Operation & Maintenance Manuals London, United Kingdom NEC
233423
HVAC Power Ventilators Table of Contents
Section Page
Power Ventilators Product Data/Descriptions
SUBMITTAL
Job Title: LONDON 12-827-822-2014
Elevation: (m) 25 Date: 10/16/14 Submitted By: Scott Thompson
AIR-TECH INCORPORATED
15 WEST PARK CIRCLE
BIRMINGHAM , AL 35211-4474
US
Phone: (205)942-7081 Fax: (205)942-7098 Email Address: SCOTT@AIRTECHAL.COM
P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 1 of 216Specification 233423 - Page 1 of 217
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 79 85 79 75 75 69 61 57 79 68 15.9
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
1,168
1,489
Model: CUBE-360XP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 134
Weight w/ Acc's (kg) 159
Max T Motor Frame Size 215
Roof Opening (mm) 978 x 978
Performance Requested Volume (L/sec) 2,750
Actual Volume (L/sec) 2,750
External SP (Pa) 375
Total SP (Pa) 375
Fan RPM 1010
Operating Power (hp) 2.55
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 4.5
Tip Speed (m/sec) 36.266
Static Eff. (%) 57
Motor Motor Mounted Yes
Size (hp) 3
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-1Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 2 of 216Specification 233423 - Page 2 of 217
Model: CUBE-360XP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-14 Motor VFD Rated without Shaft Grounding Protection UL/cUL 762 Listed - "Power Ventilators for Rest. Exh. Appliances" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Hinged Base (Attached) Curb Seal (Attached) Non-Stick Coated Wheel (Teflon) Grease Trap (PN 475538) Birdscreen: Aluminum Heat Baffle (Attached) Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Clean-out Port Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 3 of 216Specification 233423 - Page 3 of 217
Disconnect Switch Enclosure Rating: NEMA-3R Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 3 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 4 of 216Specification 233423 - Page 4 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 73 73 74 63 58 52 49 45 68 56 8.2
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
Model: G-097-VG Direct Drive Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 16
Weight w/ Acc's (kg) 36
Optional Damper (mm) 305 x 305
Roof Opening (mm) 368 x 368
Performance Requested Volume (L/sec) 71
Actual Volume (L/sec) 71
External SP (Pa) 250
Total SP (Pa) 250
Fan RPM 1608
Operating Power (hp) 0.09
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Tip Speed (m/sec) 23.922
Static Eff. (%) 26
Motor Motor Mounted Yes
Size (hp) 1/4
V/C/P 230/50/1
Enclosure ODP
Motor RPM 1725
Windings 1 FLA (Amps) 2.3
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-2Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 195 of 216Specification 233423 - Page 5 of 217
Scott Highlight
Model: G-097-VG Direct Drive Centrifugal Roof Exhaust Fan Standard Construction Features:
Model G Centrifugal Roof Exhaust Fans are direct drive. These fans are specifically designed for roof mounted applications exhausting relatively clean air.
Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:
Motor - Vari-Green EC motor w/Mounted Potentiometer Dial UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPI-483-305-G457, Under Sized 38 mm Total, Tray, 51 mm Insulation, Coated Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-12X12, Gravity Operated (Loose), Not Coated Coated with Hi-Pro Polyester, Concrete Gray-RAL 7023, Fan And Attached Acc Stainless Steel Fasteners - 300 Series Birdscreen: StainlessSteel (Attached) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-2Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 196 of 216Specification 233423 - Page 6 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/4 hp Voltage: 230 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1725 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 197 of 216Specification 233423 - Page 7 of 217
Vari-Green
Motor & Control Options An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the motor enclosure adjusts the speed (RPM) down 80%.
