This document provides details on a federal solicitation for pier recapitalization work at Naval Station Norfolk in Virginia. The solicitation number is N4008521R0219 and is being issued by the Department of the Navy Naval Facilities Engineering Command for pier recapitalization services at Pier 3. Offerors are invited to submit proposals in response to requirements for recapitalization of Pier 3, including replacement of piles, decking, utilities and other pier infrastructure elements. The deadline for proposal submission is not specified in this document.
View the file
Other files
Show 40 more
Latest 50 of 79 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCU
MV
MV
TO/FROM CONDENSER
WATER RETURN LINES
MANUAL VENT 1/2" VALVE,
NIPPLE AND CAP.
TEST CONNECTION FOR TESTING WITH
PRESSURE GAUGE OR THERMOMETER (TYP.)
UNION (TYP.)
1/2" BALL VALVE,
NIPPLE AND CAP
SEE A5 / AM502
THREE WAY CONTROL VALVE
CALIBRATED BALANCING
VALVE (NOTE 1)
NOTES:
1. INSTALL CALIBRATED BALANCING VALVES IN CONFORMANCE WITH
VALVE MANUFACTURER'S RECOMMENDED SPACING UP AND
DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR OTHER
VALVES AND COMPONENTS IN THE PIPING.
STRAINER WITH
BLOWDOWN VALVE
INLINE PUMP
M
FLEXIBLE CONNECTION
(TYP.)
UNIT
DRAIN
PAN
INTERNAL
OPERATING
NEGATIVE STATIC
PRESSURE ("WG)
NOTES:
1. DIMENSION EQUAL TO MAXIMUM FAN INLET PRESSURE (INCH WC) +1"(MIN.)
2. DIMENSION EQUAL TO /2 (MIN.)
DRAW THRU UNIT
RETURN BEND
(CLOSED)
FAN INLET
PRESSURE
(NEGATIVE)
A
A
B
A
AHU CABINET WALL
FOR MIN SIZE SEE
CHART, SLOPE TO
DRAIN
PITCH (1/8" PER
FOOT) (TYP.)
NPT DRAIN
CONNECTION
ADAPTER
HAND-TIGHT
CLEANOUT PLUG
B
NOTES:
1. DRAIN SIZE FROM TABLE 307.2.2 (2018) IMC.
2. SIZE DSS AS RECOMMENDED BY THE DSS MANUFACTURER
MINIMUM CONDENSATE
DRAIN SIZE
EQUIPMENT CAPACITY
(TONS OF REFRIGERATION)
SIZE (IN)
3/4"
NOTES
1, 2UP TO 20
CONDENSATE DRAIN
PIPING FROM UNITS
PAVEMENT (TYP.)
EARTH (TYP.)
12"⌀ CONCRETE PIPE
18" LONG
PROVIDE STANDARD
PEA GRAVEL
FILL GRAVEL TO
APPROX. 2" FROM
THE TOP
MV MV
CONDENSER WATER SUPPLY
AND RETURN LINES
MANUAL VENT 1/2" VALVE,
NIPPLE AND CAP.
UNION (TYP.)
1/2" BALL VALVE,
NIPPLE AND CAP
SEE A5 / AM502
TWO WAY TWO
POSITION CONTROL VALVE
M
CALIBRATED BALANCING
VALVE (NOTE 1)
NOTES:
1. INSTALL CALIBRATED BALANCING VALVES IN CONFORMANCE WITH
VALVE MANUFACTURER'S RECOMMENDED SPACING UP AND
DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR OTHER
VALVES AND COMPONENTS IN THE PIPING.
MEDIUM OR HIGH PRESSURE
AIR COMPRESSOR
STRAINER WITH
BLOWDOWN VALVE
FLEXIBLE PIPE CONNECTOR (TYP.)
(TYP.)
COMPRESSE AIR
SYSTEM EQUIPMENT
BID OPTION
PROVIDE BLIND FLANGE
AS PART OF BASE BID
(TYP)
PRESSURE GAGE (TYP.)
THERMOMETER (TYP.)
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:4
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AM501
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
M E
C H
A N
IC
A
L D
E
TA
IL
S
S
H E
E T
O
F
CMG
12829434
CPM CPM
1614696
NOT TO SCALEC4
FAN COIL UNIT PIPING DETAIL
NOT TO SCALEA1
CONDENSATE TRAP DRAIN DETAIL
NOT TO SCALE
C1
CONDENSATE DRAIN DETAIL
NOT TO SCALEA4
AIR COMPRESSOR CONDENSER WATER PIPING DETAIL
B
ID
O
P
TI
O N
S 9/
/2
D K
H
1. TOTAL CONDENSER WATER FLOW IS 301.2 GPM WHICH IS BASED ON (3) MPAC AND (2) HPAC. COMPRESSORS ARE N+1 REDUNDANT. FC-1 THRU FC-4 CONNECT SUPPLY AND RETURN TO CWR TO RECOVER HEAT BUT THEY DON'T AFFECT THE
TOTAL FLOW.
NOTES:
1. TOTAL CONDENSER WATER FLOW IS 301.2 GPM. PUMPS ARE N+1 REDUNDANT (PRIMARY AND STANDBY).
2. PUMPS MUST BE PROVIDE WITH HIGH EFFICIENCY MOTORS (INVERTER DUTY).
3. MINIMUM FLOW IS BASED ON 30% OF THE TOTAL FLOW.
NOTES:
1. TOTAL CONDENSER WATER FLOW IS 301.2 GPM CLOSED CIRCUIT COOLERS ARE N+1 REDUNDANT (PRIMARY AND STANDBY).
2. HEIGHT OF UNIT MUST NOT EXCEED THE NORTH WALL HEIGHT. SEE DRAWINGS FOR EXACT HEIGHT OF WALL.
3. UNIT MUST BE PROVIDED WITH SINGLE POINT CONNECTION AND CONTROL PANEL.
4. UNIT MUST BE ALL STAINLESS STEEL CONSTRUCTION CASING AND COPPER COILS.
5. UNIT IS SIZED BASED ON 30% PROPYLENE GLYCOL.
6. UNIT MUST MEET OR EXCEED ASHRAE 90.1 REQUIREMENTS.
7. UNIT MUST BE PROVIDED WITH ACCESS LADDER AND PLATFORM.
8. UNIT MUST BE PROVIDED WITH FLOAT SWITCH FOR COLD WATER MAKE UP.
9. COORDINATE WITH MANUFACTURER TO VERIFY CLEARANCES AROUND UNITS AND PROVIDE ANY DERATING TO ASSURE
PROPER CAPACITY. ONLY ONE UNIT OPERATES AT A TIME.
NOTES:
1. PROVIDE WITH HORIZONTAL MOUNTING BRACKETS AND LIFTING LUGS.
2. PROVIDE WITH FLEXIBLE CONNECTION/EXPANSION JOINT ON INLET AND OUTLET.
3. PROVIDE MUFFLER THAT IS COMPATIBLE WITH THE GENERATOR. SEE SPECIFICATION SECTION 26 32 15.00 ENGINE-
GENERATOR SET STATIONARY 15-2500KW, WITH AUXILIARIES.
