Central_Station_Air_Handling_Units_O&M.PDF

PDF 9 MB Posted

Attached to
HVAC Maintenance services for US Embassy London UK
Solicitation number
19GE5018R0023
Issued by

About this file

Central Station Air Handling Units

View the file

Other files

File Type Posted
Exhibit_A.pdf PDF
Exhibit_B.pdf PDF
Exhibit_D.pdf PDF
Exhibit_C.pdf PDF
O&M_Hydronic_Pumps_-_5.pdf PDF
O&M_Hydronic_Pumps_-_2.pdf PDF
O&M_Hydronic_Pumps_-_6.pdf PDF
O&M_Hydronic_Pumps_-_0.1.pdf PDF
Centrifugal_Water_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_0.pdf PDF
Computer_Room_AC_O&M.PDF PDF
DHR_Modular_Chiller_O&M_-_1_of_2.pdf PDF
Soliciation_19GE5018R0023.pdf PDF
O&M_Hydronic_Pumps_-_4.2.pdf PDF
HX_1&2_O&M.PDF PDF
Cooling_Towers_O&M.PDF PDF
HVAC_Power_Ventilators_O&M.PDF PDF
Heat_Echangers_for_HVAC_Schedule.pdf PDF
HVAC_Ventilators_Schedule.pdf PDF
Hydronic_Pumps_Schedule.pdf PDF
Air_Terminal_Units_(VAV)_-_O&M.PDF PDF
O&M_Hydronic_Pumps_-_3.pdf PDF
DHR_Modular_Chiller_O&M_-_2_of_2.pdf PDF
O&M_Hydronic_Pumps_-_1.pdf PDF
Air_Cooled_Modular_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_4.1.pdf PDF
Original_Signed_letter_19GE5018R0023.pdf PDF
HX_3&4_O&M.PDF PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Operation & Maintenance Manuals London, United Kingdom NEC

237315

CENTRAL - STATION AIR - HANDLING

UNITS

Table of Contents Page Trane Unit Construction Product Description 1

Thermal Break 6 Twin City Fan and Blower Product Data 16 Spare Filter Schedule 83 CamSorb CH Product Data 86 Durafil ES Product Data 88 Filtra 2000 Gel Product Data 90 HEGA Product Data 92 Opti-Pac Product Data 96 RUSKIN - Control Damper Product Description 108

Electrical and Controls 112 Electrical Data Sheets 114

Schneider Limit Switch Product Description 115 Midget Relays Product Description 117 AC Switch Features Product Data 119 Central Station AHUs - Genie Lift Information 123

Job: US Embassy London EQ Number: 16751 Date: Jan 10, 2014

Rev.: 1

Aire Systems a division of American Standard 9900 Aire Circle, Fort Smith, AR 72916 Phone: (479) 648-7400 Fax: (479) 648-7499

UNIT CONSTRUCTION

BASE FRAME Carbon steel structural intermediate supports installed a minimum 24” centers.

Perimeter base frame is painted Trane Slate Gray

CABINET FLOOR Surface consists of continuous welded 1/8” Aluminum treadplate.

1 ½ ” aluminum floor drains as indicated on the drawings. Drains are stubbed through the perimeter channel. Floor drains are provided with caps.

2” turned up lip to create a waterdam at each section and all opening in the base.

WALLS (exterior) 2” Class “A” thermal break panel construction.

18 ga,galvaneal solid exterior.

18 ga, galvanized steel solid inner liner.

Internal tunnel walls (i.e. fan/damper/blender walls) are un-insulated, 16ga. galvanized single wall C-panels.

ROOF 2” Class “A” thermal break panel construction.

18 ga,galvaneal solid exterior.

18 ga, galvanized steel solid inner liner.

SAFING All safing will be galvanized safing unless otherwise stated.

Cooling coil safing will be stainless steel Heating coil safing will be galvanized steel.

Filter rack safing will be galvanized steel.

INSULATION 2” Injected foam installed in walls and roof. Foam is polyurethane foam isocyanate

Insulation in compliance with NFPA90A 3” polyurethane foam sprayed onto the underside of the floor liner.

Foam Insulation is R-13 Minimum.

EXTERIOR PAINT Unit color will be Trane Slate Grey.

Paint system to meet 1000 hr salt spray requirements

DRAIN PANS 16 ga. stainless steel, double-sloped insulated drain pans with 1-1/2in stainless steel MPT drain.

Specification 237315, Page 1 of 124

Date: Jan 10, 2014

Rev.: 1

Aire Systems a division of American Standard 9900 Aire Circle, Fort Smith, AR 72916 Phone: (479) 648-7400 Fax: (479) 648-7499

ACCESS DOORS Door thickness

Exterior material

Interior material

Insulation

Handles

Hinge

Windows

Options

2”

16 gauge

20 gauge galvanized

2.25#/ft3 polyurethane foam insulation

Pad Lockable Allegis

Continuous stainless steel piano Hinge

No windows

IP-4 test ports installed in Prefilter access doors.

UNIT SUPPORT

REQUIREMENTS

Unit requires full perimeter support. Units shipped in multiple sections require additional support at each of the shipping split locations.

Installation co-ordination and AHU mounting details need to be made available to AHU manufacturer for review to ensure no interference issues occur at the jobsite. Installation contractor is responsible for providing these details to the AHU manufacturer. Contractor to work with local Trane office and AHU manufacturer.

COIL TEST AND OPERATING

PRESSURES

Coils are designed for 250 psi max operating pressure and max fluid temp of 350F. Coils are factory tested to 315 psi air pressure.

PIPE CONNECTIONS Heating and cooling coil supply and return connections, plus the vent and drain, will be extended to the outside of the unit for connection by others. For units with corridors, the pipes will terminate inside the corridor for connection by others.

Pipe penetrations are sealed with Rubber grommets, or if space restraints exist, sheet metal collars rings.

Pipe extension material is Sch. 40 brass.

Vent and drain material is Sch. 40 brass.

All pipe insulation is by others.

SHIP LOOSE Filter clips to ship with filters from FARR.

SPARE PARTS Primary Door gasket Secondary Door gasket Filter Gauges

ELECTRICAL Units are ETL labeled

See included electrical diagram

EMT Conduit, Zinc Die-cast Compression Connector, and Flexible Metal Conduit (FMC) are standard conduits.

Power wiring splices are connected with a power distribution block mounted in a NEMA 1 enclosure located on the ceiling/sidewall of the unit.

Control wiring splices are connected with MOLEX type connectors mounted in a NEMA 1 enclosure located on the ceiling/sidewall of the unit.

Electrical enclosures downstream (2 feet) of the cooling coil and downstream of the humidifier grid are to be rated for ‘damp location’.

Specification 237315, Page 2 of 124

Date: Jan 10, 2014

Rev.: 1

Aire Systems a division of American Standard 9900 Aire Circle, Fort Smith, AR 72916 Phone: (479) 648-7400 Fax: (479) 648-7499

CONTROLS Controls not provided by Trane Custom.

¾” Conduit penetration in unit casing provided for controls installation by others.

TESTING Unit will be tested for leakage to confirm a maximum leakage rate of 2% at 10” (2.48 kPa) pressure. Positive pressure for positive sections, and negative test for negative sections.

Deflection test performed to confirm maximum L/240 deflection, where L is defined as the panel height. Deflection will be measured at the mid-point of the worst case wall panel of each shipping section.

