B09_Amendment_10_SR_NPDES_AZ0022152_GCSR_Permit_SIGNED_ISSUED_122222_0010.pdf
PDF 927 KB Posted
- Solicitation number
- 140P2026R0101
About this file
This is an Arizona Pollutant Discharge Elimination System (AZPDES) permit authorizing the discharge of treated domestic wastewater from the South Rim Wastewater Treatment Plant at Grand Canyon National Park. The permit, issued December 7, 2022, is effective December 22, 2022, and expires December 21, 2027, with a permitted flow of 750,000 gallons per day. The National Park Service must comply with all effluent limitations, monitoring requirements, and conditions outlined in the permit.
The permit establishes comprehensive discharge requirements including effluent limitations for biochemical oxygen demand, total suspended solids, E. coli, ammonia, total residual chlorine, copper, cyanide, and other parameters, with specified monitoring frequencies ranging from weekly to annually. The permittee must monitor biosolids for pathogen reduction, vector attraction reduction, and metal concentrations before land application or surface disposal, maintaining compliance with 40 CFR 503 and Arizona Administrative Code requirements. Reporting obligations include monthly discharge monitoring reports submitted electronically through myDEQ, 24-hour notification of noncompliance events, annual ammonia data logs, and annual biosolids reports by February 19. The permit incorporates standard AZPDES conditions addressing proper operation and maintenance, quality assurance procedures, inspection and entry rights, record retention for three to five years, bypass and upset provisions, and signatory requirements. An annual registration fee applies based on the permitted flow, and the permit may be reopened if Assessment Levels are exceeded or new water quality standards are adopted.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
www.azdeq.gov
Southern
Regional
Office
400 West
Congress
Street Suite
433 Tucson, AZ 85701
(520) 628-
ADEQ Inventory No. 100751 Permit No. AZ0022152
LTF No. 95360 Place ID No. 1081
AUTHORIZATION TO DISCHARGE UNDER THE
ARIZONA POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provisions of Arizona Revised Statutes (A.R.S.) Title 49, Chapter 2, Article 3.1; the Federal Water
Pollution Control Act, (33 U.S.C. §1251 et seq., as amended), and Arizona Administrative Code (A.A.C.) Title 18, Chapter
9, Articles 9 and 10, and amendments thereto the, United States Department of Interior National Park Service - Grand Canyon National Park
South Rim Wastewater Treatment Plant P.O. Box 129
Grand Canyon, Arizona 86023 is authorized to discharge treated domestic wastewater from the wastewater treatment plant located at Building 467, Rowe Well Rd, serving Grand Canyon national Park / Grand Canyon Village in Coconino County, Arizona to Bright Angel
Wash, tributary to the Colorado River, in the Colorado – Grand Canyon River Basin at:
Outfall No. Latitude Longitude Legal
001 36˚ 02’ 58.8” N 112˚ 09’ 5.82” W Township 31 N, Range 2 E, Section 26 in accordance with effluent limitations, monitoring requirements and other conditions set forth herein, and in the attached “Standard AZPDES Permit Conditions.”
Annual Registration Fee [A.R.S. 49-255.01 and A.A.C. R18-14-104]
The annual registration fee for this permit is payable to ADEQ each year. The permitted flow for fee calculation is
750,000 gallons per day (gpd). If the facility is not yet constructed or is incapable of discharge at this time, the permittee may be eligible for reduced fees under rule. Send all correspondence requesting reduced fees to the Water Quality
Division of ADEQ. Please reference the permit number, LTF number and why reduced fees are requested under rule.
This permit shall become effective on _________________________________________, 2022.
This permit and the authorization to discharge shall expire on ________________________________, 2027.
Signed _________________________________________________________________.
Trevor Baggiore, Director Water Quality Division Arizona Department of Environmental Quality
DocuSign Envelope ID: 137659CE-A2AD-4743-90CD-5C4044E37604
December 7, 2022
December 21
December 22
PERMIT NO. AZ0022152
Table of Contents
PART I. EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
A. Effluent Limitations and Monitoring Requirements
B. Trace Substance Monitoring
C. Whole Effluent Toxicity Monitoring
D. Effluent Characterization Testing
E. Surface Water Quality Standards
PART II. MONITORING AND REPORTING
A. Sample Collection and Analysis
B. Reporting of Monitoring Results
C. Twenty-four Hour Reporting of Noncompliance
PART III. BIOSOLIDS / SEWAGE SLUDGE REQUIREMENTS
A. Use of Disposal Requirements
B. Biosolids Preparer’s Responsibility
C. Duty to Mitigate
D. General Requirements
E. Biosolids Storage
F. Surface Water Protection
G. Facilities with Pretreatment Programs
H. Inspection and Entry
I. General Biosolids Monitoring Requirements (dry weight testing)
J. Biosolids Limitations and Monitoring Requirements for Land Applications
K. Management Practices for Land Applications
L. Biosolids/Sewage Sludge Limitations and Monitoring Requirements for Surface Disposal
M. Biosolids Monitoring Requirements for Disposal in a Municipal Landfill
N. On-site Management Plan
O. Record Keeping
P. Notification Requirements
Q. Annual Report for all Permittees
R. Reporting
PART IV. WHOLE EFFLUENT TOXICITY TESTING REQUIREMENTS
A. General Conditions
B. Chronic Toxicity
C. Quality Assurance
D. Toxicity Identification Evaluation (TIE)/Toxicity Reduction Evaluation (TRE) Process
DocuSign Envelope ID: 137659CE-A2AD-4743-90CD-5C4044E37604
E. WET Reporting
PART V. SPECIAL CONDITIONS
A. Operation
B. Reopener
Appendix A. Part A: Acronyms
Appendix A. Part B: Definitions
Appendix B. AZPDES Discharge Flow Record
Appendix C. Ammonia Data Log
Appendix D. Standard AZPDES Permit Conditions & Notifications
PART I. EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
A. Effluent Limitations and Monitoring Requirements
1. The Permittee shall limit and monitor discharges from Outfall 001 as specified in Table 1 which follows.
These requirements are based on a design capacity of 0.75 million gallons per day (MGD).
