HVAC_Power_Ventilators_O&M.PDF

PDF 5 MB Posted

Attached to
HVAC Maintenance services for US Embassy London UK
Solicitation number
19GE5018R0023
Issued by

About this file

HVAC Power ventilators

View the file

Other files

File Type Posted
Exhibit_A.pdf PDF
Exhibit_B.pdf PDF
Exhibit_D.pdf PDF
Exhibit_C.pdf PDF
O&M_Hydronic_Pumps_-_5.pdf PDF
O&M_Hydronic_Pumps_-_2.pdf PDF
O&M_Hydronic_Pumps_-_6.pdf PDF
O&M_Hydronic_Pumps_-_0.1.pdf PDF
Centrifugal_Water_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_0.pdf PDF
Computer_Room_AC_O&M.PDF PDF
DHR_Modular_Chiller_O&M_-_1_of_2.pdf PDF
Soliciation_19GE5018R0023.pdf PDF
O&M_Hydronic_Pumps_-_4.2.pdf PDF
HX_1&2_O&M.PDF PDF
Cooling_Towers_O&M.PDF PDF
Heat_Echangers_for_HVAC_Schedule.pdf PDF
HVAC_Ventilators_Schedule.pdf PDF
Hydronic_Pumps_Schedule.pdf PDF
Air_Terminal_Units_(VAV)_-_O&M.PDF PDF
O&M_Hydronic_Pumps_-_3.pdf PDF
DHR_Modular_Chiller_O&M_-_2_of_2.pdf PDF
O&M_Hydronic_Pumps_-_1.pdf PDF
Air_Cooled_Modular_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_4.1.pdf PDF
Original_Signed_letter_19GE5018R0023.pdf PDF
HX_3&4_O&M.PDF PDF
Central_Station_Air_Handling_Units_O&M.PDF PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Operation & Maintenance Manuals London, United Kingdom NEC

233423

HVAC Power Ventilators Table of Contents

Section Page

Power Ventilators Product Data/Descriptions

SUBMITTAL

Job Title: LONDON 12-827-822-2014

Elevation: (m) 25 Date: 10/16/14 Submitted By: Scott Thompson

AIR-TECH INCORPORATED

15 WEST PARK CIRCLE

BIRMINGHAM , AL 35211-4474

US

Phone: (205)942-7081 Fax: (205)942-7098 Email Address: SCOTT@AIRTECHAL.COM

P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 1 of 216Specification 233423 - Page 1 of 217

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 79 85 79 75 75 69 61 57 79 68 15.9

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

1,168

1,489

Model: CUBE-360XP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 134

Weight w/ Acc's (kg) 159

Max T Motor Frame Size 215

Roof Opening (mm) 978 x 978

Performance Requested Volume (L/sec) 2,750

Actual Volume (L/sec) 2,750

External SP (Pa) 375

Total SP (Pa) 375

Fan RPM 1010

Operating Power (hp) 2.55

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 4.5

Tip Speed (m/sec) 36.266

Static Eff. (%) 57

Motor Motor Mounted Yes

Size (hp) 3

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-1Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 2 of 216Specification 233423 - Page 2 of 217

Model: CUBE-360XP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:

NEMA Premium Efficient Motor - meets NEMA Table 12-14 Motor VFD Rated without Shaft Grounding Protection UL/cUL 762 Listed - "Power Ventilators for Rest. Exh. Appliances" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Hinged Base (Attached) Curb Seal (Attached) Non-Stick Coated Wheel (Teflon) Grease Trap (PN 475538) Birdscreen: Aluminum Heat Baffle (Attached) Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Clean-out Port Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 3 of 216Specification 233423 - Page 3 of 217

Disconnect Switch Enclosure Rating: NEMA-3R Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 3 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 4 of 216Specification 233423 - Page 4 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 73 73 74 63 58 52 49 45 68 56 8.2

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

Model: G-097-VG Direct Drive Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 16

Weight w/ Acc's (kg) 36

Optional Damper (mm) 305 x 305

Roof Opening (mm) 368 x 368

Performance Requested Volume (L/sec) 71

Actual Volume (L/sec) 71

External SP (Pa) 250

Total SP (Pa) 250

Fan RPM 1608

Operating Power (hp) 0.09

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Tip Speed (m/sec) 23.922

Static Eff. (%) 26

Motor Motor Mounted Yes

Size (hp) 1/4

V/C/P 230/50/1

Enclosure ODP

Motor RPM 1725

Windings 1 FLA (Amps) 2.3

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-2Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 195 of 216Specification 233423 - Page 5 of 217

Scott Highlight

Model: G-097-VG Direct Drive Centrifugal Roof Exhaust Fan Standard Construction Features:

Model G Centrifugal Roof Exhaust Fans are direct drive. These fans are specifically designed for roof mounted applications exhausting relatively clean air.

