B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part6_0002.pdf
PDF 25 MB Posted
- Attached to
- YELL 326141 YELLOWSTONE MODULAR HOUSING
- Solicitation number
- 140P2026R0078
About this file
This file contains revised final construction drawings for modular housing units at Yellowstone National Park, specifically plumbing plans and renderings for two-bedroom, three-bedroom, and accessible (ABA) unit configurations. The drawings are preliminary and marked "Not for Construction," indicating they are for general information and coordination purposes only. The document is dated June 18, 2026, and prepared by Stantec (Cheyenne, WY) as the prime A/E firm, with PMIS/PKG No. 94 and Drawing No. 198433.
The plumbing plans illustrate schematic layouts for kitchen, bathroom, laundry, and utility areas across multiple unit types, showing pipe sizes and routing for water supply, drainage, and vent systems. Critical notes specify that mechanical, electrical, and plumbing systems are to be engineered by the residential modular building manufacturer, with all shown engineering serving as reference only. Final design, sizing, and routing of plumbing systems remain the responsibility of the modular housing manufacturer and must comply with manufacturer recommendations, applicable codes, and Authority Having Jurisdiction (AHJ) requirements. The drawings include details on freeze-protected hose bibb locations and ADA-accessible shower provisions where applicable. All renderings are for reference purposes only and depict kitchen and common areas in day and evening conditions.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B
C
PRELIMINARY
NOT FOR
CONSTRUCTION
Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.
YELLOWSTONE NATIONAL PARK
TITLE OF SHEET
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.DESIGNED:
JC
CADD:
BB/PS/AS
TECH. REVIEW:
LF
DATE:
A/E: FIRM
PRIME:
STANTEC
CHEYENNE, WY
SHEET
OF
P
LO
T D
A
TE
R
E V
IT
V
E R
SI
O
N
198433
:2
:4
P M
A u to d e sk
D o c s:
Y
E L L N
P S /0 a rc h b d r.
rv t
3BR RENDERINGS
326141A901C
Designer 06/12/2026
KITCHEN - DAY
KITCHEN - EVENING
ALL RENDERINGS FOR REFERENCE ONLY
OF 9476D7606/18/2026
A
B
C
PRELIMINARY
NOT FOR
CONSTRUCTION
Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.
YELLOWSTONE NATIONAL PARK
TITLE OF SHEET
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.DESIGNED:
JC
CADD:
BB/PS/AS
TECH. REVIEW:
LF
DATE:
A/E: FIRM
PRIME:
STANTEC
CHEYENNE, WY
SHEET
OF
P
LO
T D
A
TE
R
E V
IT
V
E R
SI
O
N
198433
:3
:4
P M
A u to d e sk
D o c s:
/1
Y
E L L N
P S a rc h b d r_ a d a .r v t
3BR ABA RENDERINGS
326141A901D
06/12/2026
KITCHEN - DAY
KITCHEN - EVENING
ALL RENDERINGS FOR REFERENCE ONLY
06/18/2026
R a n g e
WH
FD
R e fr ig e ra to r
DW
A
C
B
1 2 3
BEDROOM 01
BEDROOM 02
BATH 02
LAUNDRY/UTILITY
KITCHEN
GREAT ROOM
MUD ROOM
BATH 01
HALL
DISHWASHER
A5
A10
PROVIDE FREEZE-PROTECTED HOSE BIBB.
LOCATION MAY VARY. COORDINATE WITH
MODULAR BUILDINGS MANUFACTURER.
RE: SHOP DRAWINGS.
3"
2"
SHOWER
1 1/2"
3"
2"
2"
DRAIN
VENT
1 1/2"
LAV
WC
OWNER/PURCHASER
RESPONSIBILITY
BATH 01
3" VTR
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
BATH 02
LAUNDRY/
UTILITY
KITCHEN
3" VTR
3"
3"
2"
2"
2"
2"
3"
1 1/2"
1 1/2"
1 1/2"
1 1/2" 1 1/2"
1 1/2"
1 1/2"
LAV
WC
FLOOR
DRAIN
2"
KIT.SINK
2"
WASHER
2" TUB/
SHOWER
1 1/2"
DRAIN
VENT
OWNER/PURCHASER
RESPONSIBILITY
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
A
B
C
PRELIMINARY
NOT FOR
CONSTRUCTION
Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.
