1601000 J Utility Management.pdf
PDF 237 KB Posted
- Solicitation number
- N6247025R0020
About this file
This document is Section J, an attachment containing multiple supplementary documents for a federal utility management contract. It includes nine attachments covering definitions, references, historical workloads, utility map attributes, outage reporting requirements, asset tagging guidance, specification attributes, asset inventory, and meter group/condition rating guidance.
Key details include specific requirements for utility asset management such as detailed tagging protocols for utility assets (using synthetic, durable 2.43x3 inch labels), comprehensive asset classification with required specification fields for various equipment types, and a condition rating system using a Degradation Index ranging from 0 (fully functional) to 4 (extensively deteriorated). The historical utility service order workload shows 120 emergency and 1,062 routine electrical service orders, 278 emergency and 844 routine wastewater service orders, and 66 emergency and 130 routine water service orders annually. Referencing documents include various Unified Facilities Criteria (UFC) standards, Navy facilities management manuals, and cybersecurity guidelines. Most detailed attachment information is contained in referenced Excel files not included in this document.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION J
DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
TABLE OF CONTENTS
ATTACHMENT
NUMBER
ATTACHMENT TITLE
J-1601000-01 Definitions And Acronyms J-1601000-02 References And Technical Documents J-1601000-03 Historical Utility Service Order Workloads J-1601000-04 Attributes Required for Utility Maps J-1601000-05 Utility Outage Reporting Requirements J-1601000-06 Utility Asset Tagging Guidance J-1601000-07 Specification Attributes J-1601000-08 Utility Asset Inventory J-1601000-09 UEM-DI Meter Group And Direct Condition Rating Guidance
ATTACHMENT J-1601000-01
DEFINITIONS AND ACRONYMS
Definition/Acronym Description Assessment A general term referring to either a survey or inspection of a facility to determine condition.
Asset A general term used to refer to an item, such as a component, system, building or facility, that is managed by an automated data management program, e.g., UICAP.
Business Process Management System (BPMS)
A web-based tool that provides a systematic method for the management of business processes, common practices, and process quality improvements that produce and support the most efficient and effective delivery of NAVFAC’s products and services.
Customer Average Interruption Duration Index
(CAIDI)
Customer average interruption duration in minutes per year. The electrical reliability benchmark is 60 minutes per year.
Facility Related Control System
Facility-related control systems are a subset of control systems that are used to monitor and control equipment and systems related to DoD real property facilities (e.g., building control systems, utility control systems, electronic security systems, and fire and life safety systems).
Industrial Control System Most specifically a control system which controls an industrial process.
Sometimes also used to refer to other types of control systems, particularly utility control systems such as electrical, gas, or water distribution systems. ICS includes PLCs, field sensors, field actuators, meters, transducers, relays, protection relays, contactors, electrical current, potential transformers, etc.
Integrated Maintenance Plan IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness.
In-house Performed by Government employees.
Inspection A rigorous, detailed assessment of the condition of a facility performed to generate a fundable scope and cost estimate for prioritization and funding of maintenance and repair.
Job or Work Order An authorization for work that requires planning and estimating and has an individual line of accounting for financial and performance evaluation.
Planned Utility Outage A Planned Utility Outage is a scheduled utility service interruption at or before the utility service point affecting at least one occupied facility, pier, or berth. The Service/Trouble Desk personnel gather pertinent information from customers prior to the outage event and from the field after the event, and then they record the outage event in the Maximo™ Work Order Outage Log. These events require planning and coordination with customers at a minimum of 10 days for routine (and 3 to 4 days for urgent requests) in advance of the outage. Planned utility outages that occur without notification to proceed (after a request to defer the outage cannot be met) are reclassified as unplanned utility outages. Deferred outages are reserved for critical facilities that would sustain severe mission impact if an outage were to occur.
Reportable Utility Outage A reportable utility outage is defined as a loss of NAVFAC delivered utility services to an occupied facility, pier or berth that is greater than 5 minutes in duration. Utility system failures that do not cause a disruption of services to occupied facilities, piers, or berths are not considered an outage.
Supervisory Control And Data Acquisition (SCADA)
A version of telemetry commonly used in wide-area industrial applications, such as electrical power generation and distribution and water distribution, which includes supervisory control of remote stations as well as data acquisition from those stations over a bidirectional communications link.
