This solicitation is for design-bid-build services for an F-35 Training and Simulator Facility at Marine Corps Air Station Cherry Point in North Carolina. Key details include a solicitation number of N40085-20-R-0015, proposals due by April 9, 2020 at 2:00 EDT, pre-proposal inquiries due by March 30th at 5:00 PM EDT, an estimated construction magnitude between $25-100 million, NAICS code 236210 for industrial building construction with a small business size standard of $39.5 million, and the acquisition being unrestricted and fully competitive. The wage determination is General Decision Number NC20200065 from January 3, 2020.
View the file
Other files
Show 40 more
Latest 50 of 69 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANEL LP1A
100A, 208Y/120V-3P, 4W
FED FROM PANEL MDP
INSTALLED 2016
DRAWING NO. 15,350,896
DEVICE ID
DEVICE RATING
POWER SOURCE
INSTALLATION DATE
NAVFAC DRAWING NUMBER
SYMBOL MODIFIERS
AC
AD
AV
C
CL
CO
D
EXP
EWC
F
GFI
P
REF
SF
S
TS
TV
VM
W
WP
WPIU
SYMBOLS - ONE-LINE DIAGRAM
CONNECTION
MANHOLE
FUSED DISCONNECT SWITCH
TRANSFORMER
GROUND
DELTA - WYE TRANSFORMER CONNECTION
METER
DIGITAL METER
BRANCH CIRCUIT MONITORING
SURGE PROTECTION DEVICE
VARIABLE FREQUENCY DRIVE
PROGRAMMABLE LOGIC CONTROLLER
HUMAN MACHINE INTERFACE
SHUNT TRIP
REMOTE ANNUNCIATOR PANEL
MEDIA CONVERTER
CONTROL POWER TRANSFORMER
DRAW OUT CIRCUIT BREAKER
MOTOR OPERATED DRAW OUT CIRCUIT BREAKER
CIRCUIT BREAKER
SWITCH
DISCONNECT SWITCH
PANELBOARD (PANELBOARD NAMED 'M')
MOTOR
GENERATOR
UNINTERRUPTIBLE POWER SUPPLY
ELECTRONIC INTERLOCK CONTROL ID.
KEYED INTERLOCK CONTROL ID.
BUSHING WELL
BUSHING INSERT
LOADBREAK
M
M
GROUND ROD, SUBSCRIPT INDICATES TYPE
T = TEST WELL
GROUND BUS, TYPE AS INDICATED.
DIRECT DIGITAL CONTROL PANEL
ROOM TAG
ILLUMINATION SPACE TAG
30 fc = FOOT-CANDLE LEVEL
2' - 6" = CALCULATION WORKPLANE AFF
PHOTOELECTRIC SENSOR
PUSH TO ACTIVATE/PULL TO RELEASE MUSHROOM
PUSHBUTTON.
J RECESSED JBOX, WALL MTD, SUBSCRIPT INDICATES
TYPE AND HEIGHT ABOVE AFF.
SURFACE JBOX, WALL MTD, SUBSCRIPT INDICATES TYPE
AND HEIGHT ABOVE AFF.
JBOX RECESSED IN FLOOR, SUBSCRIPT INDICATES TYPE
AND HEIGHT ABOVE AFF.
JBOX
C = ABOVE CEILING
MECHANICAL EQUIPMENT CONNECTION
EQUIPMENT CONNECTION OR BONDING CONNECTION
DOWN CONDUCTOR
AIR TERMINAL
J
J
FUSED DISCONNECT SWITCH. MTD 6'-0" TO TOP.
COMBO MOTOR STARTER/DISCONNECT. MTD 6'-0" TO TOP.
COMBO VFD/DISCONNECT. MTD 6'-0" TO TOP.
TYPICAL FOR ALL DISCONNECTS:
ELECTRICAL LEGEND
WIRE IN CONDUIT, RUN CONCEALED ABOVE CEILING OR IN
WALL
ABOVE COUNTER, SEE E-002 "DEVICE MOUNTING NOTES", NOTE 1
ABOVE DOOR, +6" ABOVE DOOR FRAME
AUDIO/VISUAL. COORDINATE FINAL WITH AV DESIGN, BY GOV'T
RECESSED IN CEILING
CLOCK, PROVIDE CLOCK HANGAR TYPE
COPIER, +18" AFF
DIMMING
EXPLOSION PROOF
ELECTRIC WATER COOLER
RECESSED IN FLOOR
GROUND FAULT CIRCUIT INTERRUPTER
PILOT LIGHT (INDICATING SWITCH IS ON)
REFRIGERATOR, +48" AFF
SYSTEMS FURNITURE FEED. SEE A1/EP501.
SECURITY OR OTHER SPECIAL SYSTEMS, COORDINATE EXACT
PLACEMENT WITH DIV 27/28
TOUCH SCREEN
TELEVISION +55" AFF
VENDING MACHINE, +24" AFF
WALL MOUNTED, +48" AFF
WEATHERPROOF
WEATHERPROOF WHILE IN USE
INTEGRATE WITH CASEWORK, COORD WITH DIV 06
CONDUIT TURNED UP
CONDUIT TURNED DOWN
2'x4' FIXTURE
1'x4' FIXTURE
EMERGENCY FIXTURE. FIXTURE ID INCLUDES AN "E" SUFFIX
EXTERIOR WALL MOUNTED FIXTURE
DOWNLIGHT OR PENDANT FIXTURE
EXTERIOR POLE-MTD FIXTURE
EXIT SIGNS, CEILING: ARROW INDICATES EGRESS
EXIT SIGNS, WALL: ARROW INDICATES EGRESS
OCCUPANCY SENSOR. DUAL TECHNOLOGY.
DAYLIGHT SENSOR.
PARTITION SENSOR
SWITCH, SUBSCRIPT INDICATES SWITCH ZONE
DIMMER SWITCH, SUBSCRIPT INDICATES SWITCH ZONE
3-WAY, SUBSCRIPT INDICATES SWITCH ZONE
4-WAY, SUBSCRIPT INDICATES SWITCH ZONE
MOTOR RATED SWITCH
SCENE CONTROLLER
TOUCH SCREEN
RECESSED SIMPLEX RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
RECESSED DUPLEX RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
RECESSED QUAD RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
SURFACE DUPLEX RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
SURFACE QUAD RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
CEILING DUPLEX RECEPTACLE, SUBSCRIPT INDICATES
TYPE.
SPECIAL RECEPTACLE, SUBSCRIPT INDICATES TYPE.
A NEMA 14-30R
B NEMA 14-50R
C NEMA L21-30R
D NEMA L6-15R
E NEMA L5-20R
F NEMA L6-20R
G NEMA L6-30P
FLOOR BOX, SUBSCRIPT INDICATES ID #. REFERENCE
COMBINATION FLOOR BOX SCHEDULE SHEET EP606.
SP = SPARE.
EPO PUSHBUTTON
LUMINAIRE TYPE
a
F1E
'E' DENOTES EMERGENCY BALLAST
LOWER CASE LETTER DENOTES SWITCH 'LEG'. THE
SWITCH WITH SAME LETTER OPERATES THIS FIXTURE
LUMINAIRE GENERAL
INFORMATION:
MH
SPD
VFD
ST
CLASSROOM
MANHOLE
HANDHOLE. SUBSCRIPT INDICATES TYPE.
MH
T
J PLC
HMI
OS
Ma
Da
3a
4a
M
30A
2 NF 4X
30A
2 NF 4X
30A
2 NF 4X
SF
60"
SF
60"
SF
60"
C
A
MSB1
EQUIPMENT NUMBER
SWITCHBOARD/SWITCHGEAR
NAMING CONVENTION:
DM
HH
DISCONNECT RATING
ENCLOSURE NEMA RATING
FUSE SIZE, NF = NON-FUSED
NUMBER OF POLES
DDC
PE
30 fc @ 2'-6"
8'-0" MOUNTING HEIGHT
SHALL BE SAME AS CEILING UON.
DS
RAP
G
M
I#
K#
L1
PANEL TYPE:
L: LOW VOLTAGE, 208/120V
H: HIGH VOLTAGE, 480/277V
C: COMMUNICATIONS, 208/120V
E: EMERGENCY
PANEL NUMBER
PANELBOARD NAMING
CONVENTION:
PREFIX:
MSB: MAIN SWITCHBOARD
SWBD: SWITCHBOARD
ATS-LS 1
EQUIP TYPE:
T: TRANSFORMER
ATS: AUTOMATIC TRANSFER SWITCH
STS: STATIC TRANSFER SWITCH
RPP: REMOTE POWER PANEL
EQUIP NUMBER
EQUIPMENT NAMING CONVENTION:
PS
M
EQUIP TYPE:
LS: LIFE SAFETY
E: EMERGENCY
C: COMMUNICATIONS
MC
CPT
SC
BCM
TS
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :2
A
M
E-001
LE
G
E N
D A
N D
G E
N E
R A
L N
O
TE
S
KMS
12804250
LAW JAB
GENERAL NOTES
1. ALL ELECTRICAL WORK AND MATERIAL IS NEW AND SHALL BE PROVIDED
BY THE CONTRACTOR UNLESS OTHERWISE NOTED.
2. AN EQUIPMENT INSULATED GREEN GROUND WIRE SHALL BE RUN WITH
FEEDERS AND BRANCH CIRCUITS.
3. WIRING SHALL BE AS PER NATIONAL ELECTRICAL CODE (NEC).
4. ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED AND LABELED.
5. FEEDERS/CIRCUITS SHALL BE IDENTIFIED AT EACH END OF THE WIRE AND
AT EVERY SPLICE OR JUNCTION/PULL BOX.
6. PROVIDE NAMEPLATES ON THE EXTERIOR OF ELECTRICAL PANELS AND
ENCLOSURES AS FOLLOWS:
FOR DISCONNECT SWITCHES AND MOTOR STARTERS, THE TOP LINE SHALL
BE THE NAME/DESIGNATION OF EQUIPMENT BEING FED BY SAME.
7. PROVIDE NEW TYPED DIRECTORIES FOR PANELS (NEW OR EXISTING)
INCLUDED IN THIS PROJECT.
8. INTERIOR WIRING SYSTEMS SHALL BE CONCEALED WITH FLUSH
MOUNTED BOXES/DEVICES, UON.
9. DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD
INVESTIGATIONS. CONTRACTOR SHALL VISIT THE EXISTING BUILDING AND
ACQUAINT HIMSELF/HERSELF WITH THE EXISTING CONDITIONS.
CONTRACTOR SHALL EXAMINE DRAWINGS TO AVOID CONFLICT.
10. COORDINATE LOCATION AND POWER REQUIREMENTS OF ELECTRICAL
DEVICES WITH MECHANICAL, PLUMBING, ARCHITECTURAL AND FIRE
PROTECTION DRAWINGS.
11. ELECTRICAL DEVICES SHOWN BUT NOT CIRCUITED SHALL REMAIN ON
THEIR EXISTING CIRCUIT.
12. PROVIDE ARC-FLASH LABELS ON ALL PANELS/DISCONNECT SWITCHES
BASED ON ARC-FLASH STUDY PROVIDED PER SPEC 26 28 00.00 10.
PROVIDE LABELS PER UFC 3-560-01 AND NFPA 70E.
13. SINGLE PHASE (120/208V) BRANCH CIRCUITS SHALL CONSIST OF 2#12 & 1#
12 GND. IN 1/2"C UON. THREE PHASE BRANCH CIRCUITS CONSIST OF 3#12 &
1#12 GND IN 1/2"C UON.
14. REFER TO PLANS FOR CONDUCTOR SIZING. COMPLY WITH THE
FOLLOWING GUIDELINES FOR CONDUCTOR RUN LENGTHS:
20A, 120V CIRCUITS LONGER THAN 100' - USE #10 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 120V CIRCUITS LONGER THAN 150' - USE #8 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 277V CIRCUITS LONGER THAN 150' - USE #10 AWG TO
LIMIT VOLTAGE DROP ON BRANCH CIRCUITS TO 3%
15. BEFORE SUBMITTING SHOP DRAWINGS, SHOP DRAWING APPROVAL AND
BEFORE ORDERING EQUIPMENT COORDINATE ELECTRICAL WORK WITH
ARCHITECTURAL, MECHANICAL AND FIRE PROTECTION WORK PRIOR TO
FABRICATION AND INSTALLATION TO PREVENT CONFLICTS. NOTIFY
CONTRACTING OFFICER WHERE CONFLICTS ARE DISCOVERED PRIOR TO
CONSTRUCTION AND BEFORE BEGINNING WORK IN THOSE AREAS. ALL
CONFLICTS THAT ARISE DUE TO LACK OF COORDINATION SHALL BE
RECTIFIED BY THE CONTRACTOR AT NO COST TO THE GOVERNMENT.
16. REFER TO GI101 FOR FIRE AND SMOKE RATED PARTITION LOCATIONS.
REFER TO A-501 AND A-502 FOR PARTITION TYPES AND DETAILS.
CONSTRUCTION NOTES
1. CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 WEEKS NOTICE OF POWER
OUTAGES TO ACTIVITY AND GOVERNMENT OFFICIAL.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
DONALD ELLIOT
(BY EMAIL 08JAN2020)
EXIT
NOTE 4
N O
T E
NOTE 2
SINK OR
BASIN
CEILING
FINISHED
FLOOR
DEVICE MOUNTING NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
COORDINATE ABOVE COUNTER DEVICES AND RECEPTACLES WITH CASEWORK OR COUNTERS SUCH THAT THE DEVICES AND RECEPTACLES ARE LOCATED AT +42" AFF OR 6" ABOVE THE COUNTERTOP OR BACKSPLASH, WHICHEVER IS HIGHER
ALL RECEPTACLES INSTALLED WITHIN 6'-0" OF ANY SINK OR BASIN SHALL BE GFI RECEPTACLES. DO NOT INSTALL RECEPTACLES WITHIN 12" OF THE
EDGE OF A SINK OR BASIN
COORDINATE WITH DIV 27 AND 28 TO ENSURE THAT A DUPLEX RECEPTACLE IS INSTALLED WITHIN 6" HORIZONTAL TO ALL SIGNAL, CATV, AV, AND DATA
DEVICE LOCATIONS
SWITCHES AND OTHER FLUSH WALL-MOUNTED DEVICES SHALL BE MOUNTED WITHIN 12" OF DOOR FRAME. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR DOORS WITH ADJACENT SIDELIGHTS. WHERE DEVICES ARE SHOWN ADJACENT TO THE DOOR ON THE HINGE-SIDE OF THE DOOR
MOUNT THE DEVICE 12" BEYOND THE DOOR SWING.
COORDINATE ROUGH-IN LOCATIONS WITH DIV. 27 AND 28 DEVICES. COORDINATE MOUNTING LOCATION WITH OTHER TRADES TO ENSURE A UNIFORM
MOUNTING AND AESTHETICALLY-PLEASING APPEARANCE.
MOUNTING HEIGHT INDICATED IN LEGEND AND ON THE DRAWINGS SHALL BE THE DISTANCE MEASURED FROM THE CENTER OF THE DEVICE TO THE
FINISHED FLOOR.
PROVIDE PRINTED LABELING AS SPECIFIED FOR ALL DEVICES, POWER RECEPTACLES AND JUNCTION BOXES TO INCLUDE PANEL AND CIRCUIT NUMBERS.
COORDINATE EXIT SIGN LOCATION WITH MASS NOTIFICATION SIGNAGE. SEE DETAIL FA501 FOR MASS NOTIFICATION SIGNAGE MOUNTING DETAIL.
NOTE 3
12"
S
TYPICAL DEVICE MOUNTING DETAIL
NOTE 5
GENERAL NOTES
ALL CONDUCTORS SHALL BE RUN IN CONDUIT, AND ALL CONDUIT SHALL
BE CONCEALED UNLESS OTHERWISE NOTED ON THE DRAWINGS.
ALL SWITCHGEAR, SWITCHBOARDS, AND PANELBOARDS SHALL BE FIELD
MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC
FLASH HAZARD IN ACCORDANCE WITH NFPA 70 AND 70E. PROVIDE ARC
FLASH LABELS FOR ALL ELECTRICAL DISTRIBUTION EQUIPMENT.
ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL
CONTRACTOR REGARDING ELECTRICAL REQUIREMENTS OF ACTUAL
EQUIPMENT PROVIDED.
MOUNTING HEIGHT NOTED FOR LIGHT FIXTURES SHALL BE FROM THE
BOTTOM OF FIXTURES TO THE FINISHED FLOOR.
ALL SYSTEMS THAT REQUIRE COORDINATION BETWEEN TRADES SHALL
BE TO THE SATISFACTION OF THE CONTRACTING OFFICER. ANY
DEFICIENCIES, INCONSISTENCIES, OR POORLY COORDINATED
INSTALLATIONS SHALL BE CORRECTED BY THE CONTRACTOR AT NO
EXTRA COST TO THE GOVERNMENT.
ALL ELECTRICAL WORK SHALL COMPLY WITH NEC (NFPA 70), NFPA 72,
NFPA 101, AND APPLICABLE MILITARY CODES OR TECHNICAL LETTERS, IN
ADDITION TO LOCAL CODES AND ORDINANCES. ALL GROUNDING SHALL
COMPLY WITH NFPA 70, ART. 250 AND MIL-STD-419A.
PROVIDE A GREEN CONTINUOUS INSULATED EQUIPMENT GROUNDING
CONDUCTOR IN ALL ELECTRICAL AND CONTROL CONDUIT, TO ALL
ELECTRICAL, TELECOMMUNICATIONS, AND SECURITY EQUIPMENT SIZED
PER NEC 250.122.
DO NOT PENETRATE FLOOR OR ROOF SLAB WITHIN 4' OF EXTERIOR
PERIMETER WALL. INSTALL ALL RISERS IN ELECTRICAL OR
TELECOMMUNICATION ROOMS. INSTALL ALL EQUIPOTENTIAL
GROUNDING AND LPS CONDUCTORS AND CONDUITS EMBEDDED IN
CONCRETE WALLS AND FLOORS. SEE STRUCTURAL PROGRESSIVE
COLLAPSE PREVENTION DWGS FOR ADDITIONAL DETAIL.
ALL EQUIPMENT GROUND CONDUCTORS AND GROUND BUS
CONDUCTORS ASSOCIATED WITH THE TBB AND TELECOMMUNICATIONS
ARE SIZED 2KCMIL PER LINEAR FOOT. ANY ALTERATIONS TO EQUIPMENT
LAYOUT OR GROUND DESIGN WILL REQUIRE RESIZING AND BE THE
RESPONSIBILITY OF THE CONTRACTOR. SEE TABLE ON SHEET EG701.
PROVIDE SOUND ATTENUATION PER DETAILS ON SHEET EP503.
COORDINATE STC RATED WALLS WITH SHEETS A100-A104.
ALL POWER CONDUITS SHALL BE SEPARATED FROM RED (CLAS)
NETWORKS BY A MINIMUM OF 6" (15CM) OVER A 98' (30M) PARALLEL RUN
OR 2" (5 CM) OTHERWISE. COORDINATE NETWORK ROUTING LOCATIONS
WITH TN DRAWINGS AND LOW VOLTAGE CONTRACTOR.
ELECTRICAL DEMOLITION PLANS SHOW EXISTING CONDITIONS BASED ON
FIELD OBSERVATIONS AND ORIGINAL DRAWINGS. ADDITIONAL
COMPONENTS AND CONDITIONS THAT ARE NOT SHOWN ON THE DRAWINGS
MAY EXIST AND MAY REQUIRE CERTAIN REMODELING OR ADJUSTMENTS
THAT ARE NOT NOTED ON THE DRAWINGS. FIELD VERIFY THE LOCATIONS
OF ALL EXISTING EQUIPMENT AND DEVICES SHOWN ON THE DRAWINGS
PRIOR TO BIDDING.
OBTAIN WRITTEN PERMISSION FROM THE CONTRACTING OFFICER PRIOR
TO SHUTTING OFF SERVICES OR SYSTEMS WHICH MAY AFFECT OTHER
AREAS BEYOND THE LIMITS OF THE DEMOLITION AREA. ALL OUTAGES
SHALL BE COORDIANTED WITH THE CONTRACTING OFFICER.
NOT ALL EXISTING UTILITIES AND OR ELECTRICAL SYSTEMS ARE SHOWN ON
PLANS. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL
EXISTING CONDITIONS PRIOR TO COMMENCING WORK. COORDINATE WITH
THE CONTRACTING OFFICER PRIOR TO COMMENCING WORK.
ALL ELECTRICAL EQUIPMENT AND DEVICES TO BE REMOVED: COMPLETELY
REMOVE ALL CONDUCTORS AND CONDUIT TO THE DEVICE. WHERE
CONDUIT REMOVAL IS NOT POSSIBLE, CAP CONDUIT AND MAKE SAFE.
WHERE BACKBOXES CANNOT BE REMOVED, PROVIDE A BLANK
COVERPLATE. ALL REMOVED CONDUIT, BOXES, WIRING AND
MISCELLANEOUS ELECTRICAL SCRAP SHALL BE REMOVED FROM THE JOB
SITE AND DISPOSED OF PROPERLY.
DEWATER, CLEAN, INSPECT FOR ASBESTOS AND RELABEL CONDUCTORS
FOR EXISTING MANHOLES AND CABLES AFFECTED BY PROJECT. PROVIDE
ASBESTOS MITIGATION FOR ALL MANHOLES DISCOVERED TO HAVE
ASBESTOS INSULATION.
SPARE CONDUITS CREATED DURING DEMOLITION SHALL BE PROPERLY
IDENTIFIED AND A TEMPORARY REMOVABLE CAP PROVIDED.
DEMOLITION NOTES
1.
2.
3.
4.
5.
6.
ABBREVIATIONS
A AMPERES
AC ABOVE COUNTER
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFRMS ARC FLASH REDUCTION MAINTENANCE SYSTEM
AIC AMPERES INTERRUPTING CAPACITY
AV AUDIO/VIDEO
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BFG BELOW FINISHED GRADE
BN BONDING NETWORK
C CONDUIT
CAT CATEGORY
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CH CHILLED WATER
CL CENTERLINE
COMM COMMUNICATIONS
CT CABLE TRAY
CU COPPER
CUP CENTRAL UTILITY PLANT
CO COPIER
CW CONDENSER WATER
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DISC DISCONNECT
DN DOWN
EBC EQUIPMENT BONDING CONDUCTOR
EC EMPTY CONDUIT
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING CONDUCTOR
EGP EQUIPOTENTIAL GROUNDING PLANE
EHF EXTRA HIGH FREQUENCY
EIA ELECTRONICS INDUSTRIES ASSOCIATIONS
EM/NL EMERGENCY / NIGHT LIGHT
EMT ELECTRICAL METALLIC TUBING
EO ELECTRICALLY OPERATED BREAKER
EOOW ENGINEERING OFFICER OF THE WATCH
EPDM ETHYLENE PROPYLENE DIEN TERPOLYMER
EPO EMERGENCY POWER OFF
EPSS EMERGENCY POWER SUPPLY SYSTEM
ESD ELECTROSTATIC DISCHARGE
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX OR EXST EXISTING
EXP EXPLOSION PROOF
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OTHERS
FIG FIGURE
FO FIBER OPTIC
FPD FLAT PANEL DISPLAY
FSCP FIRE SYSTEM CONTROL PANEL
FT FEET OR FOOT
GBC GROUND BUS CONDUCTOR
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFGI GOVERNMENT FURNISHED AND INSTALLED
GFI GROUND FAULT INTERRUPTER
GND GROUND
GFE GOVERNMENT FURNISHED EQUIPMENT
GFR GROUND FAULT RELAY
GFP GROUND FAULT PROTECTION
GRS GALVANIZED RIGID STEEL
HMI HUMAN MACHINE INTERFACE
HID HIGH INTENSITY DISCHARGE
HZ HERTZ
IAW IN ACCORDANCE WITH
ID INSIDE DIAMETER
IDS INTRUSION DETECTION SYSTEM
IG ISOLATED GROUND
IPGB INTERIOR PERIMETER GROUND BUS
JBOX JUNCTION BOX
JTS JOINTS
K KILO
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOURS
LC LIGHTING CONTACTOR
LOC LIMITS OF CONSTRUCTION
LP LIGHTNING PROTECTION
LPS LIGHTNING PROTECTION SYSTEM
LTC LIQUID TIGHT CONNECTOR
LW LOCKABLE WIREWAY
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MN/PA MASS NOTIFICATION/PUBLIC ADDRESS
MNS MASS NOTIFICATION CONTROL PANEL
MTD MOUNTED
N NEUTRAL CONDUCTOR
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NETA ATS NATIONAL ELECTRICAL TESTING ASSOCIATION ACCEPTANCE TESTING SPECIFICATIONS NETA MTS NATIONAL ELECTRICAL TESTING ASSOCIATION MAINTENANCE TESTING SPECIFICATIONS
NF NOT FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
OSP OUTSIDE PLATE
P POLE
PDU POWER DISTRIBUTION UNIT
PIV POST INDICATOR VALVE
PLC PROGRAMMABLE LOGIC CONTROLLER
PR PAIR
PVC POLYVINYL CHLORIDE
QTY QUANTITY
REF REFERENCE
RGS RIGID GALVANIZED STEEL CONDUIT
RL RELOCATE
RM ROOM
RN REPLACE WITH NEW
RMC RIGID METAL CONDUIT
SAPF SPECIAL ACCESS PROGRAM FACILITIES
SCCR SHORT CIRCUIT CURRENT RATING
SCHED SCHEDULE
SCI SENSITIVE COMPARTMENTALIZED INFORMATION
SF SYSTEMS FURNITURE
SPD SURGE PROTECTIVE DEVICE
SPECS CONTRACT SPECIFICATIONS
SPST SINGLE POLE SINGLE THROW
SRG SIGNAL REFERENCE GRID
SS STAINLESS STEEL
ST SHUNT TRIP
STR STRAND
STS STATIC TRANSFER SWITCH
SW SWITCH
T TRANSFORMER
TBB TELECOMMUNICATIONS BONDING BACKBONE
T.O. TOP OF
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TYP TYPICAL
UFC UNIFIED FACILITIES CRITERIA
UGE UNDERGROUND ELECTRICAL
EXISTING CONDITIONS
THE ELECTRICAL CONTRACTOR SHALL PERFORM SITE INVESTIGATION
OF THE EXISTING CONDITIONS PRIOR TO COMMENCING WORK TO
VERIFY ACTIVE MEDIUM VOLTAGE FEEDERS, MANHOLE/HANDHOLE
LOCATIONS & CONDITIONS. COORDINATE ALL SITE INVESTIGATIONS
WITH THE CONTRACTING OFFICER PRIOR TO COMMENCEMENT OF
DEMOLITION WORK.
UNLESS INDICATED AS EXISTING, ALL MATERIALS AND LABOR SHALL BE
CONSIDERED NEW.
ALL EXISTING EQUIPMENT AND DEVICES TO REMAIN SHALL STAY INTACT
AND OPERATIONAL DURING THE CONSTRUCTION PROCESS. IF A DEVICE
REQUIRING POWER IS DISTURBED OR INTERRUPTED, RESTORE THE
DEVICE TO ITS ORIGINAL OPERATIONAL STATE. ANY DEMOLITION WORK
REQUIRING MODIFICATION OF EXISTING ELECTRICAL SYSTEMS SHALL
NOT COMPROMISE THE SYSTEMS TO REMAIN. INSTALL NEW CONDUIT
AND WIRING WHERE NECESSARY TO RESTORE POWER PER NEC
REQUIREMENTS.
THE CONTRACTOR SHALL BE RESPONSIBLE TO RESTORE ALL
INTERIOR/EXTERIOR WALLS, CEILINGS, FLOORS, AND CONCRETE WORK
REQUIRING PATCHING, PLASTERING, PAINTING AND ANY OTHER
REPAIRS DUE TO ELECTRICAL WORK TO RESTORE THE ORIGINAL FINISH
AND APPEARANCE.
1.
2.
3.
4.
J
1.
2.
3.
4.
5.
6.
7.
E
Q
AD
E Q
DOOR
SECURITY NOTES
SEE SHEETS EP502 AND EP503 FOR SPECIAL PENETRATION DETAILS
WHEN CROSSING A SECURE BOUNDARY.
ONLY PENETRATE THE SECURE BOUNDARY FOR CONNECTIONS WITHIN
THE SECURE AREA. DO NOT ROUTE CONDUIT THROUGH THE SECURE
AREA TO REACH OTHER LESS SECURE AREAS.
ALL WORK IN AND AROUND SECURE AREAS SHALL BE PERFORMED IN
COMPLIANCE WITH UFC 4-010-05.
A MINIMUM OF 3" SEPARATION SHALL BE MAINTAINED BETWEEN
CLASSIFIED, UNCLASSIFIED AND POWER DISTRIBUTION.
1.
2.
3.
4.
8.
9.
MONITOR, TYP.
TV
AV
CONDUIT SIZE ONE SHOT/FULL SHOE OTHER BENDS
1/2" 4" 4" 3/4" 4-1/2" 5" 1" 5-3/4" 6" 1-1/4' 7-1/4" 8" 1-1/2" 8-1/4" 10" 2" 9-1/2" 12" 2-1/2" 10-1/2" 15" 3" 13" 18" 3-1/2" 15" 21" 4" 16" 24" 5" 24" 30" 6" 30" 36"
MINIMUM RADIUS OF CONDUIT AND
TUBING BENDS
GFI
UL UNDERWRITERS' LABORATORIES
UNC UNIFIED COURSE
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
VFI VACUUM FAULT INTERRUPTER
W WIRE OR WATT
WPIU WEATHER PROOF IN USE
XFMR TRANSFORMER
XRL EXISTING TO BE RELOCATED
Z IMPEDANCE
10.
11.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :2
A
M
E-002
G E
N E
R A
L N
O
TE
S A
N D
A B
B R
E V
IA
TI
O N
S
KMS
12804251
LAW JAB
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
W W
FP G
G
G
G
G
G
G
G G G G G G G G
W W
W W
W W
W W
C O
S
SSSS
S
S
S S
S S
S S
SS SS
23+00
30+00
ST
W W
W
10+0011+0012+00
15+00 16+00
16+95
DN
TR
MECH
DMRT
MATSS MISSION PLANNING
COMMAND CTR & OBSERV
CORR
NECC ADMIN
SHIPPING / RECEIVING / SUPPLY
CONFERENCE
FMS REPAIR SHOP / MAINT STOR
MECH / ELEC
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
CORR
MANTRAP
ISEO
ISEO
ISEO
WHITE CELL EVAL
MECH
ELEC
ELEC
ISE LAB
ISEO
CORR
CBT
AUDIOVISUAL
MANTRAP
MENS
WOMENS
BREAK
MENS
WOMENS
PSO SEC CONF
APSO / GSSO
PSO SERVER
PSO
PATCH PANEL
JANITOR
TR
LOBBY
MATSS TRAINING
CORR
MENS
WOMENS
JAN
MOTHER'S RM
BREAK
RECEPTION
TLT
SEC OFFICE
SEC BADGE
SEC MGR
CORR
ISEO
ISEO
VEST
SEC SUPPLY / EQUIP
STO
TR
REPRO
EVAL / PROGRAM / MATSS SUPPORT
MATSS CONFERENCE
JPO
MATSS
MATSS
MATSS
MATSS
SITCC /
JMPS
COMMANDER
TRAINING OPS MGR
CONTRACT PILOT INST MGR
LM
MATSS TRAINING
CORR
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
MECH / ELEC
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
MECH / ELEC
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
FMS/OTW
IOS ROOM
COMP EQUIP ROOM
SERVER
BRIEF
DEBRIEF
CORR
CORR
CORR
CORR
CORR
CORR
CORR
LOCKER
LOCKER
CONFERENCE
COMP SUPPORT
IAM / ISSO
FIRE PUMP
SIM / HELMET PAD STOR
ELEC
MH
EXST MH 11B
ELEC
E
E
E
E
E
E
E
E
E
E
E
E
E
E E E E E
E
E
E
E
E
LSMDP-15
E
E
E
E
E
E
E
E
E
E
E
E
P
G1
UT-1
ELEC
E
P
E
P
MTS-LS
0'-0" - 6'-0"
B4
CS503
B4
CS503
HH HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
E
E
E
E
E
E
E
E
E
E E
E E
E E
E E
E
E
E
E
E
E E
E E
E E
E
E
E
E
E
E
E
E E
E E
E E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
C1
ES502
(TYP)
B4
CS503
C1
ES502
(TYP)
P5
25'-0"
P5
25'-0"
P5
25'-0"
P4
25'-0"
P4
25'-0"
P2
25'-0"
P4
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
P2
25'-0"
P3
25'-0"
P2
25'-0"
P2
25'-0"
P4
25'-0"
E
E
E
E P
E
P
E
P
E L
E C
T R
I C
A L
S
I T
E
P
L A
N
A
R E
A
ES101
P -2
F
-3
TR
A
IN
IN
G A
N D
S
IM
U
LA
TO
R
F A
C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
PLAN
NORTH
SCALE: 1" = 30'
ELECTRICAL SITE PLAN - AREA 1
0 30' 60'
M A
T C
H
L I N
E
S
E
H E
T
1. PROVIDE CONNECTION TO MEDIUM VOLTAGE CONDUCTORS PER
SHEET EP601 AND EP602.
2. PROVIDE 2-WAY, 2 X 1 DUCTBANK; SEE DETAIL A4/ES501. SAW CUT
AND PATCH ROAD CROSSING ON 5TH AVENUE.
3. PROVIDE 1" EB SCH 20 PVC CONDUIT 18" BFG FOR LIGHTING
CIRCUIT.
GENERAL NOTES
WORK NOTES
A1
KEYPLAN
AREA 2
AREA 1
AREA 3
PLAN
NORTH
3 (TYP)
LAW JAB KMS
A4
ES501
1 2
DUCTBANK CABLE AND FEEDER SCHEDULE
# WIRE CONDUIT DESCRIPTION NOTES
3#4/0 1/C, TAPE SHIELD, 15KV EPR 133%
INSULATION CU CONDCUTOR & 1#1 AWG
(600V) GROUND.
5" EB SCH 20 PVC MV POWER
2 SPARE 5" EB SCH 20 PVC MV POWER
3 4#600KCMIL CU & 1#3/0 CU GND 4" EB SCH 20 PVC POWER
4 4#300KCMIL CU & 1#2/0 CU GND 4" EB SCH 20 PVC POWER
5 4#4/0 CU & 1#2 CU GND 4" EB SCH 20 PVC POWER
6 3#4 CU & 1#8 CU GND 4" EB SCH 20 PVC POWER
7 SPARE 3-1/2" EB SCH 20 PVC POWER
8 SPARE 2-1/2" EB SCH 20 PVC POWER
9 SPARE 4" EB SCH 20 PVC POWER
A1
ES501
1. SEE ES501 FOR ELECTRICAL SITE DETAILS.
2. CONNECT SITE LIGHTING VIA LIGHTING CONTROL PANEL. SEE LIGHTING
CONTROL SYSTEM DETAIL B2 SHEET EL503.
MANHOLE, SUBSCRIPT INDICATES POSSIBLE
DEPTHS OF EXISTING DUCTBANK BELOW
FINISHED GRADE.
LEGEND
DOMESTIC SERVICE WATER LINE
SANITARY SEWER LINE
FIRE HYDRANT
WATER VALVE
SMH
FHYD
WV
SECURITY FENCE
SEWER MANHOLE
FDC
PIV
FIRE DEPARTMENT CONNECTION
POST INDICATOR VALVE
NATURAL GAS LINE
G
UNDERGROUND ELECTRICAL LINE
E
REMOVABLE BOLLARD
DW
SAN
FIRE SERVICE WATER LINE
FW
SINGLE HEAD SITE LIGHT
MH
EP
UNDERGROUND ELECTRIC SECONDARY
UNDERGROUND ELECTRIC PRIMARY
ES
DUCTBANK CALLOUT.
SEE DUCTBANK CABLE AND FEEDER
HH
HANDHOLE, SUBSCRIPT INDICATES TYPE.
P2
SUBSCRIPT INDICATES TYPES
0'-0" - 6'-0"
SCHEDULE THIS SHEET.
I S
S U
D
F
O R
C
N
S T
R U
C T
I O
N
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
P3
25'-0"
HH
E
E
E L
E C
T R
I C
T
E
P
L A
N
A
R E
A
ES102
P -2
F
-3
TR
A
IN
IN
G A
N D
S
IM
U
LA
TO
R
F A
C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
PLAN
NORTH
SCALE: 1" = 30'
ELECTRICAL SITE PLAN - AREA 2
0 30' 60'
M A
T C
H
L
I N
E
S
E
1. PROVIDE 1" EB SCH 20 PVC CONDUIT 18" BFG FOR LIGHTING CIRCUIT.
GENERAL NOTES
WORK NOTES
A1
LEGEND
KEYPLAN
1. SEE ES501 FOR ELECTRICAL SITE DETAILS.
2. CONNECT SITE LIGHTING VIA LIGHTING CONTROL PANEL. SEE LIGHTING
CONTROL SYSTEM DETAIL B2 SHEET EL503.
AREA 2
AREA 1
AREA 3
PLAN
NORTH
LAW JAB KMS
I S
S U
N
S T
R U
C T
I O
N
DOMESTIC SERVICE WATER LINE
SANITARY SEWER LINE
FIRE HYDRANT
WATER VALVE
SMH
FHYD
WV
SECURITY FENCE
SEWER MANHOLE
FDC
PIV
FIRE DEPARTMENT CONNECTION
POST INDICATOR VALVE
NATURAL GAS LINE
G
UNDERGROUND ELECTRICAL LINE
E
REMOVABLE BOLLARD
DW
SAN
FIRE SERVICE WATER LINE
FW
SINGLE HEAD SITE LIGHT
MH
MANHOLE
EP
UNDERGROUND ELECTRIC SECONDARY
UNDERGROUND ELECTRIC PRIMARY
ES
HH
HANDHOLE, SUBSCRIPT INDICATES TYPE.
P2
SUBSCRIPT INDICATES TYPES
0'-0" - 6'-0"
DUCTBANK CALLOUT.
SEE DUCTBANK CABLE AND FEEDER
SCHEDULE THIS SHEET.
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
P
E
E
MH
EXST MH17
C3
ES502
A4
ES502
UT-2
P5
25'-0"
E
E
E
E E
E E
E
E
E
E
E
E
E
E
E
E
E
E
TB
0'-0" - 6'-0"
HH
HH
HH
HH
HH
HH
C1
ES502
(TYP) (TYP)
C1
ES501
P5
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
P5
25'-0"
E L
E C
T R
I C
T
E
P
L A
N
A
R E
A
ES103
P -2
F
-3
TR
A
IN
IN
G A
N D
S
IM
U
LA
TO
R
F A
C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
PLAN
NORTH
SCALE: 1" = 30'
ELECTRICAL SITE PLAN - AREA 3
0 30' 60'
GENERAL NOTES
WORK NOTES
A1
KEYPLAN
AREA 2
AREA 1
AREA 3
PLAN
NORTH
1. PROVIDE 1" EB SCH 20 PVC CONDUIT 18" BFG FOR LIGHTING CIRCUIT.
2. EXISTING TAP BOX. SEE EP602 FOR ONE-LINE DIAGRAM.
3. PROVIDE 2-WAY, 2 X 1 DUCTBANK; SEE DETAIL A4/ES501.
LAW JAB KMS
1. SEE ES501 FOR ELECTRICAL SITE DETAILS.
2. CONNECT SITE LIGHTING VIA LIGHTING CONTROL PANEL. SEE LIGHTING
CONTROL SYSTEM DETAIL B2 SHEET EL503.
A4
ES501
1 9
1 9
A4
ES501
1 (TYP)
LEGEND
DOMESTIC SERVICE WATER LINE
SANITARY SEWER LINE
FIRE HYDRANT
WATER VALVE
SMH
FHYD
WV
SECURITY FENCE
SEWER MANHOLE
FDC
PIV
FIRE DEPARTMENT CONNECTION
POST INDICATOR VALVE
NATURAL GAS LINE
G
UNDERGROUND ELECTRICAL LINE
E
REMOVABLE BOLLARD
DW
SAN
FIRE SERVICE WATER LINE
FW
SINGLE HEAD SITE LIGHT
MH
MANHOLE
EP
UNDERGROUND ELECTRIC SECONDARY
UNDERGROUND ELECTRIC PRIMARY
ES
HH
HANDHOLE, SUBSCRIPT INDICATES TYPE.
P2
SUBSCRIPT INDICATES TYPES
0'-0" - 6'-0"
DUCTBANK CALLOUT.
SEE DUCTBANK CABLE AND FEEDER
SCHEDULE THIS SHEET.
DUCTBANK CABLE AND FEEDER SCHEDULE
# WIRE CONDUIT DESCRIPTION NOTES
3#4/0 1/C, TAPE SHIELD, 15KV EPR 133%
INSULATION CU CONDCUTOR & 1#1 AWG
(600V) GROUND.
5" EB SCH 20 PVC MV POWER
2 SPARE 5" EB SCH 20 PVC MV POWER
3 4#600KCMIL CU & 1#3/0 CU GND 4" EB SCH 20 PVC POWER
4 4#300KCMIL CU & 1#2/0 CU GND 4" EB SCH 20 PVC POWER
5 4#4/0 CU & 1#2 CU GND 4" EB SCH 20 PVC POWER
6 3#4 CU & 1#8 CU GND 4" EB SCH 20 PVC POWER
7 SPARE 3-1/2" EB SCH 20 PVC POWER
8 SPARE 2-1/2" EB SCH 20 PVC POWER
9 SPARE 4" EB SCH 20 PVC POWER
I S
S U
N
S T
R U
C T
I O
N
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
E
E
E
E
E
E E E E E E
HH
HH
HH
HH
EEEEEEEEE
C1
ES502
(TYP)
P3
25'-0"
P3
25'-0"
P3
25'-0"
P3
25'-0"
E L
E C
T R
I C
T
E
P
L A
N
A
R E
B
P T
I O
N
ES104
P -2
F
-3
TR
A
IN
IN
G A
N D
S
IM
U
LA
TO
R
F A
C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
PLAN
NORTH
SCALE: 1" = 30'
ELECTRICAL SITE PLAN - AREA 2 - BID OPTION
0 30' 60'
M A
T C
H
L
I N
E
S
E
1. PROVIDE 1" EB SCH 20 PVC CONDUIT 18" BFG FOR LIGHTING CIRCUIT.
GENERAL NOTES
WORK NOTES
A1
LEGEND
KEYPLAN
1. SEE ES501 FOR ELECTRICAL SITE DETAILS.
2. CONNECT SITE LIGHTING VIA LIGHTING CONTROL PANEL. SEE LIGHTING
CONTROL SYSTEM DETAIL B2 SHEET EL503.
AREA 2
AREA 1
AREA 3
PLAN
NORTH
(TYP)
LAW JAB KMS
DOMESTIC SERVICE WATER LINE
SANITARY SEWER LINE
FIRE HYDRANT
WATER VALVE
SMH
FHYD
WV
SECURITY FENCE
SEWER MANHOLE
FDC
PIV
FIRE DEPARTMENT CONNECTION
POST INDICATOR VALVE
NATURAL GAS LINE
G
UNDERGROUND ELECTRICAL LINE
E
REMOVABLE BOLLARD
DW
SAN
FIRE SERVICE WATER LINE
FW
SINGLE HEAD SITE LIGHT
MH
MANHOLE
EP
UNDERGROUND ELECTRIC SECONDARY
UNDERGROUND ELECTRIC PRIMARY
ES
HH
HANDHOLE, SUBSCRIPT INDICATES TYPE.
P2
SUBSCRIPT INDICATES TYPES
0'-0" - 6'-0"
DUCTBANK CALLOUT.
SEE DUCTBANK CABLE AND FEEDER
SCHEDULE THIS SHEET.
I S
S U
N
S T
R U
C T
I O
N
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
MECH
SHIPPING / RECEIVING / SUPPLY
ISEO
ISEO
ISEO
ELEC
ELEC
ISE LAB
ISEO
CORR
AUDIOVISUAL
MENS
WOMENS
MATSS TRAINING
ISEO
ISEO
TR
MATSS TRAINING
FIRE PUMP
MECH
SHIPPING / RECEIVING / SUPPLY
ISEO
ISEO
ISEO
ELEC
ELEC
ISE LAB
ISEO
CORR
AUDIOVISUAL
MENS
WOMENS
MATSS TRAINING
ISEO
ISEO
TR
MATSS TRAINING
FIRE PUMP
W W W
FP
FP
F
P
G G
G
G G G G G
G
S
S
S
SSSSSSSSSSSS
S
S S
S S
S S
S S
S S
S S
STSTSTSTST
ST
S T
W W W W W W W
W
W
W
W
E
P
E
P
E
S
E
S
E
S
ELEC
G1
UT-1
E
E
E
LSMDP1-15
ELEC
E
E
E
E
E
E
E
E
MTS-LS
E
E S
E
P
MDP1-1,2
E
S
FIRE
PUMP
E
E
E
E
E N
L A
R G
T
E
P
L A
N
A
R E
A
ES401
P -2
F
-3
TR
A
IN
IN
G A
N D
S
IM
U
LA
TO
R
F A
C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
PLAN
NORTH
SCALE: 1" = 30'
ENLARGED SITE PLAN - AREA 1
0 30' 60'
M A
T C
H
L
I N
E
S
E
1. PROVIDE 6-WAY, 3 X 2 DUCTBANK 54" BFG. USE SPARE CONDUIT
FOR REMOTE ANNUNCIATOR CABLING PATHWAY INTO BUILDING.
2. PROVIDE 8-WAY, 4 X 2 DUCTBANK 54" BFG.
3. STUB UP CONDUITS IN ELECTRICAL ROOM AND CONNECT
CONDUCTORS TO SECONDARY SIDE OF ATS. COORDINATE STUB UP
WITH A3/EP401.
4. STUB UP CONDUITS IN ELECTRICAL ROOM AND CONNECT
CONDUCTORS TO MSB1. COORDINATE STUB UP WITH A3/EP401.
5. PROVIDE PAD MOUNTED 1500KVA OIL FILLED TRANSFORMER.
6. PROVIDE 750KW DIESEL GENERATOR WITH A 72 HOUR BELLY TANK.
PROVIDE A PLATFORM 48'' IN WIDTH ON EACH SIDE OF THE
GENERATOR. PLATFORM SHALL INCLUDE STAIRS AND HANDRAILS
PER OSHA REGULATION.
7. PROVIDE 8-WAY, 4 X 2 DUCTBANK. STUB OPPOSITE END UP INTO
MAIN SECTION OF FUTURE SWITCHBOARD.
8. PROVIDE CONCRETE PAD FOR FUTURE SWITCHBOARD FOR DMRTs, TRANSFORMER AND FUTURE TRANSFORMER.
9. PROVIDE 10-WAY, 5 X 2 DUCTBANK INTO HANDHOLE AT 36" BFG.
10. PROVIDE (2) 1" SCH 40 PVC CONDUIT 54" BFG FOR HOT BOX CIRCUIT
AND FIRE ALARM LOW VOLTAGE CABLING.
11. PROVIDE 72" X 48" HANDHOLE.
12. PROVIDE 1" EB SCH 20 PVC CONDUIT 54" BFG FOR LIGHTING
CIRCUIT.
13. PROVIDE 2-WAY, 2 X 1 DUCTBANK 54" BFG.
14. PROVIDE (2) DUPLEX RECEPTACLES INSIDE HOTBOX. PROVIDE ONE
RECEPTACLE PER CIRCUIT.
15. PROVIDE CONDUIT 54" BFG. STUB UP INTO FIRE PUMP
CONTROLLER. COORDINATE FIRE PUMP CONTROLLER LOCATION
WITH A3/EP401.
16. PROVIDE 2-WAY, 2X1 DUCTBANK 54" BFG CONDUIT TO CHILLERS.
PROVIDE CONDUCTORS IN CONDUITS AS INDICATED IN PANEL
EMDP1 SEE SHEET EP704.
17. MOUNT CHILLLER DISCONNECTS TO EQUPMENT RACK.
GENERAL NOTES
WORK NOTES
A1
KEYPLAN
AREA 2
AREA 1
AREA 3
PLAN
NORTH
LAW JAB KMS
A4
ES501
1 2
A4
ES501
DUCTBANK CABLE AND FEEDER SCHEDULE
# WIRE CONDUIT DESCRIPTION NOTES
3#4/0 1/C, TAPE SHIELD, 15KV EPR 133%
INSULATION CU CONDCUTOR & 1#1 AWG
(600V) GROUND.
5" EB SCH 20 PVC MV POWER
2 SPARE 5" EB SCH 20 PVC MV POWER
3 4#600KCMIL CU & 1#3/0 CU GND 4" EB SCH 20 PVC POWER
4 4#300KCMIL CU & 1#2/0 CU GND 4" EB SCH 20 PVC POWER
5 4#4/0 CU & 1#2 CU GND 4" EB SCH 20 PVC POWER
6 3#4 CU & 1#8 CU GND 4" EB SCH 20 PVC POWER
7 SPARE 3-1/2" EB SCH 20 PVC POWER
8 SPARE 2-1/2" EB SCH 20 PVC POWER
9 SPARE 4" EB SCH 20 PVC POWER
6 5 4
9 9 9
A4
ES501
3 3 3 6
3 3 3 9
8 8 8 8 8
8 8 8 8 8
A4
ES501
1. SEE ES501 FOR ELECTRICAL SITE DETAILS.
2. CONNECT SITE LIGHTING VIA LIGHTING CONTROL PANEL. SEE LIGHTING
CONTROL SYSTEM DETAIL B2 SHEET EL503.
A4
ES501
2 2
A4
ES501
7 5
A4
ES501
7 7 7 7
7 7 7 7
A4
ES501
7 5
I S
S U
N
S T
R U
C T
I O
N
MANHOLE, SUBSCRIPT INDICATES POSSIBLE
DEPTHS OF EXISTING DUCTBANK BELOW
FINISHED GRADE.
LEGEND
DOMESTIC SERVICE WATER LINE
SANITARY SEWER LINE
FIRE HYDRANT
WATER VALVE
SMH
FHYD
WV
SECURITY FENCE
SEWER MANHOLE
FDC
PIV
FIRE DEPARTMENT CONNECTION
POST INDICATOR VALVE
NATURAL GAS LINE
G
UNDERGROUND ELECTRICAL LINE
E
REMOVABLE BOLLARD
DW
SAN
FIRE SERVICE WATER LINE
FW
SINGLE HEAD SITE LIGHT
MH
EP
UNDERGROUND ELECTRIC SECONDARY
UNDERGROUND ELECTRIC PRIMARY
ES
HH
HANDHOLE, SUBSCRIPT INDICATES TYPE.
P2
SUBSCRIPT INDICATES TYPES
0'-0" - 6'-0"
CONDUIT STUB UP
DUCTBANK CALLOUT.
SEE DUCTBANK CABLE AND FEEDER
SCHEDULE THIS SHEET.
A4
ES501
6 15
3 3 3
3 3 3 9
A4
ES501
A4
ES501
A4
ES501
5 4
9 9 9
B3
ES501
8 8
A1
ES502
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
TOP OF PAVEMENT SUBGRADE OR GRADE
3"
3"
3"
3" 3" 3" 3"
NOTES:
1.
2.
FOR MEDIUM VOLTAGE DUCTBANKS.
PROVIDE #4/0 AWG
BARE COPPER CONDUCTOR IN
BOTTOM OF DUCTBANK.
3.
USE PLASTIC CONDUIT SPACERS
AT 5'-0" OC.
DUCTBANK IS IDENTIFIED AS FOLLOWS:
3 X 2. FIRST NUMBER INDICATES COLUMNS.
SECOND NUMBER INDICATES ROWS. PROVIDE
DUCTBANK AS INDICATED. DETAIL ALSO APPLIES
TO OTHER DUCTBANK SIZES.
ALTER DUCTBANK CONFIGURATIONS AS REQUIRED
TO PROPERLY ENTER HANDHOLES.
YELLOW WARNING TAPE WITH WIRE,
12" BELOW GRADE
SELECT BACKFILL
PVC CONDUIT
SIZE AS INDICATED
MULTIPLEX
POLYESTER ROPE
ROWS
3000 PSI CONCRETE
M
IN
, U O
N
C O
LU
M
N S
6X6 - W2.9 x W2.9 MESH
1/2" CHAMFER
GRADE
WELL
COMPACTED
GRAVEL BASE
NOTE:
PROVIDE CONDUIT TURN-UPS, CUT OFF 3"
ABOVE SLAB AND INSTALL BUSHINGS. SEAL
VOIDS AROUND CONDUIT WITH WATER AND OIL
RESISTANT CAULKING OR SEALANT.
TRANSFORMER/SWITCH
8"
8" CONCRETE SLAB
4"
6" 8"
140A BAYONET OIL-
IMMERSED
EXPULSION FUSES
ARRESTERS
SURGE
PRIMARY COMPARTMENT
PRIMARY CIRCUIT
GROUND ALL
FOUR BOLLARDS
NOTES:
1. COORDINATE WITH ACTIVITY FOR ADDITIONAL METERING INPUT (GAS, STEAM OR WATER SYSTEMS).
2. MAKE ALL CONNECTIONS USING EXOTHERMIC WELDS.
3. GROUND BUSHING WELL INSERTS PER MANUFACTURER'S INSTRUCTIONS.
CABLE WELL
#4/0 BARE
#4/0 BARE COPPER GROUND
LOOP
ENCIRCLING ENTIRE CONCRETE
PAD. MIN 30" BELOW FINISHED
GRADE AND 30'' FROM PAD.
SECONDARY CIRCUIT
TRANSFORMER BUSHING WELL
OIL-IMMERSED X0
CURRENT-LIMITING FUSES
BUSHING INSERT
PRIMARY NEUTRAL
LOAD
BREAK
CONNECTOR
SECONDARY COMPARTMENT
LOW VOLTAGE CABLE
TERMINATIONS
GROUND PAD (TYP OF 2)
CONCRETE PAD
GRADE
COPPER GROUNDING CONDUCTORS
TO ANTENNA A2/ES502.
GROUND ROD,
TYP
OF 4, 1 AT EACH
CORNER OF PAD.
600V INSULATION
SEE RISER DIAGRAM
EP601
4 POSITION LOAD
BREAK OIL SWITCH
CURRENT TRANSFORMERS
3-POLE FUSE BLOCK
AMI
2'-0" MIN.
AMI METER.
TOP OF
CONCRETE
OR GRADE
TRANSITION COUPLING
4" MAX
18" MIN BELOW SLAB
INCREASE DEPTH AS REQD
TO ALLOW FOR NEC MIN.
BEND RADIUS PROVIDE MIN BEND
RADIUS FOR CONDUIT
IAW NEC.
PVC COATED GRS ELBOW
SCH 40 TO PVC COATED GRS CONDUIT ADAPTER
SCH 40 PVC CONDUIT
PROVIDE REBAR TIES
TO SUPPORT UNDERGROUND
CONDUIT FROM SLAB REBAR 60'' OC.
NOTES:
1. PROVIDE REBAR TIES WHEN LOCATED UNDER SLAB.
ENCIRCLING ENTIRE CONCRETE
#4/0 BARE COPPER GROUND LOOP
PAD. MIN 18" BELOW FINISHED
BUSHING INSERT,
PRIMARY NEUTRAL
PRIMARY CIRCUIT. SEE
RESPECTIVE ES SHEETS
TYP OF 2
MIN
2'-0"
GRADE
CONDUCTORS
COPPER GROUNDING
GROUND ROD, TYP
OF 4, 1 AT EACH
SECONDARY CIRCUIT. SEE
RESPECTIVE ES SHEETS
CORNER OF PAD
#4/0, 600V INSULATION
GRADE
GROUND PAD
CABLE
TERMINATIONS
TYP. OF 2
LOW VOLTAGE
"CLAM-SHELL" ENCLOSURE
OIL-IMMERSED
CURRENT-LIMITING
NEUTRAL CENTER TAP
LOAD BREAK CONNECTOR,
TYP OF 2
TRANSFORMER BUSHING
WELL, TYP OF 2
FUSE
BAYONET OIL-IMMERSED
EXPULSION FUSE
SURGE
ARRESTER
#4/0
BARE
#4/0, 600V
INSULATION
CABLE WELL
A3
ES501
3 POS LOAD
BREAK OIL
SWITCH
AMI
A B
C
AMI METER.
TO ANTENNA C3/ES502.
NOTES:
2. COORDINATE WITH ACTIVITY FOR ADDITIONAL METERING INPUT (GAS, STEAM OR WATER SYSTEMS).
2. MAKE ALL CONNECTIONS USING EXOTHERMIC WELDS.
4. GROUND BUSHING WELL INSERTS PER MANUFACTURER'S INSTRUCTIONS.
1. PROVIDE PAD PER DETAIL A3/ES501.
3"
YELLOW WARNING TAPE, 12" BELOW
GRADE
SELECT BACKFILL
3" 3" 3"
M
IN
, U O
N
3"
3"
3"
PVC CONDUIT
SIZE AS INDICATED
MULTIPLEX
POLYESTER ROPE
3000 PSI CONCRETE
TOP OF PAVEMENT SUBGRADE OR GRADE
FOR MEDIUM VOLTAGE DUCTBANKS.
PROVIDE #4/0 AWG
BARE COPPER CONDUCTOR IN
BOTTOM OF DUCTBANK.
NOTES:
1.
2.
3.
USE PLASTIC CONDUIT SPACERS
AT 5'-0" OC.
DUCTBANK IS IDENTIFIED AS FOLLOWS:
2 X 2. FIRST NUMBER INDICATES COLUMNS.
SECOND NUMBER INDICATES ROWS. PROVIDE
DUCTBANK AS INDICATED. DETAIL ALSO APPLIES TO
OTHER DUCTBANK SIZES.
ALTER DUCTBANK CONFIGURATIONS AS REQUIRED
TO PROPERLY ENTER HANDHOLES.
ROWS
C O
LU
M
N S
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :1
A
M
ES501
S
IT
E D
E
TA
IL
S
KMS
12804257
LAW JAB
NOT TO SCALE
A4
TYPICAL CONCRETE ENCASED DUCT BANK
DETAIL
NOT TO SCALE
A3
TRANSFORMER PAD DETAIL
NOT TO SCALE
A1
THREE PHASE PAD MOUNTED
TRANSFORMER DETAIL
NOT TO SCALE
C4
DIRECT BURIED CONDUIT AND DUCTBANK
RISER DETAIL
NOT TO SCALE
C1
SINGLE PHASE PAD MOUNTED XFMR1
NOT TO SCALE
B3
TYPICAL DUCTBANK DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
SITE LIGHTING
TRANSFORMER
15KVA
7.2KV/12.47KV - 277/480V
1 PHASE
2 #8 IN 1" C 3
FUSED
SAFETY
SWITCH
60A
NEMA 4X-
SS
LIGHTING
PANEL
SITE AND PARKING LIGHT SEQUENCE OF OPERATIONS:
1. LIGHTS SHALL TURN ON WHEN LIGHT LEVELS HAVE DROPPED BELOW
10FC.
2. LIGHTS SHALL TURN OFF WHEN LIGHT LEVELS INCREASE TO 10FC OR
MORE.
PC
PHOTOCELL MOUNTED TO
TOP OF ENCLOSURE OR
CANOPY
12" W X 24" L X 8"
4-POLE LIGHTING
CONTACTOR. MOUNT
INSIDE ENCLOSURE
ENLARGED DETAIL - LIGHTING CONTACTOR PANEL WITH ENCLOSURE
EXTERIOR LIGHTING
1'' PVC COATED RGS CONDUIT
1. INCOMING POWER FROM SWITCH OR SECTIONALIZER CABINET.
2. PHOTOELECTRIC CELL. SEE SEQUENCE OF OPERATION THIS
DETAIL FOR PHOTOELECTRIC CELL OPERATION.
3. BRANCH CIRCUIT TO SITE LIGHTING.
4. SEE DETAIL A1 THIS SHEET FOR RACK DETAIL.
5. ENLARGED DETAIL OF LIGHTING CONTACTOR PANEL THIS DETAIL.
6. PROVIDE MULTI-FUNCTION METER ON TRANSFORMER. CONNECT
TO MCAS ENERGY MONITORING AND CONTROL SYSTEM (EMCS) VIA
BACNET.
7. PROVIDE 1"C FROM AMI METER TO TRANSFORMER METER
COMPARTMENT. PROVIDE PVC UNDERGROUND AND RGS ABOVE
GROUND.
WORK NOTES:
#8
C1
ES501
A1
EP602
. C1
EG501
C4
ES501
PROVIDE 60A
RK5 FUSES.
AMI METER.7
3" CLR
1" MAX.
' P
O
LE
, U O
N
1" MAX (NOTE 2)
M
IN
2' -0
2' -0
M
IN
6' -0
M
IN
NOTES:
ATTACH GROUND TO
LIGHTING STANDARD (TYP)
HANDHOLE
24" DIA, FORMED FOR SMOOTH
SURFACE ABOVE FINISHED GRADE
ANCHOR BOLT
GRADE
SCH 40 PVC
CONDUIT AND
CABLE (AS
INDICATED)
24" DIA AUGERED HOLE
WITH CONCRETE CAST
AGAINST SOIL WALLS
#3 TIES
@12"
6#6
#6
BARE
POLE AS
INDICATED
3 TIES @
AT TOP
COVER, MATCH
FINISH TO POLE
COORDINATE BASE PLATE
AND BOLT HOLE PATTERN
WITH APPROVED POLE.
GROUND ROD
6" MIN.
1. FOR ALL POLE ACCESSORIES, ARMS, ENCLOSURES, BOXES:
PAINT TO MATCH APPROVED POLE FINISH.
2. PROVIDE CONCRETE BASE WITH BLACK AND YELLOW REFLECTIVE
WARNING BANDING 8" FROM TOP.
MOUNT EXTERNAL SPD IN POLE ACCESSIBLE FROM HANDHOLE.
SIDEWALK
HANDHOLE
36"
EXTERNAL
SPD
3.
LOCATE ANTENNA TO
MAXIMIZE RADIO SIGNAL
TRANSMISSION/ RECEPTION
AND TO OPTIMIZE
MAINTAINABILITY
AMI METER
ANTENNA
ROOF
STRAP CONDUIT WITHIN 36 INCHES
OF FITTINGS AND 120 INCHES O.C.
WITH STAINLESS STEEL
FASTENERS INTO WALL
MOUNT ANTENNA TO
WITHSTAND 200 MPH
WIND VELOCITY
BUILDING EXTERIOR
WALL
LIGHTNING ARRESTER WITH
ENCLOSURE PIPE PENETRATION
TO TRANSFORMER. SEE DETAIL A1/ES501.
EAVE
J-BOX WITH 1-1/4"
GROMETTED
FACEPLATE
GROUND WIRE TO BUILDING COUNTERPOISE
HIGH FLEX COAX
CABLE
2.
3.
4.
5.
1.
REQUIRED
BOXES WHEN
STACK
HANDHOLE REQUIREMENTS:
HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE
FIBERGLASS REINFORCING WITH COMPRESSIVE STRENGTH OF NO LESS THAN 10,000
PSI.
COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 15,000 LBS
OVER A 10" X 10" AREA.
PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
PROVIDE WITH (2) 2 1/2" MOUSEHOLES.
PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "TELEPHONE" FOR
TELEPHONE HANDHOLES, OR AS INDICATED.
CRUSHED ROCK
COMPACTED EARTH
TYPE
30" X 48" X 24" DEEP
24" X 36" X 24" DEEP
12" X 24" X 24" DEEP
12" X 18" X 24" DEEP
12" X 12" X 24" DEEP
HANDHOLE SIZING
48" X 48" X 60" DEEP
6"
SURFACE
RESISTANT
SKID
6"
STAINLESS STEEL HEX BOLT
AND WASHER
PULL SLOT
CONCRETE RING
AROUND BOX
6"
10"
COVER
BOX AND
LABEL
4" RIGID GALVANIZED
STEEL PIPE WITH CAP
A P
P R
O X
1-5/8" GALVANIZED STEEL
C-CHANNEL FRAMING
4" RIGID GALVANIZED
STEEL PIPE WITH CAP
1-5/8" GALVANIZED STEEL
UNI-STRUT CHANNEL
1/2" GALVANIZED U-BOLT, TYP.
12"
FINISHED GRADE
CONCRETE
P1001 OR EQUAL
1" FINISHED GRADE
36"
FOR MULTIPLE PIECES OF EQUIPMENT PROVIDE MULTIPLE STEEL PIPE
SUPPORTS AND SPAN C-CHANNEL BETWEEN SUPPORTS. MOUNT
EQUIPMENT TO C-CHANNEL SUPPORTS.
1.
NOTES:
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :2
A
M
ES502
S
IT
E D
E
TA
IL
S
KMS
12804258
LAW JAB
NOT TO SCALE
C3
SITE LIGHTING XFMR-LC PANEL DETAIL
(TYPICAL)
NOT TO SCALE
A4
SITE LIGHTING POLE FOUNDATION (FLUSH
BASE)
NOT TO SCALE
A2
AMI ANTENNA MOUNT DETAIL
NOT TO SCALE
C1
TYPICAL ELECTRICAL HANDHOLE
NOT TO SCALE
A1
TYPICAL EXTERIOR EQUIPMENT MOUNTING
RACK DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
M
TYP
C1
EG501
EG804 A1
EG801
A2
EG803A2
EG802
A1
3 (TYP)
5 6
G1
UT-1
TW18
TW17 TW16 TW15
TW14
TW12
TW11
TW10
TW9
TW8
TW7TW5TW4TW3
TW2
TW1
TW19
TW0
TW21TW22TW23TW24
TW25
TW26
TW6
4' -0
- 8
'-0
8'-0" MAX
6' -0
M
A X
3' -5
E
A V
E
T Y
P
6' -0
M
A X
7'-6" MIN.
TW13
8' -6
M
A X
6'-6" MAX.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :2
A
M
EG101
G R
O U
N D
IN
G
L
IG
H
TN
IN
G P
R O
TE
C
TI
O
N P
LA
N
KMS
12804259
LAW BKG
PLAN
NORTH
A B
C
D
KEY PLAN
1/16" = 1'-0" A1
LIGHTNING PROTECTION PLAN
PLAN
NORTH
8' 16' 32'0'
WORK NOTES
1. SEE SHEET E-001 FOR ELECTRICAL GENERAL NOTES, SYMBOL LEGEND AND
ABBREVIATIONS.
2. PROVIDE A GROUNDING SYSTEM IN ACCORDANCE WITH SHEET EG501 - EG502
AND THE NATIONAL ELECTRIC CODE.
3. PROVIDE FRANKLIN ROD TYPE LIGHTNING PROTECTION SYSTEM WITH A UL
MASTER LABEL. CONTRACTOR TO PROVIDE AND SUBMIT A LIGHTNING
PROTECTION PLAN WITH ALL SUPPORTING DETAILS.
4. DESIGN EXCEEDS NFPA 780 CLASS II REQUIREMENTS. SUBMITTED PLAN SHALL
PROVIDE INDICATED DESIGN AT A MINIMUM AND SHALL NOT BE REDESIGNED
TO A LOWER REQUIREMENT/PERFORMANCE.
5. COORDINATE GROUND ROD LOCATIONS AND COUNTERPOISE PLACEMENT
WITH ALL UNDERGROUND UTILITIES AND STRUCTURES.
6. PROVIDE AIR TERMINALS WITHIN 2' OF ALL ROOF CORNERS.
GENERAL NOTES
1. PROVIDE #4/0 AWG BARE COPPE GROUND COUNTERPOISE 30" BFG. PROVIDE
COUNTERPOISE 18" OUTSIDE OF BUILDING DRIPLINE.
2. PROIVDE 192,000 CIRCULAR MILS ALUMINUM MAIN CONDUCTOR.
3. PROVIDE DOWN CONDUCTOR PER A2/EG501. PROVIDE CONNECTION TO
GROUND ROD PER DETAIL C1/EG501.
4. PROVIDE GROUNDING CONNECTION TO GENERATOR ALTERNATOR WITH #4/0
AWG BARE COPPER CONDUCTOR.
5. PROVIDE BONDING CONNECTION TO INCOMING WATER PIPE WITH #4/0 AWG
BARE COPPER CONDUCTOR.
6. PROVIDE BONDING CONNECTION TO INCOMING GAS PIPE WITH #4/0 AWG BARE
COPPER CONDUCTOR.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
EG401
B1
(28) #1/0 AWG, 4" EMTMGB
ELEC
PATCH PANEL
COMP EQUIP
ROOM
COMP EQUIP
ROOM
COMP EQUIP
ROOM
COMP EQUIP
ROOM
COMP EQUIP
ROOM
COMP EQUIP
ROOM
EG401
B1
SIM
EG401
B1
SIM
EG401
B1
SIM
EG401
B1
SIM
EG401
B1
SIM
EG401
A2
B3
EP502
(8) #1/0 AWG, 2-1/2" EMT
#1/0 AWG,1" EMT
(14) 1/0 AWG, 3" EMT
(7) #1/0 AWG,2" EMT
(5) 1/0 AWG, 2" EMT
(5) 1/0 AWG, 2" EMT
(7) 1/0 AWG, 2" EMT
(1) 1/0 AWG, 2" EMT
(5) 1/0 AWG, 2" EMT
(4) 1/0 AWG, 2" EMT
(5) 1/0 AWG, 2" EMT
(7) #1/0 AWG,2" EMT
TR
TR
ELEC
AUDIOVISUAL
(5) 1/0 AWG, 2" EMT
(5) 1/0 AWG, 2" EMT (5) 1/0 AWG, 2" EMT
(5) 1/0 AWG, 2" EMT (5) 1/0 AWG, 2" EMT
TR
B3
EP502
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :3
A
M
EG102
G R
O U
N D
IN
G
C O
N D
U C
TO
R
R O
U
TI
N G
P
LA
N
KMS
12804260
LAW JAB
1/16" = 1'-0" A1
FLOOR PLAN - OVERALL FMS GROUNDING
8' 16' 32'0'
PLAN
NORTH
1. SEE SHEET E-001 FOR ELECTRICAL GENERAL NOTES, SYMBOL LEGEND AND
ABBREVIATIONS.
2. PROVIDE A GROUNDING SYSTEM IN ACCORDANCE WITH SHEET EG501 - EG502
AND THE NATIONAL ELECTRICAL CODE.
3. DO NOT SPLICE GROUNDING CONDUCTORS. PROVIDE DIRECT CONNECTION
FROM GROUND BARS TO MAIN GROUND BAR; SEE C1/EG501 AND C1/EG701.
GENERAL NOTES
1. PROVIDE EXOTHERMIC CONNECTION OF BONDING CONDUCTORS TO MGB.
2. PROVIDE EXOTHERMIC CONNECTION AT TELECOM GROUND BAR IN ROOM.
WORK NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
1 2 3 4 5 6 7
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
16 17 18 19 20
21 22
Q
R
T
U
V
TYP
A4
EG505
TYP
A1
EG505
S
208 215
206205204
211 210
223 225
226224
122107
130 228
161160
155 147
231232
177 176
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :3
A
M
EG103
S
TR
U C
TU
R
A L
S
TE
E L
G R
O U
N D
IN
G
P
LA
N
KMS
12804261
LAW JAB
1/16" = 1'-0" A1
STRUCTURAL STEEL GROUNDING PLAN
1. SEE SHEET E-001 FOR ELECTRICAL GENERAL NOTES, SYMBOL LEGEND AND
ABBREVIATIONS.
2. PROVIDE A GROUNDING SYSTEM IN ACCORDANCE WITH SHEET EG501 - EG502
AND THE NATIONAL ELECTRIC CODE.
GENERAL NOTES
ROOM SCHEDULEROOM SCHEDULE ROOM SCHEDULE
172 CONFERENCE
173 MENS
174 WOMENS
175 CORR
176 PSO
177 APSO / GSSO
178 PSO SERVER
179 PSO SEC CONF
180 BREAK
181 JANITOR
182 FMS REPAIR SHOP /
MAINT STOR
183 SIM / HELMET PAD
STOR
184 CONFERENCE
185 MANTRAP
186 CORR
187 WHITE CELL EVAL
188 AUDITORIUM
189 Space
189 STORAGE
190 STAIR
191 AUDIOVISUAL
192 MENS
193 WOMENS
194 CORR
195 SHIPPING /
RECEIVING / SUPPLY
196 CORR
197 MATSS TRAINING
198 MATSS TRAINING
199 TR
200 ISEO
201 ISEO
202 ISEO
203 ISE LAB
204 ISEO
205 ISEO
206 ISEO
207 SITCC / JMPS
208 REPRO
209 EVAL / PROGRAM /
MATSS SUPPORT
210 MATSS
211 MATSS
212 MATSS
CONFERENCE
213 JPO
214 MATSS
215 MATSS
216 LM
217 COMMANDER
218 TRAINING OPS MGR
219 CONTRACT PILOT
INST MGR
220 TR
221 BREAK
222 MOTHER'S RM
223 WOMENS
224 LOCKER
225 MENS
226 LOCKER
227 JAN
228 MECH / ELEC
229 MECH / ELEC
230 MECH / ELEC
231 MECH
232 ELEC
233 MECH
234 ELEC
235 FIRE PUMP
236 Space
ROOM SCHEDULE
101 VEST
102 LOBBY
103 TLT
104 CORR
105 RECEPTION
106 MANTRAP
107 SEC OFFICE
108 SEC BADGE
109 SEC MGR
110 SEC SUPPLY / EQUIP
111 CBT
112 CORR
113 PATCH PANEL
114 CORR
115 COMP SUPPORT
116 MATSS MISSION
PLANNING
117 NECC ADMIN
119 COMMAND CTR &
OBSERV
120 IAM / ISSO
121 CORR
122 BRIEF
123 SERVER
124 DEBRIEF
125 IOS ROOM
126 COMP EQUIP ROOM
127 FMS/OTW
128 CORR
129 ELEC
130 TR
132 CORR
133 BRIEF
134 SERVER
135 DEBRIEF
136 IOS ROOM
137 COMP EQUIP ROOM
138 FMS/OTW
139 CORR
139 Space
140 BRIEF
141 SERVER
142 DEBRIEF
143 IOS ROOM
144 COMP EQUIP ROOM
145 FMS/OTW
146 STO
147 CORR
148 CORR
149 BRIEF
150 SERVER
151 DEBRIEF
152 IOS ROOM
153 COMP EQUIP ROOM
154 FMS/OTW
155 CORR
156 CORR
157 BRIEF
158 SERVER
159 DEBRIEF
160 IOS ROOM
161 COMP EQUIP ROOM
162 FMS/OTW
163 CORR
164 CORR
165 BRIEF
166 SERVER
167 DEBRIEF
168 IOS ROOM
169 COMP EQUIP ROOM
170 FMS/OTW
171 DMRT
8' 16' 32'0'
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
J
K
19 20 21 22
TO
MGB
TYP
C3
EG503
#6
#6
#6
A2
EG503
A2
EG503
A2
EG503
A4
EG504
POWER TRENCH
COMMS TRENCH
#2
#2
#2
#2
TYP
C1
EG503
GB
GB
GB GB
GB
CRAH-2-126B
CRAH-2-126A
H-2-126
#61
GB
A4
EG504
A4
EG504
1 #6
GB
TELECOM BONDING BACKBONE (TBB)
CABLETRAY BUS CONDUCTOR
BONDING CONDUCTOR
BONDING CONNECTION
F
G
17 18
M
G B
TYP
C3
EG503
#6
#6
#6 C1
EG503
CRAH-1-113
C4
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 12 APRIL 2018
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
C
I C
O R
E N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
IR
G
IN
IA
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
O R
T H
C A
R O
L
IN
A
AS NOTED
P -2
F
-3
T R
A
IN
IN
G
A N
D S
IM
U
L A
T O
R F
A C
IL
IT
Y
1305 EXECUTIVE BLVD.
SUITE 160
CHESAPEAKE, VA 23320
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
1596300
CJC/RMS
469C
R e v it P ro je c ts
\B L D
G P
-1
-E
-C e n tr a l_ la w o o d ru ff b u rn s m c d .c o m
.r v t
/6
/2
:1 :4
A
M
EG401
E N
LA
R
G E
D P
LA
N
S
G R
O U
N D
IN
G
B
O N
D
IN
G
KMS
12804262
LAW JAB
1/4" = 1'-0" (EG102)
B1
ENLARGED PLAN - GROUNDING & BONDING -
TYPICAL FMS/OTW POD
LEGEND
1. PROVIDE IRREVERSIBLE MECHANICAL BONDING CONNECTION TO MESH BN
UNDERFLOOR.
2. MOUNT GROUND BUS TO SIDEWALL IN ELECTRICAL TRENCH.
WORK NOTES
GENERAL NOTES
1. PROVIDE CORE DRILL THROUGH ACCESS FLOOR WHEN CONDUCTORS ARE TO
PASS FROM UNDER FLOOR TO ABOVE FLOOR.
3/8" = 1'-0" (EG102)
A2
ENALRGED PLAN - GROUNDING & BONDING -
PATCH PANEL 113
0' 2' 4' 6'
2' 4' 8'0'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/
/2
N40085-20-R-0015 rosie.shanks Typewritten Text
MCAS CP
1/2" X 24"
ALUMINUM SAFETY
AIR TERMINAL, UON
CLASS II
ALUMINUM MAIN CONDUCTOR
ALUMINUM STANDING SEAM
POINT BASE
ALUMINUM
CABLE HOLDER
A B
O V
E F
L O
O R
GROUND CONDUCTOR
GREEN STRANDED
IRREVERSIBLE CRIMP
COORDINATE MOUNTING HARDWARE
BUILDING WALL
NOTES:
2 HOLE LUG
LOCKWASHER
GROUNDING CONNECTION
EXTERIOR TOOTH
HEX NUT
FLAT WASHER
HEX BOLT DIA AS REQD
TOP VIEW
HEX HEAD BOLT WITH NUT AND
LOCK WASHERS SIZE AS
REQUIRED.
LUGS TO BE 2-HOLE TYPE.
GROUND BAR OR
METAL ENCLOSURE
GREEN STRANDED
GROUND CONDUCTOR
1. PROVIDE NUMBER AND SIZE OF CONNECTORS AND GROUND CONDUCTORS AND LENGTH OF GROUND BAR AS
REQUIRED FOR EACH GROUND BAR LOCATION.
2. PROVIDE GROUND BUS IN ACCORDANCE WITH EIA/TIA-607 GROUNDING STANDARDS.
3. DETAIL IS USED AN EXAMPLE. HOLE SIZE, SPACING AND PATTERN SHALL BE IN ACCORDANCE WITH TIA-607B.
4. PROVIDE UL LISTED GROUND BUS.
GREEN STRANDED
COPPER…