This is a lighting plans document for the 16th Street NE Bridge Project prepared by Kissinger Campo and Associates Corp. for Collier County Transportation Management Services Department in Florida. The project involves the installation of roadway lighting along 16th Street NE from Golden Gate Boulevard to Randall Boulevard, with five light poles specified for installation. The lighting design includes LED luminaires manufactured by Apollo Metro Solutions (Model SL5 Mini LED) rated at 158 watts, 480 volts, with 4000K color temperature and Type 3 light distribution. The project requires installation of 312 linear feet of open trench conduit, 74 linear feet of directional bore conduit, one load center assembly rated for 240/480V single-phase operation with a 100-amp main breaker, and associated electrical components including pull boxes, service disconnect switches, and concrete poles. Additionally, the work includes installation of 2,721 linear feet of insulated lighting conductors (No. 8-6 AWG), three light poles with standard foundations at 35-foot mounting heights with 12-foot arms, and a pole cable distribution system. The design adheres to Florida Department of Transportation FY 2024-25 Standard Specifications and Collier County Traffic Operations Roadway Lighting Design Standards (2018).
The lighting design specifies design criteria including a maximum/minimum uniformity ratio of 10:1 or less at signalized intersections and 4:1 or less average/minimum uniformity, with average initial horizontal illumination of 1.5 to 3.0 foot-candles and vertical illumination of 1.2 to 1.5 foot-candles. The design wind speed is 160 miles per hour. All electrical work must comply with the National Electric Code, Florida standards, and Collier County specifications. Contractors are required to obtain approval from the Traffic Operations Department prior to equipment ordering and submit two full-size as-built plans to the county upon completion. The contractor bears responsibility for all workmanship and defective components for one year after final acceptance. All conduit must be Schedule 40 PVC for open trench installation or high-density polyethylene for directional bore work. The plans were digitally signed and sealed by M. Fathy Abdalla, P.E. (License No. 63914) on March 7, 2025, with the project managed under Collier County Project No. 60212.1, State Project No. 63914, and Financial Project ID 451283-1-58-01 utilizing federal funds.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
https://goo.gl/maps/8h4bPNnURfNHNu42A
CONTRACT PLANS
COLLIER COUNTY
16TH STREET NE
FROM GOLDEN GATE BOULEVARD TO RANDALL BOULEVARD
DENNIS F. McCOY, P.E.
PROJECT MANAGER:
COLLIER COUNTY
c:\pww\kca_prod\dms38691\KEYSLT01.dgnirojas 3/7/2025 4:08:40 PM Default
NO.
SHEET
YEAR
FISCAL
L-1 25
EXPRESSWAY
T U
R N P
IK
E
PENSACOLA FORT WALTON
BEACH
PANAMA
CITY
CHIPLEY
TALLAHASSEE
JACKSONVILLE
ST AUGUSTINE
GAINESVILLE
OCALA DAYTONA BEACH
DELAND
NEW PORT RICHEY
TAMPA
LAKELAND
MELBOURNE -
COCOA
ORLANDO
BARTOWST PETERSBURG
SARASOTA -
BRADENTON
FT PIERCE
FT MYERS
WEST PALM
BEACH
FT LAUDERDALE
MIAMI
NAPLES
KEY WEST
CITY
LAKE
F
LO
R
ID
A 'S
BEACH LINE
SHEET DESCRIPTIONSHEET NO.
GOVERNING STANDARD SPECIFICATIONS:
ENGINEER OF RECORD:
LIGHTING PLANS
http://www.fdot.gov/programmanagement/Implemented/SpecBooks for Road and Bridge Construction at the following website:
Florida Department of Transportation, FY 2024-25 Standard Specifications
GOVERNING STANDARD PLANS:
INDEX OF LIGHTING PLANS
COLLIER COUNTY PROJECT NO. 60212.1
STATE OF
No 63914
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
A
LL
ADBA YHTAF .
M
VENDOR NO.: F59-1677145
CONTRACT NO.: 22-7944
PHONE: (813) 871-5331
TAMPA, FLORIDA 33602
201 NORTH FRANKLIN STREET, SUITE 900
KISINGER CAMPO AND ASSOCIATES CORP.