NOTES:
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AM602
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L S
C H
E D
U
LE
S
CMG
12829440
DKH DKH
1614696
CLOSED CIRCUIT COOLER SCHEDULE
MARK
LOCATION SERVICE
FLOW
(GPM)
LWT
(DEG F)
EWT
(DEG F)
COIL
PRESSURE
DROP (PSI)
AMBIENT WET
BULB
TEMPERATURE
(DEG F)
PROPYLENE
GLYCOL
CONTENT
FANS PER
CELL
FAN MOTOR
CAPACITY
PER CELL
(HP)
FAN SPEED
(RPM)
NO. OF
PUMPS
PUMP MOTOR
OUTPUT PER CELL
(HP)
NO. OF
ELECTRIC
HEATERS
HEATER
CAPACITY
(KW) FLA MOCP VOLTS PHASE HZ
OPERATING
WEIGHT
(LBS) NOTES
CCC-1 EQUIPMENT YARD USB0 CONDENSER WATER 301.2 90 110 3.0 79.00 30.0 2 20.00 1800 1 5 1 4.5 48 90 460 3 60 13300 1,2,3,4,5,6,7,8,9
CCC-2 EQUIPMENT YARD USB0 CONDENSER WATER 301.2 90 110 3.0 79.00 30.0 2 20.00 1800 1 5 1 4.5 48 90 460 3 60 13300 1,2,3,4,5,6,7,8,9
PUMP SCHEDULE
MARK TYPE LOCATION SERVICE
CAPACITY
(GPM)
PUMP HEAD
(FEET OF
HEAD)
SUCTION SIZE
(IN)
DISCHARGE SIZE
(IN)
PUMP
EFFICIENCY (%)
IMPELLER
SIZE (IN)
ELECTRICAL DATA
NOTES
MOTOR SPEED
(RPM)
MOTOR
SIZE (HP)
MOTOR OPERATING
BHP
SPEED
CONTROL
TYPE VOLTS PHASE HZ
P-1 CLOSE-COUPLED VERTICAL IN-LINE MEDIUM PRESSURE AIR ROOM USB4 CONDENSER WATER 301.2 126 4 4 71 11 1760 15 13.95 VFD 460 3 60 1,2,3
P-2 CLOSE-COUPLED VERTICAL IN-LINE MEDIUM PRESSURE AIR ROOM USB4 CONDENSER WATER 301.2 126 4 4 71 11 1760 15 13.95 VFD 460 3 60 1,2,3
P-3 IN-LINE CIRCULATOR FRESH WATER PUMP ROOM USB2 HEATING HOT WATER 2.0 5 3/4 3/4 >50 - 1725 1/8 <1/8 NONE 120 1 60
P-4 IN-LINE CIRCULATOR PURE WATER ROOM USB3 HEATING HOT WATER 2.5 5 1-1/4 1-1/4 >50 - 1725 1/8 <1/8 NONE 120 1 60
P-5 IN-LINE CIRCULATOR MEDIUM PRESSURE AIR ROOM USB4 HEATING HOT WATER 2.5 5 1-1/2 1-1/2 >50 - 1725 1/8 <1/8 NONE 120 1 60
P-6 IN-LINE CIRCULATOR HIGH PRESSURE AIR ROOM USB5 HEATING HOT WATER 2.5 5 1-1/2 1-1/2 >50 - 1725 1/8 <1/8 NONE 120 1 60
VALVE SCHEDULE
MARK LOCATION SERVICE TYPE
WATER FLOW
(GPM)
PRESSURE DROP
(PSI)
VALVE
CV NOTES
VLV-1 MECHANICAL YARD USB0 CCC-1 ISOLATION BUTTERFLY TWO WAY TWO POSITION 301.2 3 173 1
VLV-2 MECHANICAL YARD USB0 CCC-2 ISOLATION BUTTERFLY TWO WAY TWO POSITION 301.2 3 173 1
VLV-3 PURE WATER ROOM USB3 CCC BYPASS BUTTERFLY TWO WAY TWO POSITION 88 3 50
VLV-4 MEDIUM PRESSURE ROOM USB4 MPAC-1 ISOLATION BUTTERFLY TWO WAY TWO POSITION 56.4 3 32.5
VLV-5 MEDIUM PRESSURE ROOM USB4 MPAC-2 ISOLATION BUTTERFLY TWO WAY TWO POSITION 56.4 3 32.5
VLV-6 MEDIUM PRESSURE ROOM USB4 MPAC-3 ISOLATION BUTTERFLY TWO WAY TWO POSITION 56.4 3 32.5
VLV-7 MEDIUM PRESSURE ROOM USB4 MPAC-4 ISOLATION BUTTERFLY TWO WAY TWO POSITION 56.4 3 32.5
VLV-8 HIGH PRESSURE AIR ROOM USB5 HPAC-1 ISOLATION BUTTERFLY TWO WAY TWO POSITION 66.0 3 36
VLV-9 HIGH PRESSURE AIR ROOM USB5 HPAC-2 ISOLATION BUTTERFLY TWO WAY TWO POSITION 66.0 3 36
VLV-10 HIGH PRESSURE AIR ROOM USB5 HPAC-3 ISOLATION BUTTERFLY TWO WAY TWO POSITION 66.0 3 36
VLV-11 HIGH PRESSURE AIR ROOM USB5 CONDENSER WATER MINIMUM FLOW BALL VALVE TWO WAY MODULATING 88.0 3 50
VLV-12 FRESH WATER PUMP ROOM USB2 FC-1 BALL VALVE THREE WAY MODULATING 2.0 3 1.1
VLV-13 PURE WATER ROOM USB3 FC-2 BALL VALVE THREE WAY MODULATING 2.5 3 1.4
VLV-14 MEDIUM PRESSURE ROOM USB4 FC-3 BALL VALVE THREE WAY MODULATING 2.5 3 1.4
VLV-15 MEDIUM PRESSURE ROOM USB4 FC-4 BALL VALVE THREE WAY MODULATING 2.5 3 1.4
VLV-24
MUFFLER SCHEDULE
MARK LOCATION SERVICE TYPE
INLET/OUTLET
(IN.) DIA (IN.)
BACK PRESSURE
(IN. W.C.) LENGTH (IN.)
CONNECTION
TYPE
CONSTRUCTION
TYPE MOUNTING INSULATION
ATTENUATION IN dB AT EACH FREQUENCY
NOTES63 HZ 125 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ 8000 HZ
M-1 GENERATOR ROOM USB7 BACKUP GENERATOR 1 RESIDENTAL 8 16 4.4 46 ANSI PATTERN
FLANGES
STEEL HORIZONTAL THERMAL INSULATION BLANKETS 10 25 32 30 25 25 24 23 1,2,3
M-2 GENERATOR ROOM USB7 BACKUP GENERATOR 2 RESIDENTAL 8 16 4.4 46 ANSI PATTERN
FLANGES
STEEL HORIZONTAL THERMAL INSULATION BLANKETS 10 25 32 30 25 25 24 23 1,2,3
GLYCOL FEED SYSTEM
MARK LOCATION SERVICE TYPE
TANK SIZE (GAL)
WATER FLOW
(GPM)
PRESSURE RANGE
(PSI)
MOTOR (HP) VOLTS PHASE
HERTZ
WEIGHT
(LBS) NOTES
GFS-1 MEDIUM PRESSURE AIR ROOM USB4 CONDENSER WATER AUTOMATIC 50 1.8 10-70 1/3 120 1 60 134
EXPANSION TANK SCHEDULE
MARK SYSTEM TYPE
TANK VOLUME
(GAL)
ACCEPTANCE VOLUME
(GAL)
TEMPERATURE
RATING (°F)
PRESSURE
RATING (PSIG)
ET-1 CONDENSER WATER 53 53 240 125
AIR SEPARATOR SCHEDULE
MARK INLET SIZE (IN) FLOWRATE (GPM)
AS-1 4 301.2
B
ID
O
P
TI
O N
S 9/
/2
D K
H
COMPRESSED AIR
SYSTEM
EQUIPMENT BID
OPTION
M
DRAIN VALVE
WITH HOSE
CONNECTION
(TYP.)
V-1
NO
CCC-1
DRAIN
VALVE
(TYP.)
TO SITE
DRAIN
OVERFLOW
(TYP.)
0-60
PSIG
0-200o F
FLEXIBLE
CONNECTION
(TYP.)
STRAINER
WITH BLOW
DOWN (TYP.)
0-60
PSIG
0-200o F
MANUAL
BALANCING
VALVE
(TYP.)
1" DCW SEE PLUMBING
FLOOR PLAN - AREA A
SHEET AP101 FOR
CONTINUATION
0-60
PSIG
0-200o F
M
H
EH
0-200o F
FM
P-1
P-2
P-3
V-12
FC-1
AS-1
MPAC-1
0-60
PSIG
0-200o F
M
ET-1
AUTOMATIC
AIR VENT
DRAIN VALVE
WITH HOSE
CONNECTION
MANUAL
AIR VENT
FLOW METER - PROVIDE
STRAIGHT RUNS OF PIPE BEFORE
AND AFTER PER MANUFACTURER'S
RECOMMENDATIONS
MANUAL BALANCE
VALVE (TYP.)
STRAINER WITH
BLOWDOWN
(TYP.)
CHECK VALVE
(TYP.)