System Average Interruption Duration Index (SAIDI)
SAIDI is defined as the average duration of interruptions per consumer during the year. It is the ratio of the annual duration of interruptions (sustained) to the number of consumers. If duration is specified in minutes, SAIDI is given as consumer minutes. [SAIDI = Total duration of sustained interruptions in a year / Total number of consumers]. SAIDI is an Installation level metric that is the yearly average outage duration for the average customer served at a particular Installation.
The electrical reliability benchmark is 120 minutes per year.
System Average Interruption Frequency Index (SAIFI)
SAIFI is defined as the average number of sustained interruptions per consumer during the year. It is the ratio of the annual number of interruptions to the number of consumers. [SAIFI = Total number of sustained interruptions in a year / Total number of consumers]. SAIFI is an Installation level metric that is the yearly average number of interruption occurrences experienced by a customer served at a particular Installation. The electrical reliability benchmark is two (02) occurrence per year.
Service Point The service point is the point of connection between the serving utility and the facility and is also the ’Point of Demarcation’ where ownership changes. This is the transition between NAVFAC UEM and customer funding for maintenance and repair services on equipment.
Unplanned Utility Outage An Unplanned Utility Outage is an unscheduled utility service interruption at or before the utility service point affecting at least one occupied facility, pier, or berth, and lasting longer than 5 minutes in duration. Service/Trouble Desk personnel enter information from the field about the incident, response, and the repair in a MAXIMO Work Order Outage Log. Facilities experiencing an unplanned utility outage greater than five minutes should contact their Building Monitor or Facility Coordinator who can report the outage to the Service/Trouble Desk.
Utility Investment Strategy The Contractor shall engage in the Navy’s utility investment strategy to provide efficient and effective utilites that directly support warfighter readiness at the lowest possible life cycle cost, while maintaining fully functional capabilities.
Utilities Maintenance Management
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of utility maintenance operations to support the CNO/NAVFAC utilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
Utility Service Interruption A Momentary Utility Service Interruptions of five minutes or less in duration are not considered a long duration utility outage, and therefore not required to be recorded in the MAXIMO system. NAVFAC Utilities does not provide nor guarantee uninterruptible utility services.
Utilities Infrastructure Condition Assessment Program
(UICAP)
A Navy automated data management program that utilizes historical asset lifecycle data and a structured assessment process to evaluate the condition of utility systems and their components.
AC Alternating Current (electricity) AIS Automated Information System AMI Advanced Metering Infrastructure ANSI American National Standards Institute ArcGIS Geographic Information System (developed by ESRI) BCS Building Control System CAIDI Customer Average Interruption Duration Index CIRCUITS Centralized and Integrated Reporting for the Comprehensive Utilities DI Degradation Index
DDC Direct Digital Control Systems ESRI Environmental Systems Research Institute FPOC Facility Point of Connection FRCS Facility Related Control System GIG Global Information Grid GIS Geospatial Information System ICS Industrial Control Systems IMP Integrated Maintenance Program iNFADS Internet Navy Facilities Assets Data Store SAIDI System Average Interruption Duration Index SAIFI System Average Frequency Interruption Index SCADA Supervisory Control And Data Acquisition STIG Security Technical Implementation Guide WIB Work Induction Board WIS Work Induction System UEM Utilities and Energy Management UEM-DI Utilities and Energy Management Degradation Index UICAP Utility Infrastructure Condition Assessment COF Consequence of Failure LOF Likelihood of Failure UEM Utility Energy Management UFC Unified Facilities Criteria UMIG Utilities Mission Integration Group UCS Utility Control System
ATTACHMENT 1601000-02
REFERENCES AND TECHNICAL DOCUMENTS
Reference Title UFC 3-540-01 Engine-Driven Generator Systems For Backup Power Applications UFC 3-230-01 Water Storage, Distribution, And Transmission UFC 3-501-01 Electrical Engineering UFC 3-550-01 Exterior Electrical Power Distribution MO-221 Utilities Metering MO-321 Facilities Management MO-209 Engineering Criteria UFC 3-501-01 Electrical Engineering UFC 3-550-01 Exterior Electrical Power Distribution UFC 3-560-01 Electrical Safety O&M UFC 4-010-06 Cybersecurity FRCS SECNAV M-5239.3 Department of the Navy Cybersecurity Manual AR 420-49 Heating, Energy Selection and Fuel Storage, Distribution, and Dispensing
Systems NAVFAC P-602 3 Pillars of Energy Security NAVFAC P-603 Utilities Infrastructure Management Manual
ATTACHMENT J-1601000-03
ANNUAL HISTORICAL UTILITY SERVICE ORDER WORKLOAD
Service Order
Type Utility Annex
Electrical Wastewater Water Emergency 120 278 66
Routine 1,062 844 130
ATTACHMENT J-1601000-04
UTILITY MAP ATTRIBUTES
Refer to MS Excel file “J-1601000-05 Utility Map Attributes Management.xlsx.” for information.
