B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part4_0002.pdf

PDF 18 MB Posted

Attached to
YELL 326141 YELLOWSTONE MODULAR HOUSING
Solicitation number
140P2026R0078
Issued by

About this file

This document is a preliminary architectural drawing set for residential modular buildings at Yellowstone National Park, consisting of design plans and specifications for 2-bedroom and 3-bedroom units with standard and ADA-accessible variants.

The project includes four primary building configurations: a 2-bedroom standard unit, a 2-bedroom ABA (Americans with Disabilities Act) accessible unit, a 3-bedroom standard unit, and a 3-bedroom ABA accessible unit. Key building specifications include fiberglass windows with specifications referenced to 08 54 13 and 06 20 23, metal standing seam roof panels, and cement fiber siding. Windows are specified as DW1 through DW5 types with dimensions ranging from 3'-0" to 5'-0" wide and 1'-6" to 5'-6" tall. All bedroom windows must comply with 2024 IRC Section R319 minimum egress requirements. Interior finishes include gypsum board ceilings at 8-9 feet elevation with Level 5 finishes and P-1 flat sheen paint. ABA units feature accessible kitchens with removable cabinet faces, accessible bathrooms with grab bars and reinforced blocking, accessible showers with controls, ABA-compliant ranges and dishwashers, and ramp designs conforming to ABA and IBC 2021 standards with slope, width, landing, handrail, and surface requirements. The drawings indicate fire suppression systems are delegated design items requiring UPONOR AQUASAFE systems or approved equivalents with manufacturer product data sheets and hydraulic calculations submitted for NPS Fire Code Official approval. Night sky compliance is required per NPS lighting guidelines using low-level, downward-focused fixtures and low-pressure sodium lamps. Drawing sheets are marked preliminary and not for construction, dated 06/18/2026, with PMIS/PKG No. 198433 and designed by Stantec Cheyenne, WY.

View the file

Other files

File Type Posted
B09-140P2026R0078-Amd_4_0004.pdf PDF
Sol_140P2026R0078_Amd_0004.pdf PDF
B08_Attachment_7_Limitations_on_Subcontracting_Report_0004.xlsx XLSX spreadsheet
B09_Amendment_3__Past_Performance_Questionnaire_0003.docx DOCX document
B09_Amendment_3__Project_Experience_Questionnaire_0003.docx DOCX document
Sol_140P2026R0078_Amd_0003.pdf PDF
B09_Amendment_3_Questions_and_Answers_0003.pdf PDF
B09_Amendment_3_estimated_cut_and_fill_quantities_0003.pdf PDF
B09_Amendment_3_General_References_0003.docx DOCX document
B09_Amendment_3_Yellowstone_Mammoth_Project_Report_0003.pdf PDF
B09_Amendment_3_Yellowstone_NE_Entrance_Project_Report_0003.pdf PDF
B09_Amendment_3_Yellowstone_Canyon_Project_Report_0003.pdf PDF
B09-Attachment_1_-_Revised_Final_CD_Specifications_2026_08_18_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part7_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part3_0002.pdf PDF
Sol_140P2026R0078_Amd_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part1_0002.pdf PDF
B09-140P2026R0078-Amd_2_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part2_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part6_0002.pdf PDF
B09-Attachment_2_-_Revised_Final_Construction_Drawings_2026_08_18_Part5_0002.pdf PDF
B08-YELL_326141_MODULAR_HOUSING_Preproposal__0001.pdf PDF
Sign_In_Sheet_Page_1_0001.jpg JPG image
Sol_140P2026R0078_Amd_0001.pdf PDF
Sign_In_Sheet_Page_2_0001.jpg JPG image
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part4.pdf PDF
B08-Attachment_1A-03_YELL_326141_Final_Specification_Appendicies_2026_07_22.pdf PDF
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part6.pdf PDF
B08-Attachment_1_-_02_YELL_326141_Final_Specifications_2026_07_22.pdf PDF
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part1.pdf PDF
E15_Deliverables_LmtOnSubconRpt_REQD.xlsx XLSX spreadsheet
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part3.pdf PDF
Sol_140P2026R0078.pdf PDF
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part2.pdf PDF
B08_Solitation-140P2026R0078_v16_17June2026.pdf PDF
B08-YELL_326141_pre-proposal_project_overview_and_site_visit_(002).pdf PDF
B08-Attachment_2-01_YELL_326141_Final_CD_Plans_2026_07_22_Part5.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PRE-FINISHED WINDOW TRIM

WINDOW

PRE-FINISHED WINDOW TRIM

WINDOW

PRE-FINISHED WINDOW TRIM

WINDOW

PRE-FINISHED WINDOW TRIM

WINDOW

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:3

:4

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

3BR ABA WINDOW TYPES

/ SCHEDULES / DETAILS

326141A006D

06/12/2026

WINDOW SCHEDULE

Type Mark Width Height MATERIAL Comments DW1 3'-0" 5'-6" FIBERGLASS REFERENCE SPECIFICATION 08 54 13 FIBERGLASS WINDOWS & 06 20 23 INTERIOR FINISH CARPENTRY; ALL WINDOWS TO RECEIVE

STORM SCREENS.