Fan wheels are centrifugal, backward inclined, and constructed of aluminum.

Options & Accessories:

Motor - Vari-Green EC motor w/Mounted Potentiometer Dial UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPI-483-305-G457, Under Sized 38 mm Total, Tray, 51 mm Insulation, Coated Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-12X12, Gravity Operated (Loose), Not Coated Coated with Hi-Pro Polyester, Concrete Gray-RAL 7023, Fan And Attached Acc Stainless Steel Fasteners - 300 Series Birdscreen: StainlessSteel (Attached) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-2Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 196 of 216Specification 233423 - Page 6 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 1/4 hp Voltage: 230 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1725 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 197 of 216Specification 233423 - Page 7 of 217

Vari-Green

Motor & Control Options An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the motor enclosure adjusts the speed (RPM) down 80%.

Wiring DiagramMotor Type: Dial on Motor

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 198 of 216Specification 233423 - Page 8 of 217

DAMPER TYP. SECTION VIEW

305305

Standard Construction Features:

- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Horizontal Mount Exhaust Damper Model: WD-100

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 199 of 216Specification 233423 - Page 9 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 67 77 65 60 60 54 47 45 66 54 7.5

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

Model: CUE-141-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 28

Weight w/ Acc's (kg) 49

Optional Damper (mm) 406 x 406

Roof Opening (mm) 470 x 470

Performance Requested Volume (L/sec) 490

Actual Volume (L/sec) 490

External SP (Pa) 125

Total SP (Pa) 125

Fan RPM 951

Operating Power (hp) 0.16

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Tip Speed (m/sec) 18.501

Static Eff. (%) 52

Motor Motor Mounted Yes

Size (hp) 1/4

V/C/P 230/50/1

Enclosure ODP

Motor RPM 1000

Windings 1 FLA (Amps) 2.3

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-3Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 5 of 216Specification 233423 - Page 10 of 217

Model: CUE-141-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Aluminum curb cap with prepunched mounting holes - Drain trough - Ball bearing motors (sizes 98-160), sleeve bearing motors (sizes 60-95) - Motor isolated on shock mounts - Corrosion resistant fasteners Options & Accessories:

Motor - Vari-Green EC motor 0-10 VDC Input Signal Control - Vari-Green Constant Pressure, Indoor, Duct Tap Qty 1 Control - Vari-Green Transformer 115/230 VAC to 24 VDC, Mounted & Wired UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-559-G610, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-16X16, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 6 of 216Specification 233423 - Page 11 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 1/4 hp Voltage: 230 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1000 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 7 of 216Specification 233423 - Page 12 of 217

An EC motor that uses AC input power and internally converts it to DC power. Motor accepts a 0-10VDC control signal. Motor is operable in the 2-10VDC range and off while in the 0-1.9VDC range.

Control package specifically designed to control a fan with a Vari-Green motor via the inlet or outlet of the fan. The package includes the constant pressure controller and pressure tap. Control range is +/-1 inch of pressure (wg).