Table 1. Effluent Limitations and Monitoring Requirements
Parameter
Maximum Allowable Discharge Limitations (4) Monitoring Requirement
(2) (3) Mass Limits (1) Concentration Limits
Monthly Average
Weekly Average
Daily Maximum
Monthly Average Weekly Average
Daily Maximum
Monitoring Frequency
Sample Type
Discharge Flow (MGD) REPORT (5) --- REPORT --- --- --- Continuous Metered
Biochemical Oxygen Demand (BOD) (5-day) (7)
85.2 kg/day 127.7 kg/day
--- 30 mg/L mg/L
--- 1x/Month 8-hour Composite (6)
BOD (7) --- --- --
85% REMOVAL
MINIMUM
--- --- 1x/Month 8-hour Composite
Total Suspended Solids
(TSS) (7)
85.2 kg/day
127.7 kg/day
--- 30 mg/L mg/L
--- 1x/Month 8-hour Composite
TSS (7) --- --- ---
85% REMOVAL
MINIMUM
--- --- 1x/Month 8-hour Composite
E. coli --- --- ---cfu/100 mL (8)
575 cfu/100 mL (8)
4x/Month (8)
Discrete
Ammonia (9) --- --- --- REPORT [mg/L] --- REPORT [mg/L] 1x/Month Discrete
Ammonia Impact Ratio
(AIR) (10)
--- --- --- 1 --- 2 1x/Month Discrete
Total Dissolved Solids (TDS) (Source Water) (11)
--- --- --- REPORT [mg/L] --- REPORT [mg/L] 1x/Quarter Discrete
TDS (Effluent) (11) --- --- --- REPORT [mg/L] --- REPORT [mg/L] 1x/Quarter Discrete
TDS (Net Increase) (11) --- ---kg/day
REPORT [mg/L] --- REPORT [mg/L] 1x/Quarter Discrete
Chlorine, Total Residual
(TRC) (12) (13)
26 g/day --- 51 g/day 9.0 µg/L --- 18 µg/L 1x/Week Discrete
Copper, Total (14) 42 g/day --- 69 g/day 15 µg/L --- 24 µg/L 1x/6 Months
8-hour Composite
Cyanide 22 g/day --- 45 g/day 7.9 µg/L --- 16 µg/L 1x/6 Months
Discrete
Hardness (CaCO3) - Effluent (14)
REPORT
[mg/L]
REPORT
[mg/L]
1x/6 Months
8-hour Composite
Ceriodaphnia dubia (Water flea)
See Table 3 for Limits 1x/Year 8-hour Composite
Pimephales promelas (Fathead minnow)
See Table 3 for Limits 1x/Year 8-hour Composite
Pseudo-kirchneriella subcapitata (Green algae) (15)
See Table 3 for Limits 1x/Year 8-hour Composite
Temperature (9)(13) REPORT [oC] 1x/Month Discrete pH (13) Not less than 6.5 standard units (S.U.) nor greater than 9.0 S.U. 1x/Week Discrete
Footnotes 1 Mass values are to be calculated and reported using the following formulas: 1) Mass in kilograms per day = 3.785 x flow in MGD x concentration in mg/L, and 2) mass in grams per day = 3.785 x flow in MGD x concentration in µg/L.
2 Testing must coincide with the Whole Effluent Toxicity Test (WET) samples, if any, taken during that monitoring period as per Part
I.C, Table 3 of the permit. See Part IV of the permit.
3 If discharge is infrequent, see Part I.D for minimum effluent characterization monitoring requirements 4 All metals effluent Limits are for total recoverable metals.
5 Monitoring and reporting is required. No limit set at this time. In addition to the average and maximum flows reported on the
Discharge Monitoring Forms (DMR), daily discharge flow shall be recorded on the Discharge Flow Record provided in Appendix B.
See Part II.B for reporting requirements.
6 For the purposes of this permit, an “8-hour composite” sample has been defined as a flow-proportioned mixture of not less than two discrete samples (aliquots) obtained at equal time intervals during an 8-hour period. The volume of each aliquot shall be directly proportional to the discharge flow rate at the time of sampling.
7 Both the influent and the effluent shall be monitored.
8 cfu = colony forming units; “most probable number” (mpn) is considered equivalent for reporting purposes. The monthly average for E. coli is calculated as a geometric mean. A minimum of 4 samples (one sample per week of each month) are required in order to report a geometric mean. See the definition for “Monthly or Weekly Average Concentration Limit“ in Appendix A.
9 The ammonia limit is dependent on pH and temperature. The effluent must be tested for pH and temperature at the same time that the ammonia samples are taken. In addition to reporting the ammonia values on the DMRs, the ammonia data log shall also be completed including values of the effluent pH and temperature at the time the ammonia sample is taken. See Part II.B of the permit.
10 The Ammonia Impact Ratio (AIR) is calculated as the ratio of the reported effluent ammonia concentration and the calculated ammonia standard as determined by comparing concurrent measurement of the effluent pH and temperature with the values in the ammonia criteria table in Appendix C. In addition to reporting the AIRs on the DMRs, the ammonia data log in Appendix C shall also be completed. See Part II.B of the permit.
11 The permittee shall monitor and report both the source water and the effluent for TDS and calculate and report the difference between the two as the net increase, or “incremental increase”. “Source water” is defined in Appendix A. Part B as untreated water from streams, rivers, lakes or underground aquifers that is used to provide public drinking water as well as to supply private wells used for human consumption. Permit limit is established in accordance with the “2014 Review, Water Quality Standards for Salinity Colorado River System” developed by the Colorado River Basin Salinity Control Forum. The mass limit is calculated and reported in kg/day using the following conversion formula: Mass in kilograms per day = Mass in metric tons per day x 1000.
12 Sample when chlorine or bromine compounds are used for disinfection. See Part II.A.7 for specific monitoring requirements for chlorine.
13 pH, Temperature, and TRC must be measured at the time of sampling and do not require use of a certified laboratory.
Measurements must be obtained in accordance with the applicable method and must meet all method quality assurance/quality control requirements to be considered valid data.
14 Effluent permit limits listed are based on the average effluent hardness of 200 mg/L as CaCO3. The effluent must be tested for hardness at the same time that these metal samples are taken. Please see the hardness definition in Appendix A, Part B.