DW3 4'-0" 4'-0" FIBERGLASS REFERENCE SPECIFICATION 08 54 13 FIBERGLASS WINDOWS & 06 20 23 INTERIOR FINISH CARPENTRY; ALL WINDOWS TO RECEIVE

STORM SCREENS.

DW4 3'-6" 1'-6" FIBERGLASS REFERENCE SPECIFICATION 08 54 13 FIBERGLASS WINDOWS & 06 20 23 INTERIOR FINISH CARPENTRY; ALL WINDOWS TO RECEIVE

STORM SCREENS.

DW5 5'-0" 2'-0" FIBERGLASS REFERENCE SPECIFICATION 08 54 13 FIBERGLASS WINDOWS & 06 20 23 INTERIOR FINISH CARPENTRY; ALL WINDOWS TO RECEIVE

STORM SCREENS.

DW1

DW2

DW3

DW4

WINDOW TYPES

* ALL BEDROOMS TO RECEIVE AW1 WINDOWS IN COMPLIANCE WITH 2024 IRC SECTION R319 MINIMUMS.

DW1

NET CLEAR WIDTH: 34" - 36"

NET CLEAR OPENING HEIGHT: 32" - 34"

NET CLEAR OPENING AREA: 8.0SF - 8.5SF

IRC MINIMUMS

NET CLEAR WIDTH: 20"

NET CLEAR HEIGHT:24"

NET CLEAR OPENING AREA: 5.7SF

06/18/2026

R a n g e

WH

FD

R e fr ig e ra to r

DW

SD

SD

SD/CO

SD

A610A

A6

A610A

A9

A610A A4

A8

A610AA2

A1

B1

A200A

A

A A

A1

A200A

B

A A

A610A A3

A610A

A7

BEDROOM 02

A106A

AW2 AW2

AW1

AW1

AW1

AW1

AW1AW1

AW1

AW1

GREAT ROOM

KITCHEN

BATH 02

HALL

LAUNDRY/UTILITY

BEDROOM 01

BATH 01

MUD ROOM

A106C

A107

A101

A

A

A

A105A

A105B

A106B

LVP-1

LVP-1

TL-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

CPT-1

CPT-1

A

C

B

1 2 3

48'-0"

40'-0" 8'-0"

'-0

'-0

'-0

'-0

7'-8 1/2"

3'-8 1/2"

3'-0"

6'-7"

'-6

'-8

6" 12'-0" 5'-4 1/2" 8" 8 1/2"

4'-10" 6'-0 1/2" 4'-0" 5'-4 1/2" 6"

'-3

/2

'-3

'-6

'-9

/2

'-8

/2

'-6

'-1

/2

8'-0"40'-0"

48'-0"

'-0

BENCH &

COAT RACK

INCLUDE BLOCKING

FOR TV MOUNT

ABOVE RECEPTACLE

BRACED WALL

BEHIND WALL FINISH

2X6 WALL FOR DRYER VENT

TO CLEAR TRUSS

BRACED WALL

BEHIND WALL FINISH

WOOD STOVE W/

48"X48" HEARTH PAD

1'-0"

1'-4" MIN CLR

1'-11" MIN CLR

DISHWASHER

EXTERIOR VENT

RANGE HOOD W/ MICROWAVE

PANTRY

CABINET

LINEN

CABINET

4" RADON PIPE

LINEN CABINET

WASHER

& DRYER

5X SHELVES

6X6 POST

8X8

POST

8X8

POST

8X8

POST

8X8

POST

8X8

POST

6X6 POST

CRAWL

SPACE

ACCESS

'-6

/8

'-1

/2

'-2

/2

'-6

'-1

/2

'-5

'-4

/2

'-4

/2

10'-8"

2'-8"

'-2

6" 12'-0" 5'-9 1/2" 5'-3" 6'-6 1/2" 9'-5" 6"

/2

/2

A5

A10

PROVIDE STAIRS AS

REQUIRED BY SITE SPECIFIC

GRADING; RE CIVIL

ELEV=100'-0"