Wiring DiagramMotor Type: Dial on Motor
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 198 of 216Specification 233423 - Page 8 of 217
DAMPER TYP. SECTION VIEW
305305
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Horizontal Mount Exhaust Damper Model: WD-100
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 199 of 216Specification 233423 - Page 9 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 67 77 65 60 60 54 47 45 66 54 7.5
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
Model: CUE-141-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 28
Weight w/ Acc's (kg) 49
Optional Damper (mm) 406 x 406
Roof Opening (mm) 470 x 470
Performance Requested Volume (L/sec) 490
Actual Volume (L/sec) 490
External SP (Pa) 125
Total SP (Pa) 125
Fan RPM 951
Operating Power (hp) 0.16
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Tip Speed (m/sec) 18.501
Static Eff. (%) 52
Motor Motor Mounted Yes
Size (hp) 1/4
V/C/P 230/50/1
Enclosure ODP
Motor RPM 1000
Windings 1 FLA (Amps) 2.3
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-3Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 5 of 216Specification 233423 - Page 10 of 217
Model: CUE-141-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Aluminum curb cap with prepunched mounting holes - Drain trough - Ball bearing motors (sizes 98-160), sleeve bearing motors (sizes 60-95) - Motor isolated on shock mounts - Corrosion resistant fasteners Options & Accessories:
Motor - Vari-Green EC motor 0-10 VDC Input Signal Control - Vari-Green Constant Pressure, Indoor, Duct Tap Qty 1 Control - Vari-Green Transformer 115/230 VAC to 24 VDC, Mounted & Wired UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-559-G610, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-16X16, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 6 of 216Specification 233423 - Page 11 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/4 hp Voltage: 230 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1000 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 7 of 216Specification 233423 - Page 12 of 217
An EC motor that uses AC input power and internally converts it to DC power. Motor accepts a 0-10VDC control signal. Motor is operable in the 2-10VDC range and off while in the 0-1.9VDC range.
Control package specifically designed to control a fan with a Vari-Green motor via the inlet or outlet of the fan. The package includes the constant pressure controller and pressure tap. Control range is +/-1 inch of pressure (wg).
Wiring DiagramMotor Type: 0-10 VDC
Control Type: Constant Pressure
Transformer: Mounted and Wired
Control Location: Indoor
Measuring Location:Duct
Pressure Tap Qty: 1
Dimensional Detail
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 8 of 216Specification 233423 - Page 13 of 217
406406
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Horizontal Mount Exhaust Damper Model: WD-100
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 9 of 216Specification 233423 - Page 14 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 86 95 87 81 80 76 71 67 86 74 26
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
1,168
1,489
Model: CUBE-360HP-7.5KW Belt Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 166
Weight w/ Acc's (kg) 225
Max T Motor Frame Size 132
Optional Damper (mm) 914 x 914
Roof Opening (mm) 978 x 978
Performance Requested Volume (L/sec) 5,620
Actual Volume (L/sec) 5,620
External SP (Pa) 540
Total SP (Pa) 540
Fan RPM 832
Operating Power (hp) 7.25
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 3.7
Tip Speed (m/sec) 39.832
Static Eff. (%) 58
Motor Motor Mounted Yes
Size (kW) 7.5
V/C/P 400/50/3
Enclosure IP55
Motor RPM 1425
Windings 1
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-4Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 10 of 216Specification 233423 - Page 15 of 217
Model: CUBE-360HP-7.5KW
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:
Motor meets IE2 High Efficiency UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-1,168-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-36X36, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 11 of 216Specification 233423 - Page 16 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 7.5 kW Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 12 of 216Specification 233423 - Page 17 of 217
914914
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Horizontal Mount Exhaust Damper Model: WD-100
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 13 of 216Specification 233423 - Page 18 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 68 80 71 65 61 61 53 50 70 58 9.7
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
Model: CUBE-141-3 Belt Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 34