15 Formerly known as Selenastrum capricornutum or Raphidocelis subcapitata.
B. Trace Substance Monitoring
1. The permittee shall monitor discharges from Outfall 001 as specified in Table 2. Monitoring results above the Assessment Levels (ALs) listed below do not constitute a permit violation, but may trigger evaluation of
Reasonable Potential (RP) by ADEQ. The permittee shall use an approved analytical method with a Limit of
Quantitation (LOQ) lower than the AL values as described in Part II.A.5.
Table 2. Assessment Level Monitoring
Parameter Assessment Levels (1) (2) Monitoring Requirements (3) (4)
Monthly Average Daily Maximum Monitoring Frequency Sample Type
Hydrogen sulfide (5) 2 µg/L 3 µg/L 1x/6 Months Discrete
Mercury 0.01 µg/L 0.02 µg/L 1x/6 Months Discrete
Oil & Grease 10 mg/L 15 mg/L 1x/6 Months Discrete
Sulfides (5) REPORT [µg/L] (5) REPORT [µg/L] (5) 1x/6 Months Discrete
Footnotes 1 Concentration values are calculated based on Arizona Water Quality Standards. Monitoring and reporting required.
2 All metals effluent Assessment Levels are for total recoverable metals, except for chromium VI, for which the assessment levels listed are dissolved.
3 Testing must coincide with the Whole Effluent Toxicity Test (WET) samples, if any, taken during that monitoring period as per Part
I.C, Table 3 of the permit. See Part IV of the permit.
4 If discharge is infrequent see Part I.D for minimum effluent characterization monitoring requirements.
5 With a detection limit no higher than 100 µg/L, any detection of sulfides shall trigger monitoring for hydrogen sulfide for the remainder of the permit term. Monitoring for hydrogen sulfide is only required if sulfide is detected.
C. Whole Effluent Toxicity Monitoring
1. The permittee shall monitor discharges from Outfall 001 for Whole Effluent Toxicity (WET) as specified in
Table 3 which follows. If toxicity is detected above a Limit specified as follows, the permittee must perform follow-up testing and, as applicable, follow the TIE/TRE processes in Part IV.D of the permit.
Table 3. WET Testing
Effluent Characteristic (1)
Effluent Limits Monitoring Requirements
Daily Maximum (2) (3) Monthly Median (3) Monitoring Frequency (4)
Sample Type
Chronic Toxicity Pseudokirchneriella subcapitata (Green algae) (5)
1.6 TUc 1.0 TUc 1x/Year 8-hr Composite
Chronic Toxicity Pimephales promelas (Fathead minnow)
1.6 TUc 1.0 TUc 1x/Year 8-hr Composite
Chronic Toxicity Ceriodaphnia dubia (Water flea)
1.6 TUc 1.0 TUc 1x/Year 8-hr Composite
Footnotes 1 See Part IV for additional requirements for testing and reporting Whole Effluent Toxicity (WET).
2 Since completion of one chronic WET test takes more than 24 hours, the daily maximum is considered to be the highest allowable test result.
3 If chronic toxicity is detected above the Effluent Limits in this table or an acute test fails, the permittee must perform follow-up testing. See Part IV for details.
4 If discharge is infrequent see Part I.D for minimum effluent characterization monitoring requirements.
5 Formerly known as Selenastrum capricornutum or Raphidocelis subcapitata.
D. Effluent Characterization Testing
1. The permittee shall monitor to characterize the facility’s effluent for the parameters listed in Tables 4.a – e, whether discharging or not. When the facility discharges, monitoring is to be conducted at the frequency indicated in Tables 1 through 3. No limits or ALs are established, but the LOQ must be low enough to allow comparison of the results to the applicable water quality standards (WQS). If a LOQ below the WQS cannot be achieved, then the permittee shall use the method expected to achieve the lowest LOQ, as defined in
Appendix A of this permit. Samples are to be representative of any seasonal variation in the discharge:
Table 4.a. Effluent Characterization Testing—General Chemistry and Microbiology
Parameter Reporting Units
Monitoring Requirements
Monitoring Frequency (1) Sample Type
Ammonia (as N) (2) mg/L 1x/Quarter Discrete
Biochemical Oxygen Demand (BOD-5) mg/L 1x/Quarter 8-hour Composite
Chlorine, Total Residual (TRC) (4)(5) µg/L 1x/Quarter Discrete
Dissolved Oxygen (5) mg/L 1x/Year Discrete
E. coli cfu/100 mL (3) 1x/Quarter Discrete
Nitrate/Nitrite (as N) mg/L 1x/Quarter 8-hour Composite
Nitrogen, Total Kjeldahl (TKN) mg/L 1x/Quarter 8-hour Composite
Oil and Grease mg/L 1x/6 Months Discrete pH (5) S.U. 1x/Quarter Discrete
Phosphorus mg/L 1x/Quarter 8-hour Composite
Temperature (5) °Celsius 1x/Quarter Discrete
Total Dissolved Solids (TDS) mg/L 1x/Quarter 8-hour Composite
Total Suspended Solids (TSS) mg/L 1x/Quarter 8-hour Composite
Footnotes 1 If more frequent monitoring of any of these parameters is required by another part of this permit, those sampling results may be used to satisfy Table 4.a. requirements.
2 When sampling for ammonia, temperature and pH must be determined concurrently and the results recorded on the Ammonia Data Log provided in Appendix C. See Part II.B for reporting requirements.
3 cfu = colony forming units; “most probable number” (mpn) is considered equivalent for reporting purposes 4 Sample when chlorine or bromine compounds are used for disinfection. See Part II.A.7 for specific monitoring requirements for chlorine 5 Temperature, pH, TRC and dissolved oxygen must be measured at the time of sampling and do not require use of a certified laboratory.
See Part II.A.7 for methods of analyses for chlorine. Measurements must be obtained in accordance with the applicable method and must meet all method quality assurance/quality control requirements to be considered valid data.
Table 4.b. Effluent Characterization Testing—Selected Metals, Trace Substances and WET
Parameter (1)
Repor ting Units
Monitoring Requirements
Monitoring Frequency (2) Sample Type
Antimony µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Arsenic µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Beryllium µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Cadmium µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Chromium (4) µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Chromium VI (4) µg/L 1x/year in years 2024,2025,2026 of permit term Discrete
Copper µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Hydrogen Sulfide (5) µg/L 1x/year in years 2024,2025,2026 of permit term Discrete
Iron µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Lead µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Mercury µg/L 1x/year in years 2024,2025,2026 of permit term Discrete
Nickel µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Selenium µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Silver µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Sulfides (5) µg/L 1x/year in years 2024,2025,2026 of permit term Discrete
Thallium µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Zinc µg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Hardness mg/L 1x/year in years 2024,2025,2026 of permit term 8-hour Composite
Cyanide µg/L 1x/year in years 2024,2025,2026 of permit term Discrete
Whole Effluent Toxicity – chronic (all 3 species) (3) TUc 1x/year in 2025 8-hour Composite
Footnotes 1 All metals analyses shall be for total recoverable metals, except chromium VI, which is dissolved.