ELEV=100'-0"

ELEV=100'-0"

ELEV=100'-0"

A

C

B

1 2 3

2'-1 1/2"

2'-0"1'-10"

3'-9"

'-0

'-5

'-1

10'-7"

4'-10"

CENTER

CENTER

E Q

E Q

CENTER CENTER

CENTER

CENTER

WALL MOUNTED

LINEAR LED LIGHT

FAN WITH INTEGRATED

LED LIGHT

FAN WITH INTEGRATED

LED LIGHT

2'-2"

'-8

CENTER LIGHT

ABOVE SINK

'-0

'-3

/2

CEILING

ACCESS

PANEL

FIRE SUPPRESSION SYSTEM TO BE PROVIDED.

DELEGATED DESIGN. PROVIDE UPONOR AQUASAFE

SYSTEM OR APPROVED EQUAL. PROVIDE FIRE

SUPPRESSION SYSTEM DRAWINGS, HYDRAULIC

CALCULATIONS, AND MANUFACTURER'S PRODUCT

DATA SHEETS FOR REVIEW AND APPROVAL BY THE

NPS FIRE CODE OFFICIAL/AHJ OR DESIGNEE, PRIOR

TO INSTALLATION.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:4

:0

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

2BR FLOOR & REFLECTED

CEILING PLAN

326141A101A

06/12/2026

1/4" = 1'-0"A101A

A1 FLOOR PLAN

1/4" = 1'-0"A101A

C1 REFLECTED CEILING PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE

NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED

GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION

CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 ALL DIFFUSERS / GRILLS IN GYP. CEILING TO BE PAINTED TO MATCH ADJACENT FINISH. ALL COVE HEATERS

TO MATCH CEILING FINISH.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECIEVE UNDER-CABINET LIGHTING.

10 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR

BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL

SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS, ALL APPLICABLE CODES AND AHJ

REQUIREMENTS.

LIGHT FIXTURE SCHEDULE

FIXTURE COUNT

LED WALL MOUNTED LIGHT FIXTURE 2

LED WALL MOUNTED SCONCE 4

UNDER CABINET LIGHTING 5

CEILING FAN WITH LED LIGHT FIXTURE 3

BATH FAN WITH LED LIGHT FIXTURE 2

RECESSED CANNED LIGHTING 10

EXTERIOR DOWNLIGHT; COMPLY WITH EXTERIOR LIGHT REGULATIONS 2

n g e

M ic ro w a v e

WH

FD

R e fr ig e ra to r

DW

SD

SD

SD/CO

A610B

B7

A610B B4

B6

A610BB2

B1

B1

A200B

A

A B

A1

A200B

B

A B

A610B B3

B5

BATH 01

MUD ROOM

BATH 02 ABA

KITCHEN

GREAT ROOM

HALL

BEDROOM 01

BEDROOM 02

CPT-1

CPT-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

B

LVP-1

B101

B

B

B105A

B105B

B106A

B106B

B106C

B106D

BW1

BW1

BW1 BW1

BW1

BW1

BW1

BW1

BW2BW2

A

B

C

1 2 3

40'-0" 8'-0"

'-0

'-0

'-0

8'-1 1/2"

'-0

3'-4 1/2"

5'-0"

3'-1 1/4"

'-2

'-6

'-2

'-5

/2

'-4

/2

'-4

'-0

FILLER PANEL

1/4" FILLER NEEDED BETWEEN

FRIDGE PANEL AND WALL CABINET

1/4" FILLER NEEDED BETWEEN

FRIDGE PANEL AND WALL CABINET

BENCH &

COAT RACK

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

BRACED WALL

BEHIND WALL FINISH

CRAWL

SPACE

ACCESS

ABA SINK

ABA SHOWER

4" RADON PIPE

ATTIC

ACCESS

DRYER WASHER

ABA RANGE

ABA DISHWASHERABA COUNTERTOP

MICROWAVE

EXTERIOR RANGE VENT

BRACED WALL BEHIND

WALL FINISH

PANTRY

CABINET

10 1/2"

8X8

POST

6X6 POST

8X8

POST

8X8

POST

8X8

POST

8X8

POST6X6 POST

'-2

2'-8"

6" 12'-0" 5'-4 1/2" 8"

8 1/2"

10'-10 1/2" 4'-0" 5'-4 1/2" 6" 8'-0"

'-3

/2

'-3

'-6

'-9

/2

'-8

/2

'-6

'-1

/2

6" 12'-0" 5'-9 1/2" 5'-11" 6'-3 3/4"