FROM GFS-1 GLYCOL FEED
SYSTEM SEE DETAIL A1/AM505
M V-2
NO
CCC-2
0-60
PSIG
0-200o F
0-60
PSIG
0-200o F
V-3
M
V-11
0-200o F
M
NO
0-60
PSIG
MPAC-2
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
MPAC-3
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
MPAC-4
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
HPAC-1
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
HPAC-2
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
HPAC-3
0-60
PSIG
0-200o F
0-200o F
M
NO
0-60
PSIG
0-60
PSIG
0-200o F
M
H
EH
0-200o F
P-4
V-13
FC-2
0-60
PSIG
0-200o F
M
H
EH
0-200o F
P-5
V-14
FC-3
0-60
PSIG
0-200o F
M
H
EH
0-200o F
P-6
V-15
FC-4
V-4 V-5 V-6 V-7 V-8 V-9
V-10
RELIEF VALVE SET AT 30
PSIG - ROUTE DISCHARGE
TO GLYCOL FEED
TANK
36 36 36 36
(TYP.)
HEAT TRACE ALL
DCW 7 W/LF AT
120 VOLTS, 1 PH
LOCATED IN
EQUIPMENT YARD
NO
COMPRESSED AIR SYSTEM
EQUIPMENT BID OPTION
1. REFER TO DRAWING AM001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND
NOTES.
2. LOCATE ALL THERMOSTAT AND TEMPERATURE SENSORS 5'-0" AFF.
GENERAL NOTES WORK NOTES
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AM610
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L P
IP
IN
G D
IA
G
R A
M
CMG
12829442
DKH DKH
1614696
NOT TO SCALEA1
USB CONDENSER WATER PIPING DIAGRAM
24 SEE INLINE PUMP DETAIL C1/AM504.
25 SEE AIR COMPRESSOR CONDENSER WATER PIPING DETAIL A4/AM501.
36 SEE FAN COIL UNIT PIPING DETAIL C4/AM501.
66 SEE AIR SEPARATOR DETAIL C2/AM505.
67 SEE EXPANSION TANK DETAIL B4/AM505.
B
ID
O
P
TI
O N
S 9/
/2
D K
H
AI-1 T
BO-1
AI-2 T
CCC-1
MS
BO-7BI-1
BI-3 VS
VFDVFD
AI-9
BI-7
BI-8
BO-4
AO-3
T
AI-3
BO-2
AI-4 T
CCC-2
MS
BO-8BI-2
BI-4 VS
VFDVFD
AI-10
BI-9
BI-10
BO-5
AO-4
T
AI-5
T
AI-6
VFDVFD
AI-12
BI-13
BI-14
BO-9
AO-6
VFDVFD
AI-13
BI-15
BI-16
BO-10
AO-7
T
AI-7
AI-14
P-1
P-2
CWR
BI-17
BO-11
MPAC-1
T AI-15
BI-18
BO-12
MPAC-2
T AI-16
BI-19
BO-13
MPAC-3
T AI-17
BI-20
BO-14
MPAC-4
T AI-18
BI-21
BO-15
HPAC-1
T AI-19
BI-22
BO-16
HPAC-2
T AI-20
BI-23
BO-17
HPAC-3
T AI-21
AO-8
MINIMUM FLOW
BY-PASS VALVE
CWS
CWS
CWR
SPRAY
PUMP
SPRAY
PUMP
NC
V-2
NO V-3
FM
CWS
C W
R
NC
V-4
NC
V-5
NC
V-6
NC
V-7
NC
V-8
NC
V-9
NC
V-10
NO
V-11
FC-1
SEE A1/AM704 (TYP)
FC-2 FC-3
SEE A1/AM704
FC-4
SEE A1/AM704
AO-1
V-1
VFDVFD
AI-8
BI-5
BI-6
BO-3
AO-2
FAN A
FAN B
FAN A
FAN B VFDVFD
AI-11
BI-11
BI-12
BO-6
AO-5
NC
COMPRESSED
AIR SYSTEM
EQUIPMENT BID
OPTION
J
(TYP)
J J J J J J
1. REFER TO DRAWING AP701 FOR PROCESS CONTROLS LEGEND,
ABBREVIATIONS AND NOTES.
GENERAL NOTES
WORK NOTES
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:0
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AM702
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L C
O N
TR
O
LS
S H
E E
T
O F
CMG
12829444
DKH CPM
1614696
NOT TO SCALE
A1
CONDENSER WATER DIAGRAM
B
ID
O
P
TI
O N
S 9/
/2
D K
H
80 FOR BID OPTION TERMINAL CONTROL WIRING FOR ALL SENSORS, DEVICES
AND EQUIPMENT AT AIR COMPRESSORS IN JUNCTION NEAR THE LOCATION
OF THE EQUIPMENT.
CONDENSER WATER SYSTEM POINTS LIST
MARK DESCRIPTION ALARM TREND
ANALOG INPUT
AI-1 MAIN CWR TEMPERATURE YES YES
AI-2 CWR TEMPERATURE BEFORE CCC-1 YES YES
AI-3 CWR TEMPERATURE AFTER CCC-1 YES YES
AI-4 CWR TEMPERATURE BEFORE CCC-2 YES YES
AI-5 CWR TEMPERATURE AFTER CCC-2 YES YES
AI-6 CWR TEMPERATURE BEFORE PUMPS YES YES
AI-7 CWS TEMPERATURE AFTER PUMPS YES YES
AI-8 CCC-1 FAN A SPEED NO YES
AI-9 CCC-1 FAN B SPEED NO YES
AI-10
P-1 PUMP SPEED
NO YES
AI-11
P-2 PUMP SPEED
NO YES
AI-12
CWS FLOW
NO YES
AI-13
MPAC-1 CWR TEMPERATURE
YES YES
AI-14
MPAC-2 CWR TEMPERATURE
YES YES
AI-15
MPAC-3 CWR TEMPERATURE
YES YES
AI-16
MPAC-4 CWR TEMPERATURE
YES YES
AI-17
HPAC-1 CWR TEMPERATURE
YES YES
AI-18
HPAC-2 CWR TEMPERATURE
YES YES
AI-19
HPAC-3 CWR TEMPERATURE
YES YES
ANALOG OUTPUT
AO-1 BYPASS VALVE NO YES
AO-2 CCC-1 FAN A SPEED NO YES
AO-3 CCC-1 FAN B SPEED NO YES
AO-4
P-1 PUMP SPEED
NO YES
AO-5
P-2 PUMP SPEED
NO YES
AO-6
MINIMUM FLOW BYPASS VALVE
NO YES
BINARY INPUT
BI-1 CCC-1 SPRAY PUMP STATUS NO NO
BI-2 CCC-2 SPRAY PUMP STATUS NO NO
BI-3 CCC-1 SPRAY VIBRATION SWITCH NO NO
BI-4 CCC-2 SPRAY VIBRATION SWITCH NO NO
BI-5 CCC-1 FAN A STATUS NO YES
BI-6 CCC-1 FAN A ALARM NO NO
BI-7 CCC-1 FAN B STATUS NO YES
BI-8 CCC-1 FAN B ALARM NO NO
BI-9 NO YES
BI-10 NO NO
BI-11 NO YES
BI-12 NO NO
BI-13 NO NO
BI-14 NO NO
BI-15 NO NO
BI-16 NO NO
BI-17 MPAC-1 STATUS OFF/ON NO NO
BI-18 MPAC-1 STATUS OFF/ON NO NO
BI-19 MPAC-1 STATUS OFF/ON NO NO
BINARY OUTPUT
BO-1 CCC-1 SHUTOFF VALVE NO YES
BO-2 CCC-2 SHUTOFF VALVE NO YES
BO-3 CCC-1 FAN A ENABLE/DISABLE NO YES
BO-4 CCC-1 FAN B ENABLE/DISABLE NO YES
BO-5
CCC-1 SPRAY PUMP START/STOP
NO YES
BO-6
CCC-2 SPRAY PUMP START/STOP
NO YES
BO-7
P-1 PUMP ENABLE/DISABLE
NO YES
BO-8
P-2 PUMP ENABLE/DISABLE
NO YES
BO-9
MPAC-1 SHUTOFF VALVE
NO YES
BO-10
MPAC-2 SHUTOFF VALVE
NO YES
BO-11
MPAC-3 SHUTOFF VALVE
NO YES
BO-12
MPAC-4 SHUTOFF VALVE
NO YES
BO-13
HPAC-1 SHUTOFF VALVE
NO YES
BO-14
HPAC-2 SHUTOFF VALVE
NO YES
BO-15
HPAC-3 SHUTOFF VALVE
NO YES
BI-20 MPAC-1 STATUS OFF/ON NO NO
BI-21 HPAC-1 STATUS OFF/ON NO NO
BI-22 HPAC-2 STATUS OFF/ON NO NO
BI-23 HPAC-3 STATUS OFF/ON NO NO
P-1 PUMP STATUS
CCC-2 FAN A STATUS
CCC-2 FAN A ALARM
CCC-2 FAN B STATUS
CCC-2 FAN B ALARM
P-1 PUMP ALARM
P-2 PUMP STATUS
P-2 PUMP ALARM
AO-7
AO-8
CCC-2 FAN A SPEED
CCC-2 FAN B SPEED
AI-20 YES YES
AI-21 YES YES
CCC-2 FAN A SPEED
CCC-2 FAN B SPEED
BO-16
BO-17
CCC-2 FAN A ENABLE/DISABLE
CCC-2 FAN B ENABLE/DISABLE
NO YES
NO YES
NO YES
NO YES
CONDENSER WATER SYSTEM POINTS LIST
MARK DESCRIPTION ALARM TREND
COMPRESSED AIR
SYSTEM
EQUIPMENT BID
OPTION
CONDENSER WATER SYSTEM
INSTALL DDC HARDWARE TO PERFORM THIS SEQUENCE OF OPERATION AND TO PROVIDE INPUTS AND OUTPUTS AS SPECIFIED AND SHOWN ON THE POINTS SCHEDULE. UNLESS OTHERWISE SPECIFIED, ALL MODULATING CONTROL MUST BE PROPORTIONAL-INTEGRAL (PI) CONTROL.