2 If more frequent monitoring of any of these parameters is required by another part of this permit, those sampling results may be used to satisfy Table 4.b. requirements.
3 If chronic toxicity is detected above the Effluent Limits specified in Table 3 or an acute test fails, the permittee must perform follow-up testing and, as applicable, follow the TIE/TRE processes in Part IV.D of the permit, whether discharging or not. See Part IV for additional information on requirements for testing and reporting Whole Effluent Toxicity (WET).
4 If total chromium exceeds 8 µg/L, the permittee must conduct sampling for chromium VI for the remainder of the permit. Otherwise, monitoring for chromium VI is not required.
5 The permittee may initially monitor for sulfide instead of hydrogen sulfide. The limit of quantification shall be no higher than 100 µg/L, and any detection of sulfides shall trigger monitoring for hydrogen sulfide for the reminder of the permit term.
Table 4.c. Effluent Characterization Testing—Selected Volatile Organic Compounds
Parameter Reporting Units
Monitoring Requirements
Monitoring Frequency Sample Type
Acrolein µg/L 1x/year in years 2025 Discrete
Acrylonitrile µg/L 1x/year in years 2025 Discrete
Benzene µg/L 1x/year in years 2025 Discrete
Bromoform µg/L 1x/year in years 2025 Discrete
Carbon tetrachloride µg/L 1x/year in years 2025 Discrete
Chlorobenzene µg/L 1x/year in years 2025 Discrete
Chlorodibromomethane µg/L 1x/year in years 2025 Discrete
Chloroethane µg/L 1x/year in years 2025 Discrete
2-chloroethylvinyl ether µg/L 1x/year in years 2025 Discrete
Chloroform µg/L 1x/year in years 2025 Discrete
Dichlorobromomethane µg/L 1x/year in years 2025 Discrete
1,1-dichloroethane µg/L 1x/year in years 2025 Discrete
1,2-dichloroethane µg/L 1x/year in years 2025 Discrete
Trans-1,2-dichloroethylene µg/L 1x/year in years 2025 Discrete
1,1-dichloroethylene µg/L 1x/year in years 2025 Discrete
1,2-dichloropropane µg/L 1x/year in years 2025 Discrete
1,3-dichloropropylene µg/L 1x/year in years 2025 Discrete
Ethylbenzene µg/L 1x/year in years 2025 Discrete
Methyl bromide µg/L 1x/year in years 2025 Discrete
Methyl chloride µg/L 1x/year in years 2025 Discrete
Methylene chloride µg/L 1x/year in years 2025 Discrete
1,1,2,2-tetrachloroethane µg/L 1x/year in years 2025 Discrete
Tetrachloroethylene µg/L 1x/year in years 2025 Discrete
Toluene µg/L 1x/year in years 2025 Discrete
1,1,1-trichloroethane µg/L 1x/year in years 2025 Discrete
1,1,2-trichloroethane µg/L 1x/year in years 2025 Discrete
Trichloroethylene µg/L 1x/year in years 2025 Discrete
Vinyl chloride µg/L 1x/year in years 2025 Discrete
Table 4.d. Effluent Characterization Testing—Selected Acid Extractable Compounds
Reporting Units
Monitoring Requirements
Monitoring Frequency Sample Type
P-chloro-m-cresol µg/L 1x/year in years 2025 8-hour Composite
2-chlorophenol µg/L 1x/year in years 2025 8-hour Composite
2,4-dichlorophenol µg/L 1x/year in years 2025 8-hour Composite
2,4-dimethylphenol µg/L 1x/year in years 2025 8-hour Composite
4,6-dinitro-o-cresol µg/L 1x/year in years 2025 8-hour Composite
2,4-dinitrophenol µg/L 1x/year in years 2025 8-hour Composite
2-nitrophenol µg/L 1x/year in years 2025 8-hour Composite
4-nitrophenol µg/L 1x/year in years 2025 8-hour Composite
Pentachlorophenol µg/L 1x/year in years 2025 8-hour Composite
Phenol µg/L 1x/year in years 2025 8-hour Composite
2,4,6- trichlorophenol µg/L 1x/year in years 2025 8-hour Composite
Table 4.e. Effluent Characterization Testing—Selected Base Neutral Compounds
Reporting Units
Monitoring Requirements
Monitoring Frequency Sample Type
Acenaphthene µg/L 1x/year in years 2025 8-hour Composite
Acenaphthylene µg/L 1x/year in years 2025 8-hour Composite
Anthracene µg/L 1x/year in years 2025 8-hour Composite
Benzidine µg/L 1x/year in years 2025 8-hour Composite
Benzo(a)anthracene µg/L 1x/year in years 2025 8-hour Composite
Benzo(a)pyrene µg/L 1x/year in years 2025 8-hour Composite
3,4 benzofluoranthene µg/L 1x/year in years 2025 8-hour Composite
Benzo(ghi)perylene µg/L 1x/year in years 2025 8-hour Composite
Benzo(k)fluoranthene µg/L 1x/year in years 2025 8-hour Composite
Bis (2-chloroethoxy) methane µg/L 1x/year in years 2025 8-hour Composite
Bis (2-chloroethyl) ether µg/L 1x/year in years 2025 8-hour Composite
Bis(2-chloroisopropyl) ether µg/L 1x/year in years 2025 8-hour Composite
Bis (2-ethylhexyl) phthalate µg/L 1x/year in years 2025 8-hour Composite
4-bromophenyl phenyl ether µg/L 1x/year in years 2025 8-hour Composite
Butyl benzyl phthalate µg/L 1x/year in years 2025 8-hour Composite
2-chloronaphthalene µg/L 1x/year in years 2025 8-hour Composite
4-chlorophenyl phenyl ether µg/L 1x/year in years 2025 8-hour Composite
Reporting Units
Monitoring Requirements
Monitoring Frequency Sample Type
Chrysene µg/L 1x/year in years 2025 8-hour Composite
Di-n-butyl phthalate µg/L 1x/year in years 2025 8-hour Composite
Di-n-octyl phthalate µg/L 1x/year in years 2025 8-hour Composite
Dibenzo(a,h)anthracene µg/L 1x/year in years 2025 8-hour Composite
1,2-dichlorobenzene µg/L 1x/year in years 2025 8-hour Composite
1,3-dichlorobenzene µg/L 1x/year in years 2025 8-hour Composite
1,4-dichlorobenzene µg/L 1x/year in years 2025 8-hour Composite
3,3-dichlorobenzidine µg/L 1x/year in years 2025 8-hour Composite
Diethyl phthalate µg/L 1x/year in years 2025 8-hour Composite
Dimethyl phthalate µg/L 1x/year in years 2025 8-hour Composite