WOOD STOVE W/

48"X48" HEARTH PAD

1'-4" MIN CLR

1'-11" MIN CLR

/2

/2

B8

ELEV=100'-0"

RAMP DESIGN TO CONFORM TO ABA

STANDARDS FOR ACCESSIBLE DESIGN,

INCLUDING SLOPE, WIDTH, LANDINGS,

HANDRAILS, AND SURFACE REQUIREMENTS

RAMP DESIGN TO CONFORM

TO ABA STANDARDS FOR

ACCESSIBLE DESIGN,

INCLUDING SLOPE, WIDTH,

LANDINGS, HANDRAILS, AND

SURFACE REQUIREMENTS

A

B

C

1 2 3

'-0

1'-9"

CENTER

CENTER

E Q

E Q 2'-11 1/2"

CENTERCENTER

CENTER

4'-10"

10'-7" '-1

'-5

CENTER

WALL MOUNTED

LINEAR LED LIGHT

FAN WITH INTEGRATED

LED LIGHT

FAN WITH INTEGRATED

LED LIGHT

2'-2"

'-8

CENTER LIGHT

ABOVE SINK

'-3

CEILING

ACCESS

PANEL

FIRE SUPPRESSION SYSTEM TO BE PROVIDED.

DELEGATED DESIGN. PROVIDE UPONOR AQUASAFE

SYSTEM OR APPROVED EQUAL. PROVIDE FIRE

SUPPRESSION SYSTEM DRAWINGS, HYDRAULIC

CALCULATIONS, AND MANUFACTURER'S PRODUCT

DATA SHEETS FOR REVIEW AND APPROVAL BY THE

NPS FIRE CODE OFFICIAL/AHJ OR DESIGNEE, PRIOR

TO INSTALLATION.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:0

:1

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

2BR ABA FLOOR &

REFLECTED CEILING

PLAN

326141A/326104A101B

05/28/25

1/4" = 1'-0"A101B

A1 ABA FLOOR PLAN

1/4" = 1'-0"A101B

C1 REFLECTED CEILING PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE

NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED

GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION

CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 ALL DIFFUSERS / GRILLS IN GYP. CEILING TO BE PAINTED TO MATCH ADJACENT FINISH. ALL COVE HEATERS

TO MATCH CEILING FINISH.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECIEVE UNDER COUNTER LIGHTING.

10 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR

BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL

SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS, ALL APPLICABLE CODES AND AHJ

REQUIREMENTS.

LIGHT FIXTURE SCHEDULE

FIXTURE COUNT

LED WALL MOUNTED LIGHT FIXTURE 2

LED WALL MOUNTED SCONCE 2

UNDER CABINET LIGHTING 5

CEILING FAN WITH LED LIGHT FIXTURE 3

BATH FAN WITH LED LIGHT FIXTURE 2

RECESSED CANNED LIGHTING 9

EXTERIOR DOWNLIGHT; COMPY WITH EXTERIOR LIGHT REGULATIONS 2

06/12/202606/18/2026 n g e

R e fr ig e ra to r

WH

FD

D W

UP

B1 A200C

A

A

0C

A1 A200C

B

A

0C

A610C B2

A610C C3 A610C C1C2

A610C A1

BEDROOM 03

BATH 02

CW1 CW4 CW4 CW3

CW5

CW1CW1

CW1

C

4A

C

C

1B C

1A

C113

C

C107B

C106A

C111B

C

7A

C

BEDROOM 02

WIC 01

DINING

KITCHEN

HALL

LAUNDRY

FOYER

LIVING ROOM

6"

2' -1

4'-6"

9' -2

3'-10"

CPT-1

CPT-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

CPT-1

LVP-1

BATH 01

LVP-1

A

B

C

2 3

A610C

B3

20'-0" 56'-0"

4" RADON

REVENT

STACKED

W/D

'-0

'-0

'-0

EXTERIOR VENT

RANGE HOOD W/

MICROWAVE

SHORT

PLUMBING WALL

CRAWL

SPACE

ACCESS

76'-0"

6" 9'-9" 9'-8 7/8" 5'-3" 9'-0 5/8" 2'-5" 9'-0 5/8" 6'-9 1/4" 5'-0 1/4" 4'-7" 8'-11 3/4" 4'-4 3/4" 6"

CW1

6" 6'

-6

6' -8

'-1 0"

6"

2'-4" 7'-11" 7'-11" 2'-3 7/8" 6'-0 1/2" 3'-5 1/2" 3'-5 1/2" 5'-2 1/4" 11'-3 3/16" 6'-0" 6'-7 11/16" 3'-5 1/2" 3'-5 1/2" 6'-0 1/2"