Specification 237315, Page 3 of 124

Date: Jan 10, 2014

Rev.: 1

Aire Systems a division of American Standard 9900 Aire Circle, Fort Smith, AR 72916 Phone: (479) 648-7400 Fax: (479) 648-7499

Job Specific Testing requirements for Production

Job Name ------ US Embassy London

Eq Number ----- 16751

Sales Order ---- J4J757

CUSTOMER WITNESS (YES/NO) YES

LEAKAGE TEST REQUIREMENTS DEFLECTION TEST REQUIREMENTS AIRFLOW TEST VIBRA

TION

TESTPOSITIVE TEST NEGATIVE TEST

AHU

TAG

TOTAL ALLOWABLE

LEAKAGE IN CFM

(POS & NEG.

COMBINED

TEST

PRESSUR

E inches

W.C.

C

W

TEST

PRESSUR

E inches

W.C.

C

W

DEFLECTI

ON SPEC.

EX.

L/200

ALLOWABLE

PANEL

DEFLECTION

inches

TEST

PRESSU

RE

inches

W.C.

C

W

MEASUREM

ENT

METHOD,

PITOT

TRAVERSE /

PIEZOMETER

TES

T

DUC

T

SIZE

CW

Y

E

S

N

O

AHU-

LL-1

80 10 Y 10 Y L/240 .383 10 Y N/A N/A N N

AHU-

LL-2

222 10 Y 10 Y L/240 .383 10 Y N/A N/A N N

AHU-

LL-3

224 10 Y 10 Y L/240 .383 10 Y N/A N/A N N

AHU-

CC

183 10 Y 10 Y L/240 .316 10 Y N/A N/A N N

AHU-

MC

55 10 Y 10 Y L/240 .249 10 Y N/A N/A N N

AHU-

SC

121 10 Y 10 Y L/240 .249 10 Y N/A N/A N N

Specification 237315, Page 4 of 124

Conditions above the curve can cause condensation on the unit exterior. The delta between the curve and each condition, as well as the length of time the condition is sustained, will impact the degree of condensation. Additional factors, such as field modifications to units, can also impact the degree of condensation.

52 oF Supply Air Temperature

20 Feet above sea level

86 oF Dry Bulb 65 oF Wet Bulb

Trane Climate Changer

Casing Thermal Performance Predictor

Data Revision: C

Casing thermal performance is for double-wall solid panels. Air handler casings designed with double-wall perforated panels only do not provide a thermal break. To achieve the thermal performance modeled above with perforated liners, a perforated panel with fiberglass should be provided on the unit interior in addition to a thermally-broken, double-wall solid panel.

Page 1 of 1Trane Climate Changer Casing Thermal Performance Predictor

3/17/2014http://tbsnet/portlets/custom_dashboard/frminterface.aspx

Specification 237315, Page 5 of 124

Trane custom class “a” thermal break

Specification 237315, Page 6 of 124

Specification 237315, Page 7 of 124

Specification 237315, Page 8 of 124

Specification 237315, Page 9 of 124

Specification 237315, Page 10 of 124

Specification 237315, Page 11 of 124

Specification 237315, Page 12 of 124

Job: LONDON EMBASSY

Date: 01/10/14

SOUND POWER ESTIMATE SCHEDULE Revision 0

LL-1 Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 73 71 68 66 64 62 53 52

Ducted Inlet Lw 52 54 58 49 50 47 29 19

Casing Lw 78 74 77 74 75 57 42 45

LL-2 Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 81 78 73 73 68 68 64 60

Ducted Inlet Lw 66 64 64 64 58 55 40 29

Casing Lw 86 80 79 82 80 61 45 48

LL-3 Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 74 73 71 68 66 65 56 54

Ducted Inlet Lw 60 62 61 58 58 53 35 27

Casing Lw 80 77 80 77 77 59 45 47

AHU-CC Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 72 69 68 63 61 60 51 52

Ducted Inlet Lw 53 53 58 49 49 45 29 19

Casing Lw 78 74 77 74 73 55 41 45

AHU-MC Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 68 64 52 58 50 49 44 43

Ducted Inlet Lw 46 50 41 37 33 34 21 10

Casing Lw 70 66 62 69 60 45 30 31

AHU-SC Overall 63 125 250 500 1K 2K 4K 8K

Discharge Lw 76 68 64 63 58 53 53 50

Ducted Inlet Lw 57 53 50 43 44 39 32 19

Casing Lw 78 72 71 72 66 47 33 34

Specification 237315, Page 13 of 124

Date: 1/10/2014 Revision 2

Fan Unit No. Fan Tag Service Total L/S Fan TSP , (Pa) Elevation, M RPM Brake KW Motor Nominal KW AMCA Class Manufacturer & Model Fan Size AHU-LL-1 SF-LL.1 Supply 4410 1870 0 1660 10.95 15.00 II Twin City EPQN 300

Unit No. Fan Tag Motor Manufacturer Motor Model

Number Volts/PH/HZ Motor

Enclosure Motor

Efficiency Isolator Type Feature Codes Wheel Width, % Wheel Diameter, % AHU-LL-1 SF-LL.1 Baldor Custom 400/3/50 TEFC Premium AMSR-2D IS WC EL SG 58 100

Cooling Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators AHU-LL-1 CC-LL-1 4410 2.22 2 6 3.93 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa)

AHU-LL-1 CC-LL-1 C 4.0 16.0 230

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model AHU-LL-1 CC-LL-1 Water Copper, .19mm Copper, .9mm SS N/A N/A 0 HEATCRAFT 5Wl1106C 1028.7 x 965.2

Heating Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators Coil Tag HC-LL-1 1110 0.60 1 1 2.36 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa) Coil Tag HC-LL-1 A 0.5 4.0 0

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model Coil Tag HC-LL-1 Water Copper, .19mm Copper, .9mm Galvanized N/A N/A 0 HEATCRAFT 5MI0601A 1905.0 x 965.2

Dampers Unit No. Qty. Service Damper W (mm) Damper H (mm) L/S Velocity (M/S) Blade Action Torque (NM) Manufacturer Model Feature Codes AHU-LL-1 1 RA 1219 610 4410 5.9 Opposed 6.3 Ruskin CD-60 FF AHU-LL-1 1 OA 1219 610 4410 5.9 Opposed 6.3 Ruskin CD-60 FF

Prefilters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 13/300mm AHU-LL-1 Pleated 2 4410 1.98 6 C-80 SS Type 8 FARR DURAFIL ES Dwyer 605, 500 Pa Upstream

HEPA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access 99.97% AHU-LL-1 HEPA 2 4410 1.98 6 SWING BOLT FARR FARR FA1570A-01-01 Dwyer 605, 500 Pa Upstream

HEGA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access AHU-LL-1 HEGA 2 4410 1.98 6 FARR FARR FARR CF-F242419-121-TP Dwyer 605, 1000 Pa Side

Post Filters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 11/100mm AHU-LL-1 Pleated 2 4410 1.98 6 FARR FARR FARR OPTIPAC MERV 11 N/A Side

Feature Codes IV Inlet Vanes CF Companion Flange FF Front Flange IS Inlet Screen WC Wheel Cage SG Shaft Grounding OS Outlet Screen DE Duct Equalizer UB Unitary Base DEF Duct Equalizer /w Flange IB Inertia Base SSO Short Silencer (outlet) EL Extended Lube Fittings LSO Long Silencer (outlet) LLX Lube Lines to Case Exterior OG OSHA Drive Guard SP Special Coatings TR Thrust Restraints

Initial Final AHU-LL-1 Airflow 4410 L/s 9344 cfm AHU-LL-1 Airflow 4410 L/s 9344 cfm

Filters Filters 6 6

12" 85% 52 pa 0.21 w.g. 12" 85% 291 pa 1.17 w.g.