ATTACHMENT J-1601000-05
UTILITY OUTAGE REPORTING REQUIREMENTS
In accordance with the BPMS B-5.2.14 and NAVFAC MAXIMO data requirements provided in Spec Item 2.6.8 in Annex 0200000, the Contractor shall log and track all utility planned and unplanned outages including the following information for work order data related to utility outages:
• Receive service call.
• Create Service Request for the utility outage following the Service Desk Guide for Utility Outages.
• Create Work Order for response by utilities personnel as soon as the outage is reported and/or when the service request is received. Initial Work Order shall be recorded in NAVFAC MAXIMO no later than the close of next business day.
• Utility outage responding personnel will report the number of buildings and pier berths affected by the outage to the Service/Trouble Desk.
• Update outage information and actions taken to restore service on Work Order as information becomes available to include: for example, Master System Affected, Outage Start Date, Number of Buildings Affected, Outage End Date, and outage cause. Once the work is completed, update records to add any missing data within 30 days and prior to work order close-out.
Utility Outage Cause Codes:
Code 0 - False Alarm - A False Alarm, determined not an outage Code 1 - Commercial Power/Utility Loss - Outage caused when commercial service provider fails to supply a NAVFAC utility distribution system, such as a loss of generation Code 2 - Weather - Outage caused by named storms, tornados, lightning strikes, flood, or during a severe weather warning / watch Code 3 - Equipment Failure - Outage caused by failed circuits, transformers, breaks, leaks, etc.
Code 4 - Animal - Outage caused by animal/pest damage from birds, squirrels, reptiles, etc.
Code 5 - Vegetation - Outage caused by vegetation damage not due to severe weather, such as those due to neglecting to maintain of right of ways Code 6 - Foreign Interference - Outage caused by excavation, customer interference, vandalism, etc.
Code 7 - Ship - Outage caused by actions aboard ship or by ship personnel Code 8 - Operational Error - Unplanned outage caused by utilities personnel Code 9 - Navy Power/Utility Loss – Outage by other utility causes, such as planned.
ATTACHMENT J-1601000-06
UTILITY ASSET TAGGING GUIDANCE
The Contractor shall label all utility assets following the format below. All fields indicated align to asset data stored in NAVFAC MAXIMO.
Installation of these tags shall be phased in over the base year to occur as inventory is completed. As equipment is replaced or new equipment installed, the Contractor shall attach new tags and provide an update of all equipment information within the NAVFAC Maximo. The Contractor shall regularly maintain and replace tags found to be damaged, deteriorated, or unreadable. The application for printing barcode labels and instructions is also available in P-603.
All equipment tags used shall be synthetic, durable, resist caustics/acids and abrasion, and shall be water, heat and weather resistant. Tags shall be made of polypropylene, thermal transfer printable labels with a matte finish, with thickness of 2.4 mil. Affixing method with a permanent-all temp adhesive. The dimensions are 2.43 inches by 3 inches to fit into the Zebra Technology International P4T Mobile Thermal Transfer Printer with ink ribbon or similar.
Equipment tags shall match the asset number of the equipment per record in NAVFAC Maximo.
ATTACHMENT J-1601000-07
SPECIFICATION ATTRIBUTES
CLASSIFICATION REQUIRED SPECIFICATION FIELD
Actuator Actuator Type
Actuator Rated Pressure
Actuator Rated Pressure UOM
AirDryer Air Dryer Type
Barscreen Bar Screen Type
BatterySystem Battery Role
BatterySystem Battery Type/Battery Ampere Hour
BatterySystem Number Of Batteries
Boiler Type ID
Boiler National Board No.