Wiring DiagramMotor Type: 0-10 VDC

Control Type: Constant Pressure

Transformer: Mounted and Wired

Control Location: Indoor

Measuring Location:Duct

Pressure Tap Qty: 1

Dimensional Detail

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 8 of 216Specification 233423 - Page 13 of 217

406406

Standard Construction Features:

- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Horizontal Mount Exhaust Damper Model: WD-100

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 9 of 216Specification 233423 - Page 14 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 86 95 87 81 80 76 71 67 86 74 26

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

1,168

1,489

Model: CUBE-360HP-7.5KW Belt Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 166

Weight w/ Acc's (kg) 225

Max T Motor Frame Size 132

Optional Damper (mm) 914 x 914

Roof Opening (mm) 978 x 978

Performance Requested Volume (L/sec) 5,620

Actual Volume (L/sec) 5,620

External SP (Pa) 540

Total SP (Pa) 540

Fan RPM 832

Operating Power (hp) 7.25

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 3.7

Tip Speed (m/sec) 39.832

Static Eff. (%) 58

Motor Motor Mounted Yes

Size (kW) 7.5

V/C/P 400/50/3

Enclosure IP55

Motor RPM 1425

Windings 1

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-4Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 10 of 216Specification 233423 - Page 15 of 217

Model: CUBE-360HP-7.5KW

Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:

Motor meets IE2 High Efficiency UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-1,168-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-36X36, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 11 of 216Specification 233423 - Page 16 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 7.5 kW Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 12 of 216Specification 233423 - Page 17 of 217

914914

Standard Construction Features:

- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Horizontal Mount Exhaust Damper Model: WD-100

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 13 of 216Specification 233423 - Page 18 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 68 80 71 65 61 61 53 50 70 58 9.7

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

Model: CUBE-141-3 Belt Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 34

Weight w/ Acc's (kg) 56

Max T Motor Frame Size 145

Optional Damper (mm) 406 x 406

Roof Opening (mm) 470 x 470

Performance Requested Volume (L/sec) 635

Actual Volume (L/sec) 635

External SP (Pa) 140

Total SP (Pa) 140

Fan RPM 1079

Operating Power (hp) 0.27

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 11.7

Tip Speed (m/sec) 20.980

Static Eff. (%) 50

Motor Motor Mounted Yes

Size (hp) 1/3

V/C/P 220/50/1

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-5Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 14 of 216Specification 233423 - Page 19 of 217

Model: CUBE-141-3

Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:

Motor with Thermal Overload UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-559-G610, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-16X16, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 15 of 216Specification 233423 - Page 20 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 1/3 hp Voltage: 220 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 16 of 216Specification 233423 - Page 21 of 217

406406

Standard Construction Features:

- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Horizontal Mount Exhaust Damper Model: WD-100

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 17 of 216Specification 233423 - Page 22 of 217

Performance Quantity 1

Volume (L/sec) 1,000 External SP (Pa) 435

Total SP (Pa) 499.8 Operating Power (hp) 1.68

Start-Up Power (hp) 1.68 Fan RPM 3409

Max Fan RPM 4,000 Elevation (m) 25

Start-up Temp.(C) 21 Operating Temp.(C) 21

Fan Configuration Size 9

Class II Arrangement 9

Discharge Position Horizontal Mounting Ceiling Hung

Material Type Steel

Equipment Weights Fan (LMD)(kg) 77

Motor/Drive (kg) 46 Accessories (kg) 15

Misc Fan Data

FEG 60

Outlet Velocity (m/sec) 6.856 Static Efficiency (%) 42 Wheel WR2 (kg-m2) 0.15

Tip Speed (MPH) 68.001

Motor and Drives Motor Supplier Greenheck

Size (hp) 2

RPM 2900

Enclosure TEFC Voltage 400

Cycle 50 Phase 3

Frame Size 145T Max Frame Size 184

Location A Pulley Type Constant

Drive Loss (%) 5.1 Drives Dual

Drive Service Factor 1.5

Model: QEI-9-II-20 Mixed Flow Fan

Operating Performance

External SP 435 Pa Belt Tube 64.8 Pa Total SP 499.8 Pa

Note: Using External SP only, the fan would have been incorrectly selected at:

3350 RPM 1.54 hp

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 78 81 82 78 80 80 76 73 85 74 23 Outlet 90 88 89 81 84 82 77 73 89 77 28

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 1.52 m- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-6Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 113 of 216Specification 233423 - Page 23 of 217

Model: QEI-9-II-20 Mixed Flow Fan

Standard Construction Features:

HOUSING: Continuously welded steel housing. Welded steel air straightening vanes. Lifting lugs. Slip-fit inlet and outlet collars. Heavy duty, steel motor supports with adjustment screws for belt tensioning.

Structural parts are phosphatized and coated with Permatector.