Hepa Filter 169 pa 0.68 w.g. Hepa Filter 338 pa 1.36 w.g.

Carbon Filter 426 pa 1.71 w.g. Carbon Filter 426 pa 1.71 w.g.

Post Filter 64 pa 0.26 w.g. Post Filter 0 pa 0.00 w.g.

Heating Coil 12 pa 0.05 w.g. Heating Coil 12 pa 0.05 w.g.

Cooling Coil 230 pa 0.93 w.g. Cooling Coil 230 pa 0.93 w.g.

ESP 572 pa 2.30 w.g. ESP 572 pa 2.30 w.g.

Total pa. 1526 Calculated 6.13 Calculated Total pa. 1870 Calculated 7.51 Calculated 1786 Scheduled 7.18 Scheduled

Model No. and Size, HXW 5Wl1106C 1028.7 x 965.2

Capacity TOTAL/SENSIBLE, KW 118.9/84.29

Air Ent Temp DB/WB (C) 26.60/18.80

Air Lvg Temp DB/WB (C) 10.96/10.52

Fluid Ent Temp/Lvng Temp (C)

6.70/13.79

7.2 24.3 60.00/49.66

Model No. and Size, HXW Capacity TOTAL/SENSIBLE, KW 5MI0601A 1905.0 x 965.2 23.0

Air Ent Temp DB/WB (C) Air Lvg Temp DB/WB (C) Fluid Ent Temp/Lvng Temp

Specification 237315, Page 14 of 124

Specification 237315, Page 15 of 124

Customer: W/A May 29, 2014 Job Name: London Embassy Page 1 Job ID: 16751

Fan Description Fan Performance Motor Data

Tag . . . . . . . . . . . . . . . . . SF-LL.1 l/sec . . . . . . . . . . . . . . . . . . . 4,410 HP (kW) Quantity . . . . . . . . . . . . . . . . . . . . 1 Operating SP (Pa) . . . . . . . . 1,870 RPM Type . . . . . . . . . . . . . . . . . . . EPQN Standard SP (Pa) . . . . . . . . 1,870 Voltage . . . . . . . . . . . . . . . . . 400V Size . . . . . . . . . . . . . . . . . . . . . 300 RPM . . . . . . . . . . . . . . . . . . . . 1660 Phase Width . . . . . . . . . . . . . . . . . . SWSI Tip Speed (m/sec) . . . . . . . . . 66.2 Hz Arrangement . . . . . . . . . . . . . . . . 4 Oper. BHP (kW) . . . . . . . . . 10.95 Enclosure . . . . . TEFC - Premium Class . . . . . . . . . . . . . . . . . . . . . . II Standard BHP (kW) . . . . . . . 10.95 Frame . . . . . . . . . . . . . . . . . . 254T Rotation . . . . . . . . . . . . . . . . . W/A Outlet area (m²) . . . . . . . . . . 0.377 Design VFD Op. Freq.(hz) Discharge . . . . . . . . . . . . . . . HOR Outlet Velocity (m/sec) . . . . . 11.7 Wheel diameter (m) . . . . . . . . 0.76 Temperature (°C) Drive method . . . 50 Hz direct drive Altitude (m) Percentage width . . . . . . . . . . 58% Density (kg/m³) . . . . . . . . . . 1.201 Percentage diameter . . . . . . 100% Max RPM for Class

Static Efficiency . . . . . . . . . . 75.21 Total Efficiency . . . . . . . . . . 78.52

Modifiers

% width: 58%, Outlet Diffuser

Sound

Sound Power Levels in dB re. 10 -12 Watts:

Octave Bands 1 2 3 4 5 6 7 8 LwA Level at Inlet 84 86 92 95 81 79 75 69 93 Level at Outlet 89 86 93 96 86 82 77 71 95

Estimated sound pressure level in dBA (re: 0.0002 microbar) based on a single* ducted installation:

Distance in m 0.3 0.91 1.52 dBA at Inlet 93 83 79 dBA at Outlet 95 85 81

*To estimate dBA level for ducted inlet and ducted outlet (into and out of the room) type installation, deduct 20 from the LwA value shown.

Using a directivity factor of 1.

Estimated Sound Pressure based on free field, spherical (Q = 1) radiation at the stated distance.

Definitions:

LwA The overall (single value) fan sound power level, 'A' weighted.

dBA The environment for each fan installation influences its measured sound value, therefore dBA levels cannot be guaranteed. Consult AMCA Publication 303 for further details.

A fan's dBA is influenced by nearby reflective surfaces.

Ver 9.930X - Report B Job created 01-06-2014

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 16 of 124

Job Name: London Embassy Page 2 Job ID: 16751

Accessories Included

EPQN 300, Class II, Arrangement 4 Bare fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Net 209 kg Guard - Protective Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 kg Screen - Inlet, Std Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Special Width Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Wheel - Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Diffusers - Aero Acoustic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 kg 15 kW, 1500 RPM, 400V, 3Ph, 50Hz, TEFC - Premium, 254T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Mount TCF Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg

Total Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238 kg

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 17 of 124

Specification 237315, Page 18 of 124

Specification 237315, Page 19 of 124

N A M E P L A T E -

NP2717L -

CAT NO -

SPEC. CUSTOM -

HP 20 PH 3 -

VOLTS 400 -

AMP 28 -

RPM 1460 -

FRAME 256T HZ 50 I.P. 54 -

SER.F. 1.15 CODE H DES B CL H -

NEMA-NOM-EFF 91.2 % (100%) -

PF 83 USABLE AT 208V -

RATING 40C AMB-CONT CC -

DE BRG 6309 ODE 6208 -

ENCL TEFC SN -

BLANK IE2-92.4(75%)92.0(50%) -

*** End of Report ***

Specification 237315, Page 20 of 124

Customer: Date: 5/12/2014 Contact: From:

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

Construction Air Side Item: CC-LL-1 (3x2) Air Flow (Sl/s) 4410.0 Coils Per Bank: 2 Altitude M: 0.00 Allow Opp. End: No Ent. Air DB/WB °C: 26.60 / 18.80 Tube OD mm: 15.87 Lvg. Air DB/WB °C: 11.10 / 10.90 Coil Duty: Cool-Standard Total / Sensible kW: 0.00 / 0.00 Fin Spacing(mm): 2.31 Max Air PD kPa: 0.00 Rows: 6 Fin Surface: Optimize ABC Fluid Side Fin Height (mm): 1028.7 Fluid Type: Water Finned Length (mm): 965.2 Ent. Fluid : 6.70 Tubing Mat. (mm): 0.889 Copper Lvg. Fluid : 0.00 TurboSpirals: Yes Fluid Flow l/s: 4.00 Fin Mat. (mm): 0.1905 Copper Max FPD kPa: 26.80 Conn Qty/Size (mm): 1 / Optimize Circuiting: Three Quarter Face Area (SQ M): 1.9858 O U T P U T D A T A Most Economical Specified Coil

Coil 1 Coil 2 Coil 3 Coil 4 Coil 5 Coil 6 Model Number: 5WL1106C Air Velocity: (Sm/s) 2.22 Total Capacity: kW 118.9 Sens. Capacity: kW 84.29 Lvg. Air DB: °C 10.96 Lvg. Air WB: °C 10.52 Standard APD kPa 0.23 Lvg. Fluid: °C 13.79 Fluid Flow: l/s 4.00 Fluid PD: kPa 16.02 Fluid Vel.: ft/s 1.91 Conn Size: IN (1) 1.500 Internal Volume: in^3 2078.9 Weight (Dry): lbm 469.5 Weight (w/Fluid): lbm 546.9 Notes: BCL

Notes:

B) Coil is Outside of the scope of AHRI Standard 410. L) Coil rating valid for Heatcraft coils only.