Boiler Capacity
Boiler Capacity UOM
Boiler Primary Fuel Type
Boiler Secondary Fuel Type
Burner UL Number
Burner Fuel Type
CapacitorBank Cap Bank Type
CapacitorBank Control Type
CapacitorBank Install Type
CapacitorBank Nominal Voltage
CapacitorBank Voltage Class
CapacitorBank Total Bank KVAR
ChemicalAddtion Chemical Type
Chiller Capacity
Chiller Capacity UOM
Chiller Compressor Type
Compressor NFAID
Compressor Compressor Type
CondensateCollector Steam Condensate Collector Type
CondensateCollector Associated Line Type
ControlSystem Type
ControlSystem Voltage
ControlValve Type
ControlValve Diameter
ControlValve Diameter UOM
ControlValve Regulation Type
Classification Required Specification Field
ControlValve Material
DeaeratorAndStorageTank Deaerator Type
DeaeratorAndStorageTank Deaerator Capacity
DeaeratorAndStorageTank Deaerator Capacity UOM
DeaeratorAndStorageTank Storage Tank Volume
DeaeratorAndStorageTank Volume UOM
DeaeratorAndStorageTank Tank Material
DifferentialRelay Differential Relay Type
DifferentialRelay Calibration Date
DynamicProtectiveDevice Dyn Pro Dev Type
DynamicProtectiveDevice Device Control
DynamicProtectiveDevice Voltage Class
DynamicProtectiveDevice Interr Mechanism
DynamicProtectiveDevice Gang Operated
DynamicProtectiveDevice Interr Medium
DynamicProtectiveDevice Install Type
DynamicProtectiveDevice Nominal Voltage
ElectricLine Electric Line Type
ElectricLine Circuit Length
ElectricLine Length UOM
ElectricLine Voltage Class
ElectricLine Conductors per Phase
ElectricLine Install Type
ElectricLine Nominal Voltage
ElectricLine Radial Feeder
ElectricLine Cable in Conduit
ElectricMeter Electric Meter Role
ElectricMeter Meter Form
ElectricMeter Meter Class
ElectricMeter Nominal Voltage
ElectricPanel Panel Type
ElectricPanel Voltage
ElectricPanel Amp Rating
ElectricPanel Number Spaces
ElectroMechanicalRelay Relay Type
ElectroMechanicalRelay IEEE Device No
ElectroMechanicalRelay Calibration Date
ElectroMechanicalRelay Voltage Class
Enclosure Enclosure Type
Engine Driven Asset
Engine Fuel Type
ExpansionJoint Steam Exp Joint Type
ExpansionJoint Assoc Line Type
ExpansionJoint Diameter
ExpansionJoint Diameter UOM
ExpansionJoint Material
ExteriorLights Exterior Lights Type
ExteriorLights Nominal Voltage
ExteriorLights Light Ownership
ExteriorLights Wattage
ExteriorLights Lamp Type
ExteriorLights Quantity
Fan Fan Role
Filter Filter Type
Filter Filter Material
Filter Capacity
Filter Capacity UOM
Filter Rated Flow
Filter Rated Flow UOM
GearDrive Shaft Alignment
GearDrive Rated Power
GearDrive Power UOM
Generator Rated KW
Generator Generator Type
Generator Voltage Class
Generator Nominal Voltage
GreaseTrapAndOilWaterSeparator Pretreatment Device Type
GreaseTrapAndOilWaterSeparator System Type
GreaseTrapAndOilWaterSeparator Material
GritRemoval Grit Removal Type
Ground Grounding Device Type
Ground Ground Type
HeatExchanger Heat Exchanger Role
Hydrant Year Manufactured
Hydrant Bonnet Color
Hydrant Material
Hydrant Hydrant Type
Hydrant Seat Diameter
Hydrant Diameter UOM
Instrumentation Instrumentation Type
Insulator Insulator Type
Insulator Insulator Material
Insulator Install Type
Insulator Voltage Class
IonExchangeUnit Capacity
IonExchangeUnit Capacity UOM
LVBreakerPanel Install Type
LVBreakerPanel Nominal Voltage
LVBreakerPanel Wire
LVBreakerPanel Rated Ampacity
LVBreakerPanel Number Phases
LVBreakerPanel Number Spaces
LVBreakerPanel Spaces Filled
MechanicalMeter Mech Meter Role
MechanicalMeter Mech Meter Billing Type
MechanicalMeter Remote Read Indicator
MechanicalMeter Material
MechanicalMeter Meter Type
Mixer Mixer Type
Motor Motor Type
Motor Motor Control Type
Motor RPM
Motor Rated HP
Motor Nominal Voltage
Motor Voltage Class
OvercurrentRelay Overcurrent Relay Type
OvercurrentRelay Calibration Date/Setting of Relay
Pipe Service Area
Pipe Line Type
Pipe Pipe Length
Pipe Pipe Length UOM
Pipe Material
Pipe Pipe GPM
PowerInverter Nom. Input Volt.
