260553-RIB-Identification for Electrical Systems-12-24-2025.pdf
PDF 76 KB Posted
- Attached to
- CBI GJ HVAC/Lighting Upgrade Project
- Solicitation number
- IFB1 REAA 2027000005 3
- Issued by
- Morgan County, Colorado
About this file
This is a technical specification document for Section 260553 - Identification for Electrical Systems, part of the 25-388 CBI HVAC and Lighting Upgrade project. The specification establishes comprehensive requirements for identifying electrical systems, equipment, and conductors throughout the project. Key identification requirements include nameplates for switchgear, switchboards, panelboards, transformers, circuit breakers, and motor controllers; voltage and phase designations; circuit numbering and load identification; arc flash hazard warning labels for equipment likely to require energized maintenance; and wire and cable markers. All identification products must comply with ANSI Z535.2, ANSI Z535.4, NFPA 70, NFPA 70E, and UL 969 standards. Approved manufacturers for nameplates and labels include Brimar Industries, Kolbi Pipe Marker Co, Seton Identification Products, Brady Corporation, HellermannTyton, Panduit Corp, and Clarion Safety Systems. The specification requires factory pre-printed or machine-printed text rather than handwritten identification, with specific size, color, and material requirements for different application types.
Installation requirements mandate that all identification products be plainly visible for examination, adjustment, servicing, and maintenance, with specific placement guidelines for surface-mounted, flush-mounted, free-standing, and elevated equipment. Identification products must be installed centered, level, and parallel with items being identified, using stainless steel screws for exterior surfaces and self-adhesive backing or epoxy cement for interior surfaces. No pricing, contract term, set-asides, or award information is contained in this specification document, which functions solely as a technical requirements guide for the electrical identification work scope.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 260553 - 1 Identification for Electrical
Systems
SECTION 260553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Electrical identification requirements.
B. Identification nameplates and labels.
C. Wire and cable markers.
D. Voltage markers.
E. Underground warning tape.
F. Warning signs and labels.
1.02 RELATED REQUIREMENTS
A. Section 260519 - Low-Voltage Electrical Power Conductors and Cables: Color coding for power conductors and cables 600 V and less; vinyl color coding electrical tape.
B. Section 260536 - Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.
C. Section 262300 - Low-Voltage Switchgear: Factory-installed mimic bus.
D. Section 271000 - Structured Cabling: Identification for communications cabling and devices.
1.03 REFERENCE STANDARDS
A. ANSI Z535.2 - American National Standard for Environmental and Facility Safety Signs; 2023.
B. ANSI Z535.4 - American National Standard for Product Safety Signs and Labels; 2023.
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
D. NFPA 70E - Standard for Electrical Safety in the Workplace; 2024.
E. UL 969 - Marking and Labeling Systems; Current Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Verify final designations for equipment, systems, and components to be identified prior to fabrication of identification products.
B. Sequencing:
1. Do not conceal items to be identified, in locations such as above suspended ceilings, until identification products have been installed.
2. Do not install identification products until final surface finishes and painting are complete.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittals procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for each product.
1.06 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
1.07 FIELD CONDITIONS
A. Do not install adhesive products when ambient temperature is lower than recommended by manufacturer.
PART 2 PRODUCTS
2.01 IDENTIFICATION REQUIREMENTS
Upgrade 260553 - 2 Identification for Electrical
Systems
A. Identification for Equipment:
1. Use identification nameplate to identify each piece of electrical distribution and control equipment and associated sections, compartments, and components.
a. Switchgear:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify power source and circuit number. Include location when not within sight of equipment.
4) Use identification nameplate to identify load(s) served for each branch device.
Do not identify spares and spaces.
b. Switchboards:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify power source and circuit number. Include location when not within sight of equipment.
4) Use identification nameplate to identify load(s) served for each branch device.
Do not identify spares and spaces.
c. Panelboards:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify power source and circuit number. Include location when not within sight of equipment.
4) Use typewritten circuit directory to identify load(s) served for panelboards with a door. Identify spares and spaces using pencil.
5) For power panelboards without a door, use identification nameplate to identify load(s) served for each branch device. Do not identify spares and spaces.
d. Transformers:
1) Identify kVA rating.
2) Identify voltage and phase for primary and secondary.
e. Enclosed switches, circuit breakers, and motor controllers:
1) Identify voltage and phase.
f. Enclosed Contactors:
1) Identify ampere rating.
2) Identify voltage and phase.
g. Centralized Emergency Lighting Inverters:
1) Identify input and output voltage and phase.
h. Transfer Switches:
1) Identify voltage and phase.
2) Identify short circuit current rating based on the specific overcurrent protective device type and settings protecting the transfer switch.
2. Service Equipment:
a. Use identification nameplate to identify each service disconnecting means.
3. Emergency System Equipment:
a. Use identification nameplate or voltage marker to identify emergency system equipment in accordance with NFPA 70.
b. Use identification nameplate at each piece of service equipment to identify type and location of on-site emergency power sources.
4. Available Fault Current Documentation: Use identification label to identify the available fault current and date calculations were performed at locations requiring documentation by NFPA 70 including but not limited to the following.
a. Service equipment.
b. Industrial control panels.
c. Motor control centers.
Upgrade 260553 - 3 Identification for Electrical
Systems
d. Elevator control panels.
e. Industrial machinery.