C) Coil is NOT certified by AHRI.

HEATCRAFT FLUID SELECTION 7.05.32.3

Copyright 2003 Luvata Grenada LLC Confidential and Proprietary. This design is for the exclusive and confidential use of Luvata Grenada LLC and its client. Any duplication made for the purpose of disclosing this design or any part of the design to a competitor of Luvata Grenada LLC is in direct violation of this confidentiality. Any duplication must be approved in writing by Luvata Grenada LLC.

Page 1Specification 237315, Page 21 of 124

HEATCRAFT CERTIFIED DRAWING 7.05.32.3

Confidential and proprietary. All copyrights in this work are owned by Luvata Grenada LLC. This drawing is for the exclusive and confidential use of Luvata Grenada LLC and its client. This drawing may not be reproduced or distributed or displayed to any third party whatsoever without the prior written consent of Luvata Grenada LLC.

Customer: Date: 5/12/2014 Contact: From:

Telephone: Company:

Fax: Return Tel:

Job: Return Fax:

MODEL NUMBER

ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND

CC-LL-1 (3x2) 2 5WL 11 06 C 40.50 38.00 Right

MATERIALS OF CONSTRUCTION OPTIONS

Fins 0.0075 Copper Coating None Turbospirals Yes Tubes 0.035 Copper Casing Type Flanged Nitrogen Charge No Casing 304L S/S Vent & Drain .50 FPT on Face Moisture Eliminator No Conn. Material Carbon Steel Mounting Holes No Conn. Type MPT Label Kit No Conn. Size 1.500 Conn. Quantity 1 Conn. Rotation None

Vent/Drain Location

DIMENSIONAL DATA(IN)

A B C E H I J L M N R S1 S2 T W

1.75 1.75 6.00 6.00 42.00 45.00 9.00 41.00 4.50 2.50 1.50 0.75 0.75 1.50 10.00

NOTES:

GENERAL NOTES:

1. All dimensions are in (in)

2. Manually verifying dimensions is highly recommended.

3. The supply line should be connected to the lower connection on the leaving air side for counterflow operation.

4. Coils will vent and drain through factory-installed vent and drain fittings when mounted level for horizontal flow.

5. Connection location other than standard could affect vent and drain locations. Consult factory.

Specification 237315, Page 22 of 124

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

Construction Air Side Item: HC-LL-1 (3x2) Air Flow (Sl/s) 1110.0 Coils Per Bank: 1 Altitude M: 0.00 Allow Opp. End: No Ent. Air DB °C: 7.20 Tube OD mm: 15.87 Lvg. Air DB °C: 12.80 Coil Duty: Heat-Return Bend Total Capacity kW: 0.00 Fin Spacing(mm): Optimize Max Air PD kPa: 0.00 Rows: 1 Fin Surface: Optimize ABC Fluid Side Fin Height (mm): 1905.0 Fluid Type: Water Finned Length (mm): 965.2 Ent. Fluid : 60.00 Tubing Mat. (mm): 0.889 Copper Lvg. Fluid : 0.00 TurboSpirals: Yes Fluid Flow l/s: 0.54 Fin Mat. (mm): 0.1905 Copper Max FPD kPa: 0.00 Conn Qty/Size (mm): 1 / Optimize Circuiting: Optimize Face Area (SQ M): 1.8387 O U T P U T D A T A Most Economical Specified Coil

Coil 1 Coil 2 Coil 3 Coil 4 Coil 5 Coil 6 Model Number: 5MI0601A Air Velocity: (Sm/s) 0.60 Total Capacity: kW 23.01 Lvg. Air DB: °C 24.30 Standard APD kPa 0.00 Lvg. Fluid: °C 49.66 Fluid Flow: l/s 0.54 Fluid PD: kPa 4.00 Fluid Vel.: ft/s 1.29 Conn Size: IN (1) 1.500 Internal Volume: in^3 1000.3 Weight (Dry): lbm 170.4 Weight (w/Fluid): lbm 201.9 Notes: BCEKL

Notes:

B) Coil is Outside of the scope of AHRI Standard 410. K) Face and Row spacing on 1.5 inch centers.

C) Coil is NOT certified by AHRI. L) Coil rating valid for Heatcraft coils only.

E) Rating is an estimate of performance, actual performance may vary by application

HEATCRAFT FLUID SELECTION 7.05.32.3

Copyright 2003 Luvata Grenada LLC Confidential and Proprietary. This design is for the exclusive and confidential use of Luvata Grenada LLC and its client. Any duplication made for the purpose of disclosing this design or any part of the design to a competitor of Luvata Grenada LLC is in direct violation of this confidentiality. Any duplication must be approved in writing by Luvata Grenada LLC.

Page 1Specification 237315, Page 23 of 124

Confidential and proprietary. All copyrights in this work are owned by Luvata Grenada LLC. This drawing is for the exclusive and confidential use of Luvata Grenada LLC and its client. This drawing may not be reproduced or distributed or displayed to any third party whatsoever without the prior written consent of Luvata Grenada LLC.

Customer: Date: 5/12/2014 Contact: From:

Telephone: Company:

Fax: Return Tel:

Job: Return Fax:

MODEL NUMBER

ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND

HC-LL-1 (3x2) 1 5MI 06 01 A 75.00 38.00 Right

MATERIALS OF CONSTRUCTION OPTIONS

Fins 0.0075 Copper Coating None Turbospirals Yes Tubes 0.035 Copper Casing Type Flanged Nitrogen Charge No Casing Galvanized Steel Vent & Drain .50 FPT on Face Moisture Eliminator No Conn. Material Red Brass Mounting Holes No Conn. Type MPT Label Kit No Conn. Size 1.500 Conn. Quantity 1 Conn. Rotation None

Vent/Drain Location

DIMENSIONAL DATA(IN)

A B C E H I J L M N R S1 S2 T W

1.88 1.88 6.00 6.00 76.50 44.50 9.00 41.00 4.50 2.00 1.50 0.75 0.75 1.50 6.00

NOTES:

GENERAL NOTES:

1. All dimensions are in (in)

2. Manually verifying dimensions is highly recommended.

3. The supply line should be connected to the lower connection on the leaving air side for counterflow operation.

4. Coils will vent and drain through factory-installed vent and drain fittings when mounted level for horizontal flow.

Specification 237315, Page 24 of 124

Date: 1/10/2014 Revision 4

Fan Unit No. Fan Tag Service Total L/S Fan TSP , (Pa) Elevation, M RPM Brake KW Motor Nominal KW AMCA Class Manufacturer & Model Fan Size AHU-LL-2 SF-LL.2 Supply 5230 2001 0 1561 13.91 15.00 II Twin City EPQN 330