BEARINGS, SHAFT: Heavy duty, self-aligning ball or roller face mounted bearings with extended lubrication lines.

WHEEL: Welded construction. Single thickness cambered blades.

Options & Accessories:

NEMA Premium Efficient Motor - meets NEMA Table 12-14 Motor VFD Rated without Shaft Grounding Protection Motor with Class F Insulation Dual Drives Mounting Support - Universal Bearings - L(10) Life of 120k Hours Coated with Permatector, Concrete Gray-RAL 7023, Fan and Attached Accessories Hanging, Isolator-Spring, Hanging, 1 Inch Switch - NEMA-3R, Toggle, For Indoor or Outdoor Use, Ship Separate Access Door - Bolted Inlet Flange - Slip Fit Outlet Flange - Slip Fit Extended Lube Lines - Copper Belt Tube Motor Cover UL Listed for Smoke Control (500F/4hr, 572F/2 hr) UL/cUL-705 - "Power Ventilators" Housing is sealed for outdoor use

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 114 of 216Specification 233423 - Page 24 of 217

14 DIA. MOUNTING HOLES

END VIEW SHOWS FROM OUTLET END OF UNIT

AIRFLOW

MAX

435 513

Model: QEI-9-II-20 Mixed Flow Fan

Notes: All dimensions shown are in units of mm

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 115 of 216Specification 233423 - Page 25 of 217

Isolators Type: Spring, Hanging, 1 Inch Standard Construction Features:

The spring hanging isolator is designed to reduce transmission of vibration and noise produced by suspended equipment and piping.

The assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.

NEOPRENE ELEMENT

Ø 16 MAX

Notes: All dimensions shown are in units of mm **Isolator dimensions may vary with all aluminum, aluminum airstream, or Spark A construction, external inlet vane damper or with an outlet damper accessory. Consult factory for details.

Fan Configuration Model: QEI-9-II-20 Arrangement: 9 Class: II Rotation: N/A Motor Frame Size: 145T Motor Position: A Isolator/Deflection: Spring, Hanging, 1 Inch Isolator Color: Gray

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 116 of 216Specification 233423 - Page 26 of 217

Disconnect Switch Configuration Type: Toggle Motor Size: 2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship Separate RPM: 2900 Wiring (Exp. Resist.):

Disconnect Switch Enclosure Rating: NEMA-3R Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 117 of 216Specification 233423 - Page 27 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 81 86 84 81 81 76 68 63 85 73 21

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

1,168

1,489

Model: CUBE-360XP-50 Belt Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 146

Weight w/ Acc's (kg) 207

Max T Motor Frame Size 215

Optional Damper (mm) 914 x 914

Roof Opening (mm) 978 x 978

Performance Requested Volume (L/sec) 3,660

Actual Volume (L/sec) 3,660

External SP (Pa) 435

Total SP (Pa) 435

Fan RPM 1232

Operating Power (hp) 4.44

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 4.0

Tip Speed (m/sec) 44.252

Static Eff. (%) 50

Motor Motor Mounted Yes

Size (hp) 5

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-7Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 18 of 216Specification 233423 - Page 28 of 217

Model: CUBE-360XP-50

Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:

NEMA Premium Efficient Motor - meets NEMA Table 12-14 UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-1,168-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, ES-10-PB-36X36, Gravity Counterbalance Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 19 of 216Specification 233423 - Page 29 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 5 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 20 of 216Specification 233423 - Page 30 of 217

914914

Standard Construction Features:

- Model ES-10 is a horizontal mount exhaust damper (air flow up) which is constructed of 2 mm extruded Aluminum. Damper blades are 1 mm extruded aluminum with vinyl seals on the closing edge and counterbalance weights to assist opening.

Metallic axles are 6 mm, mounted in polycarbonate bushings – Synthetic axle bearings. Maximum Velocity of 23 MPH

Notes: All dimensions shown are in units of mm Width And height furnished approximately 6 mm undersize

Commercial Backdraft Damper Model: ES-10

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 21 of 216Specification 233423 - Page 31 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 81 82 90 81 77 75 69 67 85 74 23

Dia.