2,4-dinitrotoluene µg/L 1x/year in years 2025 8-hour Composite
2,6-dinitrotoluene µg/L 1x/year in years 2025 8-hour Composite
1,2-diphenylhydrazine µg/L 1x/year in years 2025 8-hour Composite
Fluoranthene µg/L 1x/year in years 2025 8-hour Composite
Fluorene µg/L 1x/year in years 2025 8-hour Composite
Hexachlorobenzene µg/L 1x/year in years 2025 8-hour Composite
Hexachlorobutadiene µg/L 1x/year in years 2025 8-hour Composite
Hexachlorocyclopentadiene µg/L 1x/year in years 2025 8-hour Composite
Hexachloroethane µg/L 1x/year in years 2025 8-hour Composite
Indeno(1,2,3-cd)pyrene µg/L 1x/year in years 2025 8-hour Composite
Isophorone µg/L 1x/year in years 2025 8-hour Composite
Naphthalene µg/L 1x/year in years 2025 8-hour Composite
Nitrobenzene µg/L 1x/year in years 2025 8-hour Composite
N-nitrosodi-n-propylamine µg/L 1x/year in years 2025 8-hour Composite
N-nitrosodimethylamine µg/L 1x/year in years 2025 8-hour Composite
N-nitrosodiphenylamine µg/L 1x/year in years 2025 8-hour Composite
Phenanthrene µg/L 1x/year in years 2025 8-hour Composite
Pyrene µg/L 1x/year in years 2025 8-hour Composite
1,2,4-trichlorobenzene µg/L 1x/year in years 2025 8-hour Composite
E. Surface Water Quality Standards
1. The discharge shall be free from pollutants in amounts or combinations that:
a. Settle to form bottom deposits that inhibit or prohibit the habitation, growth or propagation of aquatic life;
b. Cause objectionable odor in the area in which the surface water is located;
c. Cause off-flavor in aquatic organisms;
d. Are toxic to humans, animals, plants or other organisms;
e. Cause the growth of algae or aquatic plants that inhibit or prohibit the habitation, growth or propagation of other aquatic life or that impair recreational uses;
2. The discharge shall be free from oil, grease and other pollutants that float as debris, foam, or scum; or that cause a film or iridescent appearance on the surface of the water; or that cause a deposit on a shoreline, bank or aquatic vegetation.
3. The discharge shall not cause an increase in the ambient water temperature of more than 3.0 degrees
Celsius.
4. The discharge shall not cause the dissolved oxygen concentration in the receiving water to fall below 3 mg/L from 3 hours after sunrise to sunset and 1 mg/L from sunset to 3 hours after sunrise, unless the percent saturation of oxygen remains equal to or greater than 90%.
PART II. MONITORING AND REPORTING
A. Sample Collection and Analysis
1. Samples taken for the monitoring requirements specified in Part I shall be collected at the following locations:
a. Influent samples shall be taken after the last addition to the collection system and prior to the first treatment process.
b. Effluent samples shall be taken downstream from the last treatment process and prior to mixing with the receiving waters.
c. Source water samples shall be taken at the intake of untreated water (from streams, rivers, or underground aquifers) prior to treatment at the public drinking water system.
2. The permittee is responsible for the quality and accuracy of all data required under this permit.
3. The permittee shall keep a QA Manual on site that describes the sample collection and analyses processes. If the permittee collects samples or conducts sample analyses in house, the permittee shall develop a QA
Manual that addresses these activities. If a third party collects and/or analyzes samples on behalf of the permittee, the permittee shall obtain a copy of the applicable QA procedures. The QA Manual shall be available for review by ADEQ upon request. The QA Manual shall be updated as necessary to reflect current conditions, and shall describe the following:
a. Project Management, including:
i. Purpose of sample collection and sample frequency;
ii. When and where samples will be collected;
iii. How samples will be collected;
iv. Laboratory(s) that will perform analyses;
v. Any field tests to be conducted (detail methods and specify equipment, including a description of any needed calibrations); and
vi. Pollutants or analytes being measured and for each, the permit-specific limits, Assessment Levels, or thresholds, (e.g. the associated detection limits needed.)
b. Sample collection procedures including:
i. Equipment to be used;
ii. Type and number of samples to be collected including QA/QC samples (i.e., background samples, duplicates, and equipment or field blanks);
iii. Types, sizes and number of sample bottles needed;
iv. Preservatives and holding times for the samples (see methods under 40 CFR 136 or 9 A.A.C. 14, Article
6 or any condition within this permit that specifies a particular test method);
v. Chain of Custody procedures.
c. Specify approved analytical method(s) to be used and include;
i. Limits of Detection (LOD) and Limits of Quantitation (LOQs);
ii. Required quality control (QC) results to be reported (e.g., matrix spike recoveries, duplicate relative percent differences, blank contamination, laboratory control sample recoveries, surrogate spike recoveries, etc.) and acceptance criteria; and
iii. Corrective actions to be taken by the permittee or the laboratory as a result of problems identified during QC checks.
d. How the permittee will perform data review; complete DMRs and records used to report results to
ADEQ; resolve data quality issues; and identify limitations on the use of the data.
