250244_RFQ_Exhibit_A_SOW_gmedits.docx

DOCX document 32 KB Posted

Attached to
Request For Quotes (RFQ) Fire Extinguisher Maintenance Service
Solicitation number
250244
Issued by
Orange County, California

About this file

This Scope of Work document outlines fire extinguisher maintenance service requirements for the Orange County Transportation Authority (OCTA) across six designated facilities in California. OCTA requires on an as-needed basis, with no guaranteed usage, comprehensive inspection, servicing, and repair services for an approximate inventory of 1,339 fire extinguishers of various types and sizes. Services include annual inspections, six-year internal maintenance, hydrostatic testing (five-year and twelve-year intervals), recharging, leak repairs, and provision of loaner units during off-site testing. The contractor must perform weekly or on-demand recharge services and conduct annual walk-through inspections at maintenance bases, coordinating all scheduling with OCTA's Manager of Facilities Maintenance or Storeroom Supervisor. Service locations include Garden Grove Base, Anaheim Base, Santa Ana Base, OC Streetcar facility, and two Irvine bases. Written questions must be submitted by April 30, 2026, with responses issued by May 4, 2026. The contract term is two years with a budgeted amount of $55,000, and award will be made to the lowest responsive, responsible firm on a lump-sum basis.

The contractor must maintain a minimum BD license issued by the State of California Fire Marshal. Invoices must include the purchase order number, base location, service date, and itemized service details, submitted via email to VendorInvoices@octa.net. Non-compliance with invoice requirements will result in payment processing delays. Bidders must bid on all line items in the Pricing Proposal to be considered responsive. All firms certifying their quote agree to comply with Ukraine/Russia-related economic sanctions imposed by the State of California and the United States Government, including Presidential Executive Orders 13660, 13661, 13662, 13685, and 14065. The contract will be awarded without further discussion, and the successful firm must comply with all applicable Equal Employment Opportunity Laws and Regulations.

View the file

Other files

File Type Posted
250244_RFQ_Exhibit_A_SOW.pdf PDF
250244_PP_v2-APPROVED.pdf PDF
250244_PS_v2.pdf PDF
250244_PP_v2.pdf PDF
250244_PP_GMEDITS.pdf PDF
250244_RFQ_Exhibit_D_General_Provisions.pdf PDF
250244_Commodity_Code.pdf PDF
250244_ICE.pdf PDF
250244_SOWV.pdf PDF
250244_Insurance_&_Indemnification_Review.pdf PDF
250244_RFQ_Exhibit_B_Price_Summary_Sheet.pdf PDF
250244_PM_Correspondence.pdf PDF
250244_R001047.pdf PDF
250244_RFQ_Exhibit_C_Insurance.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ 250244

EXHIBIT A

SCOPE OF WORK

FIRE EXTINGUISHER MAINTENANCE SERVICE

1. GENERAL DESCRIPTION

The Orange County Transportation Authority (OCTA) requires, on an as-needed basis, with no guaranteed usage, inspection, servicing, and repairs for all designated facilities’ fire extinguisher inventory. Depending on extinguisher type and condition at the time of service, a dry chemical, Halon or Halotron fire extinguisher will require one of the following:

· An annual inspection

· A six (6)-year internal maintenance or a hydrostatic test

· CO2 extinguisher annual service or a five (5)-year high-pressure hydrostatic test

2. SERVICE REQUIREMENTS

· Contractor shall provide fire extinguisher recharge services to designated facilities weekly or on an as-needed basis.

· Service shall include leak repairs and the provision of loaner extinguishers for units sent off-site for required testing at no additional cost to OCTA.

· Contractor shall perform an annual walk-through and service fire extinguishers at all listed maintenance bases.

· Annual inspection shall be scheduled by authorized OCTA personnel and shall include annual, six (6)-year, and hydrostatic testing as required by law.

· Inspection service shall include all standard preventative maintenance parts (e.g. O-rings), weighing, inspection and continuity test, hoses, etc.

· Contractor shall coordinate inspection scheduling with the OCTA’s Manager of Facilities Maintenance or the Storeroom Supervisor.

· Item service as required:

Item
Annual Inspection
6-year maintenance
5-year hydro test
12-year hydro test
Refill
Halontron – all sizes
X
X
X
X
CO2 Extinguisher – all sizes
X

X

X

Dry Chemical – all sizes
X
X
X
X
Amerex Class D Wheeled Extinguisher – 30 lbs.
X
X

X

3. TYPES OF TESTING

· Annual Inspection Requirements:

· Weigh the extinguisher

· Check the hose or nozzle for obstructions

· Inspect the valve (under the upper handle and inside the discharge port) for obstructions

· Replace the low-pressure seal

· Sound the cylinder to confirm the powder is free-flowing and the extinguisher is properly pressurized

· Six (6) Year Internal Maintenance Requirements:

· Discharge the extinguisher into a recycling system

· Disassemble and clean the extinguisher

· Inspect the interior of the cylinder

· Inspect valve stems

· Replace the collar O-ring

· Refill with proper extinguishing agent and recharge

· Hydrostatic Testing Requirements:

· Discharge into a recycling system

· Fill and pressurize the cylinder to three times its normal operating pressure, or ¾ of the original cylinder test pressure

· Inspect the cylinder under pressure for leaks and structural integrity

· Service the extinguisher in the same manner as a six (6)-year maintenance

4. SERVICE LOCATIONS

Contractor shall provide service at the following OCTA facilities as required:

Location
Address
Garden Grove Base
11790 Cardinal Circle, Garden Grove, CA 92643
Anaheim Base
1717 E. Via Burton, Anaheim, CA 92806
Santa Ana Base
4301 W. MacArthur Boulevard, Santa Ana, CA 92704
OC Streetcar
2008 W. 5th Street, Santa Ana, CA 92703
Irvine Sand Canyon Base
14736 Sand Canyon Road, Irvine, CA 92618
Irvine Construction Circle Base
16281 W. Construction Circle, Irvine, CA 92606

5. LICENSES/CERTIFICATIONS

· Contractor must maintain, at minimum, a BD license issued by the State of California Fire Marshal. Comment by Georgia Martinez: Spell out

· Failure to provide required licenses/certifications may deem the bidder non-responsive.

6. ADDITIONAL INFORMATION

· Approximate inventory of fire extinguishers:

Description
Quantity
2½ lb Extinguisher
250
5 lb Extinguisher
660
6 lb Extinguisher
8
10 lb Extinguisher
350
20 lb Extinguisher
60
15 lb CO2 Extinguisher
2
5 lb Halotron Extinguisher
8
30 lb Wheeled Extinguisher
1

· The following parts list is provided for informational purposes only and represents parts that may be required for fire extinguishers repair and service:

O-Rings: All Types

Valve stems: All Types

Gauges

Nozzles - Dry Chemical or Halotron

Hoses - Dry Chemical or Halotron, CO2, Wheeled Engines

Hose Bands: All types

Handles – Lower, upper

Halotron, CO2, BC Powder, ABC Powder, D Powder – per pound

7. INVOICING AND PAYMENT REQUIREMENTS

· Invoice Submission

· Invoices must include the following information:

· Purchase Order Number

· Base Location where the service was performed.

· Service date and itemized details of the service.

· Invoice Submission Methods

· Invoices should be submitted via email to:

· VendorInvoices@octa.net

· Payment Processing Delays

· Failure to comply with invoice requirements (e.g., missing documentation, unclear pricing, or invoice submission method outside of what is deemed acceptable) will result in processing delays, and subsequently the payment schedule.