Heat_Echangers_for_HVAC_Schedule.pdf

PDF 46 KB Posted

Attached to
HVAC Maintenance services for US Embassy London UK
Solicitation number
19GE5018R0023
Issued by

About this file

Heat Exchangers for HVAC Schedule

View the file

Other files

File Type Posted
Exhibit_A.pdf PDF
Exhibit_B.pdf PDF
Exhibit_D.pdf PDF
Exhibit_C.pdf PDF
O&M_Hydronic_Pumps_-_5.pdf PDF
O&M_Hydronic_Pumps_-_2.pdf PDF
O&M_Hydronic_Pumps_-_6.pdf PDF
O&M_Hydronic_Pumps_-_0.1.pdf PDF
Centrifugal_Water_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_0.pdf PDF
Computer_Room_AC_O&M.PDF PDF
DHR_Modular_Chiller_O&M_-_1_of_2.pdf PDF
Soliciation_19GE5018R0023.pdf PDF
O&M_Hydronic_Pumps_-_4.2.pdf PDF
HX_1&2_O&M.PDF PDF
Cooling_Towers_O&M.PDF PDF
HVAC_Power_Ventilators_O&M.PDF PDF
HVAC_Ventilators_Schedule.pdf PDF
Hydronic_Pumps_Schedule.pdf PDF
Air_Terminal_Units_(VAV)_-_O&M.PDF PDF
O&M_Hydronic_Pumps_-_3.pdf PDF
DHR_Modular_Chiller_O&M_-_2_of_2.pdf PDF
O&M_Hydronic_Pumps_-_1.pdf PDF
Air_Cooled_Modular_Chiller_O&M.PDF PDF
O&M_Hydronic_Pumps_-_4.1.pdf PDF
Original_Signed_letter_19GE5018R0023.pdf PDF
HX_3&4_O&M.PDF PDF
Central_Station_Air_Handling_Units_O&M.PDF PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HEAT EXCHANGER SCHEDULE

ITEM

HX-1, -2

HX-3

HX-4

NOTES:

1.

2.

3.

4.

SERVICE

GROUND LOOP

DISTRICT TO BUILDING

DISTRICT TO DHW

1380 KPA OPERATING PRESSURE.

WORKING FLUID IS WATER U.O.N.

EXCEPT WHERE SKID-MOUNTED, PROVIDE 100MM HOUSEKEEPING PAD FOR EACH HEAT EXCHANGER.

PROVIDE FRAME CAPACITY FOR MIN. 10% ADDITIONAL PLATES.

LOCATION

LOWER LEVEL, NE MER

LOWER LEVEL, SW MER

LOWER LEVEL, SW MER

MANUFACTURER

BELL & GOSSETT

BELL & GOSSETT

BELL & GOSSETT

MODEL

P86

P47-DW

P14-DW

HEAT EXTRACTION MODE

COLD SIDE (BLDG)

FLOW

RATE

(L/S) 60.2 15.9 8.3

FLUID TEMP

ENT

(°C) 4.4 54.4 71.1

LVG

(°C) 7.8 82.2 82.2

MAX PRESS

DROP

(KPA)

HOT SIDE (GRND, CHP)

FLOW

RATE

(L/S) 51.4 32.2 6.7

FLUID TEMP

ENT

(°C) 9.0 96.1 96.1

LVG

(°C) 5.0 82.2 82.2

MAX PRESS

DROP

(KPA)

HEAT REJECTION MODE

COLD SIDE (GRND)

FLOW

RATE

(L/S) 61.2

FLUID TEMP

ENT

(°C) 16.0

LVG

(°C) 20.0

MAX PRESS

DROP

(KPA)

HOT SIDE (BLDG)

FLOW

RATE

(L/S) 47.9

FLUID TEMP

ENT

(°C) 21.7

LVG

(°C) 16.7

MAX PRESS

DROP

(KPA)

DRY

WT

(KG)

NOTES

DUTY / STANDBY PAIR, GROUND SIDE OF HXER IS 15% PROPLYENE GLYCOL

DOUBLE-WALL

DOUBLE-WALL

UNITED STATES DEPARTMENT OF STATE

NEW LONDON EMBASSY COMPOUND

(NLE)

LONDON, UNITED KINGDOM

DESIGN ISSUED FOR CONSTRUCTION