P.E. NO.: 63914
M. FATHY ABDALLA, P.E.
FINANCIAL PROJECT ID 451283-1-58-01 (FEDERAL FUNDS)
SIGNED AND SEALED BY
THIS ITEM HAS BEEN DIGITALLY
ON ANY ELECTRONIC COPIES.
AND THE SIGNATURE MUST BE VERIFIED
NOT CONSIDERED SIGNED AND SEALED
PRINTED COPIES OF THIS DOCUMENT ARE
ON THE DATE ADJACENT TO THE SEAL
COLLIER COUNTY (03000302)
LIGHTING PLANS
61G15-23.004 F.A.C.
SHEETS IN ACCORDANCE WITH RULE
RESPONSIBLE FOR THE FOLLOWING
THE ABOVE NAMED PROFESSIONAL IS
https://www.colliercountyfl.gov/home/showpublisheddocument/73293/636880715376970000 are available at the following website:
Collier County Traffic Operations Roadway Lighting Design Standards, 2018
Component
Standard Plans for Bridge Construction are included in the Structures Plans following website: http://www.fdot.gov/design/standardplans
Standard Plans for Road Construction and associated IRs are available at the
Bridge Construction and applicable Interim Revisions (IRs).
Florida Department of Transportation, FY 2024-25 Standard Plans for Road and
L-5
L-4
L-3
L-2
L-1 transportation management services department
LIGHTING PLAN
POLE DATA & LIGHTING LEGEND
GENERAL NOTES
TABULATION OF QUANTITIES
KEY SHEET
& ASSOCIATES
KISINGER CAMPO
Tampa, Florida 33602
201 North Franklin Street, Suite 900
P.E. No.: 63914
Engineer of Record: M. Fathy Abdalla
16TH. ST. NE
T H
E
O F
F I
C I
A L
R
C O
D
T
I
S
E E
T
E C
T R
O N
C
G I
T A
L
Y
G N
N
A L
U
D
L E
G
A
C
3/7/2025irojas c:\pww\kca_prod\dms38691\TABQLT01.dgn4:08:42 PM
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
NO.
SHEET
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
ROAD NAME
16TH. ST. NE
COUNTY
COLLIER
451283-1-58-01
COLLIER COUNTY TRANSPORTATION
MANAGEMENT SERVICES DEPARTMENT
FINANCIAL PROJECT ID
L-2
NO.
ITEM
PAY
DESCRIPTION UNIT
SHEET NUMBERS
SHEET
THIS
TOTAL
TOTAL
GRAND
L-5
PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL
0630 2 11 CONDUIT, FURNISH & INSTALL, OPEN TRENCH LF 312 312 312
0630 2 12 CONDUIT, FURNISH & INSTALL, DIRECTIONAL BORE LF 74 74 74
0635 2 11 PULL & SPLICE BOX, F&I, 13" x 24" COVER SIZE EA 10 10 10
0639 1112 ELECTRICAL POWER SERVICE, F&I, OVERHEAD METER PURCHASED BY CONTRACTOR FROM POWER COMPANY AS 1 1 1
0639 2 1 ELECTRICAL SERVICE WIRE, FURNISH & INSTALL LF 10 10 10
0639 3 11 ELECTRICAL SERVICE DISCONNECT, F&I, POLE MOUNT EA 1 1 1
0641 2 12 PRESTRESSED CONCRETE POLE, F&I, TYPE P-II SERVICE POLE EA 1 1 1
0715 1 12 LIGHTING CONDUCTORS, F&I, INSULATED, NO.8 - 6 LF 2721 2721 2721
0715 5 32
POLE
LUMINAIRE & BRACKET ARM- GALV STEEL, FURNISH & INSTALL NEW LUMINAIRE AND ARM ON NEW/EXISTING
