230719-RIB-HVAC Piping Insulation-12-24-2025.pdf

PDF 85 KB Posted

Attached to
CBI GJ HVAC/Lighting Upgrade Project
Solicitation number
IFB1 REAA 2027000005 3
Issued by
Morgan County, Colorado

About this file

This is a technical specification document for HVAC piping insulation work as part of project 25-388 CBI HVAC and Lighting Upgrade. The specification outlines comprehensive requirements for installing piping insulation systems, including flexible removable and reusable blanket insulation, rigid and flexible glass fiber insulation, hydrous calcium silicate insulation, and flexible elastomeric cellular insulation. The work encompasses insulation of heating system piping (hot water supply and return, low-pressure steam, and condensate lines), cooling system piping (chilled water, condenser water, refrigerant suction, and hot gas lines), jacketing materials, vapor barriers, inserts and shields, and engineered wall outlet seals with refrigerant piping protection systems. Installation requirements specify varying insulation thicknesses based on piping diameter and fluid temperature ranges, with hot water heating systems requiring 1 to 2 inches of rigid glass fiber insulation, steam systems requiring 4.5 to 5 inches, and refrigerant lines requiring 0.5 to 1 inch of flexible elastomeric insulation. The specification references multiple ASTM standards for thermal properties, surface burning characteristics, moisture absorption, and water penetration testing.

The document establishes product standards requiring manufacturers with a minimum of three years of documented experience and applicators with minimum three-year track records in piping insulation installation. All materials must comply with ASTM E84 or UL 723 standards with flame spread index and smoke development index not exceeding 25/50. Specific manufacturers are approved for glass fiber, calcium silicate, and elastomeric insulation products, with substitutions permitted under Section 016000 provisions. Installation must follow manufacturer instructions with particular attention to vapor barrier application for below-ambient temperature piping, exterior applications requiring aluminum jackets with UV-resistant finishes, and buried piping requiring factory-fabricated assemblies with bituminous compound protection. Field conditions must maintain ambient temperatures required by manufacturers for a minimum of 24 hours before, during, and after installation. No pricing information, award dates, response deadlines, or funding sources are specified in this technical specification document.

View the file

Other files

File Type Posted
230923 Alerton Direct Digital Control System for HVAC.pdf PDF
TYPE S1 iO-CoviO-Spec-Sheet.pdf PDF
260553-RIB-Identification for Electrical Systems-12-24-2025.pdf PDF
232113-RIB-Hydronic Piping-12-24-2025.pdf PDF
235100-RIB-Breechings, Chimneys, and Stacks-12-24-2025.pdf PDF
262726-RIB-Wiring Devices-12-24-2025.pdf PDF
260505-RIB-Selective Demolition for Electrical-12-24-2025.pdf PDF
CBI GJ Project Manual_VSS_R2.pdf PDF
TYPE EMX CMB-ISOLITE-Specification.pdf PDF
230523-RIB-General-Duty Valves for HVAC Piping-12-24-2025.pdf PDF
TYPE P2 Metalux-Cruze-Linear-Bay-spec-sheet.pdf PDF
238126.13-RIB-Small-Capacity Split-System Air Conditioners-12-24-2025.pdf PDF
Bid Questions - BCE Response - 05012026.pdf PDF
CBI GJ sign-in.pdf PDF
260519-RIB-Low-Voltage Electrical Power Conductors and Cables-12-24-2025.pdf PDF
230513-RIB-Common Motor Requirements for HVAC Equipment-12-24-2025.pdf PDF
TYPE D3 PrentaLux-CYL6-6-Sustainable-LED-Cylinder-Luminaire-Spec-Sheet.pdf PDF
232123-RIB-Hydronic Pumps-12-24-2025.pdf PDF
235216-RIB-Condensing Boilers-12-24-2025.pdf PDF
265600-RIB-Exterior Lighting-12-24-2025.pdf PDF
TYPE IU Sure-Lites-SLX-Surface-Mount-LED.pdf PDF
221006-RIB-Plumbing Piping Specialties-12-24-2025.pdf PDF
233423-RIB-HVAC Power Ventilators-12-24-2025.pdf PDF
231123-RIB-Facility Natural-Gas Piping-12-24-2025.pdf PDF
265100-RIB-Interior Lighting-12-24-2025.pdf PDF
230593-RIB-Testing, Adjusting, and Balancing for HVAC-12-24-2025.pdf PDF
232114-RIB-Hydronic Specialties-12-24-2025.pdf PDF
220529-RIB-Hangers and Supports for Plumbing Piping and Equipment-12-24-2025.pdf PDF
260923-RIB-Lighting Control Devices-12-24-2025.pdf PDF
260583-RIB-Wiring Connections-12-24-2025.pdf PDF
230800-RIB-Commissioning of HVAC-12-24-2025.pdf PDF
233100-RIB-HVAC Ducts and Casings-12-24-2025.pdf PDF
230553-RIB-Identification for HVAC Piping and Equipment-12-24-2025.pdf PDF
230913-RIB-Instrumentation and Control Devices for HVAC-12-24-2025.pdf PDF
25388-CBI 100% CD w Add1.pdf PDF
230529-RIB-Hangers and Supports for HVAC Piping and Equipment-12-24-2025.pdf PDF
220553-RIB-Identification for Plumbing Piping and Equipment-12-24-2025.pdf PDF
221005-RIB-Plumbing Piping-12-24-2025.pdf PDF
265140-LUT-Luminaires-12-24-2025.pdf PDF
Answers to Questions_IFB REAA 2027-05.pdf PDF
237413-RIB-Packaged Outdoor Central-Station Air-Handling Units-12-24-2025.pdf PDF
TYPE P1 Corelite-Iridium-i3-Suspended-specification-sheet.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