Weight w/ Acc's (kg) 56
Max T Motor Frame Size 145
Optional Damper (mm) 406 x 406
Roof Opening (mm) 470 x 470
Performance Requested Volume (L/sec) 635
Actual Volume (L/sec) 635
External SP (Pa) 140
Total SP (Pa) 140
Fan RPM 1079
Operating Power (hp) 0.27
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 11.7
Tip Speed (m/sec) 20.980
Static Eff. (%) 50
Motor Motor Mounted Yes
Size (hp) 1/3
V/C/P 220/50/1
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-5Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 14 of 216Specification 233423 - Page 19 of 217
Model: CUBE-141-3
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:
Motor with Thermal Overload UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-559-G610, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-16X16, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 15 of 216Specification 233423 - Page 20 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/3 hp Voltage: 220 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 2 Rating: 15 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 16 of 216Specification 233423 - Page 21 of 217
406406
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Horizontal Mount Exhaust Damper Model: WD-100
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 17 of 216Specification 233423 - Page 22 of 217
Performance Quantity 1
Volume (L/sec) 1,000 External SP (Pa) 435
Total SP (Pa) 499.8 Operating Power (hp) 1.68
Start-Up Power (hp) 1.68 Fan RPM 3409
Max Fan RPM 4,000 Elevation (m) 25
Start-up Temp.(C) 21 Operating Temp.(C) 21
Fan Configuration Size 9
Class II Arrangement 9
Discharge Position Horizontal Mounting Ceiling Hung
Material Type Steel
Equipment Weights Fan (LMD)(kg) 77
Motor/Drive (kg) 46 Accessories (kg) 15
Misc Fan Data
FEG 60
Outlet Velocity (m/sec) 6.856 Static Efficiency (%) 42 Wheel WR2 (kg-m2) 0.15
Tip Speed (MPH) 68.001
Motor and Drives Motor Supplier Greenheck
Size (hp) 2
RPM 2900
Enclosure TEFC Voltage 400
Cycle 50 Phase 3
Frame Size 145T Max Frame Size 184
Location A Pulley Type Constant
Drive Loss (%) 5.1 Drives Dual
Drive Service Factor 1.5
Model: QEI-9-II-20 Mixed Flow Fan
Operating Performance
External SP 435 Pa Belt Tube 64.8 Pa Total SP 499.8 Pa
Note: Using External SP only, the fan would have been incorrectly selected at:
3350 RPM 1.54 hp
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 78 81 82 78 80 80 76 73 85 74 23 Outlet 90 88 89 81 84 82 77 73 89 77 28
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 1.52 m- dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-6Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 113 of 216Specification 233423 - Page 23 of 217
Model: QEI-9-II-20 Mixed Flow Fan
Standard Construction Features:
HOUSING: Continuously welded steel housing. Welded steel air straightening vanes. Lifting lugs. Slip-fit inlet and outlet collars. Heavy duty, steel motor supports with adjustment screws for belt tensioning.
Structural parts are phosphatized and coated with Permatector.
BEARINGS, SHAFT: Heavy duty, self-aligning ball or roller face mounted bearings with extended lubrication lines.
WHEEL: Welded construction. Single thickness cambered blades.
Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-14 Motor VFD Rated without Shaft Grounding Protection Motor with Class F Insulation Dual Drives Mounting Support - Universal Bearings - L(10) Life of 120k Hours Coated with Permatector, Concrete Gray-RAL 7023, Fan and Attached Accessories Hanging, Isolator-Spring, Hanging, 1 Inch Switch - NEMA-3R, Toggle, For Indoor or Outdoor Use, Ship Separate Access Door - Bolted Inlet Flange - Slip Fit Outlet Flange - Slip Fit Extended Lube Lines - Copper Belt Tube Motor Cover UL Listed for Smoke Control (500F/4hr, 572F/2 hr) UL/cUL-705 - "Power Ventilators" Housing is sealed for outdoor use
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 114 of 216Specification 233423 - Page 24 of 217
14 DIA. MOUNTING HOLES
END VIEW SHOWS FROM OUTLET END OF UNIT
AIRFLOW
MAX
435 513
Model: QEI-9-II-20 Mixed Flow Fan
Notes: All dimensions shown are in units of mm
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 115 of 216Specification 233423 - Page 25 of 217
Isolators Type: Spring, Hanging, 1 Inch Standard Construction Features:
The spring hanging isolator is designed to reduce transmission of vibration and noise produced by suspended equipment and piping.
The assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.
NEOPRENE ELEMENT
Ø 16 MAX
Notes: All dimensions shown are in units of mm **Isolator dimensions may vary with all aluminum, aluminum airstream, or Spark A construction, external inlet vane damper or with an outlet damper accessory. Consult factory for details.
