About this file

This solicitation is for design-bid-build services for a P-204 F-35 Training and Simulator Facility at Marine Corps Air Station Cherry Point, North Carolina. Proposals are due on April 9, 2020 with inquiries by March 30, 2020. The magnitude of construction is estimated between $25-100 million. The NAICS code is 236210 for industrial building construction, and the small business size standard is $39.5 million. This is an unrestricted solicitation with full and open competition.

The selected contractor will be responsible for providing design-bid-build services to construct a new F-35 Training and Simulator Facility at MCAS Cherry Point. Proposals are due in early April with inquiries by the end of March. The project value is estimated between $25-100 million.

View the file

Other files

File Type Posted
Amendment 0009.pdf PDF
Amendment 8 P204 Drawings-Specs.pdf PDF
Amendment 0008.pdf PDF
Amendment 8 Attachment I -Updated Price Proposal Form_REVISED.pdf PDF
Amendment 0007-Update Proposal Submission.pdf PDF
Amendment 6 Attachment I-REVISED Price Proposal Form.pdf PDF
Amendment 0006.pdf PDF
Amendment 5.pdf PDF
Amendment 0005 PPI Responses.pdf PDF
Amendment 5 PPI-31_P-204 Soil Guidance Section for NEPA-PAMS.pdf PDF
Amendment 5 M-602.pdf PDF
Amendment 4 B286_Photos.zip ZIP file
Amendment 4 P204 B286 B4038 B4162 Existing FFE List Floor Plans.pdf PDF
Amendment 4 B4038_2of2.zip ZIP file
Amendment 0004.pdf PDF
Amendment 4-B286_As-Built Drawings.pdf PDF
Amendment 4 P204 FF E List for Contractors.xlsx XLSX spreadsheet
Amendment 4 B4038_1of2.zip ZIP file
Amendment 3-Attachment I - Price Proposal Form_REVISED.docx DOCX document
Amendment 3-P-204_Hazardous Survey.pdf PDF
Amendment 3-B4038_As-Built Drawings_01.pdf PDF
Amendment 3-P-204_Site Investigation Report.pdf PDF
Amendment 0003.pdf PDF
Amendment 3-B4038_As-Built Drawings_02.pdf PDF
P-204_Amendment-003.pdf PDF
Amendment 3-B4162_As-Built Drawings.pdf PDF
Amendment 0002 Extend Proposal Due Date.pdf PDF
Amendment 0001 Site Visit Cancelled.pdf PDF
Attachment I - Price Proposal Form.docx DOCX document
Attachment D - Small Business Subcontracting Record.docx DOCX document
Attachment F - Past Performance Questionnaire.docx DOCX document
1596300dwg17of26_Interiors.pdf PDF
Attachment E - Small Business Participation and Commitment Strategy.docx DOCX document
1596300dwg03of26_Civil-C.pdf PDF
1596300dwg24of26_Electrical.pdf PDF
1596300dwg11of26_Civil-CS.pdf PDF
1596300dwg25of26_Telecom-AV.pdf PDF
1596300dwg14of26_Structural.pdf PDF
1596300dwg26of26_Telecom.pdf PDF
Attachment B - SECNAV 5512.pdf PDF
1596300spc02of04.pdf PDF
1596300dwg09of26_Civil-CG.pdf PDF
Attachment J - Site Visit Map to B-163.pdf PDF
1596300dwg16of26_Architectural.pdf PDF
Attachment A - Pre-Proposal Inquiries Form.xlsx XLSX spreadsheet
1596300dwg23of26_Electrical.pdf PDF
1596300dwg06of26_Civil-CE.pdf PDF
RFP- P204.pdf PDF
Attachment G - Small Business Subcontracting Plan.docx DOCX document
1596300dwg01of26_General.pdf PDF
Show 40 more

Latest 50 of 69 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS IN

THIS SET. SHEET SPECIFIC NOTES ARE INDICATED ON EACH SHEET

UNDER GENERAL SHEET NOTES.

2. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR

REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL

SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS

REQUIRED BY CODE.

3. INSTALL ALL MECHANICAL EQUIPMENT AN APPURTENANCES IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, THIS

CONTRACT'S DOCUMENTS, AND APPLICABLE CODES AND

REGULATIONS.

4. PROVIDE VIBRATION ISOLATORS FOR ALL MECHANICAL EQUIPMENT

TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.

5. PROVIDE ACCESS PANELS IN WALLS AND CEILINGS, WHERE

REQUIRED, TO SERVE FIRE DAMPERS, VALVES, SMOKE DETECTORS,

AND OTHER CONCEALED MECHANICAL EQUIPMENT THAT REQUIRES

ROUTINE MAINTENANCE. ACCESS PANELS MUST BE LARGE ENOUGH

TO ALLOW PROPER CLEARANCE FOR ACCESS DOORS.

6. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT,

ETC., SHALL BE FIRE STOPPED.

7. LOCATE ALL HORIZONTAL DUCTWORK ABOVE THE SUSPENDED

CEILINGS UNLESS OTHERWISE INDICATED.

8. ALL 90 DEGREE RECTANGULAR MITERED DUCT ELBOWS IN THE

SUPPLY AND RETURN DUCT SHALL HAVE TURNING VANES.

9. PROVIDE PIPE SLEEVES FOR ALL PIPING PENETRATIONS THRU WALLS

AND FLOORS. EACH PIPE SHALL BE SEPARATELY SLEEVED. PROVIDE

CONTINUOUS SEALANT JOINT AROUND PIPE SLEEVE, BOTH SIDES OF

WALL, WATERTIGHT.

10. PROVIDE P-TRAPS IN CONDENSATE DRAIN PIPING AT EACH AHU

UNLESS THE AHU IS EQUIPPED WITH AN INTERNAL TRAP.

11. MOUNT THERMOSTATS, HUMIDISTATS, BSS, AND ESS 48 INCHES

ABOVE THE FINISHED FLOOR UNLESS OTHERWISE INDICATED. REFER

TO ELECTRICAL DRAWINGS FOR LOCATION OF LIGHT SWITCHES AND

COORDINATE.

12. PIPING SHOWN ON DRAWINGS IS SCHEMATIC IN NATURE AND DOES

NOT SHOW ALL FITTINGS, ELBOWS, AND COMPONENTS FOR DETAILED

CONNECTION. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ANY

ADDITIONAL FITTINGS, ELBOWS, AND COMPONENTS TO PROVIDE A

COMPLETE OPERABLE SYSTEM. PIPING CONNECTIONS SHALL ALLOW

FOR ROUTINE MAINTENANCE INCLUDING REMOVAL AND

REPLACEMENT OF FILTERS AND COILS.

13. DUCT RUNOUT SIZE TO DIFFUSER, REGISTER, OR GRILLE SHALL BE

SIZE OF DIFFUSER, REGISTER, OR GRILLE NECK AS INDICATED ON

DRAWINGS.

14. PIPE RUNOUTS SHALL BE SIZED AS INDICATED ON EQUIPMENT

SCHEDULES.

15. AFTER THE PIPING IS INSULATED, PROVIDE FACTORY-FABRICATED

PIPE LABELS AS SPECIFIED, WITH DIRECTION OF FLOW ARROWS, ON

THE FOLLOWING PIPING, AT 10 FOOT ON CENTER ON THE PIPING

MAINS AND 5 FOOT ON CENTER ON THE BRANCH RUNOUTS FROM THE

MAINS.

16. CONDENSATE DRAIN PIPING SHALL HAVE CLEANOUTS INSTALLED AT

EACH CHANGE IN DIRECTION GREATER THAN 45 DEGREES. WHERE

MORE THAN ONE CHANGE OF DIRECTION OCCURS IN A RUN OF

PIPING, ONLY ONE CLEANOUT SHALL BE REQUIRED FOR EACH 45 FEET

OF DEVELOPED LENGTH. COMBINATION OF WYE AND 1/8 BENDS

SHALL BE USED IN LIEU OF TEES.

17. INSTALL MECHANICAL DUCT AND PIPE HANGERS SUCH THAT THE

SINGLE POINT DEAD LOAD APPLIED TO ANY STRUCTURAL MEMBER

SHALL NOT EXCEED 250 LBS. PROVIDE TRAPEZE HANGARS TO

DISTRIBUTE THE LOAD BETWEEN STRUCTURAL MEMBERS WHERE A

SINGLE HANGER EXCEEDS THE LIMITATIONS.

18. DESIGN AND PROVIDE EQUIPMENT AND MECHANICAL COMPONENT

MOUNTINGS WEIGHING 31 POUNDS OR MORE TO RESIST FORCES OF

0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION

AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD

DIRECTION.