25-388 CBI HVAC and Lighting Upgrade 230719 - 1 HVAC Piping Insulation

SECTION 230719

HVAC PIPING INSULATION

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Piping insulation.

B. Flexible removable and reusable blanket insulation.

C. Jacketing and accessories.

D. Engineered wall outlet seals and refrigerant piping insulation protection.

1.02 RELATED REQUIREMENTS

A. Section 078400 - Firestopping.

B. Section 232113 - Hydronic Piping: Placement of hangers and hanger inserts.

C. Section 232300 - Refrigerant Piping: Placement of inserts.

1.03 REFERENCE STANDARDS

A. ASTM C177 - Standard Test Method for Steady-State Heat Flux Measurements and Thermal

Transmission Properties by Means of the Guarded-Hot-Plate Apparatus; 2019, with Editorial Revision (2023).

B. ASTM C195 - Standard Specification for Mineral Fiber Thermal Insulating Cement; 2007 (Reapproved 2024).

C. ASTM C449 - Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement; 2007 (Reapproved 2024).

D. ASTM C518 - Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus; 2021.

E. ASTM C533 - Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation;

2017 (Reapproved 2023).

F. ASTM C534/C534M - Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form; 2025.

G. ASTM C547 - Standard Specification for Mineral Fiber Pipe Insulation; 2022a.

H. ASTM C553 - Standard Specification for Mineral Fiber Blanket Thermal Insulation for

Commercial and Industrial Applications; 2024.

I. ASTM C795 - Standard Specification for Thermal Insulation for Use in Contact with Austenitic

Stainless Steel; 2008 (Reapproved 2023).

J. ASTM D570 - Standard Test Method for Water Absorption of Plastics; 2022.

K. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;

2024.

L. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor

Transmission Rate of Materials; 2024a.

M. ASTM E283/E283M - Standard Test Method for Determining Rate of Air Leakage Through

Exterior Windows, Skylights, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen; 2019.

N. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference; 2000 (Reapproved 2023).

O. ASTM E2178 - Standard Test Method for Determining Air Leakage Rate and Calculation of Air Permeance of Building Materials; 2021a.