Unit No. Fan Tag Motor Manufacturer Motor Model

Number Volts/PH/HZ Motor

Enclosure Motor

Efficiency Isolator Type Feature Codes Wheel Width, % Wheel Diameter, % AHU-LL-2 SF-LL.2 Baldor Custom 400/3/50 TEFC Premium AMSR-2D IS WC EL SG 55 100

Cooling Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators AHU-LL-2 CC-LL-2 5230 1.53 2 6 3.93 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa)

AHU-LL-2 CC-LL-2 C 6.1 9.9 110

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model AHU-LL-2 CC-LL-2 Water Copper, .19mm Copper, .9mm SS N/A N/A 0 HEATCRAFT 5WM0906C 990.6 x 1727.2

Heating Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators Coil Tag HC-LL-2 5230 1.61 1 1 2.36 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa) Coil Tag HC-LL-2 A 0.9 4.2 0

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model Coil Tag HC-LL-2 Water Copper, .19mm Copper, .9mm Galvanized N/A N/A 0 HEATCRAFT 5MQ0601A 2057.4 x 1574.8

Dampers Unit No. Qty. Service Damper W (mm) Damper H (mm) L/S Velocity (M/S) Blade Action Torque (NM) Manufacturer Model Feature Codes AHU-LL-2 1 RA 1829 610 5230 4.7 Opposed 9.5 Ruskin CD-60 FF AHU-LL-2 1 OA 1829 610 5230 4.7 Opposed 9.5 Ruskin CD-60 FF

Prefilters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 13/300mm AHU-LL-2 Pleated 2 5230 1.56 9 C-80 SS Type 8 FARR DURAFIL ES Dwyer 605, 500 Pa Upstream

HEPA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access 99.97% AHU-LL-2 HEPA 2 5230 1.56 9 SWING BOLT FARR FARR FA1570A-01-01 Dwyer 605, 500 Pa Upstream

HEGA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access AHU-LL-2 HEGA 2 5230 1.56 9 FARR FARR FARR CF-F242419-121-TP Dwyer 605, 1000 Pa Side

Post Filters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 11/100mm AHU-LL-2 Pleated 2 5230 1.56 9 FARR FARR FARR OPTIPAC MERV 11 N/A Side

Feature Codes IV Inlet Vanes CF Companion Flange FF Front Flange IS Inlet Screen WC Wheel Cage SG Shaft Grounding OS Outlet Screen DE Duct Equalizer UB Unitary Base DEF Duct Equalizer /w Flange IB Inertia Base SSO Short Silencer (outlet) EL Extended Lube Fittings LSO Long Silencer (outlet) LLX Lube Lines to Case Exterior OG OSHA Drive Guard SP Special Coatings TR Thrust Restraints

Initial Final AHU-LL-2 Airflow 5230 L/s 11082 cfm AHU-LL-2 Airflow 5230 L/s 11082 cfm

Filters Filters 9 9

12" 85% 41 pa 0.17 w.g. 12" 85% 230 pa 0.92 w.g.

Hepa Filter 134 pa 0.54 w.g. Hepa Filter 267 pa 1.07 w.g.

Carbon Filter 337 pa 1.35 w.g. Carbon Filter 337 pa 1.35 w.g.

Post Filter 51 pa 0.20 w.g. Post Filter 0 pa 0.00 w.g.

Heating Coil 12 pa 0.05 w.g. Heating Coil 12 pa 0.05 w.g.

Cooling Coil 109 pa 0.44 w.g. Cooling Coil 109 pa 0.44 w.g.

ESP 1045 pa 4.20 w.g. ESP 1045 pa 4.20 w.g.

Total pa. 1730 Calculated 6.95 Calculated Total pa. 2001 Calculated 8.04 Calculated 1888 Scheduled 7.59 Scheduled

Model No. and Size, HXW Capacity TOTAL/SENSIBLE, KW 5WM0906C 990.6 x 1727.2 168.3/108.6

Air Ent Temp DB/WB (C) Air Lvg Temp DB/WB (C) Fluid Ent Temp/Lvng Temp

(C) 28.10/20.20 11.11/10.67 6.70/13.30

Model No. and Size, HXW Capacity TOTAL/SENSIBLE, KW 5MQ0601A 2057.4 x 1574.8 68.9

Air Ent Temp DB/WB (C) Air Lvg Temp DB/WB (C) Fluid Ent Temp/Lvng Temp

4.4 15.3 60.00/41.46

Specification 237315, Page 25 of 124

Specification 237315, Page 26 of 124

Customer: W/A April 17, 2014

Job ID: 16751

Fan Description Fan Performance Motor Data

Tag . . . . . . . . . . . . . . . . . SF-LL.2 l/sec . . . . . . . . . . . . . . . . . . . 5,230 HP (kW) Quantity . . . . . . . . . . . . . . . . . . . . 1 Operating SP (Pa) . . . . . . . . 2,001 RPM Type . . . . . . . . . . . . . . . . . . . EPQN Standard SP (Pa) . . . . . . . . 2,001 Voltage . . . . . . . . . . . . . . . . . 400V Size . . . . . . . . . . . . . . . . . . . . . 330 RPM . . . . . . . . . . . . . . . . . . . . 1561 Phase Width . . . . . . . . . . . . . . . . . . SWSI Tip Speed (m/sec) . . . . . . . . . 68.5 Hz Arrangement . . . . . . . . . . . . . . . . 4 Oper. BHP (kW) . . . . . . . . . 13.91 Enclosure . . . . . TEFC - Premium Class . . . . . . . . . . . . . . . . . . . . . . II Standard BHP (kW) . . . . . . . 13.91 Frame . . . . . . . . . . . . . . . . . . 256T Rotation . . . . . . . . . . . . . . . . . W/A Outlet area (m²) . . . . . . . . . . 0.432 Design VFD Op. Freq.(hz) Discharge . . . . . . . . . . . . . . . HOR Outlet Velocity (m/sec) . . . . . 12.1 Wheel diameter (m) . . . . . . . . 0.84 Temperature (°C) Drive method . . . 50 Hz direct drive Altitude (m) Percentage width . . . . . . . . . . 55% Density (kg/m³) . . . . . . . . . . 1.201 Percentage diameter . . . . . . 100% Max RPM for Class

Static Efficiency . . . . . . . . . . 75.15 Total Efficiency . . . . . . . . . . 78.46

Modifiers

% width: 55%, Outlet Diffuser

Sound

Sound Power Levels in dB re. 10 -12 Watts:

Octave Bands 1 2 3 4 5 6 7 8 LwA Level at Inlet 86 87 95 96 82 81 76 70 95 Level at Outlet 90 86 95 97 87 83 77 72 96

Estimated sound pressure level in dBA (re: 0.0002 microbar) based on a single* ducted installation:

Distance in m 0.3 0.91 1.52 dBA at Inlet 95 85 81 dBA at Outlet 96 86 82

*To estimate dBA level for ducted inlet and ducted outlet (into and out of the room) type installation, deduct 20 from the LwA value shown.

Using a directivity factor of 1.

Estimated Sound Pressure based on free field, spherical (Q = 1) radiation at the stated distance.

Definitions:

LwA The overall (single value) fan sound power level, 'A' weighted.

dBA The environment for each fan installation influences its measured sound value, therefore dBA levels cannot be guaranteed. Consult AMCA Publication 303 for further details.