Fan Configuration Model: QEI-9-II-20 Arrangement: 9 Class: II Rotation: N/A Motor Frame Size: 145T Motor Position: A Isolator/Deflection: Spring, Hanging, 1 Inch Isolator Color: Gray
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 116 of 216Specification 233423 - Page 26 of 217
Disconnect Switch Configuration Type: Toggle Motor Size: 2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship Separate RPM: 2900 Wiring (Exp. Resist.):
Disconnect Switch Enclosure Rating: NEMA-3R Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 117 of 216Specification 233423 - Page 27 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 81 86 84 81 81 76 68 63 85 73 21
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
1,168
1,489
Model: CUBE-360XP-50 Belt Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 146
Weight w/ Acc's (kg) 207
Max T Motor Frame Size 215
Optional Damper (mm) 914 x 914
Roof Opening (mm) 978 x 978
Performance Requested Volume (L/sec) 3,660
Actual Volume (L/sec) 3,660
External SP (Pa) 435
Total SP (Pa) 435
Fan RPM 1232
Operating Power (hp) 4.44
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 4.0
Tip Speed (m/sec) 44.252
Static Eff. (%) 50
Motor Motor Mounted Yes
Size (hp) 5
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-7Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 18 of 216Specification 233423 - Page 28 of 217
Model: CUBE-360XP-50
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-14 UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-1,168-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, ES-10-PB-36X36, Gravity Counterbalance Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 19 of 216Specification 233423 - Page 29 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 5 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 20 of 216Specification 233423 - Page 30 of 217
914914
Standard Construction Features:
- Model ES-10 is a horizontal mount exhaust damper (air flow up) which is constructed of 2 mm extruded Aluminum. Damper blades are 1 mm extruded aluminum with vinyl seals on the closing edge and counterbalance weights to assist opening.
Metallic axles are 6 mm, mounted in polycarbonate bushings – Synthetic axle bearings. Maximum Velocity of 23 MPH
Notes: All dimensions shown are in units of mm Width And height furnished approximately 6 mm undersize
Commercial Backdraft Damper Model: ES-10
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 21 of 216Specification 233423 - Page 31 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 81 82 90 81 77 75 69 67 85 74 23
Dia.
Reference assembly view drawings for actual dimensions with mounted accessories
*Overall height may be greater depending on motor
1,086
Model: CUBE-220HP-30 Belt Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 85
Weight w/ Acc's (kg) 126
Max T Motor Frame Size 184
Optional Damper (mm) 610 x 610
Roof Opening (mm) 673 x 673
Performance Requested Volume (L/sec) 2,610
Actual Volume (L/sec) 2,610
External SP (Pa) 355
Total SP (Pa) 355
Fan RPM 1175
Operating Power (hp) 2.73
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 4.5
Tip Speed (m/sec) 38.288
Static Eff. (%) 48
Motor Motor Mounted Yes
Size (hp) 3
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-8Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 22 of 216Specification 233423 - Page 32 of 217
Model: CUBE-220HP-30
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Drain trough - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Internal lifting lugs Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-14 UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Junction Box Mounted & Wired Roof Curb-Galv., GPFV-864-G508, Under Sized 25 mm Total Hinged Base (Attached) Curb Seal (Attached) Damper, WD-100-PB-24X24, Gravity Operated (Loose), Not Coated Birdscreen: Aluminum Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 23 of 216Specification 233423 - Page 33 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 3 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Mounted and Wired RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 24 of 216Specification 233423 - Page 34 of 217
610610
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 1.3 mm galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Steel axles are 5 mm diameter zinc plated mounted in acetal bushings - Synthetic axle bearings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Horizontal Mount Exhaust Damper Model: WD-100