EA 2 2 2
0715 7 11 LOAD CENTER, F&I, SECONDARY VOLTAGE EA 1 1 1
0715 61242
LENGTH
LIGHT POLE COMPLETE, F&I, STANDARD POLE STANDARD FOUNDATION, 35' MOUNTING HEIGHT, 12' ARM
EA 3 3 3
0715500 1 POLE CABLE DISTRIBUTION SYSTEM, FURNISH AND INSTALL, CONVENTIONAL EA 3 3 3
Tampa, Florida 33602
201 North Franklin Street, Suite 900
P.E. No.: 63914
Engineer of Record: M. Fathy Abdalla
16TH. ST. NE
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
3/7/2025irojas c:\pww\kca_prod\dms38691\GNNTLT01.dgn4:08:44 PM
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
MANAGEMENT SERVICES DEPARTMENT
FINANCIAL PROJECT ID GENERAL NOTES
LIGHTING CRITERIA
SIGNALIZED INTERSECTION
MAX./MIN. 10:1 OR LESS
DESIGN WIND SPEED 160 MPH
UNIFORMITY RATIO AVG./MIN. 4:1 OR LESS
VEILING LUMINANCE RATIO N/A
AVERAGE INITIAL INTENSITY (VERTICAL FOOT CANDLES) 1.2 - 1.5 FOOT CANDLES
AVERAGE INITIAL INTENSITY (HORIZONTAL FOOT CANDLES) 1.5 - 3.0 FOOT CANDLES
L-3
BACK TO THE COUNTY AFTER ACCEPTANCE.
LIMITS BEFORE THE PROJECT BEGINS. COORDINATE WITH THE COUNTY TO PERFORM AN INSPECTION. HAND OVER THE MAINTENANCE
15. REQUEST THE COUNTY TO HAND OVER THE MAINTENANCE RESPONSIBILITY OF THE EXISTING LIGHTING SYSTEM WITHIN THE PROJECT
ADJUSTMENT IF NECESSARY.
SURFACE WATER, PAVED SHOULDERS OR PEDESTRIAN RAMPS, COORDINATE WITH THE ENGINEER FOR AN APPROVED OFFSET
14. LIGHT POLES MUST NOT BE LOCATED IN THE BOTTOM OF DRAINAGE SWALES AND DITCHES OR WITHIN WETLANDS, DRIVEWAYS, HEAT SHRINK TUBES OR CAPS MUST BE USED TO WATERPROOF THESE CONNECTIONS.
MULTI-DIRECTIONAL CONDUITS AS INDICATED ON PLANS. THE CONNECTION MADE AT THESE POINTS SHOULD BE PROPERLY TAPED AND
13. SPLICES AND CONNECTIONS MADE IN PULL BOXES MUST BE LIMITED TO THE SERVICE POINT AND CONDUIT JUNCTION WITH
POLE OR PULL BOX.
12. ALLOW ENOUGH SLACK IN WIRES TO PERMIT FUSE HOLDERS, SURGE PROTECTORS, AND SPLICES TO BE HANDLED TWO FEET OUTSIDE
ACCEPTANCE.
11. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORKMANSHIP AND DEFECTIVE COMPONENTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL
10. CONTACT ALL UTILITY COMPANIES PRIOR TO ANY UNDERGROUND WORK.
GROWTH MANAGEMENT DIVISION.
9. BEFORE FINAL ACCEPTANCE, PROVIDE 2 SETS OF FULL SIZE AS-BUILT PLANS TO THE TRAFFIC OPERATIONS DEPARTMENT OF THE
REQUIRED TO MATCH THE EXISTING GRADE.
8. SOD USED IN THE RESTORATION OF DISTURBED EARTH MUST MATCH EXISTING GROUND COVER AND BE DUG-IN OR ROLLED AS
NUMBER THE POLES AS SHOWN IN THE PLANS.
VERTICALLY ON THE PLATE WITH THE FOLLOWING INFORMATION: LOAD CENTER DESIGNATION, CIRCUIT NUMBER, AND THE POLE NUMBER.