SYSTEM ENABLE AND LOOP ENABLE.
CONDENSER WATER MODE
WHILE THE CWS TEMPERATURE (CWR-T) IS BELOW THE LOW LIMIT SETPOINT (CWS-T-LL) DISABLE ALL CONTROL LOOPS AND THE CLOSED- CIRCUIT COOLERS DO NOT RUN. WHEN ZN-T RISES ABOVE ZN-T-HL OPEN THE BYPASS VALVE AND ENABLE THE CLOSED-CIRCUIT COOLERS
(SYS-ENA). SEE BELOW FOR PUMP CONTROL.
CONDENSER WATER CONTROL
WHEN THE LOOP TEMPERATURE IS BELOW THE LOW LIMIT SETPOINT (ZN-T-LL) AS SENSED BY AI-1 THE BYPASS VALVE MUST OPEN AND CONDENSER WATER WILL CIRCULATE WITHIN THE BUILDING. ON A RISE IN CWR TEMPERATURE ABOVE THE LOW LIMIT SETPOINT (CWR-T- LL) THE DDC MUST OPEN THE LEAD CLOSED CIRCUIT COOLER CONTROL AND THEN MODULATE THE BYPASS VALVE TO MAINTAIN CWR TEMPERATURE (BEFORE THE PUMPS) SETPOINT (CWR-T-HL) AS SENSED BY AI-6. ONCE THE BYPASS VALVE REACHES 100% OPEN THE HIGH LIMIT SETPOINT MUST BE RESET TO THE HIGH LIMIT RESET SETPOINT (CWR-T-HLR 90 DEGREES F). ON A RISE IN CWR ABOVE THE HIGH LIMIT SETPOINT (CWR-T-HLR) MINUS 4 DEGREE DEADBAND THE SPRAY PUMP ON THE LEAD CLOSED CIRCUIT COOLER MUST BE ENERGIZED.
ON A CONTINUED RISE IN CWR TEMPERATURE ABOVE THE HIGH LIMIT RESET SETPOINT PLUS 2 DEGREES THE FANS MUST BE ENERGIZED AND MUST MODULATE TO CONTROL CWR TO THE HIGH LIMIT RESET SETPOINT (CWR-T-HLR). ON A FALL IN CWR THE REVERSE MUST
OCCUR.
PUMP CONTROL
THE DDC MUST MONITOR ALL THE AIR COMPRESSORS (MEDIUM AND HIGH PRESSURE) AND IF NONE OF THE COMPRESSORS ARE ENABLED THE LEAD AND LAG CONDENSER WATER PUMPS MUST BE OFF, THE MINIMUM BYPASS VALVE MUST BE OPEN, THE LEAD AND LAG CLOSED CIRCUIT COOLERS MUST BE DE-ENERGIZED, THE LEAD AND LAG SHUTOFF VALVES MUST BE CLOSED.
IF ANY NUMBER OF THE AIR COMPRESSORS ARE ENABLED, THE DDC MUST ENERGIZE THE LEAD CONDENSER WATER PUMP AND OPEN THE ASSOCIATED AIR COMPRESSOR SHUT OFF VALVE. THE MINIMUM FLOW BYPASS VALVE MUST SLOWLY CLOSE AND THE LEAD CONDENSER WATER PUMP MUST MODULATE SPEED TO MEET THE REQUIRED WATER FLOW OF THE AIR COMPRESSOR AS INDICATED IN THE SCHEDULE
BELOW:
1. (1) HIGH PRESSURE AC 66 GPM
2. (1) MEDIUM PRESSURE AC 56.4 GPM
3. (1) HIGH AND (1) MEDIUM PRESSURE AC 122.4 GPM
4. (1) HIGH AND (2) MEDIUM PRESSURE AC 178.8 GPM
5. (1) HIGH AND (3) MEDIUM PRESSURE AC 235.2 GPM
6. (2) HIGH AND (0) MEDIUM PRESSURE AC 132 GPM
7. (2) HIGH AND (1) MEDIUM PRESSURE AC 188.4 GPM
8. (2) HIGH AND (2) MEDIUM PRESSURE AC 244.8 GPM
9. (2) HIGH AND (3) MEDIUM PRESSURE AC 301.2 GPM
WHEN ALL THE COMPRESSORS TURN OFF THE CONDENSER WATER PUMP SPEED WILL RAMP DOWN TO MINIMUM SPEED AND THE MINIMUM FLOW BYPASS VALVE MUST MODULATE TO MAINTAIN MINIMUM FLOW. THE CONDENSER WATER PUMPS MUST REMAIN ON FOR 15 MINUTES
(ADJUSTABLE).
FAILURE MODE
IN THE EVENT THAT THE LEAD CLOSED CIRCUIT COOLER OR THE LEAD CONDENSER WATER PUMP FAILS THAT EQUIPMENT WILL BE DE- ENERGIZED AND THE STANDBY PUMP WILL BE ENERGIZED. THE DDC MUST ALTERNATE THE LEAD AND LAG EQUIPMENT BASED ON A
WEEKLY SCHEDULE AND RUNTIME.
ALARMS
HIGH CWR TEMPERATURE (SETPOINT + 3°F FOR 15 MIN)
LOW CWR TEMPERATURE (SETPOINT - 3°F FOR 15 MIN)
FAILURE OF THE LEAD CLOSED CIRCUIT COOLER
FAILURE OF THE LEAD CONDENSER WATER PUMP
HIGH CWR TEMPERATURE ON ANY ONE OF THE AIR COMPRESSORS (110 DEGREES OR HIGHER)
SETPOINTS
LOW LIMIT SETPOINT (CWR-T-LL), AS SENSED BY POINT AI-6 MAIN CWR TEMPERATURE: 55°F (ADJUSTABLE) HIGH LIMIT SETPOINT (CWR-T-HL), AS SENSED BY POINT AI-6 MAIN CWR TEMPERATURE: 80°F (ADJUSTABLE)
HIGH LIMIT RESET SETPOINT (CWR-T-HLR): 90°F (ADJUSTABLE)
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:0
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AM703
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
M E
C H
A N
IC
A
L C
O N
TR
O
LS
S
H E
E T
O
F
CMG
12829445
DKH CPM
1614696
NOT TO SCALEB4
CONDENSER WATER CONTROLS
B
ID
O
P
TI
O N
S 9/
/2
D K
H
UP
GOVERNMENT FURNISHED/GOVERNMENT
INSTALLED NITROGEN TANKS AND SUPPORT
SYSTEM
PUMP CONTROL PANEL
SAMPLING AND TESTING STATION
GOVERNMENT
FURNISHED/GOVERNMENT
INSTALLED PRIMARY
DEMINERALIZER TRAILERS
(TYP. OF 2)
FIRE PUMP
USB1
FRESH WATER
PUMP ROOM
USB2
EQUIPMENT
YARD
USB0
PURE WATER
ROOM
USB3
A1
AP313
A3
AP310
A1
AP314
A1
AP311
C1
AP311
A1
AP310
AP116
A3
AP116
A1
AP115
A1
AP114
A1
B1
AP303
A3
AP314
C1
AP313
A1
AP312
A1
AP315
PROVIDE 2" CAM LOCK CONNECTION FOR PURE WATER
TANKER CONNECTION
2"ø PWS
2"ø PWS
WORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
1. REFER TO DRAWING AP001 FOR PLUMBING LEGEND, ABBREVIATIONS AND
NOTES.