P. ASTM G21 - Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi; 2015, with Editorial Revision (2021).

Upgrade 230719 - 2 HVAC Piping Insulation

Q. ASTM G153 - Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials; 2013 (Reapproved 2021).

R. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials; Current Edition, Including All Revisions.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations.

1.05 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with not less than three years of documented experience.

B. Applicator Qualifications: Company specializing in performing the type of work specified in this section with minimum 3 years of experience.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Accept materials on site, labeled with manufacturer's identification, product density, and thickness.

1.07 FIELD CONDITIONS

A. Maintain ambient conditions required by manufacturers of each product.

B. Maintain temperature before, during, and after installation for minimum of 24 hours.

PART 2 PRODUCTS

2.01 REGULATORY REQUIREMENTS

A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.

2.02 GLASS FIBER, FLEXIBLE

A. Manufacturers:

1. JP Lamborn Co; Thermal Sleeve MT: www.jpflex.com/#sle.

2. Substitutions: See Section 016000 - Product Requirements.

B. Insulation: ASTM C553; flexible, noncombustible blanket.

1. K Value: 0.36 at 75 degrees F, when tested in accordance with ASTM C518.

2. Maximum Service Temperature: 1,200 degrees F.

3. Maximum Water Vapor Absorption: 5.0 percent by weight.

C. Vapor Barrier Jacket:

1. Kraft paper with glass fiber yarn and bonded to aluminized film.

2. Moisture Vapor Permeability: 0.02 perm inch, when tested in accordance with ASTM

E96/E96M.

3. Secure with pressure-sensitive tape.

D. Vapor Barrier Tape:

1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film with pressure-sensitive rubber-based adhesive.

E. Outdoor Vapor Barrier Mastic:

1. Vinyl emulsion type acrylic or mastic, compatible with insulation, black color.

F. Tie Wire: Annealed steel, 16 gauge, 0.0508 inch diameter.

2.03 GLASS FIBER, RIGID

A. Manufacturers:

1. CertainTeed Corporation: www.certainteed.com/#sle.

2. Johns Manville Corporation: www.jm.com/#sle.

Upgrade 230719 - 3 HVAC Piping Insulation

3. Knauf Insulation; Performance+ Earthwool 1000 Pipe Insulation:

www.knaufinsulation.com/#sle.

4. Owens Corning Corporation; Fiberglas Pipe Insulation ASJ: www.owenscorning.com/en-us/#sle.

5. Owens Corning Corporation; VaporWick Pipe Insulation: www.owenscorning.com/en-us/#sle.

6. Substitutions: See Section 016000 - Product Requirements.

B. Insulation: ASTM C547 and ASTM C795; rigid molded, noncombustible.

1. K Value: ASTM C177, 0.24 at 75 degrees F.

2. Maximum Service Temperature: 850 degrees F.

3. Maximum Moisture Absorption: 0.2 percent by volume.

C. Vapor Barrier Jacket: White kraft paper with glass fiber yarn, bonded to aluminized film;

moisture vapor transmission when tested in accordance with ASTM E96/E96M of 0.02 perm-inches.

D. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.

E. Vapor Barrier Lap Adhesive: Compatible with insulation.

F. Insulating Cement/Mastic: ASTM C195; hydraulic setting on mineral wool.

G. Fibrous Glass Fabric:

1. Cloth: Untreated; 9 oz/sq yd weight.

2. Blanket: 1.0 pcf density.

3. Weave: 5 by 5.

H. Indoor Vapor Barrier Finish:

1. Cloth: Untreated; 9 oz/sq yd weight.

2. Vinyl emulsion type acrylic, compatible with insulation, black color.

I. Outdoor Vapor Barrier Mastic: Vinyl emulsion type acrylic or mastic, compatible with insulation, black color.

J. Insulating Cement: ASTM C449.

2.04 FLEXIBLE REMOVABLE AND REUSABLE BLANKET INSULATION

A. Manufacturers:

1. Substitutions: See Section 016000 - Product Requirements.

B. Description: Custom cut and fabricated, removable and reusable blanket insulation system, consisting of inner liner, insulation layer, outer protective jacket, and fastening system.