ON THE EXTERIOR TRAFFIC LANE SIDE OF THE POLE. USE 3/4-INCH BLACK TEXT ON WHITE BACKGROUND. ORIENT THE TEXT
REQUIRING SCREWS, BOLTS, OR RIVETS, MUST BE APPROVED BY THE POLE MANUFACTURER. INSTALL PLATES FIVE FEET ABOVE GRADE
IDENTIFICATION PLATE ON EACH LIGHT POLE. ATTACH PLATES TO THE POLE AS APPROVED BY THE ENGINEER. ATTACHMENT METHODS
7. STATE HIGHWAY PER FDOT 715-10.5 POLE IDENTIFICATION PLATES: FURNISH AND INSTALL A 2 INCH BY 8-INCH ALUMINUM
EDITION.
SEALED IN ACCORDANCE WITH SECTION 630 OF THE STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, LATEST
6. AT ALL PULL BOXES AND POLE BASES, ENDS OF CONDUIT MUST BE A MINIMUM OF 2 INCHES ABOVE THE SURFACE OF THE BASE AND
SECTION 555.
5. PAYMENT FOR CONDUIT MUST INCLUDE COST OF TRENCHING AND/OR BORING AND ALL CONDUIT AND PULLING BELLS. SEE FDOT SPEC.
PRIOR TO ROADWAY WORK. CONDUIT ROUTING MUST BE POLE TO POLE MAINTAINING POLE SETBACK DISTANCE FROM EDGE OF PAVEMENT.
4. CONDUIT INSTALLATION PER FOOT STANDARD PLAN INDEX 630-001 (PULL BELLS REQUIRED). WHEN POSSIBLE CONDUIT MUST BE PLACED
STANDARD PLANS, AND THE STATE OF FLORIDA STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, LATEST EDITION
STANDARDS TECHNICAL SPECIAL PROVISIONS, NATIONAL ELECTRIC CODE, THE STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION
3. ALL ELECTRICAL WORK MUST MEET THE REQUIREMENTS OF THE LATEST EDITIONS OF THE COLLIER COUNTY ROADWAY LIGHTING DESIGN
APOLLO METRO SOLUTIONS #SL5-NW-150-L_T3 OR EQUIVALENT
LUMINAIRE, STREET LIGHT, 4000K 17,900 LUMEN, 158 W, 480 V, TYPE 3, DISTRIBUTION WITH 12' ARM AND 35' MOUNTING HEIGHT, SPECIFICALLY INCLUDE.
MANAGEMENT DIVISION, EQUIPMENT SPECIFICATIONS AND DESIGN DATA FOR ALL MATERIAL PROPOSED FOR THE PROJECT. THESE
2. PRIOR TO ANY EQUIPMENT ORDER, SUBMIT FOR APPROVAL BY THE PROJECT MANAGER, TRAFFIC OPERATIONS DEPARTMENT, GROWTH
STANDARDS, LATEST EDITION.
FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD PLANS 2024-25, AND THE COLLIER COUNTY TRAFFIC OPERATIONS DESIGN
DEPARTMENT OF TRANSPORTATION, FY 2024-2025 STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, THE STATE OF
1. EXCEPT AS NOTED ON THE ENGINEERING DESIGN PLANS, ALL WORK MUST BE IN ACCORDANCE WITH THE STATE OF FLORIDA
GENERAL NOTES
DRAWING AND CALCULATIONS, SIGNED AND SEALED BY A FLORIDA PE, FOR APPROVAL BY THE ENGINEER PRIOR TO FABRICATION
715-5-32: LUMINAIRE CLAMP DESIGN TO BE COMPLETED BY THE CONTRACTOR OR CONTRACTOR'S SPECIALTY ENGINEER. SUBMIT SHOP
MOUNTING HARDWARE AND WIRING.