2. REFER TO DRAWING AP701 FOR CONTROL LEGEND, ABBREVIATIONS, AND
NOTES.
GENERAL NOTES
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:2
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP111
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G E
N
LA
R G
E D
P
LA
N S
P
U R
E W
A
TE
R
SAS
12829459
DKH JLL
1614696
1/4" = 1'-0" A1
USB - PROCESS PLUMBING ENLARGED PLANS - PURE WATER
PLAN
NORTH
2' 4' 8'0'
PLAN
NORTH
T-001 T-002
PWP-001
PWP-002
FDM-001
FDM-002
1. TERMINATE NITROGEN TUBING WITH THREADED CAP AT 5 FT
ABOVE GRADE.
2. FINAL DEMINARALIZER UNITS. REFERENCE SPECIFICATION
SECTION 43 33 00.
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER BID
OPTION
WAR-1
WAR-2
DAR-1
DAR-3
DAR-5
DAR-2
DAR-4
MPAP-1 MPAP-2 MPAP-3 MPAP-4
3"ø MPCA 3"ø MPCA 3"ø MPCA 3"ø MPCA
6"ø MPCA
6"ø MPCA
6"ø MPCA
6"ø MPCA
6"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
6"ø MPCA 6"ø MPCA 6"ø MPCA 6"ø MPCA
6"ø MPCA
6"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
4"ø MPCA
6"ø MPCA
3"ø MPCA3"ø MPCA
3"ø MPCA
3"ø MPCA
3"ø MPCA
3"ø MPCA
CS-3
CS-4
CS-6
2"ø PWS
CS-1
CS-2
2"ø PWR
2"ø PWR 2"ø PWS
4"ø MPCA
MPAC-1 MPAC-2 MPAC-3 MPAC-4
A1
AP303
B2
AP303
MEDIUM
PRESSURE AIR
ROOM
USB4
PIPE ANCHOR
(TYP.)
PIPE GUIDE
(TYP.)
PIPE ANCHOR
(TYP.)
3"ø MPCA
3"ø MPCA
CS-5
A2
AP302
PROVIDE MANUFACTURER'S
RECOMMENDED CLEARANCES
FOR MAINTENANCE (TYP)
6"ø MPCA
2"ø PWS
2"ø PWS
2"ø PWS
PIPE ANCHOR
(TYP.) BID OPTION
BID OPTION
BID OPTION
BID OPTION
BID OPTION
WORK NOTES
KEYPLAN
UTILITY SERVICES
BUILDING (USB)
GATEHOUSE
GUARD BOOTH
1. REFER TO DRAWING AP001 FOR PLUMBING LEGEND, ABBREVIATIONS AND
NOTES.
2. REFER TO DRAWING AP701 FOR CONTROL LEGEND, ABBREVIATIONS, AND
NOTES.
GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:3
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP112
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G E
N
LA
R G
E D
P
LA
N S
M
P C
A
CMG
12829460
DKH JLL
1614696
1/4" = 1'-0" A1
USB - PROCESS PLUMBING ENLARGED PLANS - MPCA
6 SEE MECHANICAL SUPPLY UTILITIES - AREA 103 SHEET MS103 FOR
CONTINUATION.
27 PROCESS CONTROL PANEL 120V 1 PH.
PLAN
NORTH
2' 4' 8'0'
PLAN
NORTH
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER BID
OPTION
A
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
SP-1
1 1/2"ø SS
3"ø SS
1/2"ø HPCA
2"ø PWS
2"ø PWS
LOCATE DRAIN
AS LOW AS POSSIBLE
IN TRENCH
DISCHARGE 3"⌀ SS
INTO SUMP PIT
MEDIUM
PRESSURE AIR
ROOM
USB4
6"ø MPCA
SPLASH BLOCK
FOR SP-1
DISCHARGE
(TYP.)
FLANGED CONNECTION
TRANSITION FROM METAL PIPE
IN USB TO HDPE PIPE ON PIER
TRENCH DRAIN
VALVE (NORMALLY
CLOSED) OPEN TO
DRAIN TRENCH
PROVIDE SHUTOFF
VALVE IN ALL SERVICES
IN ACCESSIBLE LOCATION
IN PIT
2"ø PWR
8"ø DCW
A2
AP302
BID OPTION ABOVE
SHUTOFF VALVE
BID OPTION ABOVE
SHUTOFF VALVE
2"ø PWS
COPRESSED AIR
SYSTEM EQUIPMENT
BID OPTION
ALL MPCA, HPCA AND
PW PIPING INSIDE
BUILDING ABOVE
SHUTOFF VALVES
SUMP
PURE WATER BID
OPTION
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
3"ø DCW
8"ø DCW
2"ø SS
FD-1
PRESSURE
GAGE 0-100 PSIG
2"ø DCW
FIRE PUMP
USB1
8"ø DCW
SEE CIVIL SHEET CU-104
FOR CONTINUATION
BFP-1
DMW-1
1. REFER TO DRAWING AP001 FOR PLUMBING LEGEND, ABBREVIATIONS AND
NOTES.
2. REFER TO DRAWING AP701 FOR CONTROL LEGEND, ABBREVIATIONS, AND
NOTES.
GENERAL NOTES
WORK NOTES
FIRST FLOOR
10' - 3"
ROOF
26' - 11"
USB FLOOR LEVEL
10' - 3"
ROOF
26' - 11"
A1
AP302
SP-1 17
3"ø SS
1 1/2"ø SS
2"ø PWS
PROVIDE SHUTOFF
VALVE IN ALL SERVICES
IN ACCESSIBLE
LOCATION IN PIT
6"ø MPCA
2"ø PWR
2"ø PWS
8"ø DCW
8"ø FPW
DISCHARGE 3"⌀ SS
INTO SUMP PIT
2"ø PWR
COMPRESSED AIR
SYSTEM EQUIPMENT
BID OPTION
ALL MPCA, AND HPCA
PIPING INSIDE BUILDING
ABOVE SHUTOFF
VALVES
PURE
WATER BID
OPTION
2"ø PWS
BID OPTION
ABOVE
SHUTOFF
VALVE
2"ø PWS
PURE
WATER BID
OPTION
ABOVE
SHUTOFF
VALVE
2"ø PWS
PROVIDE 2" CAM
LOCK
CONNECTION
ABOVE SHUTOFF
VALVE
PURE WATER
BID OPTION
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:3
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP302
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P
LU
M B
IN
G
S E
C
TI
O N
S
CMG
12829468
DKH DKH
1614696
1/2" = 1'-0" (AP102)
A1
SECTION AT PIT - NORTH SOUTH
1/4" = 1'-0" (AP101)
B4
SECTION AT BFP
1' 2' 4'0'
2' 4' 8'0'
17 SEE PUMP SUMP DETAIL C1/AP500.
18 SEE WATER METER DETAIL C3/AP500.
26 SEE MAIN SERVICE DETAIL A1/AP501.
60 SEE HYDROSTATIC SEAL DETAIL A1/AM504.
1/2" = 1'-0" (AP102)
A2
SECTION AT PIT - EAST WEST
1' 2' 4'0'
B
ID
O
P
TI
O N
S 9/
/2
D K
H
28"
N1 N9 N2
N4
N5
M2
N6
N8
0°
90°
180°
270°
T-001
M1
REF. TAN. LINE
N6
N3
N7
PW-V-067
PW-V-069
PW-TI-004
/2
/4
10' - 0" ID
PW-LI-001
N9N1
N4 (BEHIND)
N5 M2
SAFETY HANDRAIL
AROUND PERIMETER
OF PLATFORM
N2
(BEHIND)