C. Provide insulation system based on surface temperature of piping, installed location of piping, and maximum safe-to-touch temperature of jacketing.

D. Performance Criteria:

1. Safe-to-Touch Temperature of Jacketing: 140 degrees F.

2.05 HYDROUS CALCIUM SILICATE

A. Manufacturers:

1. Johns Manville Corporation; ______: www.jm.com/#sle.

2. Substitutions: See Section 016000 - Product Requirements.

B. Insulation: ASTM C533 and ASTM C795; rigid molded, asbestos free, gold color.

1. K Value: 0.40 at 300 degrees F, when tested in accordance with ASTM C177 or ASTM

C518.

2. Maximum Service Temperature: 1200 degrees F.

3. Density: 15 pcf.

C. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.

D. Insulating Cement: ASTM C449.

Upgrade 230719 - 4 HVAC Piping Insulation

2.06 FLEXIBLE ELASTOMERIC CELLULAR INSULATION

A. Manufacturers:

B. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM

C534/C534M Grade 1; use molded tubular material wherever possible.

1. Minimum Service Temperature: Minus 40 degrees F.

2. Maximum Service Temperature: 180 degrees F.

3. Connection: Waterproof vapor barrier adhesive.

C. Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation.

2.07 JACKETING AND ACCESSORIES

2.08 ENGINEERED WALL OUTLET SEALS AND REFRIGERANT PIPING INSULATION

PROTECTION

A. Manufacturers:

1. Airex Manufacturing, Inc; ____: www.airexmfg.com/#sle.

2. Substitutions: See Section 016000 - Product Requirements.

B. Basis of Design: Airex Manufacturing, Inc; www.airexmfg.com/#sle.

1. Pipe Penetration Wall Seal: Airex Titan Outlet.

2. Refrigeration Pipe Insulation Protection System: Airex E-Flex Guard.

3. Pipe Penetration Wall Seal and Insulation Protection System: Airex Pro-System Kit.

C. Pipe Penetration Wall Seal: Seals HVAC piping wall penetrations with compression gasket wall mounted rigid plastic outlet cover.

1. Wall Outlet Size, Stucco and Masonry Applications: 7-1/2 inch wide by 10 inch high.

a. Elastomeric Sleeve Diameter: 1-11/16 inch.

2. Wall Outlet Size, Siding and Compact Applications: 6-7/8 inch wide by 3-7/8 inch high.

a. Elastomeric Sleeve Diameter: 1-11/16 inch.

3. Outlet Cover Color: Gray.

4. Water Penetration: Comply with ASTM E331.

5. Air Leakage: Comply with ASTM E283/E283M.

6. Air Permeance: Comply with ASTM E2178.

D. Insulation Protection System: Refrigerant piping insulation PVC protective cover.

1. PVC Insulation Cover Color: Black with full-length velcro fastener.

2. Weatherization and Ultraviolet Exposure Protection: Comply with ASTM G153.

3. Water/Vapor Permeability: Comply with ASTM E96/E96M.

4. Anti-Fungal and Anti-Microbial Resistance: Comply with ASTM G21.

5. Flame Spread and Smoke Development Rating of 24/450: Comply with ASTM E84 or UL

723.

6. Water Absorption of Plastics: Comply with ASTM D570.

7. Adhesive free.

PART 3 EXECUTION

3.01 EXAMINATION

A. Test piping for design pressure, liquid tightness, and continuity prior to applying insulation materials.

B. Verify that surfaces are clean and dry, with foreign material removed.

3.02 INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Exposed Piping: Locate insulation and cover seams in least visible locations.

C. Insulated Pipes Conveying Fluids Below Ambient Temperature:

1. Insulate entire system, including fittings, valves, unions, flanges, strainers, flexible connections, pump bodies, and expansion joints.

Upgrade 230719 - 5 HVAC Piping Insulation

D. Glass Fiber Insulated Pipes Conveying Fluids Below Ambient Temperature:

1. Provide vapor barrier jackets, factory-applied or field-applied; secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive. Secure with outward clinch expanding staples and vapor barrier mastic.

2. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe. Finish with glass cloth and vapor barrier adhesive or PVC fitting covers.

E. For hot piping conveying fluids 140 degrees F or less, do not insulate flanges and unions at equipment, but bevel and seal ends of insulation.

F. For hot piping conveying fluids over 140 degrees F, insulate flanges and unions at equipment.

G. Glass Fiber Insulated Pipes Conveying Fluids Above Ambient Temperature:

1. Provide standard jackets, with or without vapor barrier, factory-applied, or field-applied.

Secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive.

Secure with outward clinch expanding staples.

2. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe. Finish with glass cloth and adhesive or PVC fitting covers.

H. Inserts and Shields:

1. Application: Piping 1-1/2 inches diameter or larger.

2. Shields: Galvanized steel between pipe hangers or pipe hanger rolls and inserts.

3. Insert location: Between support shield and piping and under the finish jacket.

4. Insert Configuration: Minimum 6 inches long, of same thickness and contour as adjoining insulation; may be factory fabricated.

5. Insert Material: Hydrous calcium silicate insulation or other heavy density insulating material suitable for the planned temperature range.

I. Continue insulation through walls, sleeves, pipe hangers, and other pipe penetrations. Finish at supports, protrusions, and interruptions. At fire separations, see Section 078400.

J. Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces (less than 10 feet above finished floor): Finish with ASJ vapor retarder jacket and longitudinal self sealing closure.

K. Exterior Applications: Provide vapor barrier jacket. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe, and finish with glass mesh reinforced vapor barrier cement. Cover with aluminum jacket with seams located on bottom side of horizontal piping. Provide two coats of UV-resistant finish for flexible elastomeric cellular insulation without jacketing.

L. Buried Piping: Provide factory-fabricated assembly with inner all-purpose service jacket with self-sealing lap, and asphalt impregnated open mesh glass fabric, with 1 mil, 0.001 inch thick aluminum foil sandwiched between three layers of bituminous compound; outer surface faced with polyester film.

M. Heat Traced Piping: Insulate fittings, joints, and valves with insulation of like material, thickness, and finish as adjoining pipe. Size large enough to enclose pipe and heat tracer.

Cover with aluminum jacket with seams located on bottom side of horizontal piping.

3.03 SCHEDULE

A. Heating Systems:

1. Heating Water Supply and Return: Fluid range: 105-140 deg F - less than 1.5" diameter:

1" rigid glass fiber, 1-1/2" and greater diameter piping: 1.5" rigid glass fiber. Fluid range:

141-200 deg F - less than 1.5" diameter: 1.5" rigid glass fiber, 1-1/2" and greater diameter piping: 2" rigid glass fiber.

2. Low Pressure Steam Piping: Less than 1.0" diameter: 4.5" rigid glass fiber, 1.0-8" diameter piping: 5" rigid glass fiber.

3. Low Pressure Steam Condensate: Less than 1.0" diameter: 4.5" rigid glass fiber, 1.0-8" diameter piping: 5" rigid glass fiber.

B. Cooling Systems:

Upgrade 230719 - 6 HVAC Piping Insulation

1. Chilled Water: Fluid range: 40-60 deg F - less than 1.5" diameter: 0.5" rigid glass fiber, 1- 1/2" and greater diameter piping: 1" rigid glass fiber.

2. Condenser Water: Less than 1.5" diameter: 0.5" rigid glass fiber, 1-1/2" and greater diameter piping: 1" rigid glass fiber.

3. Refrigerant Suction: Less than 1" diameter piping: 0.5" flexible elastomeric, 1" and greater diameter piping: 1" flexible elastomeric insulation.

4. Refrigerant Hot Gas: Less than 1" diameter piping: 0.5" flexible elastomeric, 1" and greater diameter piping: 1" flexible elastomeric insulation.

END OF SECTION

230719 - HVAC Piping Insulation