Request For Quotes (RFQ) Fire Extinguisher Maintenance Service
Solicitation number
250244
Issued by
Orange County, California

About this file

This Scope of Work document outlines fire extinguisher maintenance service requirements for the Orange County Transportation Authority (OCTA) in California. OCTA seeks qualified contractors to provide inspection, servicing, and repair services for fire extinguishers at designated facilities on an as-needed basis with no guaranteed usage. The services encompass annual inspections, six-year internal maintenance, and hydrostatic testing for various extinguisher types including dry chemical, Halon, Halotron, and CO2 units. The OCTA maintains an approximate inventory of 1,339 fire extinguishers across multiple sizes, with the largest quantities being 660 five-pound extinguishers and 250 two-pound extinguishers. Service locations include six facilities across Orange County: Garden Grove Base, Anaheim Base, Santa Ana Base, OC Streetcar, and two Irvine locations. The contract term is two years with a total budget of $55,000. Questions or clarifications must be submitted in writing no later than 12 p.m. on April 30, 2026, with written responses issued by May 4, 2026. Award will be made on a lump sum basis to the lowest responsive and responsible firm.

Contractors must bid on all line items to be considered responsive and must maintain a Type B + Type D Concern License (BD) issued by the California Fire Marshal. Services include weekly or as-needed recharge services, leak repairs, loaner extinguisher provision during off-site testing at no additional cost, annual walk-through inspections at all maintenance bases, and coordination with OCTA's Manager of Facilities Maintenance. Contractor responsibilities also include providing standard preventative maintenance parts such as O-rings, valve stems, gauges, nozzles, hoses, handles, and various powder types. Invoicing requirements mandate inclusion of the purchase order number, base location, service date, and itemized service details submitted to VendorInvoices@octa.net. Non-compliance with invoice requirements will result in payment processing delays. Approved equals will be accepted, and firms must certify compliance with Ukraine/Russia-related economic sanctions imposed by California and the U.S. Government.

View the file

Other files

File Type Posted
250244_PP_v2-APPROVED.pdf PDF
250244_PS_v2.pdf PDF
250244_PP_v2.pdf PDF
250244_PP_GMEDITS.pdf PDF
250244_RFQ_Exhibit_A_SOW_gmedits.docx DOCX document
250244_RFQ_Exhibit_D_General_Provisions.pdf PDF
250244_Commodity_Code.pdf PDF
250244_ICE.pdf PDF
250244_SOWV.pdf PDF
250244_PM_Correspondence.pdf PDF
250244_R001047.pdf PDF
250244_RFQ_Exhibit_C_Insurance.pdf PDF
250244_Insurance_&_Indemnification_Review.pdf PDF
250244_RFQ_Exhibit_B_Price_Summary_Sheet.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ 250244

EXHIBIT A

SCOPE OF WORK

FIRE EXTINGUISHER MAINTENANCE SERVICE

1. GENERAL DESCRIPTION

The Orange County Transportation Authority (OCTA) requires, on an as-needed basis, with no guaranteed usage, inspection, servicing, and repairs for all designated facilities’ fire extinguisher inventory. Depending on extinguisher type and condition at the time of service, a dry chemical, Halon or Halotron fire extinguisher will require one of the following:

• An annual inspection

• A six (6)-year internal maintenance or a hydrostatic test

• CO2 extinguisher annual service or a five (5)-year high-pressure hydrostatic test

2. SERVICE REQUIREMENTS

• Contractor shall provide fire extinguisher recharge services to designated facilities weekly or on an as-needed basis.

• Service shall include leak repairs and the provision of loaner extinguishers for units sent off-site for required testing at no additional cost to OCTA.

• Contractor shall perform an annual walk-through and service fire extinguishers at all listed maintenance bases.

• Annual inspection shall be scheduled by authorized OCTA personnel and shall include annual, six (6)-year, and hydrostatic testing as required by law.

• Inspection service shall include all standard preventative maintenance parts (e.g.

O-rings), weighing, inspection and continuity test, hoses, etc.

• Contractor shall coordinate inspection scheduling with the OCTA’s Manager of

Facilities Maintenance or the Storeroom Supervisor.

• Item service as required:

Item Annual Inspection

6-year maintenance

5-year hydro test

12-year hydro test Refill

Halontron – all sizes X X X X

CO2 Extinguisher – all sizes X X X

Dry Chemical – all sizes X X X X

Amerex Class D Wheeled Extinguisher – 30 lbs.

X X X

3. TYPES OF TESTING

• Annual Inspection Requirements:

o Weigh the extinguisher o Check the hose or nozzle for obstructions o Inspect the valve (under the upper handle and inside the discharge port) for obstructions o Replace the low-pressure seal o Sound the cylinder to confirm the powder is free-flowing and the extinguisher is properly pressurized

• Six (6) Year Internal Maintenance Requirements:

o Discharge the extinguisher into a recycling system o Disassemble and clean the extinguisher o Inspect the interior of the cylinder o Inspect valve stems o Replace the collar O-ring o Refill with proper extinguishing agent and recharge

• Hydrostatic Testing Requirements:

o Discharge into a recycling system o Fill and pressurize the cylinder to three times its normal operating pressure, or

¾ of the original cylinder test pressure o Inspect the cylinder under pressure for leaks and structural integrity o Service the extinguisher in the same manner as a six (6)-year maintenance

4. SERVICE LOCATIONS

Contractor shall provide service at the following OCTA facilities as required:

Location Address Garden Grove Base 11790 Cardinal Circle, Garden Grove, CA 92643 Anaheim Base 1717 E. Via Burton, Anaheim, CA 92806 Santa Ana Base 4301 W. MacArthur Boulevard, Santa Ana, CA 92704 OC Streetcar 2008 W. 5th Street, Santa Ana, CA 92703 Irvine Sand Canyon Base 14736 Sand Canyon Road, Irvine, CA 92618 Irvine Construction Circle Base 16281 W. Construction Circle, Irvine, CA 92606

5. LICENSES/CERTIFICATIONS

• Contractor must maintain, at minimum, a Type B + Type D Concern License (BD) license issued by the State of California Fire Marshal.

• Failure to provide required licenses/certifications may deem the bidder non-responsive.

6. ADDITIONAL INFORMATION

• Approximate inventory of fire extinguishers:

Description Quantity 2½ lb Extinguisher 250 5 lb Extinguisher 660 6 lb Extinguisher 8 10 lb Extinguisher 350 20 lb Extinguisher 60 15 lb CO2 Extinguisher 2 5 lb Halotron Extinguisher 8 30 lb Wheeled Extinguisher 1

• The following parts list is provided for informational purposes only and represents parts that may be required for fire extinguishers repair and service:

O-Rings: All Types Valve stems: All Types Gauges Nozzles - Dry Chemical or Halotron Hoses - Dry Chemical or Halotron, CO2, Wheeled Engines Hose Bands: All types Handles – Lower, upper Halotron, CO2, BC Powder, ABC Powder, D Powder – per pound

7. INVOICING AND PAYMENT REQUIREMENTS

• Invoice Submission o Invoices must include the following information:

• Purchase Order Number

• Base Location where the service was performed.

• Service date and itemized details of the service.

• Invoice Submission Methods o Invoices should be submitted via email to:

• VendorInvoices@octa.net

• Payment Processing Delays o Failure to comply with invoice requirements (e.g., missing documentation, unclear pricing, or invoice submission method outside of what is deemed acceptable) will result in processing delays, and subsequently the payment schedule.