CENTER ASSEMBLY, PHOTOCELL, METER CAN, SAFETY SWITCH, PRESTRESSED TYPE P-II 12-FOOT POLE AND ALL NECESSARY
TRAFFIC OPERATIONS ROADWAY LIGHTING DESIGN STANDARDS. EQUIPMENT AND MATERIAL INCLUDE BUT NOT LIMITED TO THE LOAD
715-7-11: THE LOAD CENTER ASSEMBLY INCLUDES ALL COMPONENTS SPECIFIED IN THE LATEST VERSION OF THE COLLIER COUNTY
PAY ITEM NOTES
Tampa, Florida 33602
201 North Franklin Street, Suite 900
P.E. No.: 63914
Engineer of Record: M. Fathy Abdalla
16TH. ST. NE
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
3/7/2025irojas c:\pww\kca_prod\dms38691\PLDTLT01.dgn4:08:47 PM
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
MANAGEMENT SERVICES DEPARTMENT
FINANCIAL PROJECT ID
LIGHTING LEGEND
POLE DATA &
L-4
DESCRIPTION
LIGHTING LEGEND
PULL BOX
BEYOND EDGE OF PAVEMENT TO PULL BOXES.
CONDUIT. CONDUIT AND TRANSITION COUPLING MUST BE UL LISTED. EXTEND CONDUIT
(XHHW INSULATION) INSIDE CONDUIT WITH OTHER CONDUCTORS AND A SPARE
CONDUCTOR SIZE AS SHOWN ON PLAN SHEETS). RUN ONE COPPER BOND CONDUCTOR
2" HDPE CONDUIT, DIRECTIONAL BORE, WITH CONDUCTORS INSIDE (CONDUIT AND
(XHHW) INSIDE CONDUIT WITH OTHER CONDUCTORS.
CONDUCTOR SIZE AS SHOWN ON PLAN SHEETS). RUN ONE COPPER BOND CONDUCTOR
2" SCH. 40 PVC CONDUIT, OPEN TRENCH, WITH CONDUCTORS INSIDE (CONDUIT AND
SYMBOL
OUTPUT MUST BE INSTALLED WITH THE COMPLETE LIGHT POLE ASSEMBLY.
DISTRIBUTION SYSTEM. PULL BOX TO BE PAID FOR SEPARATELY. A FIELD ADJUSTABLE
INCLUDES LUMINAIRE, ARM, POLE, FOUNDATION, CONCRETE SLAB, & POLE CABLE
COLOR TEMPERATURE, AND 12' ARM LENGTH. FILE NAME: sl5-nw-150-l_t3.ies. SYMBOL
POLE, 158 WATT, 480 VOLT, LED, TYPE 3 DISTRIBUTION, 35' MOUNTING HEIGHT, 4000K
MANUFACTURER: APOLLO METRO SOLUTIONS, MODEL: SL5 MINI LED, SINGLE ARM LIGHT
PROP. CONV. LIGHT POLE WITH LED LUMINAIRE. THE BASIS OF DESIGN USED WAS:
INSTALLED WITH THE LED LUMINAIRE AND BRACKET ARM.
PULL BOX TO BE PAID FOR SEPARATELY. A FIELD ADJUSTABLE OUTPUT MUST BE
INCLUDES LUMINAIRE AND BRACKET ARM MOUNTED TO PROPOSED STEEL SIGNAL POLE.
COLOR TEMPERATURE, AND 12' ARM LENGTH. FILE NAME: sl5-nw-150-l_t3.ies. SYMBOL
POLE, 158 WATT, 480 VOLT, LED, TYPE 3 DISTRIBUTION, 35' MOUNTING HEIGHT, 4000K
MANUFACTURER: APOLLO METRO SOLUTIONS, MODEL: SL5 MINI LED, SINGLE ARM LIGHT
PROP. LED LUMINAIRE AND BRACKET ARM. THE BASIS OF DESIGN USED WAS:
POLE DATA
NO.
POLE
CIRCUIT BL OR CL STATION OFFSET
OR ARM
DIST.
WATTAGE
LUMINAIRE
HEIGHT
MOUNTING
PAY ITEM
1 A-2 CL_RANDALL 512+70.47 51.56' RT 12' 158 W 35' 715-61-242
2 SIGNAL CL_RANDALL 513+29.50 38.24' LT 12' 158 W 35' 715-5-32
3 A-2 CL_RANDALL 513+36.86 53.68' RT 12' 158 W 35' 715-61-242
4 SIGNAL CL_RANDALL 514+45.50 53.75' RT 12' 158 W 35' 715-5-32
5 A-1 CL_RANDALL 515+21.21 44.00' LT 12' 158 W 35' 715-61-242
STANDARDS
ALL WORK MUST BE COMPLETED PER COLLIER COUNTY TRAFFIC OPERATIONS SPECIFICATIONS AND CCTO ROADWAY LIGHTING DESIGN
ARRAYS.