5. Arc Flash Hazard Warning Labels: Use warning labels to identify arc flash hazards for electrical equipment, such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers that are likely to require examination, adjustment, servicing, or maintenance while energized.
a. Minimum Size: 3.5 by 5 inches.
b. Legend: Include orange header that reads "WARNING", followed by the word message "Arc Flash and Shock Hazard; Appropriate PPE Required; Do not operate controls or open covers without appropriate personal protection equipment; Failure to comply may result in injury or death; Refer to NFPA 70E for minimum PPE requirements" or approved equivalent.
c. Service Equipment: Include the following information in accordance with NFPA 70.
1) Nominal system voltage.
2) Available fault current.
3) Date label applied.
B. Identification for Conductors and Cables:
1. Color Coding for Power Conductors 600 V and Less: Comply with Section 260519.
2. Use identification nameplate or identification label to identify color code for ungrounded and grounded power conductors inside door or enclosure at each piece of feeder or branch-circuit distribution equipment when premises has feeders or branch circuits served by more than one nominal voltage system.
2.02 IDENTIFICATION NAMEPLATES AND LABELS
A. Identification Nameplates:
1. Manufacturers:
a. Brimar Industries, Inc: www.brimar.com/#sle.
b. Kolbi Pipe Marker Co: www.kolbipipemarkers.com/#sle.
c. Seton Identification Products: www.seton.com/#sle.
2. Materials:
a. Indoor Clean, Dry Locations: Use plastic nameplates.
3. Plastic Nameplates: Two-layer or three-layer laminated acrylic or electrically non-conductive phenolic with beveled edges; minimum thickness of 1/16 inch; engraved text.
4. Mounting Holes for Mechanical Fasteners: Two, centered on sides for sizes up to 1 inch high; Four, located at corners for larger sizes.
B. Identification Labels:
1. Materials: Use self-adhesive laminated plastic labels; UV, chemical, water, heat, and abrasion resistant.
2. Text: Use factory pre-printed or machine-printed text. Do not use handwritten text unless otherwise indicated.
2.03 WIRE AND CABLE MARKERS
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. HellermannTyton: www.hellermanntyton.com/#sle.
3. Panduit Corp: www.panduit.com/#sle.
B. Markers for Conductors and Cables: Use wrap-around self-adhesive vinyl cloth, wrap-around self-adhesive vinyl self-laminating, heat-shrink sleeve, plastic sleeve, plastic clip-on, or vinyl split sleeve type markers suitable for the conductor or cable to be identified.
C. Markers for Conductor and Cable Bundles: Use plastic marker tags secured by nylon cable ties.
D. Legend: Power source and circuit number or other designation indicated.
E. Text: Use factory pre-printed or machine-printed text, all capitalized unless otherwise indicated.
Upgrade 260553 - 4 Identification for Electrical
Systems
F. Minimum Text Height: 1/8 inch.
G. Color: Black text on white background unless otherwise indicated.
2.04 VOLTAGE MARKERS
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. Brimar Industries, Inc: www.brimar.com/#sle.
3. Seton Identification Products: www.seton.com/#sle.
B. Minimum Size:
1. Markers for Equipment: 1 1/8 by 4 1/2 inches.
C. Legend:
D. Color: Black text on orange background unless otherwise indicated.
2.05 WARNING SIGNS AND LABELS
A. Manufacturers:
1. Brimar Industries, Inc: www.brimar.com/#sle.
2. Clarion Safety Systems, LLC: www.clarionsafety.com/#sle.
3. Seton Identification Products: www.seton.com/#sle.
B. Comply with ANSI Z535.2 or ANSI Z535.4 as applicable.
C. Warning Signs:
1. Materials:
2. Minimum Size: 7 by 10 inches unless otherwise indicated.
D. Warning Labels:
1. Materials: Use factory pre-printed or machine-printed self-adhesive polyester or self-adhesive vinyl labels; UV, chemical, water, heat, and abrasion resistant; produced using materials recognized to UL 969.
2. Machine-Printed Labels: Use thermal transfer process printing machines and accessories recommended by label manufacturer.
3. Minimum Size: 2 by 4 inches unless otherwise indicated.
PART 3 EXECUTION
3.01 PREPARATION
A. Clean surfaces to receive adhesive products according to manufacturer's instructions.
3.02 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Install identification products to be plainly visible for examination, adjustment, servicing, and maintenance. Unless otherwise indicated, locate products as follows:
1. Surface-Mounted Equipment: Enclosure front.
2. Flush-Mounted Equipment: Inside of equipment door.
3. Free-Standing Equipment: Enclosure front; also enclosure rear for equipment with rear access.
4. Elevated Equipment: Legible from the floor or working platform.
5. Branch Devices: Adjacent to device.
6. Interior Components: Legible from the point of access.
7. Conductors and Cables: Legible from the point of access.
C. Install identification products centered, level, and parallel with lines of item being identified.
D. Secure nameplates to exterior surfaces of enclosures using stainless steel screws and to interior surfaces using self-adhesive backing or epoxy cement.
E. Install self-adhesive labels and markers to achieve maximum adhesion, with no bubbles or wrinkles and edges properly sealed.
Upgrade 260553 - 5 Identification for Electrical
Systems
F. Mark all handwritten text, where permitted, to be neat and legible.
END OF SECTION
260553 - Identification for Electrical Systems