A fan's dBA is influenced by nearby reflective surfaces.

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 27 of 124

Job ID: 16751

Accessories Included

EPQN 330, Class II, Arrangement 4 Bare fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Net 262 kg Guard - Protective Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 kg Screen - Inlet, Std Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Special Width Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Wheel - Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Diffusers - Aero Acoustic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 kg 15 kW, 1500 RPM, 400V, 3Ph, 50Hz, TEFC - Premium, 256T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Mount TCF Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg

Total Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298 kg

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 28 of 124

Specification 237315, Page 29 of 124

Specification 237315, Page 30 of 124

NP2717L -

CAT NO -

SPEC. CUSTOM -

HP 20 PH 3 -

VOLTS 400 -

AMP 28 -

RPM 1460 -

FRAME 256T HZ 50 I.P. 54 -

SER.F. 1.15 CODE H DES B CL H -

NEMA-NOM-EFF 91.2 % (100%) -

PF 83 USABLE AT 208V -

RATING 40C AMB-CONT CC -

DE BRG 6309 ODE 6208 -

ENCL TEFC SN -

BLANK IE2-92.4(75%)92.0(50%) -

Specification 237315, Page 31 of 124

Customer: Date: 7/14/2014

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

Construction Air Side Item: CC-LL-2 (3x3) Air Flow (Sl/s) 5230.0 Coils Per Bank: 2 Altitude M: 0.00 Allow Opp. End: No Ent. Air DB/WB °C: 28.10 / 20.20 Tube OD mm: 15.87 Lvg. Air DB/WB °C: 11.10 / 10.90 Coil Duty: Cool-Standard Total / Sensible kW: 0.00 / 0.00 Fin Spacing(mm): 2.82 Max Air PD kPa: 0.00 Rows: 6 Fin Surface: Optimize ABC Fluid Side Fin Height (mm): 990.6 Fluid Type: Water Finned Length (mm): 1727.2 Ent. Fluid : 6.70 Tubing Mat. (mm): 0.889 Copper Lvg. Fluid : 0.00 TurboSpirals: Yes Fluid Flow l/s: 6.08 Fin Mat. (mm): 0.1905 Copper Max FPD kPa: 23.00 Conn Qty/Size (mm): 1 / Optimize Circuiting: Optimize Face Area (SQ M): 3.4219 O U T P U T D A T A Most Economical Specified Coil

Coil 1 Coil 2 Coil 3 Coil 4 Coil 5 Coil 6 Model Number: 5WM0906C Air Velocity: (Sm/s) 1.53 Total Capacity: kW 168.3 Sens. Capacity: kW 108.6 Lvg. Air DB: °C 11.11 Lvg. Air WB: °C 10.67 Standard APD kPa 0.11 Lvg. Fluid: °C 13.30 Fluid Flow: l/s 6.07 Fluid PD: kPa 9.86 Fluid Vel.: ft/s 1.48 Conn Size: IN (1) 2.000 Internal Volume: in^3 3399.4 Weight (Dry): lbm 695.0 Weight (w/Fluid): lbm 823.9 Notes: BCL

Notes:

B) Coil is Outside of the scope of AHRI Standard 410. L) Coil rating valid for Heatcraft coils only.

C) Coil is NOT certified by AHRI.

HEATCRAFT FLUID SELECTION 7.05.32.3

Copyright 2003 Luvata Grenada LLC Confidential and Proprietary. This design is for the exclusive and confidential use of Luvata Grenada LLC and its client. Any duplication made for the purpose of disclosing this design or any part of the design to a competitor of Luvata Grenada LLC is in direct violation of this confidentiality. Any duplication must be approved in writing by Luvata Grenada LLC.

Page 1Specification 237315, Page 32 of 124

Confidential and proprietary. All copyrights in this work are owned by Luvata Grenada LLC. This drawing is for the exclusive and confidential use of Luvata Grenada LLC and its client. This drawing may not be reproduced or distributed or displayed to any third party whatsoever without the prior written consent of Luvata Grenada LLC.

Customer: Date: 6/24/2014 Contact: From:

Telephone: Company:

Fax: Return Tel:

Job: Return Fax:

MODEL NUMBER

ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND

CC-LL-2 (3x3) 2 5WM 09 06 C 39.00 68.00 Right

MATERIALS OF CONSTRUCTION OPTIONS

Fins 0.0075 Copper Coating None Turbospirals Yes Tubes 0.035 Copper Casing Type Flanged Nitrogen Charge No Casing 304L S/S Vent & Drain .50 FPT on Face Moisture Eliminator No Conn. Material Red Brass Mounting Holes No Conn. Type MPT Label Kit No Conn. Size 2.000 Conn. Quantity 1 Conn. Rotation None

Vent/Drain Location

DIMENSIONAL DATA(IN)

A B C E H I J L M N R S1 S2 T W

2.40 2.40 6.00 6.00 40.50 75.75 9.00 71.00 5.25 2.50 1.50 0.75 0.75 1.50 10.00

NOTES:

GENERAL NOTES:

1. All dimensions are in (in)

2. Manually verifying dimensions is highly recommended.

3. One intermediate tube support fabricated from stock of the same material as the casing will be provided.

4. The supply line should be connected to the lower connection on the leaving air side for counterflow operation.

5. Coils will vent and drain through factory-installed vent and drain fittings when mounted level for horizontal flow.

6. Connection location other than standard could affect vent and drain locations. Consult factory.

Specification 237315, Page 33 of 124

Customer: Date: 4/21/2014

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

Construction Air Side Item: HC-LL-2 (3x3) Air Flow (Sl/s) 5230.0 Coils Per Bank: 1 Altitude M: 0.00 Allow Opp. End: No Ent. Air DB °C: 4.40 Tube OD mm: 15.87 Lvg. Air DB °C: 12.80 Coil Duty: Heat-Return Bend Total Capacity kW: 0.00 Fin Spacing(mm): Optimize Max Air PD kPa: 0.00 Rows: Optimize Fin Surface: Optimize ABC Fluid Side Fin Height (mm): 2057.4 Fluid Type: Water Finned Length (mm): 1574.8 Ent. Fluid : 60.00 Tubing Mat. (mm): 0.889 Copper Lvg. Fluid : 0.00 TurboSpirals: Yes Fluid Flow l/s: 0.90 Fin Mat. (mm): 0.1905 Copper Max FPD kPa: 10.00 Conn Qty/Size (mm): 1 / Optimize Circuiting: Optimize Face Area (SQ M): 3.24 O U T P U T D A T A Most Economical Specified Coil

Coil 1 Coil 2 Coil 3 Coil 4 Coil 5 Coil 6 Model Number: 5MQ0601A Air Velocity: (Sm/s) 1.61 Total Capacity: kW 68.92 Lvg. Air DB: °C 15.27 Standard APD kPa 0.00 Lvg. Fluid: °C 41.46 Fluid Flow: l/s 0.90 Fluid PD: kPa 4.15 Fluid Vel.: ft/s 1.23 Conn Size: IN (1) 1.500 Internal Volume: in^3 1430.3 Weight (Dry): lbm 252.8 Weight (w/Fluid): lbm 300.5 Notes: BCKL

Notes:

B) Coil is Outside of the scope of AHRI Standard 410. K) Face and Row spacing on 1.5 inch centers.

C) Coil is NOT certified by AHRI. L) Coil rating valid for Heatcraft coils only.