PowerInverter Nom. AC Volt. Out
PowerInverter Cont/Nom Pwr Out./Ampere
Pump Type
Pump Submersible Indicator
Pump Rated Flow
Pump Rated Flow UOM
Pump Mechanical System Type
Pump Material
Pump Electrical Power Demand
Receptacle Receptacle Type
Receptacle Install Type
Receptacle Voltage Class
Receptacle Nominal Voltage
Receptacle Rated Ampacity
ReliefValve Type
ReliefValve Diameter
ReliefValve Diameter UOM
ReliefValve Material
RotatingBiologicalContactor Capacity
RotatingBiologicalContactor Capacity UOM
ShorePowerBox Shore Power Box Type
ShorePowerBox Voltage Class
ShorePowerBox Nominal Voltage
ShorePowerBox Install Type
SolidStateRelay Relay Type
SolidStateRelay IEEE Device No
SolidStateRelay Calibration Date
SolidStateRelay Voltage Class
Stack Material
Stack Height
Stack Height UOM
Stack Mult. Boilers
Stack Mounting System
StaticProtectiveDevice Device Type
StaticProtectiveDevice Install Type
StaticProtectiveDevice Voltage Class
SupportStructure Structure Material
SupportStructure Supp Struct Type
SupportStructure Thermal Support Type
SurfaceStructure Structure Material
SurfaceStructure Surface Structure Type
SwitchUnit Switch Type
SwitchUnit Voltage Class
SwitchUnit Sw Insul Medium
SwitchUnit Nominal Voltage
SwitchUnit Gang Operated
SwitchUnit Install Type
SystemValve Type
SystemValve Diameter
SystemValve Diameter UOM
SystemValve Material
Tank Type
Tank Material
Tank Contents
Tank Volume
Tank Volume UOM
Transformer TransformerType
Transformer Rated KVA
Transformer Install Type
Transformer Nominal HV
Transformer HV Protection
Transformer Nominal LV
Transformer CoolingType
Transformer HSide Taps
Trap Type
TreatmentProcessStructure Capacity
TreatmentProcessStructure Capacity UOM
UndergroundStructure Underground Struc Type
UndergroundStructure Structure Material
VoltageRegulator Volt Reg Type
VoltageRegulator Install Type
VoltageRegulator Rated KVA
VoltageRegulator Nominal Voltage
Well Rated Flow
Well Rated Flow UOM
ATTACHMENT J-1601000-08
UTILITY ASSET INVENTORY
Refer to MS Excel file “J-1601000-09 Utility Asset Inventory.xlsx.” for information.
ATTACHMENT J-1601000-09
UEM-DI METER GROUP AND THE DIRECT CONDITION RATING GUIDANCE
Likelihood Category Degradation Index
F u ll y
F un ct io n al
Negligible = 0 No noticeable defects. Some aging or wear may be visible. Fully functional.
Not Likely = 1 Only minor deterioration or defects are evident. Noticeable wear or aging is visible. Fully functional. Minor maintenance may be required.
Possible = 2 Deterioration or defects are evident. Function is not significantly affected. Minor repairs are required.
F u n ct io n
A ff ec te d
Likely = 3 Serious deterioration or defects in at least some portion of the asset.
Function is significantly affected. Extensive repairs or replacement are required.
Very Likely = 4 Extensive deterioration or defects in the asset. Not functional, barely functional, or beyond repair.
File details come from the government source that posted it. Updated .