4. Sample collection, preservation and handling shall be performed as described in 40 CFR 136 including the referenced Edition of Standard Methods for the Examination of Water and Wastewater, or by procedures referenced in A.R.S. Title 9, Chapter 14 of the Arizona Department of Health Services (ADHS) Laboratory
Licensure rules. The permittee shall outline the proper procedures in the QA Manual, and samples taken for this permit must conform to these procedures whether collection and handling is performed directly by the permittee or contracted to a third-party.
5. Analytical requirements
a. The permittee shall use a laboratory licensed by the ADHS Office of Laboratory Licensure and
Certification that has demonstrated proficiency within the last 12 months under A.A.C. R9-14-609, for each parameter to be sampled under this permit. However, this requirement does not apply to parameters which require analysis at the time of sample accordance with A.A.C. 36-495.02(A)(3). (These parameters may include flow, dissolved oxygen, pH, temperature, and total residual chlorine.)
b. The permittee must utilize analytical methods specified in this permit. If no test procedure is specified, the permittee shall analyze the pollutant using:
i. A test procedure listed in 40 CFR 136 which is also approved under A.A.C. R9-14-610 and is sufficiently sensitive in accordance with 40 CFR 136.1(c);
ii. An alternative test procedure approved by EPA as provided in 40 CFR 136 and which is also approved under A.A.C. R9-14-610;
iii. A test procedure listed in 40 CFR 136, with modifications allowed by EPA or approved as a method alteration by ADHS under A.A.C. R9-14-610C; or
iv. If no test procedure for a pollutant is available under (5)(b)(i) through (5)(b)(iii) above, any Method approved under A.A.C. R9-14-610(B) for wastewater may be used, except the use of field kits is not allowed unless otherwise specified in this permit. If there is no approved wastewater method for a parameter, any other method identified in 9 A.A.C. 14, Article 6 that will achieve appropriate detection and reporting limits may be used for analyses.
c. For results to be considered valid, all analytical work, including those tests conducted by the permittee at the time of sampling (see Part II.A.4.a), shall meet quality control standards specified in the approved methods.
d. The permittee shall use analytical methods with a Limit of Quantitation (LOQ) that is lower than the effluent limitations, Assessments Levels, Action Levels, or other water quality criteria, if any, specified in this permit. If all methods have LOQs higher than the applicable water quality criteria, the Permittee shall use the approved analytical method with the lowest LOQ.
e. The permittee shall use a standard calibration curve when applicable to the method, where the lowest standard point is equal to or less than the LOQ.
6. Mercury Monitoring - The permittee shall use an ADHS-certified low-level mercury analytical method such as EPA method 245.7 or 1631E to achieve a reporting limit at or below the discharge limitations or assessment levels for mercury as specified in this permit. The permittee shall also use a “clean hands/dirty hands” sampling technique such as EPA Method 1669 if necessary to achieve these reporting limits.
7. Chlorine Monitoring - Because of the short holding time for chlorine, samples may be analyzed on-site using
Hach Method No. 10014. Other methods are also acceptable for chlorine if the Method has a LOQ lower than discharge limits specified in this permit.
8. Metals Analyses - In accordance with 40 CFR 122.45(c), all effluent metals concentrations, with the exception of chromium VI, shall be measured as “total recoverable metals”. Discharge Limits and Assessment Levels in this permit, if any, are for total metals, except for chromium VI for which the levels listed are dissolved.
B. Reporting of Monitoring Results
1. The permittee shall report monitoring results on Discharge Monitoring Report (DMR) to the ADEQ electronic submission portal MyDEQ. The permittee shall submit results of all monitoring required by this permit in a format that will allow direct comparison with the limitations and requirements of this permit. If no discharge occurs during a reporting period, the permittee shall specify “No discharge” on the DMR. The results of all discharge analyses conducted during the monitoring period shall be included in determinations of the monthly average and daily maximums reported on the DMRs if the analyses were by methods specified in Part II.A above, as applicable.
2. DMRs and attachments are to be submitted by the 28th day of the month following the end of a monitoring period. For example, if the monitoring period ends January 31st, the permittee shall submit the DMR by
February 28th. The permittee shall electronically submit all compliance monitoring data and reports using the myDEQ electronic portal provided by ADEQ. The reports required to be electronically submitted include, but are not limited to, the following:
a. Discharge Monitoring Reports
b. Whole Effluent Toxicity (WET) reports
c. Original copies of laboratory results
d. Ammonia data logs [Note: Include the following attachments to be included with the DMR that are applicable to the permit. Delete those that do not apply]
e. AZPDES discharge flow records
f. Method detection limit studies
g. Bench sheets or similar documentation for field testing parameters
3. When sampling the effluent for ammonia, the pH and temperature of the effluent must be recorded at the time of sample collection. Results for all three parameters as well as the applicable ammonia standard and the calculated Ammonia Impact Ratio shall be recorded on the Ammonia Data Log provided in Appendix B.
The effluent ammonia concentrations, effluent pH and temperature, and calculated ammonia impact ratio shall also be recorded on DMRs. The ammonia data log shall be submitted to ADEQ annually to the address information listed in Part II.B.2, above.
4. If requested to participate, the permittee shall submit the results of the annual NPDES DMR/QA Study to ADEQ and ADHS for all laboratories used in monitoring compliance with this permit by December 31st of each year. The permittee shall also conduct any proficiency testing required by the NPDES DMR-QA Study for those parameters listed in the study that the permittee analyzes in house or tests in the field at the time of sampling (these parameters may include pH and total residual chlorine). All results of the NPDES DMR-QA Study shall be submitted to the email and addresses listed below, or submit by any other alternative mode as specified by ADEQ:
5. For the purposes of reporting, the permittee shall use the Limit of Quantitation.
6. For parameters with Daily Maximum Limits or Daily Maximum Assessment Levels in this permit, the permittee shall review the results of all samples collected during the reporting period and report as outlined in Table 5.
7. For parameters with Monthly Average Limits or Monthly Average Assessment Levels in this permit, the permittee shall review the results of all samples collected during the reporting period and report as outlined in Table 6.