HEATCRAFT FLUID SELECTION 7.05.32.3

Copyright 2003 Luvata Grenada LLC Confidential and Proprietary. This design is for the exclusive and confidential use of Luvata Grenada LLC and its client. Any duplication made for the purpose of disclosing this design or any part of the design to a competitor of Luvata Grenada LLC is in direct violation of this confidentiality. Any duplication must be approved in writing by Luvata Grenada LLC.

Page 1Specification 237315, Page 34 of 124

Confidential and proprietary. All copyrights in this work are owned by Luvata Grenada LLC. This drawing is for the exclusive and confidential use of Luvata Grenada LLC and its client. This drawing may not be reproduced or distributed or displayed to any third party whatsoever without the prior written consent of Luvata Grenada LLC.

Customer: Date: 4/21/2014 Contact: From:

Telephone: Company:

Fax: Return Tel:

Job: Return Fax:

MODEL NUMBER

ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND

HC-LL-2 (3x3) 1 5MQ 06 01 A 81.00 62.00 Right

MATERIALS OF CONSTRUCTION OPTIONS

Fins 0.0075 Copper Coating None Turbospirals Yes Tubes 0.035 Copper Casing Type Flanged Nitrogen Charge No Casing Galvanized Steel Vent & Drain .50 FPT on Face Moisture Eliminator No Conn. Material Red Brass Mounting Holes No Conn. Type MPT Label Kit No Conn. Size 1.500 Conn. Quantity 1 Conn. Rotation None

Vent/Drain Location

DIMENSIONAL DATA(IN)

A B C E H I J L M N R S1 S2 T W

1.88 1.88 6.00 6.00 82.50 68.50 9.00 65.00 4.50 2.00 1.50 0.75 0.75 1.50 6.00

NOTES:

GENERAL NOTES:

1. All dimensions are in (in)

2. Manually verifying dimensions is highly recommended.

3. One intermediate tube support fabricated from stock of the same material as the casing will be provided.

4. The supply line should be connected to the lower connection on the leaving air side for counterflow operation.

5. Coils will vent and drain through factory-installed vent and drain fittings when mounted level for horizontal flow.

Specification 237315, Page 35 of 124

Date: 1/10/2014 Revision 2

Fan Unit No. Fan Tag Service Total L/S Fan TSP , (Pa) Elevation, M RPM Brake KW Motor Nominal KW AMCA Class Manufacturer & Model Fan Size AHU-LL-3 SF-LL.3 Supply 5300 1873 0 1594 13.34 15.00 III Twin City EPQN 330

Unit No. Fan Tag Motor Manufacturer Motor Model

Number Volts/PH/HZ Motor

Enclosure Motor

Efficiency Isolator Type Feature Codes Wheel Width, % Wheel Diameter, % AHU-LL-3 SF-LL.3 Baldor Custom 400/3/50 TEFC Premium AMSR-2D IS WC EL SG 50 100

Cooling Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators AHU-LL-3 CC-LL-3 5300 1.64 2 6 3.93 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa)

AHU-LL-3 CC-LL-3 C 4.6 11.0 120

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model AHU-LL-3 CC-LL-3 Water Copper, .19mm Copper, .9mm SS N/A N/A 0 HEATCRAFT 5WC1006C 1028.7 x 1574.8

Heating Coil Unit No. Coil Tag Air Flow, (L/S) Face Velocity, (M/S) No. Coils Rows Fins per cm Turbulators Coil Tag HC-LL-3 2120 0.65 1 1 2.36 Yes

Unit No. Coil Tag Fin Design Flow Rate (L/S) Fluid Press Drop (KPa) APD (Pa) Coil Tag HC-LL-3 A 0.95 4.5 0

Unit No. Coil Tag Fluid Fin Material Tube Material Casing Material Intermediate

Drain Coating Altitude (M) Manufacturer Model Coil Tag HC-LL-3 Water Copper, .19mm Copper, .9mm Galvanized N/A N/A 0 HEATCRAFT 5MQ0601A 2057.4 x 1574.8

Dampers Unit No. Qty. Service Damper W (mm) Damper H (mm) L/S Velocity (M/S) Blade Action Torque (NM) Manufacturer Model Feature Codes AHU-LL-3 1 RA 1829 610 5300 4.8 Opposed 9.5 Ruskin CD-60 FF AHU-LL-3 1 OA 1829 610 5300 4.8 Opposed 9.5 Ruskin CD-60 FF

Prefilters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 13/300mm AHU-LL-3 Pleated 2 5300 1.58 9 C-80 SS Type 8 FARR DURAFIL ES Dwyer 605, 500 Pa Upstream

HEPA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access 99.97% AHU-LL-3 HEPA 2 5300 1.58 9 SWING BOLT FARR FARR FA1570A-01-01 Dwyer 605, 500 Pa Upstream

HEGA Filters Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access AHU-LL-3 HEGA 2 5300 1.58 9 FARR FARR FARR CF-F242419-121-TP Dwyer 605, 1000 Pa Side

Post Filters/Depth Unit No. Filter Type UL Class L/S Face Velocity

(M/S) Filter Qty Fastener Type Frame Type Manufacturer Filter Model Gauge Access MERV 11/100mm AHU-LL-3 Pleated 2 5300 1.58 9 FARR FARR FARR OPTIPAC MERV 11 N/A Side

Feature Codes IV Inlet Vanes CF Companion Flange FF Front Flange IS Inlet Screen WC Wheel Cage SG Shaft Grounding OS Outlet Screen DE Duct Equalizer UB Unitary Base DEF Duct Equalizer /w Flange IB Inertia Base SSO Short Silencer (outlet) EL Extended Lube Fittings LSO Long Silencer (outlet) LLX Lube Lines to Case Exterior OG OSHA Drive Guard SP Special Coatings TR Thrust Restraints

Initial Final AHU-LL-3 Airflow 5300 L/s 11230 cfm AHU-LL-3 Airflow 5300 L/s 11230 cfm

Filters Filters 9 9

12" 85% 42 pa 0.17 w.g. 12" 85% 233 pa 0.94 w.g.

Hepa Filter 135 pa 0.54 w.g. Hepa Filter 271 pa 1.09 w.g.

Carbon Filter 342 pa 1.37 w.g. Carbon Filter 342 pa 1.37 w.g.

Post Filter 51 pa 0.21 w.g. Post Filter 0 pa 0.00 w.g.

Heating Coil 12 pa 0.05 w.g. Heating Coil 12 pa 0.05 w.g.

Cooling Coil 119 pa 0.48 w.g. Cooling Coil 119 pa 0.48 w.g.

ESP 896 pa 3.60 w.g. ESP 896 pa 3.60 w.g.