PW-V-061
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:3
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP505
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G D
E
TA
IL
S
P
U R
E W
A
TE
R H
O
LD
IN
G
T A
N K
D E
TA
IL
SAS
12829486
JWR JWR
1614696
NOT TO SCALEA3
PURE WATER HOLDING TANK - ENLARGED PLAN
GENERAL NOTES
1. ORIENTATION SHOWN IS FOR TANK T-001.
2. REFER TO SECTION 43 41 00 - PROCESS TANKS FOR TANK REQUIREMENTS.
NOT TO SCALEA1
PURE WATER HOLDING TANK - NORTH ELEVATION
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER
BID OPTION
0°
90°
180°
270°
N5
N1N2
N3
M1
N4
USB FINISH FLOOR
10' - 3"
24" FLANGE MANWAY
(M1)
N1
N4
N5 (BEHIND)
N3
N2 (BEHIND)
48" ID
/2
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:4
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP506
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G D
E
TA
IL
S
P
O
LI
S H
IN
G
D E
M
IN
E R
A
LI
Z E
R D
E
TA
IL
SAS
12829487
JWR JWR
1614696
NOT TO SCALEA3
POLISHING DEMINERALIZER - ENLARGED PLAN
NOT TO SCALEA1
POLISHING DEMINERALIZER - ELEVATION
GENERAL NOTES
1. ORIENTATION SHOWN IS FOR FDM-001/002.
2. REFER TO SECTION 43 33 00 - DEMINERALIZERS FOR POLISHING
DEMINERALIZER REQUIREMENTS.
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER
BID OPTION
BLOCK VALVE
WELDED TUBE ENDS
1/2"
1/2" TUBE x 1/4" TUBE
REDUCING UNION, 316L SS
1/4" FNPT x 1/4" TUBE
ADAPTER, 316L SS
1/4" OD x 0.035" WALL
316L SS SMLS TUBING,
DO NOT POCKET
PIPE
PRESSURE
DEVICE,
1/4" MNPT
HORIZONTAL PIPE RUN, REMOTE-MOUNT
BLOCK VALVE
WELDED TUBE ENDS
1/2"
1/2" TUBE x 1/4" TUBE
REDUCING UNION, 316L SS
1/4" FNPT x 1/4" TUBE
ADAPTER, 316L SS
1/4" OD x 0.035" WALL
316L SS SMLS TUBING,
DO NOT POCKET
PIPE
PRESSURE
DEVICE,
1/4" MNPT
VERTICAL PIPE RUN, REMOTE-MOUNT
BLOCK VALVE
WELDED TUBE ENDS
1/2"
1/2" TUBE x 1/4" FNPT
REDUCING ADAPTER, 316L SS
PIPE
PRESSURE
DEVICE,
1/4" MNPT
HORIZONTAL PIPE RUN, CLOSE-COUPLED
1/2" TUBE x 1/4" FNPT
REDUCING ADAPTER, 316L SS
PRESSURE
DEVICE,
1/4" MNPT
BLOCK VALVE
WELDED TUBE ENDS
1/2"
PIPE
VERTICAL PIPE RUN, CLOSE-COUPLED
BLOCK VALVE
WELD x SANITARY
CLAMP ENDS
1 1/2"
1/4" MNPT x 1/4" FNPT CAPILLARY
TUBE, SS ARMORED
1 1/2" FLUSH SANITARY
CLAMP x 1/4" FNPT
DIAPHRAGM SEAL, 316L
SS, SILICONE FILL
PIPE
PRESSURE
DEVICE,
1/4" MNPT
HORIZONTAL PIPE RUN, REMOTE-MOUNT VERTICAL PIPE RUN, REMOTE-MOUNT
HORIZONTAL PIPE RUN, CLOSE-COUPLED VERTICAL PIPE RUN, CLOSE-COUPLED
BLOCK VALVE
WELD x SANITARY CLAMP ENDS
1 1/2"
1/4" MNPT x 1/4" FNPT CAPILLARY
TUBE, SS ARMORED
1 1/2" FLUSH SANITARY
CLAMP x 1/4" FNPT
DIAPHRAGM SEAL, 316L
SS, SILICONE FILL
PRESSURE
DEVICE,
1/4" MNPT
PIPE
BLOCK VALVE
WELD x SANITARY
CLAMP ENDS
1 1/2"
1 1/2" FLUSH SANITARY
CLAMP x 1/4" FNPT
DIAPHRAGM SEAL, 316L
SS, SILICONE FILL
PIPE
PRESSURE
DEVICE,
1/4" MNPT
1 1/2"
PRESSURE
DEVICE,
1/4" MNPT
BLOCK VALVE
WELD x SANITARY CLAMP ENDS
1 1/2" FLUSH SANITARY
CLAMP x 1/4" FNPT
DIAPHRAGM SEAL, 316L
SS, SILICONE FILL
PIPE
2" SANITARY CLAMP x 3/4" FNPT
THERMOMETER CAP, 316L SS
CE
.0
0°
CONDUCTIVITY PROBE
3/4" MNPT
MANUFACTURER
CABLE TO
CONTROLLER
2" PIPE TEE, WELDED
(RUNS) x SANITARY
CLAMP (BRANCH)
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:4
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP507
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G D
E
TA
IL
S
P
U R
E W
A
TE
R
IN
S
TR
U
M E
N
TA
TI
O
N D
E
TA
IL
S
SAS
12829488
JWR JWR
1614696
NOT TO SCALE
B1
PRESSURE TAP FOR PRESSURE GAUGES, DIFFERENTIAL PRESSURE GAUGES, OR PRESSURE
SWITCHES; NON-TYPE 1 CLEAN AREAS
NOT TO SCALE
B3
PRESSURE TAP FOR PRESSURE GAUGES, DIFFERENTIAL PRESSURE GAUGES, OR PRESSURE
SWITCHES; TYPE 1 CLEAN AREAS
NOT TO SCALE
A1
CONDUCTIVITY PROBE; TYPE 1 CLEAN AND NO-TYPE 1 CLEAN AREAS
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER
BID OPTION
B
W
POWER ON
A
M1 NO FLOW TRIP
SR1
SR1
TD1
M1
STARTM1
STOP
TD1CR1
NORMAL
SS1
BYPASS
xo
M1 M1
OL1
TD1
M1FSL1
N/-L/+
PW-FSL-005
10s
ON DELAY
R
M1 RUNNING
A
M1 OVERLOAD
M1
OL1
A
M2 NO FLOW TRIP
SR2
SR2
TD2
M2
STARTM2
STOP
TD2CR1
NORMAL
SS2
BYPASS
xo
M2 M2
OL2
TD2
M2FSL2
N/-L/+
PW-FSL-006
10s
ON
DELAY
R
M2 RUNNING
A
M2 OVERLOAD
M2
OL2
PSL
CR1
G
WATER AVAILABLE
PW-PSL-005
DS1
30A/3P
MCP1 M1 OL1
MCP2 M2 OL2
CPT1
480V:120V
480V 3ɸ 30A
BR
OR
YL
GN
BR
OR
YL
GN
BR
OR
YL
GN
BK WH
RD
GN
BK WH
RD
GN
RDBK
COMPONENT SPECIFICATION
COMPONENT SPECIFICATION
ENCLOSURE
NEMA 4, QUARTER-TURN LATCH WITH
HANDLE, FLANGE-MOUNT DISCONNECT,
PIANO HINGE, BACK PANEL, PADLOCK
HASP, DIMENSIONS AS REQUIRED
DS1
600-VAC, 30A, 3P, 35-kA, NON-FUSED OR 'J'
CLASS FUSES, LOAD BREAK, VISIBLE
BLADES, FLANGE-MOUNT HANDLE RATED
NEMA 4, LINE-SIDE TERMINAL COVERS
MCP1/2, M1/2,
OL1/2
NEMA SIZE 1 FVNR COMBINATION MOTOR
STARTER, MAGNETIC-ONLY MOTOR
CIRCUIT PROTECTOR, 120-VAC/60-Hz COIL, QTY 4 AUX CONTACTS, SELF-POWERED
ELECTRONIC OVERLOAD RELAY
CPT1
240x480V-120x240V, 60-Hz, SIZE AS
REQUIRED, PRIMARY AND SECONDARY
FUSES
CR1, SR1/2
120-VAC/60-Hz COIL, DPDT, CONTROL
RELAY, CONTACT RATING AS REQUIRED
TD1/2
120-VAC/60-Hz COIL, DPDT, ON-DELAY
TIMER RELAY, CONTACT RATING AS
REQUIRED
SS1/2
2-POS MAINTAINED SELECTOR SWITCH,
30.5mm, NEMA 4, BLACK OPERATOR, HEAVY-DUTY, CONTACT RATING AS
REQUIRED
PILOT LIGHTS
120-VAC, LED, 30.5mm, NEMA 4, COLORS
AS INDICATED
PUSH BUTTONS
MOMENTARY PUSH BUTTON, 30.5mm, NEMA 4, BLACK OPERATOR, HEAVY-DUTY, CONTACT RATING AS REQUIRED
ASSEMBLY UL-508A
PWP-001
7.5 HP
3600 RPM
11 FLA
PWP-002
7.5 HP
3600 RPM
11 FLA
PANEL FRONT
PUMP A PUMP B
R
START BYPASS NORMAL
STOP RUNNING
A
OVERLOAD
A
NO
FLOW
G
WATER AVAILABLE
W
POWER
ON
PUMP A
ENERGIZE
ON HIGH
CONDUCTIVITY
ANALYZER
L/+ N/-
AUTO
CLOSE
OPEN
R
VALVE OPEN
oox xoo
CONTROL STATION
20A/1P
ENERGIZE
TO OPEN
SOLENOID VALVE
BK
BK
RD
BU
BU
WH
BU
120-VAC FROM 20A SUPPLY
L/+ N/-
SUPPLY
CIRCUIT
CONTROL
STATION
ANALYZER
SOLENOID
VALVE
EMLV-2 PW-HS-001 PW-CIT-001 PW-V-005
EMLV-7 PW-HS-002 PW-CIT-002 PW-V-041
TABLE OF DEVICE TAGS
WH
WH
AUTO
CLOSE
OPEN
R
VALVE OPEN
oox xoo
CONTROL STATION
20A/1P
ENERGIZE
ON HIGH
LEVEL
LEVEL SWITCH
ENERGIZE
TO OPEN
SOLENOID VALVE
BK
BK
RD
BU
BU
WH
WH
BU
120-VAC FROM 20A SUPPLY
L/+ N/-
SUPPLY
CIRCUIT
CONTROL
STATION
LEVEL
SWITCH
SOLENOID
VALVE
EMLV-11 PW-HS-003 PW-LSH-001 PW-V-057
EMLV-16 PW-HS-004 PW-LSH-002 PW-V-060
TABLE OF DEVICE TAGS
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:4
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP508
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G D
E
TA
IL
S
P
U R
E W
A
TE
R
S C
H E
M A
TI
C
S
SAS
12829489
JWR JWR
1614696
NOT TO SCALE
A3
PURE WATER DISTRIBUTION PUMPS SCHEMATIC AND PANEL
NOT TO SCALE (AP320)
A1
HIGH CONDUCTIVITY PROTECTION SOLENOID SCEMATIC AND WIRING
NOT TO SCALE (AP322)
C1
HIGH TANK LEVEL PROTECTION SOLENOID SCHEMATIC AND WIRING
B
ID
O
P
TI
O N
S 9/
/2
D K
H
PURE WATER
BID OPTION
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:5
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP603
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G S
C H
E D
U
LE
S
S H
E E
T
O F
CMG
12829492
DKH JLL
1614696
MEDIUM PRESSURE AIR RECIEVERS
MARK LOCATION SERVICE TYPE CAPACITY (GAL)
WEIGHT
(LBS.)
APPROX DIAMETER
(IN)
APPROX HEIGHT
(IN.) INLET SIZE (IN.) OUTLET (IN.) NOTES
DAR-1 HIGH PRESSURE AIR ROOM USB5 DRY MEDIUM PRESSURE CA VERTICAL 1060 1723 40 150 4 4
DAR-2 MEDIUM PRESSURE AIR ROOM USB4 DRY MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
DAR-3 MEDIUM PRESSURE AIR ROOM USB4 DRY MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
DAR-4 MEDIUM PRESSURE AIR ROOM USB4 DRY MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
DAR-5 MEDIUM PRESSURE AIR ROOM USB4 DRY MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
WAR-1 MEDIUM PRESSURE AIR ROOM USB4 WET MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
WAR-2 MEDIUM PRESSURE AIR ROOM USB4 WET MEDIUM PRESSURE CA VERTICAL 1060 1732 40 150 4 4
MEDIUM PRESSURE AIR DRYERS/PURIFIERS
MARK LOCATION SERVICE TYPE
INLET FLOW
(SCFM)
OUTLET
(SCFM)
INLET/OUTLET
SIZE (IN)
WEIGHT
(LBS)
ELECTRICAL DATA
NOTESFLA VOLTAGE PHASE HERTZ
MPAP-1 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 366 305 2" 1405 5 120 1 60
MPAP-2 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 366 305 2" 1405 5 120 1 60
MPAP-3 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 366 305 2" 1405 5 120 1 60
MPAP-4 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 366 305 2" 1405 5 120 1 60
MEDIUM PRESSURE CONDENSATE DRAIN
MARK LOCATION SERVICE TYPE INLET (IN.) OUTLET (IN.)
PRESSURE
RATING (PSIG)
ELECTRICAL DATA
NOTESFLA VOLTAGE PHASE HERTZ
CD-1 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 1/2 3/8 230 1.0 120 1 60
CD-2 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA ZERO AIR LOSS 1/2 3/8 230 1.0 120 1 60
HIGH PRESSURE AIR COMPRESSOR
MARK LOCATION
COMPRESSOR COOLING SYSTEM
WEIGHT
(LBS)
ELECTRICAL
NOTESTYPE STAGES
STANDARD
CAPACITY
(SCFM)
MOUNTING
TYPE
MOTOR SIZE
(HP)
MOTOR
SPEED (RPM)
DRIVE
TYPE
TYPE OF
COOLING
HEAT
REJECTION
(MBH)
CONDENSER WATER
GYLCOL (%)
EWT (DEG
F) LWT (DEG F)
WATER FLOW
(GPM)
PRESS DROP (FT OF
HEAD) FLA MCA MOCP VOLTS PH HZ
HPAC-1 HIGH PRESSURE AIR ROOM USB5 RECIPROCATING FOUR 348 FLOOR 300 1750 DIRECT WATER 632 30 90 109 66.0 15 4500 359 448 800 460 3 60
HPAC-2 HIGH PRESSURE AIR ROOM USB5 RECIPROCATING FOUR 348 FLOOR 300 1750 DIRECT WATER 632 30 90 109 66.0 15 4500 359 448 800 460 3 60
HPAC-3 HIGH PRESSURE AIR ROOM USB5 RECIPROCATING FOUR 348 FLOOR 300 1750 DIRECT WATER 632 30 90 109 66.0 15 4500 350 448 800 460 3 60
MEDIUM PRESSURE AIR COMPRESSOR
MARK LOCATION
COMPRESSOR INTERNAL COOLING FAN COOLING SYSTEM
WEIGHT
(LBS)
ELECTRICAL
NOTESTYPE STAGES
STANDARD
CAPACITY (SCFM)
MOUNTING
TYPE
MOTOR
SIZE
(HP)
MOTOR
SPEED (RPM)
DRIVE
TYPE
AIRFLOW
(CFM)
ESP (IN.
WC)
MOTOR
HP
TYPE OF
COOLING
HEAT
REJECTION
(MBH)
CONDENSER WATER
GYLCOL (%)
EWT (DEG
F) LWT (DEG F)
WATER FLOW
(GPM)
PRESSURE DROP
(FT OF HEAD) FLA MCA MOCP VOLTS PH HZ
MPAC-1 MEDIUM PRESSURE AIR ROOM USB4 OIL LESS SCREW SINGLE 816 FLOOR 200 1750 DIRECT 2650 .3 .75 WATER 564 30 90 110 56.4 10.8 7825 249 311 350 460 3 60
MPAC-2 MEDIUM PRESSURE AIR ROOM USB4 OIL LESS SCREW SINGLE 816 FLOOR 200 1750 DIRECT 2650 .3 .75 WATER 564 30 90 110 56.4 10.8 7825 249 311 350 460 3 60
MPAC-3 MEDIUM PRESSURE AIR ROOM USB4 OIL LESS SCREW SINGLE 816 FLOOR 200 1750 DIRECT 2650 .3 .75 WATER 564 30 90 110 56.4 10.8 7825 249 311 350 460 3 60
MPAC-4 MEDIUM PRESSURE AIR ROOM USB4 OIL LESS SCREW SINGLE 816 FLOOR 200 1750 DIRECT 2650 .3 .75 WATER 564 30 90 110 56.4 10.8 7825 249 311 350 460 3 60
MEDIUM PRESSURE CONDENSATE SEPARATOR
MARK LOCATION SERVICE TYPE INLET (IN.) OUTLET (IN.)
PRESSURE
RATING (PSIG)
MAX CAPACITY
(CFM)
FILTER SERVICE
LIFE (HOURS)
OIL CARRY OVER
AT INSTALLATION
(PPM)
OIL CARRY OVER AT
FILTER END OF LIFE
(PPM) NOTES
CS-1 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
CS-2 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
CS-3 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
CS-4 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
CS-5 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
CS-6 MEDIUM PRESSURE AIR ROOM USB4 MEDIUM PRESSURE CA FILTER 1/2 3/4 150 2500 4000 5 20
B
ID
O
P
TI
O N
S 9/
/2
D K
H
COMPRESSED
AIR SYSTEM
EQUIPMENT
BID OPTION
1. PROVIDE WITH FLOOR MOUNTED STORAGE RACK WITH TANK STRAPS.
2. PROVIDE WITH TANK MANIFOLD, TANK VALVES, PRESSURE GAUGE, AND 1/2" CONNECTION.
NOTES:
AF-1, 2, 3, 4 - AIR FILTER, 900 CFM FLOW RATE, 0.5 MICRON RATING, 3" PORT CONNECTION, 98.5% FILTER RATING, COALESCER FILTER TYPE, DIE CAST ALUMINUM BOWL 290 PSI MAXIMUM OPERATING PRESSURE. PROVIDE WITH
AUTO DRAIN ACCESSORY.
PF-1, 2, 3, 4 - AIR FILTER, 900 CFM FLOW RATE, 0.5 MICRON RATING, 3" PORT CONNECTION, 98.5% FILTER RATING, COALESCER FILTER TYPE, DIE CAST ALUMINUM BOWL 290 PSI MAXIMUM OPERATING PRESSURE. PROVIDE WITH
AUTO DRAIN ACCESSORY.
MACD-1A, 1B, 2A, 2B, 3A, 3B, 4A, 4B - ZERO LOSS DRAIN, 232 PSIG PRESSURE RATING, 1/2" NPT
CD-1, 2 - ELECTRIC ZERO LOSS CONDENSATE DRAIN, 1/2" NPT INLET, 3/8" NPT OUTLET, 232 PSIG PRESSURE RATING, 115 VOLTS, 1 PHASE
WS-1, 2, 3, 4 - WATER SEPARATOR, 1695 SCFM, 1.0 PSIG PRESSURE DROP, 3" NPT, 22 LBS
EQUIPMENT SCHEDULE - MEDIUM PRESSURE
COMPRESSED AIR
HPCD-1A, 1B, 1C, 2A, 2B, 2C, 2D, 3A, 3B, 3C, 4A, 4B, 4C, 4D - HIGH PRESSURE CONDENSATE DRAIN, ZERO LOSS DRAIN, 232 PSIG PRESSURE RATING, 1/2" NPT
EQUIPMENT SCHEDULE - HIGH PRESSURE COMPRESSED
AIR
1. SYSTEM SHALL PROVIDE GRADE E BREATHING AIR
NOTES:
1. ALL WORK IS INCLUDED IN THE BASE BID UNLESS OTHERWISE NOTED HERE.
2. EQUIPMENT AND ACCESSORIES SHOWN WITHIN THE DASHED LINES ARE
INCLUDED IN THE IDENTIFIED BID OPTION.
BID OPTION GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
C I
C O
R E
H
A M
P T
O N
R O
A D
S N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
N O
R F
O L
K V
A
EJA
N A
V A
L S
T A
T
IO
N N
O R
F O
R
F O
L K
V
IR
G
IN
IA
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
P
LO
T T
E D
F
IL
E
N A
M E
DRAWFORM REVISION: 07 AUG 2018
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
DSN
WMS/IAS
GEOFFREY R. MOSS
DIRECTOR OF WARFARE REQUIREMENTS
SUBMARINE FORCES ATLANTIC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
03/05/2021
ALG
JAMES E. DONAHUE, R.A.
/1
/2
:1
:0
P
M C
R e v it P ro je c ts
\P
IE
R P
-1
-M
-U S
B D jli tt le jo h n .r v t
AP604
P -0
R
E P
L A
C E
S U
B M
A R
IN
E
P
IE
R
U S
B
P R
O C
E S
S P
LU
M
B
IN
G S
C H
E D
U
LE
S
S H
E E
T
O F
CMG
12829493
DKH JLL
1614696
HIGH PRESSURE AIR FILTERS
MARK LOCATION SERVICE TYPE
CAPACITY
(SCFM)
PRESSURE
RANGING (PSIG)
CONTAMINATE
REMOVAL (MICRON)
INLET/OUTLET
SIZE (IN.) WEIGHT (LBS) CONSTRUCTION NOTES
HPAF-1A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-1B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-2A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-2B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-3A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-3B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-4A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-4B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-5A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-5B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-6A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA PRE-FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HPAF-6B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA AFTER FILTER 150 5000 .01 1/2 12 316 STAINLESS STEEL
HIGH PRESSURE AIR RECIEVERS
MARK LOCATION SERVICE TYPE CAPACITY (GAL)
APPROX DIAMETER
(IN)
APPROX HEIGHT
(IN.) INLET SIZE (IN.) NOTES
HPR-1A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-1B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-1C HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-2A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-2B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-2C HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-3A HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-3B HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HPR-3C HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN VERTICAL 11 9 56 1/2 1,2
HIGH PRESSURE AIR DRYERS/PURIFIERS
MARK LOCATION SERVICE TYPE
CAPACITY
(SCFM)
PRESSURE
RANGE (PSIG)
OXYGEN CONTENT
TOTAL VOLATILE
HYDROCARBONS (PPM)
CARBON MONOXIDE
(PPM) ODOR
DEW POINT (DEGREES
F)
WATER VAPOR
CONTENT (PPM)
ELECTRICAL DATA
NOTESFLA VOLTAGE PHASE HERTZ
HPAP-1 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
HPAP-2 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
HPAP-3 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
HPAP-4 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
HPAP-5 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
HPAP-6 HIGH PRESSURE AIR ROOM USB5 HIGH PRESSURE CA TWIN TOWER DESSICANT 177 5000 20 - 22 25 10 NO NOTICEABLE -50 67 .5 120 1 60
PURE WATER PUMP SCHEDULE
MARK TYPE LOCATION SERVICE
DESIGN
CAPACITY
(GPM)
DESIGN PUMP
HEAD (TDH) % RISE TO SHUT-OFF
PUMP RUN-OUT FLOW
RATE
SUCTION SIZE
(IN)
DISCHARGE SIZE
(IN)
PUMP
EFFICIENCY (%)
ELECTRICAL DATA
REMARKS
MOTOR
SPEED (RPM)
MOTOR
SIZE (HP)
STARTER / DISCONNECT
PROVIDED BY
SPEED
CONTROL TYPE VOLTS PHASE HZ
PWP-001 HORIZONTAL
CENTRIFUGAL
PURE WATER ROOM USB3 PURE WATER DISTRIBUTION
- PIER
30 165 14% MIN FROM DESIGN TDH 124% OF RATED FLOW
(MIN)
1.5 1 21 3600 7.5 DIV 26 FIXED SPEED 460 3 60 ITT GOULDS LF3196 OR EQUAL; MUST MEET REQUIREMENTS IN SECTION 01 46 00.00 -
CLEANLINESS CONTROL
PWP-002 HORIZONTAL
CENTRIFUGAL
PURE WATER ROOM USB3 PURE WATER DISTRIBUTION
- PIER
30 165 14% MIN FROM DESIGN TDH 124% OF RATED FLOW
(MIN)
1.5 1 21 3600 7.5 DIV 26 FIXED SPEED 460 3 60 ITT…