COUNTY. THIS INCLUDES BUT IS NOT LIMITED TO BURIED OR IMBEDDED CONDUIT. GROUND CONDUCTORS, GROUND RODS, AND GROUNDING
CONTRACTOR'S RESPONSIBILITY TO EXPOSE THE QUESTIONED ITEM(S) FOR THE INSPECTORS' APPROVAL, AT NO ADDITIONAL COST TO THE
ROADWAY LIGHTING/SIGNAL INSPECTOR GIVES APPROVAL. IN THE EVENT THE FOLLOWING ITEMS ARE CONCEALED, IT WILL BE THE
CONCEALED WORK: ALL WORK WHICH WILL NOT BE READILY VISIBLE UPON COMPLETION MUST NOT BE CONCEALED UNTIL A COUNTY
COLLIER COUNTY TRAFFIC OPERATIONS ROADWAY LIGHTING DESIGN STANDARDS.
COLLIER COUNTY WILL ONLY BE RESPONSIBLE FOR MAINTAINING ASSETS THAT COMPLY WITH THE GUIDELINES WRITTEN WITHIN THE
E) EACH LIGHT POLE SHOULD MAINTAIN A MINIMUM OF TEN (10) FEET FROM FPL POWER LINES.
PVC CONDUIT AND PULLING BELLS ARE REQUIRED.
BE SMALLER THAN NO. 6 AWG. BONDING GROUND CONDUCTOR MUST HAVE A GREEN JACKET AND MUST NOT BE SMALLER THAN NO. 6 AWG.
TESTED AND LISTED BY A NRTL. SERVICE AND CIRCUIT CONDUCTORS MUST BE SINGLE-CONDUCTOR CABLE TYPE THWN-2 AND MUST NOT
D) ALL CONDUCTORS MUST BE COLOR-CODED STRANDED COPPER MEETING THE REQUIRMENTS OF NEMA WC 70. ALL CONDUCTORS MUST BE
248-14. THE RATING FOR THE FUSE HOLDERS MUST BE WATER RESISTANT OR SUBMERSIBLE RATED.
CONNECTIONS MUST UTILIZE AN ATQ OR FNQ 10-AMP TIME DELAY FUSE RATED FOR 500V. FUSES MUST BE UL LISTED TO STANDARD
AND RATED FOR 600V. THE WIRE CONNECTIONS IN THE FUSE HOLDERS MUST BE OF THE COPPER SETSCREW TYPE. FUSED
TRANSFORMER BASE. IN LINE FUSE HOLDERS MUST PROVIDE A BREAKAWAY CONNECTION AND BE UL RECOGNIZED PER GUIDE IZLT2
HEB-AW-RYC. PHASE COLOR CODE: BLACK. FUSE HOLDER, FUSE, PERMANENT FUSE NEUTRAL, AND SECONDARY SURGE ARRESTER AT
C) SURGE PROTECTORS HESCO/RL5 HE480. BREAKAWAY FUSE HOLDER ON 480 VOLT SIDE WITH 10-AMP FNQ SLOW BLOW FUSE
B) APOLLO SL5 FIXTURE
A) TB1-17 TRANSFORMER BASE WITH A ROUND, TAPERED, SINGLE-ARM ALUMINUM POLE. HINGED ACCESS DOORS ARE NOT APPROVED.