Total pa. 1598 Calculated 6.42 Calculated Total pa. 1873 Calculated 7.53 Calculated 1888 Scheduled 7.59 Scheduled

Model No. and Size, HXW Capacity TOTAL/SENSIBLE, KW 5WC1006C 1028.7 x 1574.8 138.8/102.6

Air Ent Temp DB/WB (C) Air Lvg Temp DB/WB (C) Fluid Ent Temp/Lvng Temp

(C) 26.70/18.50 10.87/10.36 6.70/13.89

Model No. and Size, HXW Capacity TOTAL/SENSIBLE, KW 5MQ0601A 2057.4 x 1574.8 44.6

Air Ent Temp DB/WB (C) Air Lvg Temp DB/WB (C) Fluid Ent Temp/Lvng Temp

4.4 21.8 60.00/48.61

Specification 237315, Page 36 of 124

Specification 237315, Page 37 of 124

Customer: W/A May 27, 2014

Job ID: 16751

Fan Description Fan Performance Motor Data

Tag . . . . . . . . . . . . . . . . . SF-LL.3 l/sec . . . . . . . . . . . . . . . . . . . 5,300 HP (kW) Quantity . . . . . . . . . . . . . . . . . . . . 1 Operating SP (Pa) . . . . . . . . 1,873 RPM Type . . . . . . . . . . . . . . . . . . . EPQN Standard SP (Pa) . . . . . . . . 1,873 Voltage . . . . . . . . . . . . . . . . . 400V Size . . . . . . . . . . . . . . . . . . . . . 330 RPM . . . . . . . . . . . . . . . . . . . . 1594 Phase Width . . . . . . . . . . . . . . . . . . SWSI Tip Speed (m/sec) . . . . . . . . . . . 70 Hz Arrangement . . . . . . . . . . . . . . . . 4 Oper. BHP (kW) . . . . . . . . . 13.34 Enclosure . . . . . TEFC - Premium Class . . . . . . . . . . . . . . . . . . . . . III Standard BHP (kW) . . . . . . . 13.34 Frame . . . . . . . . . . . . . . . . . . 256T Rotation . . . . . . . . . . . . . . . . . W/A Outlet area (m²) . . . . . . . . . . 0.393 Design VFD Op. Freq.(hz) Discharge . . . . . . . . . . . . . . . HOR Outlet Velocity (m/sec) . . . . 13.49 Wheel diameter (m) . . . . . . . . 0.84 Temperature (°C) Drive method . . . 50 Hz direct drive Altitude (m) Percentage width . . . . . . . . . . 50% Density (kg/m³) . . . . . . . . . . 1.201 Percentage diameter . . . . . . 100% Max RPM for Class

Static Efficiency . . . . . . . . . . 74.34 Total Efficiency . . . . . . . . . . 78.68

Modifiers

% width: 50%, Outlet Diffuser

Sound

Sound Power Levels in dB re. 10 -12 Watts:

Octave Bands 1 2 3 4 5 6 7 8 LwA Level at Inlet 87 89 96 98 85 83 78 73 97 Level at Outlet 90 87 97 100 90 86 80 75 99

Estimated sound pressure level in dBA (re: 0.0002 microbar) based on a single* ducted installation:

Distance in m 0.3 0.91 1.52 dBA at Inlet 97 87 83 dBA at Outlet 99 89 85

*To estimate dBA level for ducted inlet and ducted outlet (into and out of the room) type installation, deduct 20 from the LwA value shown.

Using a directivity factor of 1.

Estimated Sound Pressure based on free field, spherical (Q = 1) radiation at the stated distance.

Definitions:

LwA The overall (single value) fan sound power level, 'A' weighted.

dBA The environment for each fan installation influences its measured sound value, therefore dBA levels cannot be guaranteed. Consult AMCA Publication 303 for further details.

A fan's dBA is influenced by nearby reflective surfaces.

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 38 of 124

Customer: W/A May 27, 2014

Job ID: 16751

Accessories Included

EPQN 330, Class III, Arrangement 4 Bare fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Net 305 kg Guard - Protective Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 kg Screen - Inlet, Std Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Special Width Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Wheel - Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Diffusers - Aero Acoustic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 kg 15 kW, 1500 RPM, 400V, 3Ph, 50Hz, TEFC - Premium, 256T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg Mount TCF Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 kg

Total Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341 kg

All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf Specification 237315, Page 39 of 124

Specification 237315, Page 40 of 124

Specification 237315, Page 41 of 124

NP2717L -

CAT NO -

SPEC. CUSTOM -

HP 20 PH 3 -

VOLTS 400 -

AMP 28 -

RPM 1460 -

FRAME 256T HZ 50 I.P. 54 -

SER.F. 1.15 CODE H DES B CL H -

NEMA-NOM-EFF 91.2 % (100%) -

PF 83 USABLE AT 208V -

RATING 40C AMB-CONT CC -

DE BRG 6309 ODE 6208 -

ENCL TEFC SN -

BLANK IE2-92.4(75%)92.0(50%) -

Specification 237315, Page 42 of 124

Customer: Date: 1/8/2014

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

Construction Air Side

Item: CC-LL-3 (3x3) Air Flow (Sl/s) 5300.0 Coils Per Bank: 2 Altitude M: 0.00 Allow Opp. End: No Ent. Air DB/WB °C: 26.70 / 18.50 Tube OD mm: 15.87 Lvg. Air DB/WB °C: 11.10 / 10.90 Coil Duty: Cool-Standard Total / Sensible kW: 0.00 / 0.00 Fin Spacing(mm): 2.54 Max Air PD kPa: 0.00 Rows: Optimize Fin Surface: Optimize ABC Fluid Side

Fin Height (mm): 1028.7 Fluid Type: Water Finned Length (mm): 1574.8 Ent. Fluid : 6.70 Tubing Mat. (mm): 0.889 Copper Lvg. Fluid : 0.00 TurboSpirals: Yes Fluid Flow l/s: 4.60 Fin Mat. (mm): 0.1905 Copper Max FPD kPa: 14.50 Conn Qty/Size (mm): 1 / Optimize Circuiting: Optimize Face Area (SQ M): 3.24 O U T P U T D A T A Most Economical Specified Coil

Coil 1 Coil 2 Coil 3 Coil 4 Coil 5 Coil 6

Model Number: 5WC1006C

Air Velocity: (Sm/s) 1.64

Total Capacity: kW 138.8

Sens. Capacity: kW 102.6

Lvg. Air DB: °C 10.87

Lvg. Air WB: °C 10.36

Standard APD kPa 0.12

Lvg. Fluid: °C 13.89

Fluid Flow: l/s 4.60

Fluid PD: kPa 11.02

Fluid Vel.: ft/s 1.29

Conn Size: IN (1) 1.500

Internal Volume: in^3 3130.0

Weight (Dry): lbm 700.5

Weight (w/Fluid): lbm 819.3

Notes: BCL

Notes:

B) Coil is Outside of the scope of AHRI Standard 410. L) Coil rating valid for Heatcraft coils only.

C) Coil is NOT certified by AHRI.

HEATCRAFT FLUID SELECTION 7.05.32.3

Copyright 2003 Luvata Grenada LLC Confidential and Proprietary. This design is for the exclusive and confidential use of Luvata Grenada LLC and its client. Any duplication made for the purpose of disclosing this design or any part of the design to a competitor of Luvata Grenada LLC is in direct violation of this confidentiality. Any duplication must be approved in writing by Luvata Grenada LLC.

Page 21Specification 237315, Page 43 of 124

Customer: Date: 1/8/2014

Telephone: Company:

Cell: Return Tel:

Fax: Return Fax:

Job:

Quote #:

MODEL NUMBER

ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND

CC-LL-3 (3x3) 2 5WC 10 06 C 40.50 62.00 Left

MATERIALS OF CONSTRUCTION OPTIONS

Fins 0.0075 Copper Coating None TurboSpirals Yes Tubes 0.035 Copper Casing Type Flanged Moisture Eliminator No Casing 304L S/S Vent & Drain .50 FPT on Face Mounting Holes No Conn. Material Red Brass Label Kit No Conn.