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 25 of 216Specification 233423 - Page 35 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 80 85 79 80 70 65 63 61 80 68 16.5 Radiated 79 80 69 70 59 46 44 48 70 59 9.4
BLOWER
HOUSING Inlet
Inline Discharge
Motor Cover
ELEVATION VIEW
Inlet
Motor Cover
END VIEW
Inlet Inline
Discharge Motor Cover
PLAN VIEW
25.4
25.4 533 381
Model: BSQ-80-5 Belt Drive Centrifugal Inline Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 42
Weight w/ Acc's (kg) 55
Max T Motor Frame Size 145
Optional Damper (mm) 305 x 305
Performance Requested Volume (L/sec) 200
Actual Volume (L/sec) 200
External SP (Pa) 340
Total SP (Pa) 340
Fan RPM 2069
Operating Power (hp) 0.39
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 9.6
Tip Speed (m/sec) 30.785
Static Eff. (%) 26
Motor Motor Mounted Yes
Size (hp) 1/2
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-9Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 46 of 216Specification 233423 - Page 36 of 217
Model: BSQ-80-5 Belt Drive Centrifugal Inline Fan Standard Construction Features:
- Galvanized steel housing - Backward inclined aluminum wheel - Two bolted access panels - Integral duct connection flanges - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Static free belts - Corrosion resistant fasteners Options & Accessories:
UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Ship With Unit, Field Mounted Damper, Inline, WD-330-PB-12X12, Gravity Operated (Loose), Coated Coated with Permatector, Concrete Gray-RAL 7023, Fan And Attached Acc Insulated Housing - 25 mm Thick: Fan Housing, Motor Cover Motor Cover Isolators & Brackets, Spring Hanging (1 Kit(s): Qty 4, PN: 850344) (Shipped Loose) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 47 of 216Specification 233423 - Page 37 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship With Unit RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 48 of 216Specification 233423 - Page 38 of 217
DAMPER - INLINE
DISCHARGE TYP. SECTION VIEW
305 86
Standard Construction Features:
- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge - Steel axles are 5 mm diameter zinc plated steel - Synthetic sleeve type bushings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Vertical Mount Exhaust Damper Model: WD-330
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 49 of 216Specification 233423 - Page 39 of 217
Isolator Type: Spring Hanging Standard Construction Features:
The spring hanging isolator is designed to reduce the transmission of vibration and noise produced by suspended equipment and piping. To assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through a 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.
This part number includes 4 isolators.
Isolator Configuration Description: SH-1-70 Color: Green Manufacturer: Kinetics Noise Control Mounting: Hanging Load Capacity: 32 kg Kit Part Number: 850344 Deflection: 35 mm
NEOPRENE ELEMENT
Spring Hanging Deflection - Vibration Isolator
Ø15.875 MAX
Notes: All dimensions shown are in units of mm
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 50 of 216Specification 233423 - Page 40 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 84 76 73 73 66 64 60 54 74 62 11.8 Radiated 83 71 63 63 55 45 41 41 64 53 7.2
BLOWER
HOUSING Inlet
Inline Discharge
Motor Cover
ELEVATION VIEW
Inlet
Motor Cover
END VIEW
Inlet Inline
Discharge Motor Cover
PLAN VIEW
25.4
25.4 533 483
Model: BSQ-120-5 Belt Drive Centrifugal Inline Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 46
Weight w/ Acc's (kg) 61
Max T Motor Frame Size 145
Optional Damper (mm) 406 x 406
Performance Requested Volume (L/sec) 650
Actual Volume (L/sec) 650
External SP (Pa) 150
Total SP (Pa) 150
Fan RPM 1524
Operating Power (hp) 0.39
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 9.5
Tip Speed (m/sec) 26.599
Static Eff. (%) 37
Motor Motor Mounted Yes
Size (hp) 1/2
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-10Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 51 of 216Specification 233423 - Page 41 of 217
Model: BSQ-120-5
Standard Construction Features:
- Galvanized steel housing - Backward inclined aluminum wheel - Two bolted access panels - Integral duct connection flanges - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Static free belts - Corrosion resistant fasteners Options & Accessories:
UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-3R, Toggle, Ship With Unit, Field Mounted Damper, Inline, WD-330-PB-16X16, Gravity Operated (Loose), Coated Coated with Permatector, Concrete Gray-RAL 7023, Fan And Attached Acc Insulated Housing - 25 mm Thick: Fan Housing, Motor Cover Motor Cover Isolators & Brackets, Spring Hanging (1 Kit(s): Qty 4, PN: 850344) (Shipped Loose) Unit Warranty: 1 Yr (Standard)
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 52 of 216Specification 233423 - Page 42 of 217
Standard Construction Features:
Enclosure constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment: to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust. The enclosed equipment will be undamaged by the external formation of ice on the enclosure. This enclosure meets the rod entry, rain, external icing, outdoor corrosion protection and gasket design tests. Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of mm
Electrical Drawing Details
Wiring Schematic
134.58
23.62 63.49 110.51
60.95
73.14
Ø6.35
(2 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/2 hp Voltage: 400 UL Listed: Yes Manufacturer: Square D Cycle: 50 Amperage: 30 CSA Approved: Yes Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp Mounting: Ship With Unit RPM: 1425 Wiring (Exp. Resist.): None
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 53 of 216Specification 233423 - Page 43 of 217
406 86
Standard Construction Features:
- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes - Damper blades are 1 mm roll formed aluminum with vinyl seals on the closing edge - Steel axles are 5 mm diameter zinc plated steel - Synthetic sleeve type bushings
Notes: All dimensions shown are in units of mm Width And height furnished approximately 3 mm undersize
Vertical Mount Exhaust Damper Model: WD-330
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 54 of 216Specification 233423 - Page 44 of 217
Standard Construction Features:
The spring hanging isolator is designed to reduce the transmission of vibration and noise produced by suspended equipment and piping. To assure stability, the spring element has a minimum lateral stiffness of 1.0 times the rated vertical stiffness. The hanger will allow a support rod misalignment through a 30 degree arc and the isolation brackets will carry a 500% overload without failure. The isolator has an epoxy powder coated bracket and spring coil which is color coded according to the load capacity and has a noise isolation pad, all which is assembled into a stamped or welded hanger bracket.
This part number includes 4 isolators.
Isolator Configuration Description: SH-1-70 Color: Green Manufacturer: Kinetics Noise Control Mounting: Hanging Load Capacity: 32 kg Kit Part Number: 850344 Deflection: 35 mm
NEOPRENE ELEMENT
Spring Hanging Deflection - Vibration Isolator
Ø15.875 MAX
Notes: All dimensions shown are in units of mm
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON 12-827-822-2014.gcj Page 55 of 216Specification 233423 - Page 45 of 217
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 83 87 80 84 73 68 67 65 83 72 20 Radiated 82 82 70 74 62 49 48 52 74 62 11.3
BLOWER
HOUSING Inlet
Inline Discharge
Motor Cover
ELEVATION VIEW
Inlet
Motor Cover
END VIEW
Inlet Inline
Discharge Motor Cover
PLAN VIEW
25.4
25.4 533 381
Model: BSQ-90-7 Belt Drive Centrifugal Inline Fan
Dimensional Quantity 1
Weight w/o Acc's (kg) 42
Weight w/ Acc's (kg) 55
Max T Motor Frame Size 145
Optional Damper (mm) 305 x 305
Performance Requested Volume (L/sec) 420
Actual Volume (L/sec) 420
External SP (Pa) 312
Total SP (Pa) 312
Fan RPM 2234
Operating Power (hp) 0.63
Elevation (m) 25
Airstream Temp.(C) 21
Air Density (m3) 1.198
Drive Loss (%) 7.5
Tip Speed (m/sec) 33.244
Static Eff. (%) 30
Motor Motor Mounted Yes
Size (hp) 3/4
V/C/P 400/50/3
Enclosure TEFC
Motor RPM 1425
Windings 1 NEC FLA* (Amps) NA
Notes:
All dimensions shown are in units of mm *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 1.52 m - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 1.52 m
10/16/2014Printed Date:
LONDON 12-827-822-2014Job:
EF-11Mark:
CAPS 4.15.1679 C:\Users\scott_2\Documents\CAPS\Jobs\LONDON…
This is the start of the file's text. The full file is on GovTribe.