN

B12

B11

PARKING

N

N

SCALE: 1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - LOWER LEVEL

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #.

3. SEE EP600 SERIES FOR DETAILED CIRCUITING INFORMATION.

KEYED NOTES

1 RECONNECT LIGHTS TO EXISTING CIRCUITS.

2 INSTALL NEW LIGHTS UNDER THE WORKSHOP PLATFORM ALONG CENTRAL BEAM

NEAREST GRID LINE C.

3 LOCATE LIGHT SWTICH NEXT TO WORKSHOP PLATFORM ACCESS DOOR.

4 INSTALL NEW LIGHTS UNDER THE BOILER PLATFORM ALONG CENTERLINE.

5 MOUNT LIGHTS TO CEILING.

6 RECESS LIGHT FIXTURES IN CEILING IN BATHROOMS AND JANITOR'S CLOSET.

7 MOUNT LIGHT TO CEILING IN STAIR A002.

8 SUSPEND LIGHTS 3 FEET FROM CEILING IN STAIR A002.

9 ALL EXIT SIGNS TO BE EXIT AND EMERGENCY LIGHT COMBINATION.

Revisions: Date:

i i i i j jj

6/23/2023

MLKJHGFEDCBA

7.1

4.4

C01

D01 D01 D01

C01 C01

C01

D01 D02

D02D01

D01 D02

D02D01

D02 D01 D02 D01

D02

D01

D02

D02 D01 D02

D02 D01 D02

D02

D02 D01 D02

D02

D02 D02 D01

C01

C01

C01

C01C01

C01 C01

C01 C01

D01 D01

D01

D01

D01

FED FROM

EMERGENCY GEN PANEL

D02

D01

D01

F01

F01 F01

F01

F01

F01

G01

G01H01 H01

B01 B01 B01

B02B02B02

B01 B01

B01

5 6 a a a a a a a a a a a a aa a a a a a a a a a b b b b b b b b b b b b b b b

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

1 DP-1

DP-1

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

DP-4

I01

I01

STORAGE

A101

BOILER ROOM

A102

WORKSHOP

B101

OFFICE

B102 f f fff h h h h h h hh h h h i i i i i i i ii

I01

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

EL102

ELECTRICAL LIGHTING PLAN - UPPER

LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

KEYPLAN

B12

B11

PARKING

N

SCALE: 1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - UPPER LEVELN

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE EL601 FOR LIGHTING FIXTURE SCHEDULE.

3. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

4. SEE EP600 SERIES FOR DETAILED CIRCUITING INFORMATION.

KEYED NOTES

1 SUSPEND LIGHT FIXTURES 19 FEET ABOVE FINISHED FLOOR.

2 SUSPEND LIGHT FIXTURES 15 FEET AND 3 INCHES ABOVE MEZZANINE DECK.

3 LIGHT FIXTURES RECESSED IN CEILING OF SUPERVISOR'S OFFICE.

4 SUSPEND LIGHT FIXTURES 7 FEET AND 5 INCHES ABOVE FINISHED FLOOR.

5 SUSPEND LIGHT FIXTURES 14 FEET ABOVE FINISHED FLOOR.

6 SUSPEND LIGHT FIXTURES 18 FEET ABOVE FINISHED FLOOR.

7 SUSPEND LIGHT FIXTURES 32 FEET AND 5 INCHES ABOVE FINISHED FLOOR.

8 SUSPEND LIGHT FIXTURES 14 FEET AND 6 INCHES ABOVE FINISHED FLOOR.

9 SUSPEND LIGHT FIXTURES 15 FEET ABOVE FINISHED FLOOR.

10 RECONNECT LIGHTS TO EXISTING CIRCUIT.

Revisions: Date:

e e e e e e

MLKJ

7.1

4.4

E01

E01

E01

E01

E01

B01B01B02

B01 B02 B01

B01B01

D01

D01

D01

D01

STORAGE

A001

E01 1

I01

I01

I01

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-1

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

DP-5

3DP-1

DP-1

j

STAIRS

A002 j k k k k k k k k k

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

EL103

ELECTRICAL LIGHTING PLAN

-STORAGE A001 BLDG 12

JFF DGA

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN -STORAGE A001

KEYPLAN

B12

B11

PARKING

N

N

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE EL601 FOR LIGHTING FIXTURE SCHEDULE.

3. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

4. SEE EP600 SERIES FOR DETAILED CIRCUITING INFORMATION.

KEYED NOTES

1 WALL MOUNT FIXTURE 8 FEET ABOVE FLOOR.

2 WALL MOUNT FIXTURES 19 FEET ABOVE FLOOR.

3 SUSPEND LIGHT FIXTURES 11 FEET AND 5 INCHES ABOVE GRATED FLOOR.

4 SUSPEND LIGHT FIXTURE 17 FEET ABOVE FINISHED FLOOR.

5 SUSPEND LIGHT FIXTURE 14 FEET AND 7 INCHES ABOVE FINISHED FLOOR.

Revisions: Date:

RE-CONNECT LIGHTS ON

DP-1 6 TO EXISTING

SWITCHING CIRCUIT

NOTE:

1. ALL SUPPORTS SHALL BE ASTM A36 PLAIN CARBON STEEL, HOT DIP

GALVANIZED AFTER FABRICATION.

BLOCK WALL

RIGID CONDUIT

1/4" PLATE

WELDED TO DOOR

FRAME

DOOR FRAME

EXIST SIGN FASTENED TO

PLATE WITH NUT, BOLT &

WASHER

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION

SECTION 26 51 00

LUMINAIRE

(REFER TO

SCHEDULE)

LUMINAIRE (REFER

TO SCHEDULE)

FIXTURE WHIP FROM

JUNCTION BOX (6'-0"

LONG MAX)

LUMINAIRE SUSPENSION WIRES

REFER TO SPECIFICATION

SECTION 26 51 00

3 TWIST

MINIMUM, TYP

ARCHITECTURAL CEILING GRID

ACOUSTICAL

CEILING TILE, TYP

NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE

LIGHTING FIXTURE SCHEDULE

MARK DESCRIPTION

LAMPS

LENS FINISH MOUNTING BASIS OF DESIGN NOTES

TYPE VOLTS WATTS

A01 4FT WATERPROOF LED FIXTURE, 4000LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

29.4W FROSTED ACRYLIC FIBERGLASS REINFORCED POLYESTER SURFACE MOUNTED

DAY-BRITE / CFI VAPORLUME LED SEALED INDUSTRIAL DW BY

SIGNIFY PART# DWAE35L840-4-UNV-EMLED

WET LOCATION: 1P65

EMERGENCY BATTERY

B01 / B02

4FT GENERAL LED FIXTURE, 4000LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

31W FROSTED ACRYLIC POLYESTER POWDER FINISH SUSPENDED

DAY-BRITE / CFI LED LINEAR SUSPENDED LBX LUMINAIRES BY

SIGNIFY PART# LBX40L840-UNV

B02 ADD EMERGENCY BATTERY OPTION

C01 4FT GENERAL LED FIXTURE, 5500LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

41W FROSTED ACRYLIC POLYESTER POWDER FINISH SUSPENDED

DAY-BRITE / CFI LED LINEAR SUSPENDED LBX LUMINAIRES BY

SIGNIFY PART# LBX55L840-UNV

D01 / D02

4FT GENERAL LED FIXTURE, 9000LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

66W FROSTED ACRYLIC POLYESTER POWDER FINISH SUSPENDED

DAY-BRITE / CFI LED LINEAR SUSPENDED LBX LUMINAIRES BY

SIGNIFY PART# LBX90L840-UNV

D02 ADD EMERGENCY BATTERY OPTION

E01 4FT SEALED LED FIXTURE, 4000LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

32W

FROSTED

POLYCARBONATE

WHITE POLYCARBONATE SURFACE MOUNTED DAY-BRITE / CFI FLUXSTREAM LED SEALED STRIP BY SIGNIFY

PART# FSX440L840-UNV

IMPACT RESISTANT: IK08

F01 4FT SLATTED LED FIXTURE, 4000LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

27W FROSTED ACRYLIC POLYESTER POWDER FINISH SUSPENDED

DAY-BRITE / CFI 5FL LED SPECIFICATION INDUSTRIAL BY

SIGNIFY PART# 5FL440L840-PP2-UNV

G01 2FT x 4FT RECESSED LED FIXTURE, 3200LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

27.4W FROSTED ACRYLIC HIGH REFLECTANCE BAKED WHITE ENAMEL RECESSED

DAY-BRITE / CFI T-GRID LED TROFFER BY SIGNIFY PART#

TG32L840-4-FS-02F-UNV

H01 2FT x 2FT RECESSED LED FIXTURE, 3800LM, MIN 80 CRI LED

UNIVERSAL

(120-277V)

34W FROSTED ACRYLIC HIGH REFLECTANCE BAKED WHITE ENAMEL RECESSED

DAY-BRITE / CFI T-GRID LED TROFFER BY SIGNIFY

PART# 2STXG38B8400-2-DS-UNV-S-WL

WET LOCATION

I01 RED LED EXIT/UNIT COMBO, ROUNDLAMP HEADS LED

UNIVERSAL

(120-277V)

2W

ALL-INCLUSIVE LAMP,

REFLECTOR, AND LENS

ASSEMBLY

WHITE THERMOPLASTIC

TOP, END, OR BACK

MOUNT

LITHONIA LIGHTING CONTRACTOR SELECT

PART# ECRG RD M6

CRI: RD 80CRI

CCT: RD 6200K

RD 85 LUMENS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

EL501

ELECTRICAL LIGHTING DETAILS

BLDG 12

KRK RJB

FULLY SPRINKLERED

SCALE: NTS1

LIFE SAFETY - EXIT SIGN

SCALE: NTS2

LUMINAIRE MOUNTING - LAY-IN CEILING

Revisions: Date:

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

S B

GFCI

G F

C I

G F

C I

GFCI

GFCI

GFCI

J

GFCI

G F

C I

GFCI

G F

C I

GFCI

G F

C I

J

GFCI GFCI

G F

C I

G F

C I

GFCI

GFCI

G F

C I

G F

C I

G F C I

GFCI

G F

C I

G F

C I

MLKJHGFEDCBA

7.1

8 8

FLASH TANK

ECONOMIZER

BLOWDOWN

SEPERATOR

GENERATOR

GD-1 DISC

GD-2 DISC

480V

SWGR-ATS

VFD'S

(EXISTING)

EF-6 DISC

PP-5

EF-7 DISC

AIR COMPRESSOR

AC-1

FUEL 1 DISC

FUEL 2 DISC

EXISTING

FUEL OIL

PUMP

EXISTING

CONDENSATE

VACUUM PUMP

EUH-2 DISC

(4) 2 AWG

(1) 8 AWG GND

IN 1 1/2" RMC

(4) 2 AWG

(1) 8 AWG GND

IN 1 1/2" RMC

(4) 2 AWG

(1) 8 AWG GND

IN 1 1/2" RMC

(2) 10 AWG

(1) 12 AWG GND

IN 3/4" RMC

PP-3

DUPLEX STEAM

CONDENSATE

PUMP

DUPLEX STEAM

CONDENSATE PUMP

4.44.4

(4) 6 AWG

(1) 10 AWG GND

IN 1-1/4" RMC

PP-6

DP-4

CONDENSATE TRANSFER

PUMPS 1 & 2 (BELOW

CONDENSATE TANK)

(4) #12 AWG

(1) #12 AWG GND

IN 1" CONDUIT

TO GENERATOR

ANNUNCIATOR PANEL

TO BLDG 16

EXISTING GENERATOR STUB-UPS.

INTERCEPT AND EXTEND TO

LOCATION OF NEW GENERATOR

UTILITY ROOM

A106

CONTROL ROOM

A105

BOILER ROOM

A102

STORAGE

A101

ELECTRICAL ROOM

A103

WORKSHOP

B101

T12.1

PP-1

PP-2

PP-4

PP-4

DP-3

DP-2

DP-1

DP-4

19,21,23

DP-4

14,16,18

T12.3

EF-4

STARTER

(EXISTING)

SAF-2 DISC

12-A102-BLR-002

FIRETUBE

BOILER

12-A102-BLR-003

FIRETUBE

BOILER

12-A102-BLR-001

FIRETUBE

BOILER

12-A101-UH-006

12-A101-UH-007

DP-5

T12.4

PP-7

T12.4

HWH-3 0.6

Gallon

HWH-2

PP-3

PP-5

PP-4

DP-2

2,4,6

T12.2

HWH-4 0.6

Gallon

DP-2

1,3,5

GD-3 DISC

DP-1

17,19,21

DP-2

13,15,17

DP-2

26,28,30

DP-2

20,22,24

PP-4

PP-1

EP401

EP402

PP-3

DISC N.

DUPLEX

SUMP

PUMPS

DISC S.

DUPLEX

SUMP

PUMPS

SAH-1 DISC

EUH-1 DISC

SAF-1 DISC

SAH-2 DISCEUH-3 DISCSAF-3 DISC

STAIRS

A002

PP-5

2,4,6

CP-10

CP-11

T

PP-7

T

T

SUMP PUMPS. INTERRUPTION

OF SUMP PUMPS MUST BE

COORDINATED WITH VA COR.

IN NO CASE SHALL SUMP

PUMPS BE LEFT OFF AND

UNMONITORED.

SUMP PUMPS. INTERRUPTION

OF SUMP PUMPS MUST BE

COORDINATED WITH VA COR.

IN NO CASE SHALL SUMP

PUMPS BE LEFT OFF AND

UNMONITORED.

PP-7

PP-7

PP-7

EXISTING CONDUITS TO FORMER

FIRE PUMP CONTROLLER TO BE

ABANDONED

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING) (EXISTING)

WOMEN

A108

MEN

A107

STAIRS

A111

MECH

A104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CONSULTANT

321 4 5 6 7 8 9 10 on e ei gh th in ch o ne fo ot t h re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" t h re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot t h re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

REV 0 - 100% STAMPED FINAL DESIGN 2023-06-23

100% STAMPED FINAL

DESIGN

DESIGN BOILER REPLACEMENT -

CANANDAIGUA VAMC

400 FORT HILL AVENUE

CANANDAIGUA, NY 14424

528A5-20-502

2023-06-23

EP101

ELECTRICAL POWER PLAN - LOWER

LEVEL BLDG 12

JFF DGA

FULLY SPRINKLERED

N

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA #

3. SEE EP600 SERIES FOR DETAILED CIRCUITING INFORMATION.

KEYPLAN

B12

B11

PARKING

N

SCALE: 1/8" = 1'-0"1

ELEC…