Table 5. DMR Reporting Requirements for Daily Maximum Limits and Assessment Levels
For Daily Maximum Limits/Assessment Levels The Permittee shall Report on the DMR
When the maximum value of any analytical result is greater than or equal to the LOQ
The maximum value of all analytical results
When the maximum value detected is greater than or equal to the laboratory’s LOD but less than the LOQ
NODI (Q)
When the maximum value is less than the laboratory’s LOD NODI (B)
Arizona Department of Environmental Quality Email: AZPDES@azdeq.gov
Arizona Department of Health Services Attn: Office of Laboratory Licensure and Certification 250 North 17th Avenue Phoenix, AZ 85007
Table 6. DMR Reporting Requirements for Monthly Average Limits / Assessment Levels
For Monthly Average Limits/Assessment Levels The Permittee shall Report on the DMR
If only one sample is collected during the reporting period (monthly, quarterly, annually, etc.)
(In this case, the sample result is the monthly average.)
When the value detected is greater than or equal to the LOQ The analytical result
When the value detected is greater than or equal to the laboratory’s LOD, but less than the LOQ
NODI (Q)
When the value is less than the laboratory’s LOD NODI (B)
If more than one sample is collected during the reporting period
All samples collected in the same calendar month must be averaged.
When all results are greater than or equal to the LOQ, all values are averaged
If some results are less than the LOQ, use the LOD value in the averaging
Use ‘0’ for values less than the LOD
The highest monthly average which occurred during the reporting period
8. For all field testing, or if the information below is not included on the laboratory reports required by Part
II.B.2, the permittee shall attach a bench sheet or similar documentation to each DMR that includes, for all analytical results during the reporting period the following:
a. the analytical result,
b. the number or title of the approved analytical method, preparation and analytical procedure utilized by the field personnel or laboratory, and the LOD and LOQ for the analytical method for the parameter, and
c. any applicable data qualifiers using the most current revision of the Arizona Data Qualifiers (available online at: http://www.azdhs.gov)
C. Twenty-four Hour Reporting of Noncompliance
1. The permittee shall orally report to the Emergency Response Unit hotline at (602) 771-2330 any noncompliance that poses imminent threat to the environment or human health within 24 hours from the time the permittee becomes aware of the circumstances. The permittee shall also submit an electronic notification within 5 days of the noncompliance event using the myDEQ electronic portal provided by ADEQ.
The permittee shall include in the written notification: a description of the noncompliance and its cause; the period of noncompliance, including dates and times, and, if the noncompliance has not been corrected, the time it is expected to continue; and steps taken or planned to reduce, eliminate, and prevent reoccurrence of the noncompliance.
The following instances of noncompliance are subject to the 24-hour and 5-day reporting requirements and must be reported orally to the Emergency Response Unit hotline:
a. Any unanticipated bypass which exceeds any effluent limitations in the permit,
b. Any upset which exceeds any effluent limitation in the permit, or
c. Any spill or discharge that poses an imminent threat to human health or the environment.
2. All other instances of noncompliance remain subject to the 24-hour and 5-day reporting requirements, and must call the ADEQ AZPDES hotline at (602) 771-1440. For example, an exceedance of any maximum daily limit for the parameters listed in Part 1.A Table 1 that does not poses an imminent threat to human health or the environment.
3. The permittee shall retain the following monitoring records:
a. Date, exact location and time of sampling or measurements performed, preservatives used;
b. Individual(s) who performed the sampling or measurements;
c. Date(s) the analyses were performed;
d. Laboratory(s) which performed the analyses;
e. Analytical techniques or methods used;
f. Chain of custody forms;
g. Any comments, case narrative or summary of results produced by the laboratory. These comments should identify and discuss QA/QC analyses performed concurrently during sample analyses and should specify whether analyses met project requirements and 40 CFR 136. If results include information on initial and continuing calibration, surrogate analyses, blanks, duplicates, laboratory control samples, matrix spike and matrix spike duplicate results, sample receipt condition, or holding times and preservation, these records must also be retained.
h. Summary of data interpretation and any corrective action taken by the permittee.
PART III. BIOSOLIDS / SEWAGE SLUDGE REQUIREMENTS
Note: “Biosolids” refers to non-hazardous sewage sludge as defined in 40 CFR 503.9 and Arizona Administrative Code (A.A.C.) R18-9-1001.7. Sewage sludge that is hazardous as defined in 40 CFR 261 must be disposed of in accordance with the Resource Conservation and Recovery Act (RCRA). Sludge with PCB (polychlorinated biphenyls) levels greater than 50 mg/kg must be disposed of in accordance with 40 CFR 761.
A. Use of Disposal Requirements
1. All biosolids/sewage sludge generated and/or prepared at this facility shall be used or disposed of in compliance with the applicable portions of 18 A.A.C. 9, Article 10 and
2. 40 CFR 503 Subpart C: for biosolids that are placed on the land (surface disposal) for the purpose of disposal
(dedicated land disposal sites, lagoons, or monofills).
3. 40 CFR 258: for biosolids disposed of in municipal solid waste landfills; and
4. 40 CFR 257: for all biosolids use and disposal practices not covered under 40 CFR 258 or 503.
B. Biosolids Preparer’s Responsibility
1. The permittee is responsible for ensuring that all biosolids/sewage sludge produced or accepted at this facility are used or disposed of in accordance with 40 CFR 503 Subpart C, 257, 258 and 18 A.A.C. 9, Article
10, as applicable, whether the permittee uses or disposes of the biosolids itself or transfers them to another party for further treatment, use, or disposal. The permittee is responsible for informing any subsequent transporters, preparers, applicators, and disposers of the requirements that they must meet under 18 A.A.C.
9, Article 10.
C. Duty to Mitigate
1. The permittee shall take all reasonable steps to prevent or minimize any biosolids use or disposal which has a likelihood of adversely affecting human health or the environment.
D. General Requirements
1. The permittee shall ensure that:
a. No biosolids generated and/or prepared at this facility enter wetlands or other waters of the United
States;
b. Biosolids treatment, storage, use or disposal does not contaminate surface water or groundwater.
(Note: Surface disposal or land treatment sites for biosolids must be permitted under the aquifer protection program per A.A.C. R18-9-1002(E)(2) and may also require a separate AZPDES permit. The permittee shall ensure a site has appropriate permits before directing biosolids to a surface disposal or land treatment site.)
c. Biosolids treatment, storage, and use or disposal does not create a nuisance such as malodorous smell or attraction of flies or other disease carrying vectors.
d. Biosolids generated and/or prepared at this facility are not applied to the land or placed on a surface disposal site if the biosolids are likely to adversely affect a threatened or endangered species as listed under section 4 of the Endangered Species Act (16 U.S.C 1533), or its designated critical habitat as defined in 16 U.S.C. 1532;
e. Land application sites receiving bulk biosolids generated and/or prepared at this facility are registered with ADEQ in accordance with A.A.C. R18-9-1004.