ALL LIGHT POLES AND ASSETS MAINTAINED BY COLLIER COUNTY TRAFFIC OPERATIONS SHOULD HAVE:
LIGHTING NOTES
LUMINAIRE ELEVATION
CONNECTION
¡ LUMINAIRE
LUMINAIRE
12'
6' 6'
R
M A
X
RISE/RUN
SLOPE 11"/24"
CATENARY WIRE
(SEE SIGNAL PLANS)
MESSENGER WIRE CLAMP
(SEE SIGNAL PLANS)
CATENARY CLAMP
"' 3
STEEL POLE
DESIGNED BY CONTRACTOR
PROPOSED CONCRETE SERVICE POLE AND ELECTRIC SERVICE METER
PROPOSED LOAD CENTER RATED FOR 240/480V OPERATION, SINGLE PHASE, 2 WIRE
1171 1172 1173 1174 1175 1176
NPWNPW
NPW
NPWNPW
E L
E C
E L
E C
E L
E C
D N
U O
F
NA HCAER
X A
M
E
SAB-
T
D N
U O
F
NA HCAER
X A
M
E
SAB-
T
& ASSOCIATES
KISINGER CAMPO
Tampa, Florida 33602
201 North Franklin Street, Suite 900
P.E. No.: 63914
Engineer of Record: M. Fathy Abdalla
16TH. ST. NE
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
3/7/2025irojas c:\pww\kca_prod\dms38691\PLANLT01.dgn4:08:49 PM
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
MANAGEMENT SERVICES DEPARTMENT
FINANCIAL PROJECT ID LIGHTING PLAN
L-5
N
29 LF
74 LF630-2-12
R A
N D
A L L
B
L V
D
EXIST. R/W
RANDALL BLVD
¡ CONST.
PROPOSED. R/W
POLE NO. 1 CKT. A-2
OFF. 51.56 RT
STA. 512+70.47
16TH ST NE
¡ CONST.
CKT. A-1
2-#6, 1-#6
CKT. A-1
2-#6, 1-#6
CKT. A-1
2-#6, 1-#6
EXIST. R/W
CONDUIT PAYMENT
SEE SIGNAL PLANS FOR
2-#6, 1-#6, CKT A-2
EXIST. POLE TO REMAIN
EXIST. POLE TO REMAIN
POLE NO. 5 CKT. A-1
OFF. 44.00 LT
STA. 515+21.21
APPROACH BLVD
THIS SHEET
POLE NO. 3 CKT. A-2
OFF. 53.68 RT
STA. 513+36.86
EXIST. R/W
68 LF
101 LF
42 LF
CKT. A-2
2-#6, 1-#6
LINE (TYP.)
APPROX. PARCEL
LINE (TYP.)
APPROX. PARCEL
1 EA 641-2-12
BY FPL. CIAC CHARGES WILL APPLY.
AND HAND HOLE TO BE INSTALLED
AERIAL TRANSFORMER (480V), RISER
FPL DESIGNATED POINT OF SERVICE.
PROTECT GAS LINE
NOTE: EXPOSE AND
CKT. A-2
2-#6, 1-#6
29 LF
39 LF
CKT. A-1
4-#6, 2-#6
630-2-11
630-2-11
630-2-11
100 40
Feet
16TH STREET NE
630-2-11
630-2-11
630-2-11
CKT. A-1/CKT. A-2
4-#6, 2-#6
(MOUNTED TO SIGNAL POLE)
POLE NO. 4
OFF. 53.75 RT
STA. 514+45.50
(MOUNTED TO SIGNAL POLE)
POLE NO. 2
OFF. 38.24 LT
STA. 513+29.50
635-2-11
CONDUIT
SPARE
FPL TO REMAIN
EXIST. POWER POLE/
EXIST. R/W
EXIST. R/W
OFF. 166.69 RT
STA. 514+22.80
CKT A-2: 30 A, TWO POLE BREAKER
CKT A-1: 30 A, TWO POLE BREAKER
(100A, 480V, 2 POLE)
WITH PHOTOCELL AND CONTACTOR
100 AMP MAIN BREAKER (TWO-POLE)
3 #2 UNDERGROUND SERVICE WIRE
240V/480V SINGLE PHASE SERVICE
LOAD CENTER "A"
1 EA715-7-11
10 EA
639-2-110 LF
639-3-111 EA
1 AS 639-1-112
630-2-1110 LF
| 2025-04-25T08:59:46-0400 | |