Reference assembly view drawings for actual dimensions with mounted accessories

*Overall height may be greater depending on motor

1,086

Model: CUBE-220HP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 85

Weight w/ Acc's (kg) 126

Max T Motor Frame Size 184

Optional Damper (mm) 610 x 610

Roof Opening (mm) 673 x 673

Performance Requested Volume (L/sec) 2,610

Actual Volume (L/sec) 2,610

External SP (Pa) 355

Total SP (Pa) 355

Fan RPM 1175

Operating Power (hp) 2.73

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 4.5

Tip Speed (m/sec) 38.288

Static Eff. (%) 48

Motor Motor Mounted Yes

Size (hp) 3

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-8Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 22 of 216Specification 233423 - Page 32 of 217

Model: CUBE-220HP-30

Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:

NEMA Premium Efficient Motor - meets NEMA Table 12-14 UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-864-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-24X24, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 23 of 216Specification 233423 - Page 33 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 3 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 24 of 216Specification 233423 - Page 34 of 217

610610

Standard Construction Features:

- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Horizontal Mount Exhaust Damper Model: WD-100

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 25 of 216Specification 233423 - Page 35 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 80 85 79 80 70 65 63 61 80 68 16.5 Radiated 79 80 69 70 59 46 44 48 70 59 9.4

BLOWER

HOUSING Inlet

Inline Discharge

Motor Cover

ELEVATION VIEW

Inlet

Motor Cover

END VIEW

Inlet Inline

Discharge Motor Cover

PLAN VIEW

25.4

25.4 533 381

Model: BSQ-80-5 Belt Drive Centrifugal Inline Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 42

Weight w/ Acc's (kg) 55

Max T Motor Frame Size 145

Optional Damper (mm) 305 x 305

Performance Requested Volume (L/sec) 200

Actual Volume (L/sec) 200

External SP (Pa) 340

Total SP (Pa) 340

Fan RPM 2069

Operating Power (hp) 0.39

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 9.6

Tip Speed (m/sec) 30.785

Static Eff. (%) 26

Motor Motor Mounted Yes

Size (hp) 1/2

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-9Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 46 of 216Specification 233423 - Page 36 of 217

Model: BSQ-80-5 Belt Drive Centrifugal Inline Fan Standard Construction Features:

- Galvanized steel housing - Backward inclined aluminum wheel - Two bolted access panels - Integral duct connection flanges - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Static free belts - Corrosion resistant fasteners Options & Accessories:

UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Ship With Unit, Field Mounted Damper, Inline, WD-330-PB-12X12, Gravity Operated (Loose), Coated Coated with Permatector, Concrete Gray-RAL 7023, Fan And Attached Acc Insulated Housing - 25 mm Thick: Fan Housing, Motor Cover Motor Cover Isolators & Brackets, Spring Hanging (1 Kit(s): Qty 4, PN: 850344) (Shipped Loose) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 47 of 216Specification 233423 - Page 37 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 1/2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship With Unit RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 48 of 216Specification 233423 - Page 38 of 217

DAMPER - INLINE

DISCHARGE TYP. SECTION VIEW

305 86

Standard Construction Features:

- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge - Steel axles are 5 mm diameter zinc plated steel - Synthetic sleeve type bushings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Vertical Mount Exhaust Damper Model: WD-330

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 49 of 216Specification 233423 - Page 39 of 217

Isolator Type: Spring Hanging Standard Construction Features:

The spring hanging isolator is designed to reduce the transmission of vibration and noise produced by suspended equipment and piping. To assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through a 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.

This part number includes 4 isolators.

Isolator Configuration Description: SH-1-70 Color: Green Manufacturer: Kinetics Noise Control Mounting: Hanging Load Capacity: 32 kg Kit Part Number: 850344 Deflection: 35 mm

NEOPRENE ELEMENT

Spring Hanging Deflection - Vibration Isolator

Ø15.875 MAX

Notes: All dimensions shown are in units of mm

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 50 of 216Specification 233423 - Page 40 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 84 76 73 73 66 64 60 54 74 62 11.8 Radiated 83 71 63 63 55 45 41 41 64 53 7.2

BLOWER

HOUSING Inlet

Inline Discharge

Motor Cover

ELEVATION VIEW

Inlet

Motor Cover

END VIEW

Inlet Inline

Discharge Motor Cover

PLAN VIEW

25.4

25.4 533 483

Model: BSQ-120-5 Belt Drive Centrifugal Inline Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 46