E. Biosolids Storage
1. Biosolids shall not be stored on land for over two years from the time they are generated unless permit for surface disposal is obtained per 18 A.A.C. 9, Article 10 and 40 CFR 503 Subpart C, or written notification has been submitted to the ADEQ Surface Water Permits Unit with the information in 40 CFR 503.209(b) that sufficiently demonstrates the need for longer temporary storage.
2. For the protection of public health, biosolids shall not be stored uncovered on-site or off-site unless the permittee can demonstrate that prior to placement in storage:
a. Biosolids meet Class A or B pathogen reduction requirements established in A.A.C. R18-9-1006(D) or (E), and
b. Biosolids meet one of the vector attraction reduction alternatives in A.A.C. R18-9-1010 subsections
(A)(1) through (A)(8).
c. For biosolids which are classified as EQ or Class A, or as Class B through pathogen reduction Alternative
1, the permittee must also sample for pathogen reduction following storage and within 30 days prior to reuse/disposal or distribution (see Part III.J.2.d). Sampling before storage shall occur at least at the minimum frequencies given in Part III.I.1, and sampling after storage shall be conducted as specified in Part III.I.4.
3. Prior to storing biosolids at an off-site storage location, the permittee shall notify the ADEQ Surface Water
Permits Unit in writing where the biosolids will be stored and the expected date of final use or disposal.
F. Surface Water Protection
1. The permittee must design and operate all on-site treatment, disposal, or storage areas for biosolids to:
a. Divert surface run-on from adjacent areas to prevent contact with biosolids;
b. Protect the site boundaries from erosion; and
c. Prevent any drainage that has contacted biosolids from escaping the site.
2. These features shall be designed to be protective for at least a 25-year 24-hour storm event. If the permittee sends biosolids off-site that are not EQB, the permittee shall ensure all treatment, disposal, or storage areas that receive those biosolids have the same level of protection.
G. Facilities with Pretreatment Programs
1. Permittees with pretreatment programs shall:
a. Sample and analyze biosolids for all the priority pollutants listed under Section 307.a.1 of the Clean
Water Act, except asbestos. This shall consist of an annual full priority pollutant scan, with quarterly samples analyzed only for those pollutants detected in the full scan.
b. Sample and analyze biosolids quarterly for the following Pollutants of Concern:
Arsenic Copper Mercury Selenium
Cadmium Cyanide Molybdenum Silver
Chromium Lead Nickel Zinc
2. If any biosolids generated and/or prepared at this facility are or will be land applied, the permittee shall design local limits to achieve the ceiling and monthly average pollutant concentration levels for pollutants given in Table 9 of this permit. If pollutants in the biosolids exceed any of these monthly average pollutant concentration levels, the permittee shall revise its local limits as necessary in order to meet these levels.
H. Inspection and Entry
The permittee shall allow, directly or through contractual arrangements with their biosolids management contractors, authorized representatives of ADEQ and EPA to:
1. Enter upon all premises where biosolids are treated, stored, used, or disposed, either by the permittee or by another party to whom the permittee transfers the biosolids for treatment, storage, use, or disposal;
2. Have access to and copy any records that must be kept under the conditions of this permit and per 18 A.A.C.
9, Article 10 (including those in 40 CFR 503 Subpart C) by the permittee or by another party to whom the permittee transfers the biosolids for further treatment, storage, use, or disposal; and
3. Inspect any facilities, equipment (including monitoring and control equipment), practices, or operations used in biosolids treatment, storage, use, or disposal by the permittee or by another party to whom the permittee transfers the biosolids for treatment, use, or disposal.
I. General Biosolids Monitoring Requirements (dry weight testing)
1. Biosolids Self-monitoring Frequency Unless otherwise specified in this permit, the permittee shall conduct self-monitoring events at least at the frequency listed in Table 7 for any sampling required in Part III of this permit.
Table 7. Biosolids Self-Monitoring Frequency
Amount of Biosolids Prepared per Calendar Year
(dry metric tons)
Minimum Monitoring Frequency
> 0 to < 290 One sampling event per year
≥ 290 to < 1,500 One sampling event per quarter
≥ 1500 to < 15,000 One sampling event per 60 days
≥ to 15,000 One sampling event per month
2. Sampling and Analysis Method
a. The permittee shall ensure biosolids are tested using the methods specified in 40 CFR 503.8, as required in A.A.C. R18-9-1012(G) that are sufficiently sensitive in accordance with 40 CFR 122.21(e)(3). Testing shall be performed at a laboratory operating in compliance with A.R.S. 36-495. Because of the potential for re-growth of pathogens, for Class A or EQ biosolids, samples demonstrating pathogen reduction shall be taken within 30 days before biosolids are shipped off-site, so verification that requirements are met is obtained before the biosolids leave the site.
3. Representative Sampling:
a. The permittee shall ensure that sampling conducted during a monitoring period adequately represents the quality of all biosolids used/treated/disposed over the monitoring period. This may entail taking several samples per sampling event and/or sampling more frequently than the minimum specified.
4. Testing Stockpiled/Accumulated Biosolids Prior to Distribution or Use
a. If, after treatment, biosolids classified as EQ or Class A, or as Class B demonstrated through Alternative
1, are stockpiled or accumulated on-site prior to reuse/disposal, the permittee shall develop a sampling plan that ensures samples representative of the entire stockpile are collected and analyzed for pathogens within 30 days before distribution or use. The plan shall detail the number and location of samples to be taken from a cross section of each pile or area. The plan must include at least 1 sample for each 0-290 metric dry ton increments. More sampling is appropriate when the biosolids are inconsistent in nature or non-uniformly treated.
b. The permittee must collect and analyze representative samples per the sampling plan. Distribution or use/disposal shall not occur until the permittee verifies that the biosolids sampled meet all applicable requirements for its use/disposal.
5. Testing for Hazardous Waste Determination
a. The permittee shall test biosolids at least annually, and more frequently as necessary, to determine if biosolids are hazardous in accordance with 40 CFR 261. Initial screening of the biosolids may be conducted by analyzing biosolids for the total amount of a pollutant.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .