1614696dwg18of22_MECH-BUILD.pdf
PDF 5 MB Posted
- Attached to
- P-095 Pier 3 Recap Naval Station Norfolk, VA
- Solicitation number
- N4008521R0219
About this file
This document package includes mechanical drawings and specifications for the replacement of Pier 3 at Naval Station Norfolk in Virginia. The project involves upgrading the mechanical systems at the Utility Services Building including new HVAC equipment, ductwork, piping, controls and associated components. Detailed drawings show proposed equipment layouts, schedules list specifications for new fans, pumps, air handlers, louvers, unit heaters and other devices. The specifications include notes, details, diagrams and schedules providing requirements for installing and integrating the new mechanical systems. The federal solicitation seeks bids from contractors to complete the Pier 3 recapitalization project in accordance with the specifications in this mechanical design package.
View the file
Other files
Show 40 more
Latest 50 of 79 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS IN THIS SET.
SHEET SPECIFIC NOTES ARE INDICATED ON EACH SHEET UNDER GENERAL
SHEET NOTES.
2. PATCH ALL HOLES FROM REMOVAL OF PIPING, DUCTWORK, OR EQUIPMENT TO
MATCH ADJACENT CONSTRUCTION.
3. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON
THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
4. INSTALL ALL MECHANICAL EQUIPMENT AN APPURTENANCES IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
5. PROVIDE VIBRATION ISOLATORS AS INDICATED ON THE DRAWINGS FOR
MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO
BUILDING STRUCTURE.
6. PROVIDE ACCESS PANELS IN WALLS AND CEILINGS, WHERE REQUIRED, TO
SERVE FIRE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED
MECHANICAL EQUIPMENT THAT REQUIRES ROUTINE MAINTENANCE. ACCESS
PANELS MUST BE LARGE ENOUGH TO ALLOW PROPER CLEARANCE FOR
ACCESS DOORS. SEE ARCHITECTURAL PLANS FOR LOCATIONS. COORDINATE
PANELS WITH FINAL LOCATION OF MECHANICAL EQUIPMENT, DUCTWORK,
PIPING, VALVES, ETC.
7. PROVIDE FIRESTOP FOR ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK,
PIPING, CONDUIT, ETC.
8. EXISTING DUCT AND PIPING SIZES INDICATED ARE APPROXIMATE. FIELD VERIFY
ALL DIMENSIONS.
9. LOCATE ALL NEW HORIZONTAL DUCTWORK ABOVE THE SUSPENDED CEILINGS
UNLESS OTHERWISE INDICATED.
10. ALL 90 DEGREE RECTANGULAR MITERED DUCT ELBOWS IN THE SUPPLY,
EXHAUST, OUTSIDE, AND RETURN DUCT MUST HAVE TURNING VANES.
11. PROVIDE PIPE SLEEVES FOR ALL PIPING PENETRATIONS THRU WALLS AND
FLOORS. EACH PIPE MUST BE SEPARATELY SLEEVED. PROVIDE CONTINUOUS
SEALANT JOINT AROUND PIPE SLEEVE, BOTH SIDES OF WALL, WATERTIGHT.
12. PROVIDE P-TRAPS IN CONDENSATE DRAIN PIPING AT EACH COOLING COIL
UNLESS THE COOLING COIL IS EQUIPPED WITH AN INTERNAL TRAP.
13. AFTER THE PIPING IS INSULATED, PROVIDE FACTORY-FABRICATED PIPE
LABELS, WITH DIRECTION OF FLOW ARROWS, ON THE FOLLOWING PIPING, AT
10 FOOT ON CENTER ON THE PIPING MAINS AND 5 FOOT ON CENTER ON THE
BRANCH RUNOUTS FROM THE MAINS.
14. DUCT RUNOUT SIZE TO DIFFUSER, REGISTER, OR GRILLE MUST BE SAME AS
NECK SIZE.
15. MOUNT THERMOSTATS, HUMIDISTATS, AND ESS 48 INCHES ABOVE FINISHED
FLOOR UNLESS OTHERWISE INDICATED. REFER TO ELECTRICAL DRAWINGS
FOR LOCATION OF LIGHT SWITCHES.
16. SLOPE CONDENSATE PIPING 1/8 INCH PER FOOT DOWNWARD IN THE DIRECTION
OF FLOW. PROVIDE CLEANOUTS AT EACH CHANGE IN DIRECTION GREATER
THAN 45 DEGREES OR ONCE EVERY 45 FEET OF LINEAR PIPE LENGTH.
COMBINATION WYE AND 1/8 BENDS MUST BE USED IN LIEU OF TEES.
17. INSTALL LOUVER PLENUMS WITH MINIMUM 1/4 INCH PER FOOT SLOPE
DOWNWARDS TOWARDS EXTERIOR FOR DRAINAGE.
18. SEAL ALL UNUSED PORTIONS OF LOUVERS WITH INSULATED METAL BLANK-OFF
PANELS.
19. MECHANICAL DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL
OFFSETS, FITTINGS, AND CONNECTIONS NECESSARY FOR COMPLETE
INSTALLATION. PROVIDE ANY AND ALL ADDITIONAL OFFSETS, FITTINGS, AND
CONNECTIONS REQUIRED FOR COMPLETE AND OPERABLE SYSTEM. OFFSETS
MUST BE THE MINIMUM POSSIBLE TO MAKE THE CONNECTIONS.
20. COORDINATE INSTALLATION OF MECHANICAL SYSTEMS WITH ALL OTHER
TRADES PRIOR TO BEGINNING INSTALLATION.
21. INSTALLATION MUST ALLOW FOR SYSTEM MAINTENANCE TO OCCUR.
PROVIDED MANUFACTURER'S RECOMMENDED CLEARANCES.
22. ALL PIPE HANGERS MUST BE SECURED TO THE STRUCTURE OR CONTRACTOR
PROVIDED SUPPORTS BETWEEN THE STRUCTURE. PIPE HANGERS MUST NOT
BE HUNG FROM THE ROOF DECK.
GENERAL MECHANICAL NOTES
° DEGREES
Ø DIAMETER
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AS AIR SEPARATOR
AUX AUXILIARY
BD BALANCING DAMPER
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
CCC CLOSED CIRCUIT COOLER
CD CEILING DIFFUSER
CV LOSS COEFFICIENT
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
DB DRY BULB
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DN DOWN
DSS DUCTLESS SPLIT SYSTEM
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EP EXHAUST PIPE (GENERATOR)
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FC FAN COIL
FLA FULL LOAD AMPERAGE
FT FEET
GI GRAVITY INTAKE
GPM GALLONS PER MINUTE
GR GRAVITY RELIEF
HP HEAT PUMP, HORSEPOWER
HPAC HIGH PRESSURE AIR COMPRESSOR
HR HOUR
HZ HERTZ
IAW IN ACCORDANCE WITH
IN WC INCHES WATER COLUMN
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
L LENGTH
LS LINEAR SLOT
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSANDS OF BTU/HOUR
MCA MINIMUM CIRCUIT AMPACITY
MD MOTORIZED DAMPER
MIN MINIMUM
MINS MINUTES
MOCP MAXIMUM OVERCURRENT PROTECTION
MPAC MEDIUM PRESSURE AIR COMPRESSOR
NC NORMALLY CLOSED, NOISE CRITERIA
NO NORMALLY OPEN
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
PH PHASE
PSI POUNDS PER SQUARE INCH
RA RETURN AIR
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RR RETURN REGISTER
RS REFRIGERANT SUCTIONSA SUPPLY AIR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SG SUPPLY GRILLE
SP STATIC PRESSURE
SQ SQUARE
SS SPLIT SYSTEM
TYP TYPICAL
UH UNIT HEATER
USB UTILITY SERVICES BUILDING
VLV VALVE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WIDTH
WB WET BULB
SEE SHEET AM-701 FOR ADDITIONAL CONTROL ABBREVIATIONS.
MECHANICAL ABBREVIATIONSMECHANICAL LEGEND
T THERMOSTAT
ROUND DUCT DIMENSION
RECTANGULAR DUCT DIMENSIONS (INCHES)12x10
12"Ø
SUPPLY DUCT DOWN/UP
RETURN DUCT DOWN/UP
BUTTERFLY VALVE
PRESSURE REDUCING VALVE
DRAIN VALVE WITH HOSE CONNECTION
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
RELIEF VALVE
MANUAL AIR VENT
AUTOMATIC AIR VENT
WYE STRAINER
CLEAN OUT
UNION
PRESSURE GAUGE WITH SHUTOFF COCK
THERMOMETER
PIPE CAP
FLANGE
FLEXIBLE PIPE CONNECTOR
C.O.
EXHAUST DUCT DOWN/UP
M
M
MV
MANUAL CALIBRATED BALANCING VALVE
MOTORIZED DAMPER
MD
S TEMPERATURE SENSOR
BALL VALVE
SUPPLY CEILING DIFFUSER
RETURN CEILING DIFFUSER
EXHAUST CEILING DIFFUSER
SUPPLY CEILING DIFFUSER
SUPPLY GRILLE
RETURN/EXHAUST GRILLE
RADIUS ELBOW
MITERED ELBOW WITH TURNING VANES
PIPING TO BE REMOVED
MECHANICAL PIPING LEGEND
CONDENSER WATER RETURN PIPING
COMPRESSED AIR PIPING
CONDENSER WATER SUPPLY PIPING
CONDENSATE DRAIN PIPING
DOMESTIC COLD WATER PIPING
HEATING HOT WATER SUPPLY PIPING
HEATING HOT WATER RETURN PIPING
REFRIGERANT LIQUID PIPING
REFRIGERANT SUCTION PIPING
(NAME)
CA
CWR
CWS
CD
DCW
HHWR
HHWS
RL
RS
DOMESTIC HOT WATER PIPINGDHW
MEDIUM PRESSURE COMPRESSED AIR PIPINGMPCA
HIGH PRESSURE COMPRESSED AIR PIPINGHPCA
ROOM TAG
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL TAG
ROOM NAME
ROOM NUMBER
DETAIL NUMBER
SCALE
SHEET
REFERENCED
FROM
SECTION TAG
SECTION NUMBER
SHEET WHERE DRAWN
GENERAL PROJECT SYMBOLS
NEW WORK
KEYNOTE TAG
KEYNOTE NUMBER
DEMO
KEYNOTE TAG
KEYNOTE NUMBER
? PHOTOGRAPH TAG
PHOTOGRAPH NUMBER
SHEET WHERE SHOWN
PLAN
NORTH
SCALE
TRUE NORTH
SHEET
REFERENCED
FROM
AIR DISTRIBUTION DEVICE
IDENTIFICATION
EQUIPMENT
IDENTIFICATION
VAV - XX
EQUIPMENT
TYPE
EQUIPMENT
NUMBER
175 CFM
CD-# #x#
NECK
SIZE
(IN)
MARK
AIR FLOW
36.93 N
LONGITUDE:
ELEVATION:
LATITUDE:
SUMMER DESIGN WET BULB (0.4%):
SUMMER DESIGN DRY BULB (0.4%):
WINTER DESIGN DRY BULB (99.6%):
STANDARD OUTDOOR DESIGN CONDITIONS:
21°F
78°F 94°F
76.28 W
16 FT.
HVAC DESIGN CRITERIA
LOCATION: NAVAL STATION NORFOLK, VA
STATION ID# ICAO_KNGU
SUMMER
DESIGN DRY
BULB:
WINTER
DESIGN DRY
BULB:
STANDARD INDOOR DESIGN CONDITIONS:
78°F 50% RH 68°F NC*
SUMMER
DESIGN
HUMIDITY:
GUARD BOOTH
ROOM TYPE:
*UC - UNCONTROLLED
*NC - HUMIDITY NOT DIRECTLY CONTROLLED
WINTER
DESIGN
HUMIDITY:
CLIMATE ZONE 3A
CONDENSING UNIT (0.4% DB + 5°F): 99°F
1% HR/MCWB WET BULB
1% HR/MCWB DRY BULB
77.8°F 82.9°F
57.9°F
SUMMER
DESIGN
DEW POINT:
78°F 50% RH 68°F NC*GATEHOUSE 57.9°F
78°F 50% RH 68°F NC*ROOM USB8 TELECOM ROOM
& ROOM USB9 FIRE ALARM
CLOSET
57.9°F
UTILITY SERVICE BUILDING
UC UC 55°F NC*ALL OTHER UNOCCUPIED SPACES UC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:2
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM001
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
LE
G
E N
D , A
B R
E V
IA
T
IO
N
S , A
N D
N O
TE
S
CMG
12829422
DKH DKH
1614696
UP
1 2 3 4
A
B
C
D
AM101
A1
AM102
A1
M A
T C
H L
IN
E
S E
E T
H
IS
S H
E E
T F
O R
C O
N T
IN
U
A T
IO
N
PURE WATER
ROOM
USB3
FIRE PUMP
USB1
FRESH WATER
PUMP ROOM
USB2
EQUIPMENT
YARD
USB0
MEDIUM
PRESSURE AIR
ROOM
USB4
MECHANICAL
PIPE PIT
4 5 76
A
B
C
D
AM103
A1
AM104
A1
M A
T C
H L
IN
E
S E
E T
H
IS
S H
E E
T F
O R
C O
N T
IN
U
A T
IO
N
HIGH PRESSURE
AIR ROOM
USB5
MAIN
ELECTRICAL
ROOM
USB6
TELECOM ROOM
USB8
GENERATOR
ROOM
USB7
FIRE ALARM
CLOSET
USB9
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM100
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L O
V E
R A
LL
F
LO
O
R P
LA
N
CMG
12829423
BRF BRF
1614696
4' 8' 16'0'
PLAN
NORTH
1/8" = 1'-0" C1
MECHANICAL PLAN OVERALL - WEST
1/8" = 1'-0" A1
MECHANICAL PLAN OVERALL - EAST
4' 8' 16'0'
PLAN
NORTH
KEY PLAN
PLAN
NORTH
FC-1
FC-2
1 2 3
A
B
C
D
P-3
P-4
4"ø CWS
4"ø CWR
C1
AM301
L-10 40x32
2160 CFM
L-2 32x24
2160 CFM
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
PURE WATER
ROOM
USB3
FIRE PUMP
USB1
FRESH WATER
PUMP ROOM
USB2
EQUIPMENT
YARD
USB0
L-1 24x32
1100 CFM
EF-2
EF-1
32x24 EA
24x32 EA
20x20 EA
20x20 EA
PROVIDE 28" X 28"
EA OPENING
14x14 SA
16x16 RA
PROVIDE 22" X 22"
SA OPENINGS
PROVIDE 24" X 24"
RA OPENING
10x10 RA
RG-1 10x10
210 CFM
10x10 RA
12x12 RA
RG-1 10x10
210 CFM
14x8 SA
10x14 EA
14x14 EAPROVIDE 14" X 14"
EA OPENING -
550 CFM
SG-1 12x6
210 CFM
12x6 SA
12x6 SA
SG-1 12x6
210 CFM
16x14 RA
3/4"ø HHWR
3/4"ø HHWS 3/4"ø HHWR
3/4"ø HHWS
CCC-1 CCC-2
27 27
T
EF-1
T EF-2
VLV-12
VLV-13
14x14 EA
10x10 EA
EG-1 10x10
550 CFM 65
(TYP)
BDD
40x32 OA
50 (TYP)
L-9 24x16
550 CFM
24x16 OA
L-8 24x16
550 CFM
24x16 OA
T
T
T
FC-1
FC-1
SHUT OFF VALVE
(TYP)
56 (TYP)
63 (TYP)
(TYP)
(TYP.)
BDD
T
FC-2
4"ø CWS
4"ø CWR
4"ø CWS 4"ø CWR
VLV-1 VLV-2
VLV-3
NITROGEN STORAGE TANKS
SEE SHEET AP111
(TYP.)
(TYP)
(TYP)
MD-1 MD-2
MD-3
(TYP.)
EF-1
(TYP.)
(TYP.)
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
WORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:0
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM101
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L E
N
LA
R G
E D
F
LO
O R
P
LA
N
S H
E E
T
O F
CMG
12829424
BRF BRF
1614696
1/4" = 1'-0" A1
MECHANICAL FLOOR PLAN - HVAC - AREA A
26 SEE FAN COIL UNIT PIPING DETAIL C4/AM501.
27 SEE USB CONDENSER WATER PIPING DIAGRAM SHEET AM610.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER
OPENING.
45 DDC CONTROL PANEL 120 VOLTS 1 PHASE.
50 SEE PIPE PENETRATION DETAIL C3/AP504.
51 SEE DRAIN VALVE CONNECTION DETAIL C4/AM502.
56 SEE RECTANGULAR BRANCH DUCT TAKE-OFF DETAIL A3/AM503.
59 SEE LOW VELOCITY DUCT LAYOUT C3/AM503.
60 SEE HYDROSTATIC SEAL DETAIL A1/AM504.
61 SEE DIFFUSER, GRILLE & REGISTER CONNECTION DETAIL A4/AM504.
63 SEE RECTANGULAR FLEXIBLE CONNECTION DETAIL A2/AM505.
65 SEE CABINET OR INLINE EXHAUST FAN DETAIL C1/AM505.
75 SEE PIPE SUPPORT DETAILS A1/AM502.
76 LOCATE MECHANICAL PIPING AS INDICATED. COORDINATE WITH OTHER
TRADES WITH GRAVITY DRAINS AND DUCTWORK TAKING PRECEDENCE.
MINIMUM PIPE HEIGHT MUST BE 8'-0" AFF. SUSPEND ALL PIPING FROM
STRUCTURAL STEEL. PIPING MUST NOT BE SUPPORTED FROM THE
ROOF DECK.
2' 4' 8'0'
PLAN
NORTH
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTESWORK NOTES
FC-3
3 4
A
B
C
D
P-1 P-2
ET-1
P-5
A4
AM301
4"ø CWS
4"ø CWS
3"ø CWR
4"ø CWR
A1
AM301
L-3 48x48
6080 CFM
L-11B 72x48
4675 CFM
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
MPAC-1 MPAC-2 MPAC-3 MPAC-4
3"ø CWR
2 1/2"ø CWR 2 1/2"ø CWR 2 1/2"ø CWR 2 1/2"ø CWR
EF-3
48x48 EA
28x28 EA
28x28 EA
PROVIDE 36" X 36"
EA OPENING
14x14 SA
PROVIDE 14" X14"
SA OPENINGS
PROVIDE 24" X 24"
RA OPENING
3/4"ø HHWR
25 25 25 25
GFS-1
2 1/2"ø CWS
2 1/2"ø CWS
2 1/2"ø CWS 2 1/2"ø CWS
VLV-4 VLV-5 VLV-6
VLV-7
AS-1
T
EF-3
PIPE ANCHOR
(TYP)
MEDIUM
PRESSURE AIR
ROOM
USB4
V-14
30x30 EA
UP TO GR-1
20x12 EA20x12 EA
30x30 EA
UP TO GR-2
30x30 EA
UP TO GR-3
30x30 EA
UP TO GR-4
20x12 EA BELOW
L-11A 72x48
4675 CFM
L-11C 72x48
4675 CFM
38 72x48 OA
(TYP)
50 (TYP)
3/4" Ø DCW SEE
PLUMBING FLOOR
PLAN - AREA B
SHEET AP102 FOR
CONTINUATION
72x48 OA
72x48 OA
16x16 RA
(TYP.)
(TYP.)
BDD
(TYP.)
T
FC-3
(TYP)
MD-4 MD-5
MD-6
MD-12
MD-13
MD-14
MD-15
MD-16
MD-17 MD-18
MD-19
3/4"ø HHWS
MECHANICAL
PIPE PIT
UH-3
T
UH-3
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:0
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM102
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L E
N
LA
R G
E D
F
LO
O R
P
LA
N
S H
E E
T
O F
CMG
12829425
BRF BRF
1614696
1/4" = 1'-0" A1
MECHANICAL FLOOR PLAN - HVAC - AREA B
PLAN
NORTH
2' 4' 8'0'
PLAN
NORTH
64 SEE TYPICAL MAKEUP WATER CONNECTION DETAIL A4/AM505.
65 SEE CABINET OR INLINE EXHAUST FAN DETAIL C1/AM505.
66 SEE AIR SEPARATOR DETAIL C2/AM505.
76 LOCATE MECHANICAL PIPING AS INDICATED. COORDINATE WITH OTHER
TRADES WITH GRAVITY DRAINS AND DUCTWORK TAKING PRECEDENCE.
MINIMUM PIPE HEIGHT MUST BE 8'-0" AFF. SUSPEND ALL PIPING FROM
STRUCTURAL STEEL. PIPING MUST NOT BE SUPPORTED FROM THE ROOF
DECK.
77 PROVIDE INSULATED SUBBASE FOR TEMPERATURE SENSOR.
25 SEE AIR COMPRESSOR CONDENSER WATER PIPING DETAIL A4/AM501.
26 SEE FAN COIL UNIT PIPING DETAIL C4/AM501.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER OPENING.
45 DDC CONTROL PANEL 120 VOLTS 1 PHASE.
50 SEE PIPE PENETRATION DETAIL C3/AP504.
52 SEE MANUAL AIR VENT DETAIL A5/AM502.
53 SEE AUTOMATIC AIR VENT DETAIL C1/AM502.
54 SEE ELBOW PIPE SUPPORT DETAIL C2/AM502.
59 SEE LOW VELOCITY DUCT LAYOUT C3/AM503.
62 SEE GLYCOL FEEDER DETAIL A1/AM505.
FC-4
4 5
A
B
C
D
P-6
4"ø CWS 2 1/2"ø CWS
3"ø CWR
4"ø CWR
L-12 72x48
5500 CFM
L-4 48x48
5500 CFM
L-5 24x24
370 CFM
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
HPAC-1
HPAC-2
HPAC-3
HIGH PRESSURE
AIR ROOM
USB5
C1
AM302
EF-5
16x16 EA
EF-4
48x48 EA
24x24 EA
24x24 EA
24x24 EA
14x14 EA
14x14 EA
2 1/2"ø CWS
4"ø CWR4"ø CWR
3/4"ø HHWS
14x14 SA
PROVIDE 32 X 32
EA OPENING
PROVIDE 14" X 14"
SA OPENING
x1
S
A
16x16 RA
PROVIDE 24" X 24"
RA OPENING
3/4"ø HHWR
2 1/2"ø CWR
2 1/2"ø CWR
2 1/2"ø CWR
2 1/2"ø CWS 2 1/2"ø CWS
VLV-11
VLV-8
VLV-9
VLV-10
TEF-4
2' X 4' X 2' EXPANSION
LOOP CENTERED ON BUILDING
EXPANSION JOINT
PIPE ANCHOR
(TYP.)
V-15
72x48 OA
SHUT OFF VALVE NORMALLY
OPEN (TYP)
59 (TYP)
BDD
BDD
T
FC-4
26 (TYP.)
MD-7
UH-4
T
UH-4
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
2' X 4' X 2' EXPANSION
LOOP CENTERED ON BUILDING
EXPANSION JOINT
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTESWORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:1
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM103
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L E
N
LA
R G
E D
F
LO
O R
P
LA
N
S H
E E
T
O F
CMG
12829426
BRF BRF
1614696
1/4" = 1'-0" A1
MECHANICAL FLOOR PLAN - HVAC - AREA C
25 SEE AIR COMPRESSOR CONDENSER WATER PIPING DETAIL A4/AM501.
26 SEE FAN COIL UNIT PIPING DETAIL C4/AM501.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER
OPENING.
45 DDC CONTROL PANEL 120 VOLTS 1 PHASE.
59 SEE LOW VELOCITY DUCT LAYOUT C3/AM503.
65 SEE CABINET OR INLINE EXHAUST FAN DETAIL C1/AM505.
76 LOCATE MECHANICAL PIPING AS INDICATED. COORDINATE WITH OTHER
TRADES WITH GRAVITY DRAINS AND DUCTWORK TAKING PRECEDENCE.
MINIMUM PIPE HEIGHT MUST BE 8'-0" AFF. SUSPEND ALL PIPING FROM
STRUCTURAL STEEL. PIPING MUST NOT BE SUPPORTED FROM THE ROOF
DECK.
2' 4' 8'0'
PLAN
NORTH
DSS-1
UH-1
UH-2
CU-1
5 76
A
B
C
D
A4
AM302
96" x 96"
DUCT CONNECTION
TO LOUVER (TYP.)
54" X 46"
DUCT CONNECTION TO
GENERATOR RADIATOR -
VERIFY WITH APPROVED
EQUIPMENT MANUFACTURER
(TYP.)
GENERATOR
GENERATOR
8" EP
8" PIPE DOWN TO
FLEXIBLE EXHAUST
CONNECTION ON
GENERATOR
8" EP
8" PIPE DOWN TO
FLEXIBLE EXHAUST
CONNECTION ON
GENERATOR
54x54 OA
(TYP. 2)
L-6 48x48
5000 CFM
L-7 48x48
5000 CFM
EF-6
48x48 EA
SG-2 48x48
7500 CFM
(TYP. 8)
M A
T C
H L
IN
E
S E
E A
M
F
O R
C O
N T
MAIN
ELECTRICAL
ROOM
USB6
TELECOM ROOM
USB8
GENERATOR
ROOM
USB7
A1
AM302
EG-2 16x16
1480 CFM
FOT-1
32x32 EA x4
E
A
RECTANGULAR TO
ROUND TRANSITION
(TYP INLET/OUTLET)
x5
O
A x5
O A
FUEL OIL TANK - SEE
PLUMBING FLOOR PLAN -
AREA D SHEET AP104
MOTORIZED
DAMPER
DISCHARGE CONDENSATE
DRAIN ON SPLASH BLOCK 3/4" Ø CD
T
EF-5
T
S
DSS-1
T
EF-6
T UH-2
x5
O
A
L-13 18x18
370 CFM
L-14 96x96
30000 CFM
L-15 96x96
30000 CFM
T UH-1
(TYP OF 4)
18x18 OA
M-1
M-2
EG-3 20x20
2500 CFM
x3
E
A x4
E
A ø
E A ø
E A
PROVIDE MIN. OF 2'-0"
STRAIGHT DUCT ON INLET &
OUTLET OF FAN FULL SIZE OF
FAN CONNECTION
BDDBDD
MD-8
MD-10
MD-9
MD11
DSS-2
T
S
DSS-2
CU-2
3/4"ø RS 1/2"ø RL
1/2"ø RL
28 2930
3/4"ø CD
FIRE ALARM
CLOSET
USB9
5/8" Ø RS
32x32 EA32x32 EA
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
WORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:2
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM104
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L E
N
LA
R G
E D
F
LO
O R
P
LA
N
S H
E E
T
O F
CMG
12829427
BRF BRF
1614696
1/4" = 1'-0" A1
MECHANICAL FLOOR PLAN - HVAC - AREA D
11 ROUTE DUCT DOWN TO 1'0" AFF. PROVIDE TWO 48"x48" EGGCRATE TYPE
GRILLES FOR EACH DROP. COORDINATE DROP LOCATIONS WITH
ELECTRICAL PANELS. REFER TO A1/AM302 FOR SECTION CUT.
28 PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCE FOR AIRFLOW
AND MAINTENANCE.
29 PIPE BOLLARDS TO PROTECT CONDENSING UNIT. SEE CIVIL DRAWINGS
SHEET CS502 FOR DETAILS.
30 PROVIDE CONDENSING UNIT WITH CONCRETE PAD AND LEGS TO ELEVATE
UNIT. BOTTOM OF UNIT MUST BE AT THE ELEVATION OF THE USB FLOOR
(10'-3").
31 PROVIDE HINGED, GRAVITY-OPERATED, SELF-CLOSING RAIN COVER.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER
OPENING.
47 54x54 OA DUCT TO GRAVITY INTAKE VENTILATOR.
63 SEE RECTANGULAR FLEXIBLE CONNECTION DETAIL A2/AM505.
76 LOCATE MECHANICAL PIPING AS INDICATED. COORDINATE WITH OTHER
TRADES WITH GRAVITY DRAINS AND DUCTWORK TAKING PRECEDENCE.
MINIMUM PIPE HEIGHT MUST BE 8'-0" AFF. SUSPEND ALL PIPING FROM
STRUCTURAL STEEL. PIPING MUST NOT BE SUPPORTED FROM THE ROOF
DECK.
78 EQUIPMENT MANUFACTURER TO SIZE ALL REFRIGERANT PIPE SIZES PER
THEIR RECOMMENDATIONS FOR OPTIMAL PREFORMANCE.
PLAN
NORTH
2' 4' 8'0'
1 2 3 4
A
B
C
D
GR-1
GR-2 GR-3 GR-4
CCC-1 CCC-2
ROOF ACCESS
LADDER
71 71 71 7168 68 68 68
4 5 76
A
B
C
D
GI-3
GI-2
GI-1
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
WORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:2
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM105
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L O
V E
R A
LL
R
O O
F P
LA
N
CMG
12829428
BRF BRF
1614696
1/8" = 1'-0" C1
MECHANICAL ROOF PLAN OVERALL - WEST
1/8" = 1'-0" A1
MECHANICAL ROOF PLAN OVERALL - EAST
4' 8' 16'0'
4' 8' 16'0'
PLAN
NORTH
PLAN
NORTH
47 54x54 OA DUCT TO GRAVITY INTAKE VENTILATOR.
68 30x30 EA DUCT TO GRAVITY RELIEF VENTILATOR.
71 SEE CURB DETAIL - METAL ROOF A1/A-301.
RR-1 6x6
50 CFM
CD-1 6x6
50 CFM
EG-1 8x8
50 CFM
6x6 RA
3/4"ø CD
CO
(TYP.)
RR-2 8x8
250 CFM
RR-1 6x6
50 CFM
DSS-3
1/2"ø RS 1/4"ø RL
(TYP. 2)
8x8 SA
UP TO EF-7
ON ROOF
T
EQUIPMENT ROOM
GH04
STO
GH03
SENTRY
GH01
TOILET
GH02
C1
AM303
A1
AM303
CB
3/4"ø CD
6x6 RA
6x6 SA
SS-1
8x8 OA UP
TO GV-1
8x8 EA
(TYP.) UC
10x10 SA
SS-1
8x8 OA
20x16 RA
CD-1 6x6
50 CFM
LS-1 8ø
200 CFM
12x16 SA
ROOF ACCESS
LADDER
MD-21
T
DSS-3
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
GENERAL NOTES
WORK NOTES
HP-1
EF-7GI-1
CU-3
1/2"ø RS
1/4"ø RL
C1
AM303
A1
AM303
CB
DN TO
DSS-3
69 70
ROOF ACCESS
LADDER
72 70
UTILITY
SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GREGORY R. MOSS
DIRECTOR OF WARFARE REQIUREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:2 :5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-G H
B D d k h e n d e rs o n .r v t
AM106
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
G A
T E
H O
U S
E
H V
A C
F
LO
O R
P
LA
N S
CMG
12829429
CPM CPM
1614696
1/2" = 1'-0" C1
GATEHOUSE FLOOR PLAN - HVAC
1 REFRIGERENT LIQUID FROM ROOFTOP HEAT PUMP. REFER TO
MANUFACTURER FOR REFRIGERANT PIPING SIZE. SEE THIS SHEET FOR
CONTINUATION.
2 REFRIGERENT SUCTION TO ROOFTOP HEAT PUMP. REFER TO
MANUFACTURER FOR REFRIGERANT PIPING SIZE. SEE THIS SHEET FOR
CONTINUATION.
3 EXHAUST DUCT TO ROOF MOUNTED EXHAUST FAN. SEE THIS SHEET FOR
CONTINUATION.
7 PROVIDE SECONDARY DRAIN AND PAN.
12 PROVIDE MANUFACTURER'S RECOMMENDED CLEARENCES FOR AIRFLOW
AND MAINTENANCE.
39 EXTEND CONDENSATE DRAIN TO BACK FLOW PREVENTER DRAIN SEE
GATEHOUSE FLOOR PLAN - PLUMBING SHEET AP105.
40 SEE AHU CONDENSATE TRAP DETAIL A1/AM501.
41 SEE RECTANGULAR FLEXIBLE CONNECTION DETAIL A2/AM505.
42 SEE DUCTLESS SPLIT AC - WALL MOUNT DETAIL C4/AM505.
44 SEE ARCHITECTURAL DRAWING FOR DOOR UNDERCUT (UC).
45 DDC CONTROL PANEL 120 VOLTS 1 PHASE.
46 SEE ARCHITECURAL REFLECTED CEILING PLAN FOR ACCESS DOORS IN
CEILING A1/A-402. COORDINATE EXACT LOCATION WITH FINAL LOCATION
OF BALANCE DAMPERS.
48 PROVIDE POLYPROPYLENE PLASTIC MOUNTING PAD UNDER
CONDENSING UNIT. SIZE MUST BE 3" BIGGER THAN CONDENSING UNIT.
69 SEE LINE SHACK DETAIL C3/AM504.
70 SEE CURB DETAIL - MODIFIED BITUMEN A3/A-301.
72 SEE CENTRIFUGAL ROOF EXHAUST FAN DETAIL A2/AM504.
1' 2' 4'0'
PLAN
NORTH
1/2" = 1'-0" A1
GATEHOUSE ROOF PLAN - HVAC
1' 2' 4'0'
PLAN
NORTH
PLAN
KEY PLAN
1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
GENERAL NOTES
WORK NOTES
KEYPLAN
UTILITY
SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
1/2"ø RS
1/4"ø RL
3/4"ø CD
CU-4
DSS-4
A1
AM107
A3
AM107
T
DSS-4
(TYP.)
1 2
DSS-4
GUARD BOOTH
FLOOR LEVEL
8' - 9"
ROOF
18' - 5"
CU-4
3/4"ø CD
1/2"ø RS
1/4"ø RL
GUARD BOOTH
GB01
ABC
GUARD BOOTH
FLOOR LEVEL
8' - 9"
ROOF
18' - 5"
CU-4
1/2"ø RS
1/4"ø RL
3/4"ø CD
DSS-4
GUARD BOOTH
GB01
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
JGG/RSF
Approved by Sally Torgler, Deputy Director Facilities, with
NSWDG, via Email
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
5/19/2020
ALG
/1
/2
:5 :5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-G B
B D d k h e n d e rs o n .r v t
AM107
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
G U
A R
D B
O O
T H
H
V A
C F
LO
O
R P
LA
N
A N
D S
C H
E D
U
LE
CMG
12829430
CPM CPM
1614696
PLAN
NORTH
2' 4' 8'0'
12 PROVIDE MANUFACTURER'S RECOMMENDED CLEARENCES FOR AIRFLOW
AND MAINTENANCE.
13 PROVIDE 18" HIGH OUTDOOR UNIT STAND FOR CU-4.
14 SEE DUCTLESS SPLIT AC-WALL DETAIL C4/AM505.
15 PROVIDE CONDENSATE DRAIN SEE DETAIL C1/AM501.
16 MOUNT REMOTE CONTROLLER TO WALL AT 48" AFF.
17 COORDINATE LOCATION OF INDOOR UNIT WITH TELEPHONE EQUIPMENT
RACK. MOUNT DSS INDOOR UNIT 8'6" AFF. USE MANUFACTURER'S
PROVIDED MOUNTING HARDWARE.
18 SECURE REFRIGERANT PIPING AND DRAIN PIPING TO WALL.
19 TELEPHONE EQUIPMENT RACK.
20 PROVIDE MANUFACTURER'S RECOMMENDED PVC LINESET COVER.
33 SEE PIPE PENETRATIONS - DETAIL C3/AP504
PLAN
NORTH
1/4" = 1'-0" C1
GUARD BOOTH FLOOR PLAN
DUCTLESS SPLIT SYSTEM SCHEDULE
MARK TYPE LOCATION
REFERIGERANT
TYPE
SUPPLY FAN DATA COOLING HEATING INDOOR UNIT ELECTRICAL OUTDOOR UNIT OUTDOOR UNIT ELECTRICAL
NOTES
TOTAL AIRFLOW
(CFM)
FAN MOTOR
(WATTS)
TOTAL COOLING
(MBH)
SENSIBLE
COOLING (MBH)
EAT DB (°F) EAT WB (°F)
MIN EFFICIENCY
(SEER)
HEATING CAPACITY
AT 47 °F (MBH)
HEATING CAPACITY
AT 17 °F (MBH)
EAT DB
(°F) FLA MCA
VOLTS PH HZ MARK LOCATION FLA
MCA MOCP VOLTS PH HZ
DSS-4 WALL-MOUNTED GUARD BOOTH R-410A 370 30 12 9.6 78 65 20.8 18 11.1 68 0.33 1 208/230 1 60 CU-4 OUTSIDE 7.83 11 28 208/230 1 60 1,2,3,4,5
1/2" = 1'-0" (AM107)
A1
GUARD BOOTH SECTION 1
1' 2' 4'0' 1/2" = 1'-0" (AM107)
A3
GUARD BOOTH SECTION 2
1' 2' 4'0'
1. PROVIDE POWER AND CONTROL WIRING FROM OUTDOOR UNIT TO INDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH COASTAL COIL PROTECTION ON CONDENSING UNIT COIL.
3. PROVIDE WITH REMOTE CONTROLLER.
4. PROVIDE REFRIGERANT LINE SET PER MANUFACTURER'S RECOMMENDATION.
5. ELECTRICAL DATA FOR OUTDOOR UNIT INCLUDES INDOOR UNIT.
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
WORK NOTES
ABCD
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
CCC-2
4"ø CWR
4"ø CWS
FC-1
FRESH WATER
PUMP ROOM
USB2
EQUIPMENT
YARD
USB0
DOMESTIC WATER
BOOSTER PUMP SEE
PLUMBING SHEET AP101
ACCESS LADDER
AND PLATFORM
NORTH WALL AT
MECHANICAL YARD
STEEL SUPPORT
UNDER CLOSED
CIRCUIT COOLER
CONCRETE PAD - SEE
STRUCTURAL
DRAWING AS501
8x14 SA
SG-1 12x6
210 CFM6x12 SA14x16 RA
12x12 RA
P-3
16x24 OA
L-9 24x16
550 CFM
MD-2
4"ø CWR
4"ø CWR
4"ø CWS PIPE SUPPORT FOR
DOMESTIC COLD WATER
SEE PLUMBING FLOOR PLAN - AREA A
SHEET AP101
VLV-2
ABCD
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
MEDIUM
PRESSURE AIR
ROOM
USB4
L-11B 72x48
4675 CFM
4"ø CWR
MPAC-2
MPAP-2
2 1/2"ø CWR
CS-4
4"ø CWS
VLV-5
2"ø PWR 2"ø PWS
16x24 EA
MD
MD
30x30 EA
GR-2
12x24 EA
FULL SIZE OF UNIT
CONNECTION. PROVIDE
WITH FLEXIBLE
CONNECTION
12x20 EA 35
48x72 OA
38 (TYP.)
VIBRATION
ISOLATOR (TYP.)
BDD
L-3 48x48
6080 CFM
EF-3
28x28 EA
MD-5
ROOF
26' - 11"
P-2
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
AB
ET-1
FROM
CCC-1 & 2
TO SYSTEM
AS-1
3/4" MAKE-UP PIPE TO GLYCOL
FEEDER SEE PLUMBING ENLARGED
FLOOR PLAN SHEET 2 OF 4 SHEET
AP102 FOR CONTINUATION.
4"ø CWS
4"ø CWS
MEDIUM
PRESSURE AIR
ROOM
USB4
GFS-1
1" RELIEF VALVE
ROUTE
DISCHARGE TO
GLYCOL TANK
2"ø PWR
BUTTERFLY SHUTOFF
VALVES (TYP.)
STRAINER (TYP.)
FLOW CONTROL
BALANCE VALVE
(TYP.)
VIBRATION
ISOLATORS
(TYP.) REDUCER AS REQUIRED
TO MATCH PUMP INLET/OUTLET
(TYP.)
2"Ø
RELIEF
2"ø PWS
48x72 OA
L-11A 72x48
4675 CFM
MD-4
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:4
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM301
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L S
E C
TI
O
N S
S
H E
E T
O
F
CMG
12829431
BRF BRF
1614696
32 CLOSED CIRCUIT COOLERS CAN BE NO HIGHER THAN THE NORTH WALL AT
THE MECHANICAL YARD.
34 SEE INLINE PUMP PIPING DETAIL C1/AM504.
35 SEE AIR COMPRESSOR CONDENSER WATER PIPING DETAIL A4/AM501.
36 SEE FAN COIL UNIT PIPING DETAIL C4/AM501.
37 SEE CONDENSER WATER PIPING DIAGRAM A1/AM610.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER
OPENING.
45 DDC CONTROL PANEL 120 VOLTS 1 PHASE.
52 SEE MANUAL AIR VENT DETAIL A5/AM502.
54 SEE ELBOW PIPE SUPPORT DETAIL C2/AM502.
56 SEE RECTANGULAR BRANCH DUCT TAKE-OFF DETAIL A3/AM503.
62 SEE GLYCOL FEEDER DETAIL A1/AM505.
64 SEE TYPICAL MAKEUP WATER CONNECTION DETAIL A4/AM505.
65 SEE CABINET OR INLINE EXHAUST FAN DETAIL C1/AM505.
66 SEE AIR SEPARATOR DETAIL C2/AM505.
67 SEE EXPANSION TANK DETAIL B4/AM505.
2' 4' 8'0' 2' 4' 8'0'
2' 4' 8'0'1/4" = 1'-0" (AM101)
C1
SECTION AT USB1 AND USB0
1/4" = 1'-0" (AM102)
A1
SECTION AT USB3
1/4" = 1'-0" (AM102)
A4
SECTION AT PUMP
ABCD
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
L-12 72x48
5500 CFM
4"ø CWR
4"ø CWR
HPAC-2
HIGH PRESSURE AIR
COMPRESSOR
2 1/2"ø CWS
HPR-3A
HIGH PRESSURE
AIR RECEIVER
HIGH PRESSURE
AIR PURIFIER
L-4 48x48
5500 CFM
HIGH PRESSURE
AIR ROOM
USB5
EF-4
38 48x72 OA
BDD
24x24 EA
HPAP-4
UH-4
MD-7
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
GENERATOR
MUFFLER
x5
O
A
EF-6
SG-2 48x48
7000 CFM
SG-2 48x48
7000 CFM
8" EP54x54 OA
GI-3
L-14 96x96
30000 CFM
x5
O
A
BD
(BEYOND)
FLEXIBLE
CONNECTION
(TYP.)
DRAIN VALVE
AND CAP
VIBRATION ISOLATORS
(TYP. OF 4)
8"Ø EP
1/2"ø RS 1/2"ø RL 3/4"ø CD
MD
48x48 EA
32x32 EA
FAN
MOTOR
ABCD
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
32x32 EA
54x54 OA
SG-2 48x48
7500 CFM
(TYP OF 8)
GI-1
GI-2
GI-3
54x54 OA
54x54 OA
L-7 48x48
5000 CFM
GENERATOR (TYP)
BD
(BEYOND)
BD
(BEYOND)
BD
(BEYOND)
EF-6
UH-2
54x54 OA
55ø EA
55ø EA
8"Ø EP
8"Ø EP
CU-1
3/4"ø RS
MD
MD
MD
MUFFLER (TYP.)
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES
WORK NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM302
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L S
E C
TI
O
N S
S
H E
E T
O
F
CMG
12829432
DKH DKH
1614696
2' 4' 8'0'
1/4" = 1'-0" (AM103)
C1
SECTION AT USB
1/4" = 1'-0" (AM104)
A4
GENERATOR SECTION
1/4" = 1'-0" (AM104)
A1
SECTION AT USB
31 PROVIDE HINGED, GRAVITY-OPERATED, SELF-CLOSING RAIN COVER.
35 SEE AIR COMPRESSOR CONDENSER WATER PIPING DETAIL A4/AM501.
38 PROVIDE 16 GAGE, 2x2 MESH, GALVANIZED HARDWARE CLOTH OVER
OPENING.
65 SEE CABINET OR INLINE EXHAUST FAN DETAIL C1/AM505.
73 SEE SECTIONS B3/AS311 AND B4/AS311 FOR DETAILS ON THE STRUCTURAL
SUPPORT FOR THE FAN.
79 PROVIDE 3/4"Ø ALL THREAD ROD FROM STRUCTURE TO VIBRATION
ISOLATOR AND FROM THE VIBRATION ISOLATOR TO THE FAN. CONNECT
TO FAN PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE DOUBLE
BOLTS ON THE BOTTOM AND TOP OF THE STEEL.
2' 4' 8'0'
2' 4' 8'0'
ROOF
29' - 3"
GATEHOUSE FLOOR
LEVEL
8' - 6"
A DB C
EF-7
HP-1
GI-1
6x6 RA
8x8 SA
RR-1 6x6
50 CFM
CD-1 6x6
50 CFM
LS-1 8ø
200 CFM
3/4"ø CD TOILET
GH02
SENTRY
GH01
EQUIPMENT
GH04
8x8 EA
SS-1
EG-1 8x8
50 CFM
1 2
CU-3
8x8 RA
70 72
RR-2 8x8
250 CFM
MD-22MD-21
ROOF
29' - 3"
GATEHOUSE FLOOR
LEVEL
8' - 6"
13 2
CU-3
1/2"ø RS
3/4"Ø AUX
CONDENSATE
DRAIN
AUXILLARY DRAIN
UNDER UNIT
16x20 RA
SS-1
CD-1 6x6
50 CFM
(TYP.)
TOILET
GH02
STO
GH03
8x8 RA
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
GENERAL NOTES
WORK NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GREGORY R. MOSS
DIRECTOR OF WARFARE REQIUREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:2 :5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-G H
B D d kh e n d e rs o n .r v t
AM303
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
G A
T E
H O
U S
E
M E
C H
A N
IC
A
L S
E C
T
IO
N S
CMG
12829433
CPM CPM
1614696
1/4" = 1'-0" (AM106)
C1
NORTH VIEW - SECTION
1/4" = 1'-0" (AM106)
A1
WEST VIEW - SECTION
2' 4' 8'0'
2' 4' 8'0'
1 REFRIGERENT LIQUID FROM ROOFTOP HEAT PUMP. REFER TO
MANUFACTURER FOR REFRIGERANT PIPING SIZE. SEE THIS SHEET FOR
CONTINUATION.
2 REFRIGERENT SUCTION TO ROOFTOP HEAT PUMP. REFER TO
MANUFACTURER FOR REFRIGERANT PIPING SIZE. SEE THIS SHEET FOR
CONTINUATION.
39 EXTEND CONDENSATE DRAIN TO BACK FLOW PREVENTER DRAIN SEE
GATEHOUSE FLOOR PLAN - PLUMBING SHEET AP105.
40 SEE AHU CONDENSATE TRAP DETAIL A1/AM501.
48 PROVIDE POLYPROPYLENE PLASTIC MOUNTING PAD UNDER CONDENSING
UNIT. SIZE MUST BE 3" BIGGER THAN CONDENSING UNIT.
69 SEE LINE SHACK DETAIL C3/AM504.
70 SEE CURB DETAIL - MODIFIED BITUMEN A3/A-301.
72 SEE CENTRIFUGAL ROOF EXHAUST FAN DETAIL A2/AM504.
74 CHANNEL FRAME SUPPORT UNDER UNIT/DRAIN PAN. PROVIDE 1/2"
DIAMETER ALL THREAD ROD UP TO STRUCTURE.
FCU
MV
MV
TO/FROM CONDENSER
WATER RETURN LINES
MANUAL VENT 1/2" VALVE,
NIPPLE AND CAP.
TEST CONNECTION FOR TESTING WITH
PRESSURE GAUGE OR THERMOMETER (TYP.)
UNION (TYP.)
1/2" BALL VALVE,
NIPPLE AND CAP
SEE A5 / AM502
THREE WAY CONTROL VALVE
CALIBRATED BALANCING
VALVE (NOTE 1)
NOTES:
1. INSTALL CALIBRATED BALANCING VALVES IN CONFORMANCE WITH
VALVE MANUFACTURER'S RECOMMENDED SPACING UP AND
DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR OTHER
VALVES AND COMPONENTS IN THE PIPING.
STRAINER WITH
BLOWDOWN VALVE
INLINE PUMP
M
FLEXIBLE CONNECTION
(TYP.)
UNIT
DRAIN
PAN
INTERNAL
OPERATING
NEGATIVE STATIC
PRESSURE ("WG)
NOTES:
1. DIMENSION EQUAL TO MAXIMUM FAN INLET PRESSURE (INCH WC) +1"(MIN.)
2. DIMENSION EQUAL TO /2 (MIN.)
DRAW THRU UNIT
RETURN BEND
(CLOSED)
FAN INLET
PRESSURE
(NEGATIVE)
A
A
B
A
AHU CABINET WALL
FOR MIN SIZE SEE
CHART, SLOPE TO
DRAIN
PITCH (1/8" PER
FOOT) (TYP.)
NPT DRAIN
CONNECTION
ADAPTER
HAND-TIGHT
CLEANOUT PLUG
B
NOTES:
1. DRAIN SIZE FROM TABLE 307.2.2 (2018) IMC.
2. SIZE DSS AS RECOMMENDED BY THE DSS MANUFACTURER
MINIMUM CONDENSATE
DRAIN SIZE
EQUIPMENT CAPACITY
(TONS OF REFRIGERATION)
SIZE (IN)
3/4"
NOTES
1, 2UP TO 20
CONDENSATE DRAIN
PIPING FROM UNITS
PAVEMENT (TYP.)
EARTH (TYP.)
12"⌀ CONCRETE PIPE
18" LONG
PROVIDE STANDARD
PEA GRAVEL
FILL GRAVEL TO
APPROX. 2" FROM
THE TOP
MV MV
CONDENSER WATER SUPPLY
AND RETURN LINES
MANUAL VENT 1/2" VALVE,
NIPPLE AND CAP.
TEST CONNECTION FOR TESTING WITH
PRESSURE GAUGE OR THERMOMETER (TYP.)
UNION (TYP.)
1/2" BALL VALVE,
NIPPLE AND CAP
SEE A5 / AM502
TWO WAY TWO
POSITION CONTROL VALVE
M
CALIBRATED BALANCING
VALVE (NOTE 1)
NOTES:
1. INSTALL CALIBRATED BALANCING VALVES IN CONFORMANCE WITH
VALVE MANUFACTURER'S RECOMMENDED SPACING UP AND
DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR OTHER
VALVES AND COMPONENTS IN THE PIPING.
MEDIUM OR HIGH PRESSURE
AIR COMPRESSOR
STRAINER WITH
BLOWDOWN VALVE
FLEXIBLE PIPE CONNECTOR (TYP.)
(TYP.)
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM501
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
M E
C H
A N
IC
A
L D
E
TA
IL
S
S
H E
E T
O
F
CMG
12829434
CPM CPM
1614696
NOT TO SCALEC4
FAN COIL UNIT PIPING DETAIL
NOT TO SCALEA1
CONDENSATE TRAP DRAIN DETAIL
NOT TO SCALE
C1
CONDENSATE DRAIN DETAIL
NOT TO SCALEA4
AIR COMPRESSOR CONDENSER WATER PIPING DETAIL
FLOOR DRAIN
3/4"
MAIN LINE, AIR SEPERATOR
OR EXPANSION TANK
AUTOMATIC
AIR VENT
REDUCER FULL LINE SIZE
POCKET OR 4"
DIAMETER MAX.
1/4" COPPER TUBING, FIELD
ROUTE TO FLOOR
DRAIN
BALL VALVE
WEEP HOLE
GROUT
CONCRETE ANCHORS
WELD
1/2" PLATE
WELD
ALL CHILLED WATER FLOOR PIPE SUPPORTS TO BE FULLY
INSULATED DOWN TO AND INCLUDING PLATE SUPPORTS.
NOTE:
1.
4"
MINIMUM
NOTE:
WATER PIPING
REDUCER
3/4" BALL
VALVE
3/4"
1. VENT ALL HIGH POINTS AS
INDICATED ABOVE.
3/8" BRASS PLUG
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED BELOW.
2. WHERE DIRT LEGS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF DIRT LEG.
ELEVATION
WELDED PIPING
ELEVATION
THREADED PIPING
TYP. WATER PIPING
TYP. WATER PIPING
3/4" BALL VALVE
REDUCER, IF REQUIRED
ADAPTER TO 3/4" HOSE
THREAD, PROVIDE HOSE
CAP NUT
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE
THREAD, PROVIDE
HOSE CAP NUT
HANGER ROD
LOCKING NUT
SUPPORT NUT
INSULATION
PIPE
HEAVY DUTY
CLEVIS HANGER
14 GAUGE RIBBED SHIELD
TO PROTECT INSULATION
TO STRUCTURE
NOTE:
1. HANGERS LOCATED OUTSIDE MUST BE STAINLESS STEEL.
Level 1 10' - 3"
FIRST FLOOR
10' - 3"
USB FLOOR LEVEL
10' - 3"
DOUBLE PIPE STAND
CONDENSER WATER
PIPING (TYP.)
GUSSET PLATE
FOR SUPPORT
CONCRETE FLOOR IN
MECHANICAL YARD
HIGH DENSITY POLYPROPYLENE
PLASTIC FEET SET ON
CONCRETE
SEE PIPE HANGER
DETAIL C3/AM502
(TYP)
STAINLEES STEEL
STRUT CHANNEL (TYP)
1"ø DCW
WITH INSULATION
Level 1 10' - 3"
FIRST FLOOR
10' - 3"
USB FLOOR LEVEL
10' - 3"
CONDENSER WATER OR
DOMESTIC COLD WATER
PIPING (TYP.)
GUSSET PLATE
FOR SUPPORT
CONCRETE FLOOR IN
MECHANICAL YARD
HIGH DENSITY POLYPROPYLENE
PLASTIC FEET SET ON
CONCRETE
SEE PIPE HANGER
DETAIL C3/AM502
(TYP)
STAINLEES STEEL
STRUT CHANNEL (TYP)
SINGLE PIPE
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM502
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
M E
C H
A N
IC
A
L D
E
TA
IL
S
S
H E
E T
O
F
CMG
12829435
CPM CPM
1614696
NOT TO SCALEC1
AUTOMATIC AIR VENT DETAIL
NOT TO SCALEC2
ELBOW PIPE SUPPORT DETAIL
NOT TO SCALEA5
MANUAL AIR VENT DETAIL
NOT TO SCALEC4
LOW POINT DRAIN DETAIL
NOT TO SCALEC3
PIPE SUPPORT DETAIL
1" = 1'-0" A1
EXTERIOR PIPE STAND DETAILS
INSULATED FLEXIBLE DUCT -
MAXIMUM LENGTH = 5'-0"
LINEAR SLOT DIFFUSER WITH LINED
PLENUM BOX SEE PLANS FOR LENGTH,
NO. OF SLOTS, AND CONNECTION SIZE.
RECTANGULAR TRANSITION RECTANGULAR TO ROUND
TRANSITION
ROUND 90 ELBOW SQUARE 90 ELBOW
W
W
D
D
TURNING VANES
MAX. SLOPE 1" IN 4"
ROUND DUCT
RECTANGULAR DUCT
MAX. SLOPE 1" IN 4"
1.5 x D
KEEP ONE SIDE FLAT
WHERE POSSIBLE
SEE DETAIL A1/AM503 FOR
TURNING VANE DETAILS
R S GA
SINGLE VANE SCH.
SMALL
LARGE
51 38 24
114 83 22
45°45°
S
S S S S
L
LWW
D
S= D/6 (MIN.2")
W/S= NO. OF SPACES
R= 1 1/4 S
L= 3/4 S
RBOLT, SCREW OR
WELD TO DUCT
SCREW EVERY
SIXTH VANE
BLADES IN TRANSITION ELBOWS MUST BE
DETERMINED ACCORDING TO SMALLEST WIDTH
OF ELBOW.
NOTES:
X = 20° MAX.
J = 45°
W
L
L = 1/4 W, 4" MIN.
AIRFLOW
J
X
RECTANGULAR DUCT,
SEE PLAN FOR SIZE.
TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS REQUIRED BY PLANS.1.
BRANCH DUCT,
SEE PLAN FOR
SIZE.
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT EXTENSION
TO ALLOW OPERATION OF DAMPER WITHOUT
DAMAGE TO INSULATION.
NOTES:
TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS REQUIRED BY PLANS.1.
X = 20° MAX.
J = 45°
W
L
L = 1/4 W, 4" MIN.
AIRFLOW
X
J
RECTANGULAR DUCT,
SEE PLAN FOR SIZE.
ROUND DUCT, SEE
PLAN FOR SIZE.
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT EXTENSION
TO ALLOW OPERATION OF DAMPER WITHOUT
DAMAGE TO INSULATION.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM503
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
M E
C H
A N
IC
A
L D
E
TA
IL
S
S
H E
E T
O
F
CMG
12829436
CPM CPM
1614696
NOT TO SCALEC2
LINEAR SLOT DIFFUSER DETAIL
NOT TO SCALEC3
LOW VELOCITY DUCT LAYOUT DETAIL
NOT TO SCALEA1
RECTANGULAR DUCT ELBOW TURNING VANES DETAIL
NOT TO SCALEA3
RECTANGULAR BRANCH DUCT TAKE-OFF DETAIL
NOT TO SCALEC1
ROUND BRANCH DUCT TAKE-OFF DETAIL
INSTALL PUMP LEVEL.
INSTALL CALIBRATED BALANCING VALVES IN CONFORMANCE WITH VALVE MANUFACTURER'S
RECOMMENDED SPACING UP AND DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR
OTHER VALVES AND COMPONENTS IN THE PIPING.
4.
3.
2.
1.
INSTALLATION NOTES:
DRAIN VALVE WITH
HOSE CONNECTION
1/4 INCH GAUGE COCK (TYP.)
UNION OR FLANGE TYPE PIPE
CONNECTION SO PUMP CAN BE
REMOVED FOR SERVICE.
BALL VALVE (TYP.)
CHECK VALVE
IN-LINE PUMP
INSTALL PUMP SO THAT IT CAN BE REMOVED WITHOUT DISMANTLING
OR FORCING ADJACENT PIPE.
BEFORE START-UP, LUBRICATE PUMP IN ACCORDANCE WITH
MANUFACTURERS INSTRUCTIONS. (DO NOT RUN PUMP DRY.)
CALIBRATED BALANCING
VALVE (NOTE 2)
STRAINER WITH
BLOWDOWN VALVE
PRESSURE GAGE
0-60 PSIG RANGE
3/4" HHWS FROM
CWR
3/4" HHWS TO FAN
COIL
REDUCER AS REQUIRED
TO MATCH PUMP INLET/
OUTLET (TYP.)
EXTERIOR SIDE
INTERIOR SIDE
ELEVATION
SECTION
MULTIPLE SECTION
RUBBER SEAL (SEE
SPECIFICATIONS)
PIPE
WALL SLEEVE
WALL
SLEEVE
CONTINUOUS SEALANT
AS SPECIFIED
∅ PIPE THRU WALL
INSTALL SUCH THAT
PIPE SEAL MAY BE
TIGHTENED FROM
INTERIOR SIDE
1/2∅ HEADED STUDS @ 12"
SPACED RADIALLY
AROUND SLEEVE (4 MIN.)
AIR FLOW
DUCT
AIR FLOW
DUCT
GRIDS AND DAMPERS MUST NOT DAMAGE LINERS
NOTE:
ADJUSTABLE DAMPER
SUPPLY OUTLET
ADJUSTABLE DAMPER
SUPPLY OUTLET
QUALIZING GRID (WHEN
SPECIFIED ALTERNATIVE TO
EXTRACTOR)
REGISTER AND DIFFUSER CONTAIN VOLUME
CONTROL AT GRILLE. GRILLE HAS NO VOLUME
CONTROL.
GRILLE FLANGES MUST
COVER DUCT FLANGES.
EA
EXHAUST FAN
BACKDRAFT DAMPER
BIRDSCREEN
ROOF CURB, COORDINATE
W/EQUIPMENT FURNISHED
SEE ARCHITECTURAL DETAIL A3/A-301
FRONT
REMOVABLE COVER
CLOSED CELL
FOAM BLOCK
ROOF CURB. REFER
TO ARCHITECTURE
DETAIL A3/A-301
CLOSED CELL
FOAM BLOCK
REMOVABLE COVER
FRONT
SIDE VIEW
SECTION
REFRIGERANT PIPING
(TYP.)
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/2
/2
:1
:5
P
M C
R e v it P ro je ct s \P
IE
R
P -1
-M
-U S
B D d k h e n d e rs o n .r v t
AM504
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
M E
C H
A N
IC
A
L D
E
TA
IL
S
S
H E
E T
O
F
CMG
12829437
CPM CPM
1614696
NOT TO SCALEC1
IN-LINE PUMP PIPING DETAIL
NOT TO SCALEA1
HYDROSTATIC SEAL DETAIL
NOT TO SCALEA4
DIFFUSER, GRILLE, & REGISTER CONNECTION DETAIL
NOT TO SCALEA2
CENTRIFUGAL ROOF EXHAUST FAN
NOT TO SCALEC3
LINE SHACK DETAIL
EXHAUST FAN
VIBRATION INSULATOR
PROVIDE SPRING AND RUBBER
COMBINATION HANGER, SELECT
FOR 1 INCH DEFLECTION UNDER
CALCULTED CORNER LOAD.
FLEX
CONNECTION
HANGER ROD
MOUNTING BRACKET
OR CHANNEL
(TYP. OF INTAKE
AND DISCHARGE)
AIR SEPARATOR
FROM SYSTEM
AUTOMATIC AIR
VENT
DRAIN VALVE
TO PUMP
SUCTION
RELIEF VALVE SET
AT 30 PSI
FULL SIZE TO GYLCOL
FEED TANK
AV
BOTTOM OF VALVE
7'- 6" AFF MINIMUM
SHUT OFF VALVE
(TYP.)
LIFTING RING 3/4"
AUTOMATIC
AIR VENT
AIR CHARGE
VALVE
TO PUMP
SUCTION
EXPANSION TANK
DRAIN VALVE WITH 3/4" HOSE
CONNECTION
FINISH FLOOR
AV
HOUSEKEEPING PAD
3/4" QUICK-FILL
BYPASS
SET PRV AT 20 PSIG
FROM BACKFLOW
PREVENTER, SEE
PLUMBING FLOOR PLAN -
AREA B SHEET AP102
FOR CONTINUATION
TO GYLCOL
FEED SYSTEM
SEE DETAIL A1/AM505
RANGE OF 0-100 PSIG
DUCT
1-1/2" POCKET SLIP
1-1/2" MIN. TO 3"
MAX. INSTALLED.
6" NOMINAL WITH
MATERIAL TAUT.
WASHER
1" FLANGE AND HEM
FLEXIBLE MATERIAL
AS SPECIFIED
1" x 1/8"
BAND IRON
BOLT ON 4" CENTERS
ALTERNATE
POSITION OF BOLT
FLANGED
CONNECTION
OF FAN SIDE
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
SHEET METAL AS
SPECIFIED FOR DUCTWORK
NOTES:
1. LOCATE ON BOTH THE INTAKE AND DISCHARGE OF EQUIPMENT.
2. PROVIDE HIGH TEMPERATURE FLEXIBLE MATERIAL AT GENERATOR DISCHARGE.
GFS-1 GLYCOL FEED
SYSTEM
CONDENSER WATER
HEADER TO PUMP
SUCTION
CONDENSER WATER HEADER
FROM AIR SEPARATOR &
BEFORE PUMP SUCTION
4"
3/4" ROUTE RELIEF AND MAKE-UP
PIPING TO TOP OF GLYCOL TANK.
PROVIDE AIR GAP
NOTE: GLYCOL FEED SYSTEM INCLUDES
A PRESSURE REDUCING VALVE. SET PRV
AT 12 PSIG.
1" RELIEF PIPING FROM
AIR SEPARATOR - SEE
DETAIL C2/AM505
0-60 PSIG
3/4" DOMESTIC COLD
WATER MAKE-UP LINE - SEE
DETAIL A4/AM505
USB AND GUARD BOOTH - PROVIDE 18"
HIGH STAND AS INDICATED. BOTTOM OF
UNIT MUST STAY ABOVE 10'3" FLOOD
ELEVATION.
GATEHOUSE - PROVIDE
POLYPROPYLENE PLASTIC MOUNTING
PAD (AS SHOWN)
OUTDOOR UNIT CU-X. SECURE TO
CONCRETE PAD OR ROOF MOUNTED
WALL SLEEVE WITH CAPS
FURNISHED BY MANUFACTURER
POWER & CONTROL WIRING TO
INDOOR UNIT PER MANUFACTURER'S
RECOMMENDATIONS
AIRFLOW
AIRFLOW
TOP OF UNIT
± 8'-6" AFF
UNLESS
OTHERWISE
NOTED
INDOOR UNIT DSS-X
WALL MOUNTING BRACKET FURNISHED
BY MANUFACTURER
3/4" Ø DRAIN LINE SEE
FLOOR PLANS FOR
TERMINATION POINT
SA
INSULATED RS, RL REFRIGERANT
LINES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y…