Weight w/ Acc's (kg) 61

Max T Motor Frame Size 145

Optional Damper (mm) 406 x 406

Performance Requested Volume (L/sec) 650

Actual Volume (L/sec) 650

External SP (Pa) 150

Total SP (Pa) 150

Fan RPM 1524

Operating Power (hp) 0.39

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 9.5

Tip Speed (m/sec) 26.599

Static Eff. (%) 37

Motor Motor Mounted Yes

Size (hp) 1/2

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-10Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 51 of 216Specification 233423 - Page 41 of 217

Model: BSQ-120-5

Standard Construction Features:

- Galvanized steel housing - Backward inclined aluminum wheel - Two bolted access panels - Integral duct connection flanges - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Static free belts - Corrosion resistant fasteners Options & Accessories:

UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Ship With Unit, Field Mounted Damper, Inline, WD-330-PB-16X16, Gravity Operated (Loose), Coated Coated with Permatector, Concrete Gray-RAL 7023, Fan And Attached Acc Insulated Housing - 25 mm Thick: Fan Housing, Motor Cover Motor Cover Isolators & Brackets, Spring Hanging (1 Kit(s): Qty 4, PN: 850344) (Shipped Loose) Unit Warranty: 1 Yr (Standard)

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 52 of 216Specification 233423 - Page 42 of 217

Standard Construction Features:

Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.

Notes: All dimensions shown are in units of mm

Electrical Drawing Details

Wiring Schematic

134.58

23.62 63.49 110.51

60.95

73.14

Ø6.35

(2 HOLES)

Disconnect Switch Configuration Type: Toggle Motor Size: 1/2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship With Unit RPM: 1425 Wiring (Exp. Resist.): None

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 53 of 216Specification 233423 - Page 43 of 217

406 86

Standard Construction Features:

- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge - Steel axles are 5 mm diameter zinc plated steel - Synthetic sleeve type bushings

Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize

Vertical Mount Exhaust Damper Model: WD-330

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 54 of 216Specification 233423 - Page 44 of 217

Standard Construction Features:

The spring hanging isolator is designed to reduce the transmission of vibration and noise produced by suspended equipment and piping. To assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through a 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.

This part number includes 4 isolators.

Isolator Configuration Description: SH-1-70 Color: Green Manufacturer: Kinetics Noise Control Mounting: Hanging Load Capacity: 32 kg Kit Part Number: 850344 Deflection: 35 mm

NEOPRENE ELEMENT

Spring Hanging Deflection - Vibration Isolator

Ø15.875 MAX

Notes: All dimensions shown are in units of mm

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 55 of 216Specification 233423 - Page 45 of 217

Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 83 87 80 84 73 68 67 65 83 72 20 Radiated 82 82 70 74 62 49 48 52 74 62 11.3

BLOWER

HOUSING Inlet

Inline Discharge

Motor Cover

ELEVATION VIEW

Inlet

Motor Cover

END VIEW

Inlet Inline

Discharge Motor Cover

PLAN VIEW

25.4

25.4 533 381

Model: BSQ-90-7 Belt Drive Centrifugal Inline Fan

Dimensional Quantity 1

Weight w/o Acc's (kg) 42

Weight w/ Acc's (kg) 55

Max T Motor Frame Size 145

Optional Damper (mm) 305 x 305

Performance Requested Volume (L/sec) 420

Actual Volume (L/sec) 420

External SP (Pa) 312

Total SP (Pa) 312

Fan RPM 2234

Operating Power (hp) 0.63

Elevation (m) 25

Airstream Temp.(C) 21

Air Density (m3) 1.198

Drive Loss (%) 7.5

Tip Speed (m/sec) 33.244

Static Eff. (%) 30

Motor Motor Mounted Yes

Size (hp) 3/4

V/C/P 400/50/3

Enclosure TEFC

Motor RPM 1425

Windings 1 NEC FLA* (Amps) NA

Notes:

All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m

10/16/2014Printed Date:

LONDON 12-827-822-2014Job:

EF-11Mark:

CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON…

This is the start of the file's text. The full file is on GovTribe.