YELLOWSTONE NATIONAL PARK
TITLE OF SHEET
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.DESIGNED:
JC
CADD:
BB/PS/AS
TECH. REVIEW:
LF
DATE:
A/E: FIRM
PRIME:
STANTEC
CHEYENNE, WY
SHEET
OF
P
LO
T D
A
TE
R
E V
IT
V
E R
SI
O
N
198433
:4
:1
P M
A u to d e sk
D o c s:
Y
E L L N
P S /0 a rc h b d r.
rv t
2BR PLUMBING PLAN
326141P101A
06/12/2026
1/4" = 1'-0"P101A
A1 LEVEL 01
PLUMBING NOTES
1 SEE ALL GENERAL NOTES & DISCIPLINE NOTES LOCATED ON A001
2 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR
BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL
SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS, ALL APPLICABLE CODES AND AHJ
REQUIREMENTS.
n g e
M ic ro w a v e
WH
FD
R e fr ig e ra to r
DW
A
B
C
1 2 3
BEDROOM 02
BEDROOM 01
HALL
BATH 02 ABA
BATH 01
MUD ROOM
GREAT ROOM
KITCHEN
DISHWASHER
ADA SHOWER
B8
PROVIDE ACCESSIBLE FREEZE-PROTECTED HOSE BIBB.
LOCATION MAY VARY. COORDINATE WITH MODULAR
BUILDINGS MANUFACTURER. RE: SHOP DRAWINGS.
3"
2"
SHOWER
1 1/2"
3"
2"
2"
DRAIN
VENT
1 1/2"
LAV
WC
OWNER/PURCHASER
RESPONSIBILITY
BATH 01
3" VTR
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
BATH 02 ABA
KITCHEN
3" VTR
3"
2"
2"
2"
3"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
DRAIN
VENT
OWNER/PURCHASER
RESPONSIBILITY
2"
3"
1 1/2" 2"
WASHER
2"
SHOWER
FLOOR
DRAIN
WC
1 1/2"
LAV
2"
KIT. SINK
2"
1 1/2"
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
A
B
C
PRELIMINARY
NOT FOR
CONSTRUCTION
Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.
YELLOWSTONE NATIONAL PARK
TITLE OF SHEET
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.DESIGNED:
JC
CADD:
BB/PS/AS
TECH. REVIEW:
LF
DATE:
A/E: FIRM
PRIME:
STANTEC
CHEYENNE, WY
SHEET
OF
P
LO
T D
A
TE
R
E V
IT
V
E R
SI
O
N
198433
:0
:1
P M
A u to d e sk
D o c s:
/1
Y
E L L N
P S a rc h b d r_ a d a .r v t
2BR ABA PLUMBING PLAN
326141A/326104P101B
07/15/25
1/4" = 1'-0"P101B
A1 LEVEL 1
PLUMBING NOTES
1 SEE ALL GENERAL NOTES & DISCIPLINE NOTES LOCATED ON A001
2 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR
BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL
SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS, ALL APPLICABLE CODES AND AHJ
06/12/202606/18/2026 n g e
R e fr ig e ra to r
WH
FD
D W
A
B
C
2 31
LIVING ROOM BEDROOM 1
BATH 01
WIC 01
KITCHEN
DINING
FOYER
BEDROOM 02
LAUNDRY
HALL
BEDROOM 03
BATH 02
PROVIDE FREEZE-PROTECTED HOSE BIBB.
LOCATION MAY VARY. COORDINATE WITH
MODULAR BUILDINGS MANUFACTURER.
RE: SHOP DRAWINGS.
DRAIN
VENT
OWNER/PURCHASER
RESPONSIBILITY
BATH 01
KITCHEN
2"
SHOWER
WC
1 1/2"
LAV
2"
KIT. SINK
2"
2"
3" 2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
3"
3" VTR
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
3"
2"
SHOWER
1 1/2"
3"
2"
2"
DRAIN
VENT
1 1/2"
LAV
WC
OWNER/PURCHASER
RESPONSIBILITY
BATH 02
3" VTR
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
2"
FLOOR
DRAIN
3"
LAUNDRY
MECH/
STORAGE
2"
WASHER
***THIS PLUMBING LAYOUT IS PROVIDED FOR REFERENCE AND COORDINATION PURPOSES ONLY.
FINAL DESIGN, SIZING, AND ROUTING OF PLUMBING SYSTEMS SHALL BE COMPLETED BY
MODULAR HOUSING MANUFACTURER.
A
B
C
PRELIMINARY
NOT FOR
CONSTRUCTION
Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.
YELLOWSTONE NATIONAL PARK
TITLE OF SHEET
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.DESIGNED:
JC
CADD:
BB/PS/AS
TECH. REVIEW:
LF
DATE:
A/E: FIRM
PRIME:
STANTEC
CHEYENNE, WY
SHEET
OF
P
LO
T D
A
TE
R
E V
IT
V
E R
SI
O
N
198433
:2
:4
P M
A u to d e sk
D o c s:
Y
E L L N
P S /0 a rc h b d r.
rv t
3BR PLUMBING PLAN
326141P101C
06/12/2026
3/16" = 1'-0"P101C
1A LEVEL 01 PLUMBING PLAN
PLUMBING NOTES
1 SEE ALL GENERAL NOTES & DISCIPLINE NOTES LOCATED ON A001
2 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR
BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL
SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS AND ALL APPLICABLE CODES AND AHJ
File details come from the government source that posted it. Updated .