GENERAL MECHANICAL NOTES

° DEGREES

Ø DIAMETER

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AP ACCESS PANEL

APD AIR PRESSURE DROP

AS AIR SEPARATOR

ATFP ANTITERRORISM FORCE PROTECTION

BD BALANCING DAMPER

BHP BRAKE HORSEPOWER

BOD BOTTOM OF DUCT

BTUH BRITISH THERMAL UNITS PER HOUR

C COMMON

CAV CONSTANT AIR VOLUME

Cv LOSS COEFFICIENT

CFM CUBIC FEET PER MINUTE

CLG CEILING

COP COEFFICIENT OF PERFORMANCE

CRAH COMPUTER ROOM AIR HANDLING UNIT

CU CONDENSING UNIT

CHW CHILLED WATER

DB DRY BULB

DDC DIRECT DIGITAL CONTROL

DEG DEGREE

DOAU DEDICATED OUTSIDE AIR UNIT

DX DIRECT EXPANSION

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICENCY RATIO

EF EXHAUST FAN

EFF EFFECTIVENESS

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

F FARENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FT FEET

FT WG FEET WATER GAUGE

GPM GALLONS PER MINUTE

H HUMIDIFIER

HB HUMIDIFIER BLOWER

HGT HEIGHT

HP HEAT PUMP, HORSEPOWER

HR HOUR

HHW HEATING HOT WATER

HX HEAT EXCHANGER

kW KILOWATT

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LV LOUVER

LWT LEAVING WATER TEMPERATURE

LPS LOW PRESSURE STEAM (< 15PSIG)

MAX MAXIMUM

MIN MINIMUM

NC NORMALLY CLOSED, NOISE CRITERIA

NO NUMBER, NORMALLY OPEN

OA OUTSIDE AIR

PH PHASE

PSI POUNDS PER SQUARE INCH

QTY QUANTITY

RA RETURN AIR

RAF RELIEF AIR FAN

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

SA SUPPLY AIR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SIM SIMILAR

SP STATIC PRESSURE

TYP TYPICAL

UH UNIT HEATER

UOI UNLESS OTHERWISE INDICATED

V VOLTS

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

W WIDTH

WB WET BULB

WPD WATER PRESSURE DROP

MECHANICAL ABBREVIATIONSMECHANICAL PIPING LEGEND

CHILLED WATER SUPPLY PIPING

CHILLED WATER RETURN PIPING

CONDENSATE DRAIN PIPING

HOT WATER SUPPLY PIPING

HOT WATER RETURN PIPING

CHWR

CHWS

CD

HHWR

HHWS

MECHANICAL SYMBOLS

POINT OF CONNECTION

ROOM TAG

DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL TAG

ROOM NAME

ROOM NUMBER

WALL / PARTIAL

BUILDING SECTION

TAG

SECTION NUMBER

SHEET WHERE DRAWN

GENERAL PROJECT SYMBOLS

BUILDING SECTION

TAG

SECTION NUMBER

SHEET WHERE DRAWN

BUILDING

NEW WORK

KEYNOTE TAG

KEYNOTE NUMBER

DETAIL NUMBER

SCALE

SHEET

REFERENCED

FROM

PLAN

NORTH

SCALE

TRUE NORTH

SHEET

REFERENCED

FROM

Sim

SIMILAR (USED AS NEEDED)

AIR DISTRIBUTION

DEVICE IDENTIFICATION

MARK

175 CFM

SA-#

AIR FLOW

QTY

(?)# Ø

NECK SIZE

BALANCING VALVE

MV

AV

MANUAL AIR VENT - SEE SPECIFICATIONS

PRESSURE GAUGE

THERMOMETER

RELIEF VALVE, SAFETY OR THERMAL

Y-TYPE STRAINER

SELF CONTAINED PRESSURE

REMOVABLE CAP

REDUCING (REGULATING) VALVE

CONTROL VALVE

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

3 - WAY VALVE

BALL VALVE

AUTOMATIC AIR VENT ASSEMBLY

BLIND FLANGE

REDUCER (CONCENTRIC)

UNION

PIPE LINE ACCESSORIES

FOR APPROPRIATE VALVE TYPE.

FLEX CONNECTION

TEST CONNECTION

REDUCER (ECCENTRIC)

WITH EQUIPMENT

COMPONENTS TO BE FURNISHED

PUMP

MOTORIZED CONTROL VALVEM

METERM

BACKFLOW PREVENTION ASSEMBLY

PRESSURE REDUCING VALVE

BACKFLOW PREVENTION ASSEMBLYBP

AIRFLOW MONITORING STATIONAMS

VAV-

VARIABLE AIR VOLUME TERMINAL BOX

(SHUT OFF)

BD

BACKDRAFT DAMPER

MANUAL BALANCE DAMPER

CONTROL DAMPER, MOTOR OPERATED

FLEXIBLE DUCT CONNECTION

RECTANGULAR ELBOW W/TURNING VANES

RISE IN RESPECT TO AIR-FLOW

DROP IN RESPECT TO AIR-FLOW

SQUARE OR RECTANGULAR TO

ROUND TRANSITION

SUPPLY OR OUTSIDE AIR DUCT SECTION

RETURN OR EXHAUST AIR DUCT SECTION

SQUARE OR RECT SUPPLY DIFFUSER

THERMOSTAT

HUMIDISTAT

HVAC LEGEND

ACCESS DOOR (AD), ACCESS PANEL (AP)

AD

FIRE/SMOKE (F/SD)-

SMOKE (SD) -

DAMPERS:

AD

AD

ROUND FLEXIBLE DUCT

(5'-0" MAX LENGTH)

RECTANGULAR RADIUS ELBOW

RETURN AIR DIFFUSER

EXHAUST AIR DIFFUSER

H

T

UP

DN

FIRE (FD)-

VAV-

VARIABLE AIR VOLUME TERMINAL BOX

(SHUT OFF) WITH HEATING COIL

12x10 RECTANGULAR DUCT DIMENSIONS (IN)

12/10 FLAT OVAL DUCT DIMENSIONS (IN)

12ø ROUND DUCT DIMENSION (IN)

HVAC DESIGN CRITERIA

LOCATION: CHERRY POINT MCAS, NC LATITUDE:

LONGITUDE:

ELEVATION:

CLIMATE ZONE: 3A34.90 N

76.88 W

29 FT

STANDARD OUTDOOR DESIGN CONDITIONS:

WINTER DESIGN DRY BULB (99.6%):

SUMMER DESIGN DRY BULB (0.4%):

SUMMER DESIGN WET BULB (0.4%):

24°F

93°F

78°F

DEHUMIDIFICATION

HUMIDITY RATIO (0.4%):

DEHUMIDIFICATION DRY

BULD (0.4%):

149 GR/LB

85°F

ROOM TYPE: STANDARD INDOOR DESIGN CONDITIONS:

SUMMER

DESIGN DRY

BULB:

SUMMER

DESIGN

HUMIDITY:

WINTER

DESIGN

DRY BULB:

WINTER

DESIGN

HUMIDITY:

TYPICAL SPACES: OFFICES, CONFERENCE,

CLASSROOM, CORRIDOR, BATHROOMS

FMS/OTW SIMULATOR ROOMS

FMS COMPUTER EQUIPMENT ROOMS

MECHANICAL/ELECTRICAL ROOMS

78°F 50% RH 68°F

WMO# 723090

68°F 50% RH 68°F

72°F 50% RH 72°F

80°F 55°F

*UC - UNCONTROLLED

*NC - HUMIDITY NOT DIRECTLY CONTROLLED

50% RH

UC*

50% RH

TELECOM ROOMS 72°F 50% RH 72°F UC*

50% RH UC*

VESTIBULES UC* 50°FUC* UC*

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

M-001

LE

G

E N

D , A

B R

E V

IA

TI

O N

S A

N D

N O

TE

S

CD

12804180

RMB RLS

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

DONALD ELLIOT

(BY EMAIL 08JAN2020)

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 1718 19 2015 21 22

Q

R

S

T

U

V

OPEN STORAGE SECRET

TEMPORARY SECURE AREA

SECURE AREA

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :2

P

M

M-002

M E

C H

A N

IC

A

L D

U C

TW

O

R K

P

LA

N

F

IR

S T

F

LO

O R

S E

C U

R E

B O

U N

D A

R

IE

S

CD

12804181

RMB RLS

PLAN

NORTH

A B

C

D

KEY PLAN

1/16" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR SECURE AREAS

8' 16' 32'0'

PLAN

NORTH

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17 18 19 2015 21 22

Q

R

S

T

U

V

OPEN STORAGE SECRET

TEMPORARY SECURE AREA

SECURE AREA

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :3

P

M

M-003

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R S

E C

U R

E A

R E

A S

CD

12804182

RMB RLS

PLAN

NORTH

8' 16' 32'0' PLAN

NORTH

A B

C

D

KEY PLAN

1/16" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR SECURE AREAS

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

208 215

206205

2 209

211 210

203 234

226224

185 108

163 131

155 147

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17 18 19 2015 21 22

Q

R

S

T

U

V

176177

MATCHLINE SEE SHEET MH113

MATCHLINE SEE SHEET MH114

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :5

P

M

MH110

M E

C H

A N

IC

A

L D

U C

T W

O R

K P

LA

N

F

IR

S

T F

LO

O

R O

V E

R A

LL

CD

12804183

RMB RLS

PLAN

NORTH

8' 16' 32'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/16" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR OVERALL

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

WORK NOTES

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

V A

V -0

VAV-025

VAV-026

VAV-028

VAV-017

VAV-034

VAV-033

VAV-035

VAV-036

VAV-037

VAV-038

VAV-039

FCU-1-234

FCU-1-195

VAV-023

VAV-024

VAV-032

VAV-022

VAV-021

VAV-020

VAV-031

1 2 3 4 5 6

C

D

E

FG

H

I

J

K

L

M

N

O

P

M-403 A1

10ø CD-1

220 CFM 8x8 RG-1

200 CFM

6x6 RG-1

70 CFM

10ø CD-1

270 CFM

10ø CD-1

270 CFM

12x12 RG-1

480 CFM

6ø CD-1

90 CFM 6x6 RG-1

80 CFM

6ø CD-1

90 CFM

6x6 RG-1

90 CFM

6x6 RG-1

90 CFM

6ø CD-1

90 CFM

6ø CD-1

70 CFM

8ø CD-1

160 CFM

8ø CD-1

160 CFM

8ø CD-1

155 CFM

8ø CD-1

155 CFM

10x10 RG-1

270 CFM

12x12 RG-1

420 CFM

8ø CD-1

160 CFM

8ø CD-1

100 CFM

8x8 RG-1 (2)

100 CFM

8ø CD-1

100 CFM

10x8 SD-1 (2)

270 CFM

10ø CD-1 (2)

275 CFM

12x12 RG-1

490 CFM

8ø CD-1

100 CFM

8ø CD-1

100 CFM

8x8 RG-1 (2)

100 CFM

8ø CD-1

130 CFM

8x8 RG-1

120 CFM

8x8 RG-1

100 CFM

8ø CD-1

100 CFM

8ø CD-1

100 CFM

8x8 RG-1

100 CFM

8ø CD-1

100 CFM

10ø LSD-1 (4)

205 CFM

10ø LSD-1 (4)

200 CFM

10ø LSD-1 (4)

205 CFM

10ø LSD-1 (4)

200 CFM

16x16 RG-1 (2)

810 CFM

16x16 RG-1 (2)

810 CFM

8x8 RG-1

140 CFM

6ø CD-1

70 CFM

8ø CD-1

100 CFM

8ø CD-1 (4)

195 CFM

14x14 RG-1

690 CFM

8ø CD-1

140 CFM

8x8 RG-1

120 CFM

8ø CD-1

100 CFM

8x8 RG-1

100 CFM

6ø CD-1

90 CFM

6x6 RG-1

90 CFM

6ø CD-1

55 CFM

6ø CD-1

55 CFM

10x8 SD-1 (2)

270 CFM

6x6 RG-1

70 CFM

10x10 SA

10x10 SA

8x10 RA

12x14 RA

10x12 SA

14/12 SA

8x8 SA 8x8 RA

16/14 SA

18x16 RA 20x18 RA 24x22 RA

8x8 SA10x8 SA

28/24 SA

14x14 SA

16x16 SA

14x12 SA

14x14 SA 16x16 SA

14x12 SA

/2

S

A x2

R

A x2

R A

18x18 OA x2

R

A

28x20 RA x1

R

A

16x16 RA

8x8 RA

12x10 SA

8x10 SA

12x12 RA

8x10 SA

8ø SA

10ø SA

14/12 SA

8x8 SA

12x10 SA

12x10 SA

6x8 SA

8x8 SA

10x12 SA

8x10 SA

8x8 SA

8x8 RA

14x12 SA

8x10 SA 8x8 RA

24x22 RA

42x36 RA

M3 M3 M3

M3

FCU-5-199

16x14 RG-2

930 CFM

12x10 SD-1 (2)

465 CFM

UH-1

UH-2

8ø SA

36/28 SA

32/28 SA

10ø SA

26/22 SA

20/18 SA

CAV-011

SP

6ø LSD-1 (4)

90 CFM

6ø LSD-1

100 CFM

M39

M68

M60

18x16 EA

30x24 RA

8x8 SA

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :5

P

M

MH111

M E

C H

A N

IC

A

L D

U C

T W

O R

K P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

A

CD

12804184

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR - AREA A

ROOM SCHEDULE

NUMBER NAME

104 CORR

195 SHIPPING / RECEIVING / SUPPLY

196 CORR

197 MATSS TRAINING

198 MATSS TRAINING

199 TR

200 ISEO

201 ISEO

202 ISEO

203 ISE LAB

204 ISEO

205 ISEO

206 ISEO

207 SITCC / JMPS

208 REPRO

209 EVAL / PROGRAM / MATSS SUPPORT

210 MATSS

211 MATSS

212 MATSS CONFERENCE

213 JPO

214 MATSS

215 MATSS

216 LM

217 COMMANDER

218 TRAINING OPS MGR

219 CONTRACT PILOT INST MGR

233 MECH

234 ELEC

235 FIRE PUMP

M3 PROVIDE SECURE DUCT PENETRATION PER DETAIL A1 ON

SHEET M-507.

M39 12"x12" BELL MOUTH RETURN. BALANCE RA DAMPER TO 430

CFM.

M60 DAMPER SHALL BE PROVIDED IN VERTICAL DUCT.

M68 PROVIDE STATIC PRESSURE SENSOR.

REF. A1/M-403

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

A

T C

H L

IN

E

S E

E S

H E

E T

M H

M A

T C

H L

IN

E

S E

E S

H E

E T

M H

111227

226224

116 117

VAV-029

VAV-030

VAV-019

VAV-018

VAV-016

VAV-001

FCU-7-101

CRAH-1-113

VAV-002

V A

V -0

VAV-004

VAV-007

VAV-008

VAV-010

6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17 18 19 2015 21 22

M-401 A1 x2

R

A x2

R A

8ø CD-1 (4)

170 CFM

10x10 RG-1

310 CFM

12x12 SA

8x10 SA

24x22 RA

16x14 RA

12x12 RG-1

520 CFM

8ø CD-1 (2)

140 CFM

8ø CD-1 (2)

145 CFM

8x10 SA

12x10 SA

10ø SA

6ø CD-1

50 CFM

6ø CD-1

50 CFM

8x8 SA

6ø CD-2

50 CFM

6ø CD-2

50 CFM

178 179

FCU-2B-191

12x10 SA

12x12 RG-2

510 CFM

10x8 SD-1 (2)

255 CFM

12x12 RA

FCU-1-232

10x8 SD-1 (2)

270 CFM

12x10 SA

6ø CD-1

50 CFM

8x8 SA

16/14 SA

6ø CD-1

70 CFM

6x6 RG-1

70 CFM

8ø CD-1

100 CFM

6ø CD-2

50 CFM

6ø CD-2

50 CFM6ø CD-2

50 CFM

6ø CD-2

50 CFM

6ø CD-2

50 CFM

10x10 SA

6x6 RG-1

70 CFM

6x6 RG-1

80 CFM

6ø CD-1

80 CFM

14x12 SA

10x10 SA

8x8 SA 8x8 SA

8x8 SA

6ø LSD-1 (4)

95 CFM

6ø LSD-1 (3)

190 CFM

12x12 RG-1

570 CFM

12x10 SA

14x14 RG-1 (2)

685 CFM

8ø LSD-1 (4)

155 CFM

12x12 SA x1

S

A

12x12 SA

6ø CD-1

50 CFM

6ø CD-1

100 CFM

(TYP)(TYP)

18/16 SA

16/14 SA

12/10 SA

14x14 RG-1

740 CFM

14x14 RG-1

740 CFM 18x16 RA

6ø CD-1

90 CFM

6x6 RG-1

50 CFM

8ø CD-1 (2)

200 CFM

10x10 SA

12x12 SA

6ø CD-1

50 CFM

8x8 RG-1

220 CFM

8ø CD-1

125 CFM

8ø CD-1

125 CFM

8x8 SA

20x14 RA

24x18 RA

30x20 RA

10ø LSD-1 (6)

180 CFM

8x12 SA (TYP) 12x12 SA

16x16 SA

14x14 RG-1

665 CFM

14x14 RG-1

665 CFM

14x14 RA

18x16 RA

8x8 RG-1

100 CFM

8ø CD-1

100 CFM

12/10 SA

6x6 RG-1

50 CFM

8x8 SA

6ø CD-1

90 CFM

6x6 RG-1

90 CFM

8ø CD-1

120 CFM

10x10 RG-1

240 CFM

8ø CD-1

120 CFM

6x6 RG-1

90 CFM

6ø CD-1

90 CFM

8ø CD-1

150 CFM

8x8 RG-1

150 CFM

12x12 RA

12x10 SA

10x10 SA

6ø LSD-1 (2)

85 CFM

10x8 SA

10x10 RA

8ø CD-1 (2)

165 CFM

10x10 RG-1

330 CFM

14x12 SA

8ø CD-1 (4)

160 CFM

10x8 SA 12x12 SA

14x14 RG-1

640 CFM

18x14 RA

32/28 SA

VAV-009

10x12 SA

12x12 RG-1

460 CFM

6ø CD-1 (2)

90 CFM

8x8 RG-1

180 CFM 8x8 RG-1

100 CFM

8ø CD-1

100 CFM

FCU-2B-178

12x10 SA

12x12 RA

12x12 RG-2

510 CFM

10x8 SD-1 (2)

255 CFM

8ø CD-1

140 CFM

8x8 RG-1

140 CFM

6ø CD-2

50 CFM

6x6 EG-2

50 CFM

6x6 EG-2

50 CFM

8x8 EG-2

200 CFM

8x8 EG-2

200 CFM

8x8 EG-1

170 CFM

8x8 EG-2

100 CFM

6x6 EG-2

60 CFM

8x8 EA

8x6 EA

12x12 EA

14x14 EA

14x14 EA

8x8 EG-2

200 CFM

8x8 EG-2

200 CFM

6x6 EG-2

70 CFM

8x8 EG-1

100 CFM

8x8 EA

10x10 EG-2

250 CFM

12x12 EA

V A

V -0

18x16 EA

M41

6ø CD-1

70 CFM

10ø LSD-1

185 CFM

10ø LSD-1

185 CFM

14x12 SA

16x14 RG-5

930 CFM

16x14 RA

FCU-5-220

12x10 SD-1 (2)

465 CFM

FCU-6-115

10x10 TG-1

200 CFM

8x8 TG-2

100 CFM

8x8 TG-2

100 CFM

10x10 TA

8x8 TA

6x6 TG-2

40 CFM

6x6 TG-1

40 CFM

6x6 TA

8x8 TG-2

125 CFM

8x8 TG-1

125 CFM

8x8 TA

10x10 TG-2

150 CFM

10x10 TA

C1 M-303

18x16 SA

18x18 RA

12x12 SD-1

580 CFM

12x12 SD-1 (2)

585 CFM

18x18 RG-2

1750 CFM

8x8 SA

10x7 DG-1 (6)

155 CFM

10x7 DG-1 (3)

150 CFM

8ø CD-1 (2)

195 CFM

10ø CD-1 (2)

280 CFM

14ø SA12/10 SA

6x8 SA

10x10 SA

(TYP)

14/12 SA

CAV-013

CAV-012

CAV-015

CAV-014

8x8 SA

8x8 RA

8x8 TG-2

125 CFM

8x8 TG-1

125 CFM

14x12 EA

18/14 SA

14x14 RG-8

720 CFM

8ø LSD-1 (5)

150 CFM

8x8 SA

6ø LSD-1 (2)

80 CFM6x6 TG-1 (2)

50 CFM

8x8 TG-1 (2)

130 CFM

CORR

14x14 RG-3

740 CFM

6x6 RG-1

70 CFM

M60

M72

18x18 OA

8x8 SA

16x14 EA

16x16 EA

12x10 EA

12x10 EA

6ø LSD-1

90 CFM

14x14 EA

14x12 EA

8ø SA

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :0

P

M

MH112

M E

C H

A N

IC

A

L D

U C

TW

O

R K

P

LA

N

F

IR

S T

F

LO

O R

A

R E

A B

CD

12804185

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR - AREA B

ROOM SCHEDULE

NUMBER NAME

180 BREAK

181 JANITOR

182 FMS REPAIR SHOP / MAINT STOR

183 SIM / HELMET PAD STOR

184 CONFERENCE

185 MANTRAP

186 CORR

187 WHITE CELL EVAL

188 AUDITORIUM

189 STORAGE

190 STAIR

191 TR

192 MENS

193 WOMENS

194 CORR

220 TR

221 BREAK

222 MOTHER'S RM

223 WOMENS

224 LOCKER

225 MENS

226 LOCKER

227 JAN

231 MECH

232 ELEC

ROOM SCHEDULE

NUMBER NAME

101 VEST

102 LOBBY

103 TLT

104 CORR

105 RECEPTION

106 MANTRAP

107 SEC OFFICE

108 SEC BADGE

109 SEC MGR

110 SEC SUPPLY / EQUIP

111 CBT

112 CORR

113 PATCH PANEL

114 CORR

115 COMP SUPPORT

116 MATSS MISSION PLANNING

117 NECC ADMIN

119 COMMAND CTR & OBSERV

120 IAM / ISSO

174 WOMENS

175 CORR

176 PSO

177 APSO / GSSO

178 PSO SERVER

179 PSO SEC CONF

M41 12"x12" BELL MOUTH RETURN. BALANCE RA DAMPER TO 330 CFM.

M60 DAMPER SHALL BE PROVIDED IN VERTICAL DUCT.

M72 PROVIDE ONE INCH EXTERIOR ACOUSTICAL DUCT INSULATION FROM

AHU-1 DISCHARGE TO LOCATION SHOWN ON DRAWINGS.

REF. C1/M-303, A1/M-401

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

A

T C

H L

IN

E

S E

E S

H E

E T

M H

MATCHLINE SEE SHEET MH114

MATCHLINE SEE SHEET MH112

112VAV-005

VAV-011 20

x2

S

A

14ø SA

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17

18 19 20

21 22

Q

20x20 SA

12ø ND-1 (7)

350 CFM

20x20 SA

12ø RA

10ø SA

10ø CD-1

320 CFM

12ø ND-1 (7)

350 CFM

28x28 RA

12ø RA

10x10 RG-1

270 CFM

16x16 RA

20x20 SA

20x20 SA

14ø SA

M-405 C1

8x8 RG-1

110 CFM

16/14 SA

x2

R

A

/2

S

A

6ø SAFCU-1-171

12x10 SA 6ø CD-2

50 CFM

10x10 SA

8x8 SA

30x20 RA

10x10 RG-1

195 CFM

HB-1-127

8ø CD-1

120 CFM

H-2-126

CRAH-2-126A

CRAH-2-126B

10ø CD-1

260 CFM

8x8 RG-1

160 CFM

6ø CD-1

50 CFMVAV-041

10x10 SA

12x10 RA

10x10 RG-1

260 CFM

VAV-042

6x6 RG-1

50 CFM

16x16 RA

12x12 RG-1

530 CFM

12ø CD-1

530 CFM

10ø CD-1

360 CFM

VAV-044

VAV-043

10ø SA

10x10 RG-1

270 CFM

10ø CD-1

360 CFM

VAV-049

12ø CD-1

530 CFM

12x12 RG-1

530 CFM

10ø CD-1

320 CFM

VAV-047

10x10 RG-1

260 CFM

6ø CD-1

50 CFM

8x8 RG-1

160 CFM

10ø CD-1

260 CFM

8ø CD-1

120 CFM

H-2-137

CRAH-2-137B

CRAH-2-137A

12/10 SA

VAV-048

VAV-046

12x10 RA

10ø SA

10x10 SA

10x10 EG-2

250 CFM

FCU-5-130

16x14 RG-2

930 CFM

10x10 EG-1

230 CFM

10x10 EG-1

230 CFM

M42

M45

M43

M43

M44

M45

HB-1-138

M44

M44

6ø CD-1

90 CFM

10x10 SD-1 (3)

310 CFM

14x12 SA

16x14 RA

18/16 SA

10x10 SA

8x8 SA

16x16 SA

10x10 TG-1

150 CFM

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM

8x8 TA

8x8 TA

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM

10x10 TG-2

150 CFM

10x10 TG-1

150 CFM

10x10 TA

UH-3

B2 M-303

14ø DD-1 (4)

745 CFM

10ø SA

/2

S

A

14ø SA

18/14 SA

12x10 SA

6ø LSD-1

120 CFM

6ø LSD-1

120 CFM

6ø LSD-1

105 CFM

8ø SA

14ø SA

M41

10x10 RA

6ø LSD-1 (2)

85 CFM

6ø LSD-1 (2)

80 CFM

M44

M42

SP

M60

SP

M-408 A1

10x8 SD-1 (2)

270 CFM

10x10 SD-1

300 CFM

10x10 RG-2

300 CFM

DH-1

8x6 EA

8x6 OA

10x10 SA

10x10 RA

SP

M68

M68

14ø DD-1 (4)

745 CFM

M68

M70

M69

M60

28/26 SA

M49

M49

M-408 A1

SIM

VAV-012

6ø LSD-1

105 CFM

14x12 EA

8ø SA

18x12 RA x2

S

A x3

R

A

28x28 RA x3

R

A

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :0

P

M

MH113

M E

C H

A N

IC

A

L D

U C

TW

O

R K

P

LA

N

F

IR

S T

F

LO

O R

A

R E

A C

CD

12804186

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR - AREA C

ROOM SCHEDULE

NUMBER NAME

121 CORR

122 BRIEF

123 DISPLAY SERVER ROOM

124 DEBRIEF

125 IOS ROOM

126 COMP EQUIP ROOM

127 FMS/OTW

128 CORR

130 TR

132 CORR

133 BRIEF

134 DISPLAY SERVER ROOM

135 DEBRIEF

136 IOS ROOM

137 COMP EQUIP ROOM

138 FMS/OTW

171 DMRT

172 CONFERENCE

173 MENS

228 MECH / ELEC

M41 12"x12" BELL MOUTH RETURN. BALANCE RA DAMPER TO 330 CFM.

M42 38"x38" BELL MOUTH RETURN. BALANCE RA DAMPER TO 5030

CFM. PROVIDE HUMIDITY AND TEMPERATURE SENSOR IN

RETURN; SEE MI113 AND MI114 FOR LOCATIONS.

M43 10"x10" EA UP TO EXHAUST FAN. SEE MECHANICAL ROOF PLAN.

MAXIMUM 8"x8" ROOF PENETRATION.

M44 8" DIAMETER SA CONNECTIONS TO SIMULATOR COCKPIT.

LOCKHEED MARTIN TO PROVIDE FINAL CONNECTION. SEE DETAIL

B1 ON SHEET M-512 FOR EXACT PLACEMENT. FLEXIBLE JOINT AT

15' AFF TO ALLOW FOR DUCT REMOVAL AND REATTACHMENT

DURING FMS INSTALLATION. BALANCE EACH SUPPLY

CONNECTION TO 200 CFM.

M45 12" DIAMETER RA CONNECTION TO SIMULATOR COCKPIT.

LOCKHEED MARTIN TO PROVIDE FINAL CONNECTION. SEE DETAIL

B1 ON SHEET M-512 FOR EXACT PLACEMENT. FLEXIBLE JOINT AT

15' AFF TO ALLOW FOR DUCT REMOVAL AND REATTACHMENT

DURING FMS INSTALLATION.

M49 SEE DETAIL A2 SHEET A-527 FOR SECURE LOUVER DETAIL AND

SHEET A-613 FOR LOUVER SCHEDULE.

M60 DAMPER SHALL BE PROVIDED IN VERTICAL DUCT.

M68 PROVIDE STATIC PRESSURE SENSOR.

M69 24"x16" INTAKE PLENUM. ATTACH 8"x6" OA DUCT TO BACK OF

PLENUM. ATTACH FRONT OF PLENUM TO LOUVER. BLANK OFF

UNUSED PORTION OF LOUVER. INSULATE BLANK-OFF PANEL

SIMILAR TO PLENUM.

M70 24"x16" EXHAUST PLENUM. ATTACH 8"x6" EA DUCT TO BACK OF

PLENUM. ATTACH FRONT OF PLENUM TO LOUVER. BLANK OFF

UNUSED PORTION OF LOUVER. INSULATE BLANK-OFF PANEL

SIMILAR TO PLENUM.

REF. B2/M-303, C1/M-405, A1/M-408

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

MATCHLINE SEE SHEET MH113

163 131

155 147

11 12 13 14 16 17 18 19 2015 21 22

R

S

T

U

V

10x10 RG-1

260 CFM

14ø SA

10ø SA

20x20 SA

14ø DD-1 (4)

745 CFM

28x28 RA

12ø ND-1 (7)

350 CFM

14ø DD-1 (4)

745 CFM

12ø ND-1 (7)

350 CFM

20x20 SA

VAV-061

14ø SA

VAV-056

14ø DD-1 (4)

745 CFM

20x20 SA

14ø SA

16x16 RA

12ø ND-1 (7)

350 CFM

28x28 RA

10ø SA

10ø SA

10ø SA

10ø SA

20x20 SA

14ø SA

12ø ND-1 (7)

350 CFM

20x20 SA

VAV-051

M-406 C1

M-407 C1

HB-1-145

HB-1-154

H-2-153H-2-161

HB-1-162

HB-1-170

H-2-169

6ø CD-1

90 CFM

6ø CD-1

90 CFM

CRAH-2-144A H-2-144

8ø CD-1

120 CFM

CRAH-2-144B

10ø CD-1

260 CFM

8x8 RG-1

160 CFM

12x10 RA

6ø CD-1

50 CFM 10ø CD-1

320 CFM

VAV-052

10x10 SA

10ø SA

6x6 RG-1

50 CFM

12ø CD-1

530 CFM

12x12 RG-1

530 CFM

16x16 RA

10ø CD-1

360 CFM

10x10 RG-1

270 CFM

VAV-054

VAV-053

8ø CD-1

120 CFM

CRAH-2-153A

CRAH-2-153B

10ø CD-1

260 CFM

8x8 RG-1

160 CFM

10x10 SA

6ø CD-1

90 CFM

12x10 RA

6ø CD-1

50 CFM

10x10 RG-1

260 CFM

10ø CD-1

320 CFM

VAV-057

10x10 RG-1

270 CFM

10ø CD-1

360 CFM

VAV-059

VAV-058

12ø CD-1

530 CFM

12x12 RG-1

530 CFM

6x6 RG-1

50 CFM

10ø SA

VAV-014

10x10 RG-1

295 CFM

8x8 RG-1

140 CFM

8ø CD-1

140 CFM

18x12 RA

10x10 SA

10x8 SA

10x10 SA

VAV-015

10x8 SA

8x8 SA

6ø CD-1

90 CFM

12x12 RG-1

380 CFM

CRAH-2-161A

8ø CD-1

120 CFM

CRAH-2-161B

10ø CD-1

260 CFM

8x8 RG-1

160 CFM

10x10 SA

12x10 RA 6ø CD-1

50 CFM

10x10 RG-1

260 CFM

10ø CD-1

320 CFM

VAV-062

12ø CD-1

530 CFM

12x12 RG-1

530 CFM

VAV-063

VAV-064

10ø CD-1

360 CFM

10x10 RG-1

270 CFM

10x10 RG-1

260 CFM

10ø CD-1

320 CFM

12x10 RA 6ø CD-1

50 CFM

6x6 RG-1

50 CFM

VAV-067

12ø CD-1

530 CFM

12x12 RG-1

530 CFM

VAV-068

10ø CD-1

360 CFM

VAV-069

10x10 RG-1

270 CFM

8x8 RG-1

160 CFM

10ø CD-1

260 CFM

10x10 SA

8ø CD-1

120 CFM

CRAH-2-169A

CRAH-2-169B

VAV-066

10x10 EG-1

230 CFM

10x10 EG-1

230 CFM

10x10 EG-1

230 CFM

10x10 EG-1

230 CFM

FCU-2A-129

M42

M42

M42

M42

M43

M43

M43

M43

M45

M44

M45

M44

6x6 RG-1

50 CFM

16x16 RA

VAV-013

M44

M44 M44

M44

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM

8x8 TA 8x8 TA

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM 8x8 TG-1

100 CFM

8x8 TA8x8 TA

8x8 TG-1

100 CFM

8x8 TG-1

100 CFM

UH-6 UH-7

UH-4 UH-5

ø

S A

14ø SA

6ø LSD-1

120 CFM

6ø LSD-1

120 CFM

6ø LSD-1

130 CFM

6ø LSD-1

130 CFM

M44

M45

M44

16x16 RA

SP

SP

SP

SP

14ø DD-1 (4)

745 CFM

M68

M68

M68

M68

M-408 A1

SIM

M-408 A1

SIM

M-408 A1

SIM

M-408 A1

SIM

20x20 SA x2

S

A

10ø SA

M45 x2

S A x3

R

A

18x12 RA

12ø RA

28x28 RA x3

R

A

20x20 SA

20x20 SA x3

R

A

28x28 RA x3

R

A

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MH114

M E

C H

A N

IC

A

L D

U C

TW

O

R K

P

LA

N

F

IR

S T

F

LO

O R

A

R E

A D

CD

12804187

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL DUCTWORK PLAN - FIRST FLOOR - AREA D

ROOM SCHEDULE

NUMBER NAME

128 CORR

129 ELEC

131 CORR

139 CORR

140 BRIEF

141 DISPLAY SERVER ROOM

142 DEBRIEF

143 IOS ROOM

144 COMP EQUIP ROOM

145 FMS/OTW

146 STO

147 CORR

148 CORR

149 BRIEF

150 DISPLAY SERVER ROOM

151 DEBRIEF

152 IOS ROOM

153 COMP EQUIP ROOM

154 FMS/OTW

155 CORR

156 CORR

157 BRIEF

158 DISPLAY SERVER ROOM

159 DEBRIEF

160 IOS ROOM

161 COMP EQUIP ROOM

162 FMS/OTW

163 CORR

164 CORR

165 BRIEF

166 DISPLAY SERVER ROOM

167 DEBRIEF

168 IOS ROOM

169 COMP EQUIP ROOM

170 FMS/OTW

229 MECH / ELEC

230 MECH / ELEC

M42 38"x38" BELL MOUTH RETURN. BALANCE RA DAMPER TO 5030

CFM. PROVIDE HUMIDITY AND TEMPERATURE SENSOR IN

RETURN; SEE MI113 AND MI114 FOR LOCATIONS.

M43 10"x10" EA UP TO EXHAUST FAN. SEE MECHANICAL ROOF PLAN.

MAXIMUM 8"x8" ROOF PENETRATION.

M44 8" DIAMETER SA CONNECTIONS TO SIMULATOR COCKPIT.

LOCKHEED MARTIN TO PROVIDE FINAL CONNECTION. SEE

DETAIL B1 ON SHEET M-512 FOR EXACT PLACEMENT. FLEXIBLE

JOINT AT 15' AFF TO ALLOW FOR DUCT REMOVAL AND

REATTACHMENT DURING FMS INSTALLATION. BALANCE EACH

SUPPLY CONNECTION TO 200 CFM.

M45 12" DIAMETER RA CONNECTION TO SIMULATOR COCKPIT.

LOCKHEED MARTIN TO PROVIDE FINAL CONNECTION. SEE

DETAIL B1 ON SHEET M-512 FOR EXACT PLACEMENT. FLEXIBLE

JOINT AT 15' AFF TO ALLOW FOR DUCT REMOVAL AND

REATTACHMENT DURING FMS INSTALLATION.

M68 PROVIDE STATIC PRESSURE SENSOR.

REF. C1/M-406, C1/M-407

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17 18 19 2015 21 22

Q

R

S

T

U

V

EF-1

EF-2

EF-6

EF-3

EF-5

EF-4

PLAN

NORTH

8' 16' 32'0'

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MH120

M E

C H

A N

IC

A

L R

O O

F P

LA

N

CD

12804188

RMB RMB

1/16" = 1'-0" A1

MECHANICAL ROOF PLAN

PLAN

NORTH

A B

C

D

KEY PLAN

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17 18 19 2015 21 22

Q

R

S

T

U

V

208 215

206205204

211 210

223 225

226224

163 131

155 147

M-404 A1

M A

T C

H L

IN

E

S E

E S

H E

E T

M P

M A

T C

H L

IN

E

S E

E S

H E

E T

M P

M A

T C

H L

IN

E

S E

E S

H E

E T

M P

M A

T C

H L

IN

E

S E

E S

H E

E T

M P

MATCHLINE SEE SHEET MP113

MATCHLINE SEE SHEET MP114

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :0

P

M

MP110

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R O

V E

R A

LL

CD

12804189

RMB RLS

1/16" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR OVERALL

PLAN

NORTH

A B

C

D

KEY PLAN

PLAN

NORTH

8' 16' 32'0'

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

A

T C

H L

IN

E

S E

E S

H E

E T

M P

ISEO

ISEO

REPRO

MATSS

MATSS

JPO

ISEO

ISEO

ISEO

SITCC / JMPS

MATSS CONFERENCE

EVAL / PROGRAM /

MATSS SUPPORT

MATSS

MATSS

LM

CONTRACT PILOT INST

MGR

TRAINING OPS MGR

COMMANDER

ISEO

ISE LAB

ELEC

TR

MECH

MATSS TRAINING

CORR

CORR

MATSS TRAINING

1 2 3 4 5 6

C

D

E

FG

H

I

J

K

L

M

N

O

P

4"ø HHWS

4"ø HHWR

1 1/2"ø HHWS 1 1/2"ø HHWR

6"ø CHWS 6"ø CHWR

3"ø HHWS

3"ø HHWR

FCU-1-234

FCU-1-195

3/4"ø HHWR

3/4"ø HHWS

CORR

SHIPPING / RECEIVING /

SUPPLY

CORR

MATSS TRAINING

M-403 A3

VAV-031

VAV-027

VAV-025

VAV-026

VAV-023

VAV-024VAV-028

VAV-033

VAV-034

VAV-035 VAV-036

VAV-037

VAV-038

VAV-032

VAV-022

VAV-021

VAV-020

1"ø HHWS

1"ø HHWR

VAV-039

VAV-017

1"ø HHWS 1"ø HHWR

1 1/2"ø HHWR

1 1/2"ø HHWS

3/4"ø HHWS

3/4"ø HHWR

FCU-5-199

UH-1

UH-2

FIRE PUMP

1"ø HHWR

1"ø HHWS

3/4"ø HHWR

3/4"ø HHWS

3/4"ø HHWS 3/4"ø HHWR

3/4"ø CD

3/4"ø CD

CO

CAV-011

CAV-008

CO

CO

3/4"ø CD

M73

CO

CO

1"ø CHWR

1"ø CHWS

M73

3/4"ø HHWR

3/4"ø HHWS

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :0

P

M

MP111

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

A

CD

12804190

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR - AREA A

M73 ROUTE HHWS/R PIPING WITHIN WALL DOWN TO SERVE UH.

REF. A3/M-403

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

A

T C

H L

IN

E

S E

E S

H E

E T

M P

M A

T C

H L

IN

E

S E

E S

H E

E T

M P

MATCHLINE SEE SHEET MP113

CONFERENCE

SIM / HELMET PAD

STOR

JANITOR

MECH

WOMENS

BREAK

CBT

JAN

WOMENS

MENS

LOCKER

LOCKER

MATSS MISSION

PLANNING

NECC ADMIN

COMMAND CTR &

OBSERV

SEC MGR

WOMENS

MOTHER'S RM

BREAK

TR

FMS REPAIR SHOP /

MAINT STOR

SEC OFFICE

MANTRAP

AUDITORIUM

CORR

WHITE CELL EVAL

MANTRAP

SEC BADGE

CORR

PATCH PANEL

RECEPTION

CORR

IAM / ISSO

COMP SUPPORT

VEST

7 8 9 10

A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16

17 18 19 20

21 22

TLT

3"ø HHWR

3"ø HHWS

CRAH-1-113

FCU-7-101

FCU-1-232

COMMAND CTR &

OBSERV

LOBBY

M-402 A1

VAV-001

VAV-010

VAV-008

VAV-007

VAV-004

VAV-002

VAV-003

VAV-016

VAV-018

VAV-019

VAV-029

VAV-031

VAV-030

3"ø HHWS 3"ø HHWR

6"ø CHWS

6"ø CHWR

3/4"ø HHWS

3/4"ø HHWR

3/4"ø HHWR

3/4"ø HHWS

ELEC

2"ø HHWS 2"ø HHWR

6"ø CHWS

6"ø CHWR

VAV-048

FCU-2B-191

VAV-009

VAV-006

SEC SUPPLY / EQUIP

FCU-2B-178

M4M4

FCU-5-220

FCU-6-115

UH-2

STAIR

APSO / GSSO

PSO

CORR

PSO SEC CONF

PSO SERVER

M57

3/4"ø CD

M59

3/4"ø CD

3/4"ø CD

3/4"ø CD

3/4"ø CD

3/4"ø CD

CAV-014

CAV-012

CAV-015

CAV-013

CO

M61

CO

CO

CO

CO

3/4"ø HHWR

3/4"ø HHWS

3/4"ø CHWS 3/4"ø CHWR

3"ø HHWR 3"ø HHWS

3/4"ø CD

CO

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MP112

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

B

CD

12804191

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR - AREA B

M4 PROVIDE SECURE PIPE PENETRATION PER DETAIL C1 ON SHEET

M-507.

M57 DISCHARGE CONDENSATE TO FLOOR DRAIN ADJACENT TO UNIT.

CONDENSATE DRAIN LINE SHALL BE FULL SIZE OF UNIT

CONNECTION.

M59 CONDENSATE DOWN TO MOP SINK. TERMINATE DISCHARGE 6

INCHES ABOVE MOP SINK RIM.

M61 ROUTE CHWS/R PIPING TIGHT TO WALL DOWN TO SERVE CRAH.

REF. A1/M-402

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

A

T C

H L

IN

E

S E

E S

H E

E T

M P

MATCHLINE SEE SHEET MP114

MATCHLINE SEE SHEET MP112

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

CONFERENCE

MENS

BRIEF

DEBRIEF

FMS/OTW

IOS ROOM

CORR

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

TR

MECH / ELEC

FMS/OTW

IOS ROOM

DEBRIEF

BRIEF

CORR

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17

18 19 20

21 22

Q

2 1/2"ø HHWS

2 1/2"ø HHWR

DMRT

CORR

CRAH-2-126A

FCU-1-171

CRAH-2-137A

CRAH-2-137B

CRAH-2-126B

VAV-005

VAV-011

VAV-041

VAV-042

VAV-044

VAV-046

VAV-047

VAV-049

2"ø HHWR

2"ø HHWS

M-405 A1

3/4"ø HHWR 3/4"ø HHWS

3/4"ø HHWR

3/4"ø HHWS

1"ø HHWS

1"ø HHWR

VAV-043

3"ø CHWR

3"ø HHWR

3"ø HHWS

4"ø CHWR

4"ø CHWS

2 1/2"ø HHWS

2 1/2"ø HHWR

H-2-126

2"ø CHWR

1 1/2"ø HHWR

1 1/2"ø HHWS

3"ø HHWR 3"ø HHWS

1"ø HHWS 1"ø HHWR

2"ø HHWS

2"ø HHWR

VAV-048

FCU-5-130

UH-3

CORR

M57M57

M57

M57

M57M57

3/4"ø CD M58

3/4"ø CD

3/4"ø CD

CO

CO

CO

CO

M61

M73M61

M61

M61

2"ø CHWS

1 1/2"ø CHWS

1 1/2"ø CHWR

3"ø CHWS 6"ø CHWS

6"ø CHWR

3/4"ø CD

CO

DH-1

H-2-137

HB-1-127

HB-1-138

MATCHLINE SEE SHEET MP112

3/4"ø HHWR 3/4"ø HHWS

2 1/2"ø CHWR 2 1/2"ø CHWS

2"ø HHWS 2"ø HHWR

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MP113

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

C

CD

12804192

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR - AREA C

M57 DISCHARGE CONDENSATE TO FLOOR DRAIN ADJACENT TO

UNIT. CONDENSATE DRAIN LINE SHALL BE FULL SIZE OF UNIT

CONNECTION.

M58 CONDENSATE DOWN TO FLOOR DRAIN. TERMINATE DISCHARGE

6 INCHES ABOVE FINISH FLOOR.

M61 ROUTE CHWS/R PIPING TIGHT TO WALL DOWN TO SERVE CRAH.

M73 ROUTE HHWS/R PIPING WITHIN WALL DOWN TO SERVE UH.

REF. A1/M-405

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

MATCHLINE SEE SHEET MP113

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

CORR

IOS ROOM

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

IOS ROOM

STO

DEBRIEF

BRIEF

BRIEF

DEBRIEF

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

IOS ROOM

CORR

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

CORR

IOS ROOM

DEBRIEF

BRIEF

DEBRIEF

CORR

163 CORR

CORR

CORR

CORR

11 12 13 14 16 17 18 19 2015 21 22

R

S

T

U

V

CRAH-2-144ACRAH-2-169B

CORR

BRIEF

BRIEF

CRAH-2-161A

CRAH-2-161B

CRAH-2-153B

CRAH-2-169A

CRAH-2-144B

1 1/2"ø HHWS

1 1/2"ø HHWR

VAV-014

VAV-015

VAV-013

2 1/2"ø HHWS

2 1/2"ø HHWR

M-406 A1

M-407 A1

VAV-069

VAV-068

VAV-067

VAV-053

VAV-054

VAV-059

VAV-058

VAV-057

VAV-056

H-2-153

CRAH-2-153A

2"ø CHWR

2"ø CHWS

1 1/2"ø HHWS

1 1/2"ø HHWR

4"ø CHWS

4"ø CHWR

1 1/2"ø CHWS 1 1/2"ø CHWR

2"ø HHWR

2"ø HHWS

1 1/2"ø CHWR

2"ø HHWR

2"ø HHWS

2"ø CHWR

2"ø CHWS

1 1/2"ø HHWS

1 1/2"ø HHWR

2"ø HHWR 2"ø HHWS

1"ø HHWS

1"ø HHWR

1 1/2"ø CHWS

1 1/2"ø CHWR

1"ø HHWS

1"ø HHWR

1 1/2"ø CHWS

1 1/2"ø CHWR

VAV-064

VAV-063

VAV-062

VAV-061

VAV-052

VAV-051VAV-066

ELEC

FCU-2A-129

UH-7UH-6

UH-5UH-4

M57M57

M57

M57M57

M57

M57M57

M57

M57M57

M57

M73

M73

M62 M62

3/4"ø HHWS

3/4"ø HHWR

3/4"ø HHWR

3/4"ø HHWS

CO

2"ø HHWR 2"ø HHWS

2"ø HHWS

2"ø HHWR

1 1/2"ø CHWS

M61

M61

M61

M61

M61

M61

M61

M61

2 1/2"ø CHWR

2 1/2"ø CHWS 2 1/2"ø CHWR

2 1/2"ø CHWS

CO

H-2-144

HB-1-145

HB-1-154HB-1-162

HB-1-170

H-2-161

3/4"ø CD

2"ø HHWS 2"ø HHWR

1. REFER TO DRAWING M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS AND

NOTES.

2. SEE SHEET GI121 FOR FURTHER DETAILS OF SECURE AREA BOUNDARIES.

GENERAL NOTES

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MP114

M E

C H

A N

IC

A

L P

IP

IN

G P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

D

CD

12804193

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL PIPING PLAN - FIRST FLOOR - AREA D

M57 DISCHARGE CONDENSATE TO FLOOR DRAIN ADJACENT TO UNIT.

CONDENSATE DRAIN LINE SHALL BE FULL SIZE OF UNIT

CONNECTION.

M61 ROUTE CHWS/R PIPING TIGHT TO WALL DOWN TO SERVE CRAH.

M62 ROUTE HHWS/R PIPING TIGHT TO WALL DOWN TO SERVE UH.

M73 ROUTE HHWS/R PIPING WITHIN WALL DOWN TO SERVE UH.

REF. A1/M-406, A1/M-407

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

GENERAL NOTES

WORK NOTES

M A

T C

H L

IN

E

S E

E S

H E

E T

M I1

ISEO

ISEO

REPRO

MATSS

MATSS

JPO

ISEO

ISEO

ISEO

SITCC / JMPS

MATSS CONFERENCE

EVAL / PROGRAM /

MATSS SUPPORT

MATSS

MATSS

LM

CONTRACT PILOT INST

MGR

TRAINING OPS MGR

COMMANDER

ISEO

ISE LAB

ELEC

TR

MECH

CORR

SHIPPING / RECEIVING /

SUPPLY

MATSS TRAINING

CORR

CORR

MATSS TRAINING

1 2 3 4 5 6 A

B

C

D

E

FG

H

I

J

K

L

M

N

O

P

T

T

T T

T

T

T

T

T

T

TT

T

T

T

TT

T

T

T T T

T

VAV-027

VAV-026

VAV-028

VAV-017

VAV-024

VAV-025

VAV-023

VAV-022

VAV-020

VAV-021

VAV-034

VAV-037

VAV-036

VAV-035

VAV-038

VAV-039

FCU-1-234

FCU-3-233

FCU-1-195

VAV-033

VAV-032

VAV-031

T

FCU-1-235

FCU-5-199

LOCKABLE DDC

CONTROL CABINET

LOCKABLE DDC

CONTROL CABINET

FIRE PUMP

T

UH-1

UH-2

T

BSS

STACKED (TYP OF 3)

ESS

AHU-2

CHWP-1

CHWP-2

CHWP-3

B-3

B-2

B-1

CAV-008

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :1

P

M

MI111

M E

C H

A N

IC

A

L

IN

S

TR

U M

E N

T P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

A

CD

12804194

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL INSTRUMENT PLAN - FIRST FLOOR - AREA A

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

GENERAL NOTES

WORK NOTES

M A

T C

H L

IN

E

S E

E S

H E

E T

M I1

M A

T C

H L

IN

E

S E

E S

H E

E T

M I1

MATCHLINE SEE SHEET MI113

CONFERENCE

SIM / HELMET PAD

STOR

JANITOR

MECH

WOMENS

BREAK

CBT

JAN

WOMENS

MENS

LOCKER

LOCKER

MATSS MISSION

PLANNING

NECC ADMIN

COMMAND CTR &

OBSERV

SEC MGR

WOMENS

MOTHER'S RM

BREAK

TR

FMS REPAIR SHOP /

MAINT STOR

SEC OFFICE

MANTRAP

AUDITORIUM

CORR

WHITE CELL EVAL

MANTRAP

SEC BADGE

CORR

PATCH PANEL

LOBBY

RECEPTION

CORR

IAM / ISSO

CORR

COMP SUPPORT

VEST

6 7 8 9 10

A

B

C

D

E

FG

H

I J

K

L

M

N

O

P

11 12 13 14 16 1718

2015 21 22

T

T

T

T

T

T

T

T

T

T

T T

T

T

T

T

T

T T

T

T

T

VAV-005

VAV-004

VAV-003

VAV-002

CRAH-1-113

VAV-001

VAV-016

VAV-018

VAV-019

VAV-029

VAV-030

FCU-2B-191

FCU-1-232

FCU-4-231

FCU-2B-178

VAV-006

VAV-007

VAV-008

VAV-009

VAV-010

T

FCU-7-101

ESS

FCU-6-115

FCU-5-220

ELEC

PSO SEC CONF

PSO SERVER

APSO / GSSO

PSO

CORR

STAIR

CORR

UH-2

T

CAV-014

T

CAV-012

DOAU-1

AHU-1

CAV-009

CAV-007

CAV-010

AHU-3

CAV-015

CORR

T

UH-3

O

C S

OCS

CAV-013

C O

ESS

LOCKABLE DDC

CONTROL CABINET

AHU-3

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :2

P

M

MI112

M E

C H

A N

IC

A

L

IN

S

TR

U M

E N

T P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

B

CD

12804195

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL INSTRUMENT PLAN - FIRST FLOOR - AREA B

LOCKABLE DDC

CONTROL CABINET

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

GENERAL NOTES

WORK NOTES

M A

T C

H L

IN

E

S E

E S

H E

E T

M I1

MATCHLINE SEE SHEET MI114

MATCHLINE SEE SHEET MI112

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

CONFERENCE

MENS

DMRT

BRIEF

DEBRIEF

FMS/OTW

IOS ROOM

CORR

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

TR

MECH / ELEC

FMS/OTW

CORR

IOS ROOM

DEBRIEF

BRIEF

CORR

CORR

FG

H

I

J

K

L

M

N

O

P

11 12 13 14 16 17

21 22

Q

T

T

T

VAV-005

T

T

T

T

T

T

T

T T T T

H

H

T T T T

T H

T

T

T

T

H

VAV-011

VAV-012

VAV-013

CRAH-2-126A

CRAH-2-126B

H-2-126

VAV-041

VAV-042

VAV-043

VAV-044

HB-1-127

FCU-5-130

H-1-127 CAV-045A CAV-045B

CAV-050BCAV-050A

H-1-138

HB-1-138

FCU-3-228

VAV-049

VAV-048

VAV-047

VAV-046

CRAH-2-137A

CRAH-2-137B

H-2-137

T

FCU-1-171

AHU-FMS2

AHU-FMS1

DHOAU-1

CAV-002CAV-001

M46

LOCKABLE DDC

CONTROL CABINET

CORR

CORR

T

UH-3

DH-1

H M71

M71

ESS

ESSESS

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :2

P

M

MI113

M E

C H

A N

IC

A

L

IN

S

TR

U M

E N

T P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

C

CD

12804196

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL INSTRUMENT PLAN - FIRST FLOOR - AREA C

M46 LOCATE THERMOSTAT AND HUMIDISTAT WITHIN BELL MOUTH OF

RETURN DUCT. LINK THERMOSTAT TO ASSOCIATED CAV BOXES

AND HUMIDISTAT TO ASSOCIATED HUMIDIFIER.

M71 UPS EXHAUST FAN INDICATOR LIGHT.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

GENERAL NOTES

WORK NOTES

MATCHLINE SEE SHEET MI113

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

CORR

IOS ROOM

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

MECH / ELEC

FMS/OTW

IOS ROOM

CORR

STO

DEBRIEF

BRIEF

BRIEF

DEBRIEF

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

FMS/OTW

IOS ROOM

CORR

DISPLAY SERVER

ROOM

COMP EQUIP ROOM

MECH / ELEC

FMS/OTW

CORR

IOS ROOM

DEBRIEF

BRIEF

BRIEF

DEBRIEF

CORR

CORR

CORR

CORR

10 11 12 13 14 16 17 18 19 2015 21 22

R

S

T

U

V

T

T

T T T TT T T T

T T T T T T T T T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

H

H

H

HH

H

H T

T

H

TT

VAV-067

VAV-068

VAV-069

VAV-066

H-2-169

CRAH-2-169B

CRAH-2-169A

HB-1-170

H-1-170

CAV-070B

CAV-070A

CAV-065B CAV-065A

H-1-162

FCU-3-230

VAV-015

VAV-064

VAV-063

VAV-062 VAV-061

CRAH-2-161B

H-2-161

CRAH-2-161A

HB-1-162

VAV-014

CRAH-2-144A

H-2-144

CRAH-2-144B

VAV-051

VAV-052

VAV-053VAV-054

HB-1-145

H-1-145

CAV-055BCAV-055A

CAV-060B

CAV-060A

HB-1-154

VAV-059

VAV-058

VAV-057VAV-056

CRAH-2-153B

CRAH-2-153A

H-2-153

FCU-2A-129

M46

M46M46

M46

AHU-FMS4

AHU-FMS3

DHOAU-2

AHU-FMS6

AHU-FMS5

DHOAU-3

CAV-005

CAV-006

CAV-003

CAV-004

T

FCU-3-229

H-1-154

CORR

T T

T UH-5UH-4 T

M71

M71M71

M71

ESS

ESSESS

ELEC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

DRAWFORM REVISION: 12 APRIL 2018

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

C

I C

O R

E N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

IR

G

IN

IA

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

O R

T H

C A

R O

L

IN

A

AS NOTED

P -2

F

-3

T R

A

IN

IN

G

A N

D S

IM

U

L A

T O

R F

A C

IL

IT

Y

1305 EXECUTIVE BLVD.

SUITE 160

CHESAPEAKE, VA 23320

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

1596300

CJC/RMS

469C

R e v it P ro je c ts

\B L D

G P

-1

-M

-C e n tr a l_ rm b ro w n in g .r v t

/3

/2

:3 :3

P

M

MI114

M E

C H

A N

IC

A

L

IN

S

TR

U M

E N

T P

LA

N

F

IR

S

T F

LO

O

R

A R

E A

D

CD

12804197

RMB RLS

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

A B

C

D

KEY PLAN

1/8" = 1'-0" A1

MECHANICAL INSTRUMENT PLAN - FIRST FLOOR - AREA D

M46 LOCATE THERMOSTAT AND HUMIDISTAT WITHIN BELL MOUTH OF

RETURN DUCT. LINK THERMOSTAT TO ASSOCIATED CAV BOXES

AND HUMIDISTAT TO ASSOCIATED HUMIDIFIER.

M71 UPS EXHAUST FAN INDICATOR LIGHT.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R C

O N

S

TR

U C

T

IO

N 1/

/2

1/10/20

N40085-20-R-0015 rosie.shanks Typewritten Text

MCAS CP

GENERAL NOTES

WORK NOTES

ROOF

119' - 4"

FIRST FLOOR

100' - 0" x4

R

A

36x42 RA

/2

S

A

AHU-2

A1 M-303

SHHWP-2

2 1/2"ø HHWR

2 1/2"ø HHWS

AS-2

6"ø CHWS

6"ø CHWR

2 1/2"ø CHWS

2 1/2"ø…