CW1

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

BRACED WALL

BEHIND WALL FINISH

DISHWASHER

PANTRY

CABINET

BRACED WALL BEHIND

WALL FINISH

ELEV=100'-0"

ELEV=100'-0"

ELEV=100'-0"

ELEV=100'-0"

FIRE PROTECTION

BETWEEN GARAGE

AND LIVING UNIT

GARAGE DOOR 16' x 8'

A610C B1

S

H E

LF

/R

O D

2'-0"

2' -8

S

H E

LF

/R

O D

(5) SHELVES

1 SHELF/ROD

BEDROOM 1

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

CW1

1 SHELF/ROD

1 SHELF/ROD

S

H E

LF

/R

O D

S

H E

LF

/R

O D

C

LO

S E

T

T O

W E

R

TL-1

WOOD STOVE W/

48"X48" HEARTH PAD

1'-4" MIN CLR

RE: STRUC. GRINDER SUMP

PUMP FLUSH WITH FLOOR;

PROVIDED REMOVABLE

DIAMOND PLATED STAINLESS

STEEL PROTECTION

MECH/STORAGE

C104B

C

6B

GARAGE

D114

C111A

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:2

:3

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

3BR FLOOR PLAN

326141A101C

06/12/2026

1/4" = 1'-0"A101C

A1 FLOOR PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR BUILDING MANUFACTURER; ALL COVE HEATERS TO MATCH CEILING FINISH. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS

AND ALL APPLICABLE CODES AND AHJ REQUIREMENTS.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O.

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECEIVE UNDER COUNTER LIGHTING.

n g e

R e fr ig e ra to r

D W

M ic ro w a v e

WH

FD

B1 A200D

A

A

0D

A1 A200D

B

A

0D

A610D B2

A610D C3 A610D C1C2 A610D A1

BEDROOM 03

BEDROOM 01

DW1 DW4 DW4 DW3

DW5

DW1DW1

D

4A

D

D

1B D

1A

D

D106A

D

7A

BEDROOM 02

WIC 01

DINING

KITCHEN

HALL

LAUNDRY

FOYER

LIVING ROOM

2' -0

/2

4'-6"

9' -2

CPT-1

CPT-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

LVP-1

CPT-1

LVP-1

BATH 01

LVP-1

A

B

C

2 3

A610D

B3

'-0

RADON

VENT

'-0

'-0

6" 9'-9" 9'-8 7/8" 5'-3" 20'-6 1/8" 6'-9 1/4" 5'-0 1/4" 4'-7" 9'-8 1/2" 3'-8" 6"

20'-0" 56'-0"

76'-0"

DW1DW1

6" 6'

-6

6' -8

'-1 0"

6"

2'-4" 7'-11" 7'-11" 2'-3 7/8" 6'-0 1/2" 3'-5 1/2" 3'-5 1/2" 5'-2 1/4" 4'-7 1/2" 6'-7 3/4" 6'-0" 6'-7 3/4" 3'-5 1/2" 3'-5 1/2" 6'-0 1/2"

DW1

D R

Y E

R W

A S

H E

R

MIN CLR

6'-4 7/64"

D111B

BRACED WALL

BEHIND WALL FINISH

ABA RANGE

ABA DISHWASHER

ABA COUNTERTOP

MICROWAVE

PANTRY

CABINET

BRACED WALL BEHIND

WALL FINISH

ELEV=100'-0"

ELEV=100'-0"

REINFORCEMENT TO PERMIT

THE INSTALLATION OF GRAB

BARS

GARAGE DOOR 16' x 8'

FIRE PROTECTION

BETWEEN GARAGE

AND LIVING UNIT

RAMP DESIGN TO CONFORM TO ABA & IBC 2021

STANDARDS FOR ACCESSIBLE DESIGN,

INCLUDING SLOPE, WIDTH, LANDINGS,

HANDRAILS, AND SURFACE REQUIREMENTS

RAMP DESIGN TO CONFORM TO ABA & IBC 2021

STANDARDS FOR ACCESSIBLE DESIGN,

INCLUDING SLOPE, WIDTH, LANDINGS,

HANDRAILS, AND SURFACE REQUIREMENTS

RAMP DESIGN TO CONFORM TO ABA & IBC 2021

STANDARDS FOR ACCESSIBLE DESIGN,

INCLUDING SLOPE, WIDTH, LANDINGS,

HANDRAILS, AND SURFACE REQUIREMENTS

RE: STRUC. GRINDER SUMP

PUMP FLUSH WITH FLOOR;

PROVIDED REMOVABLE

DIAMOND PLATED STAINLESS

STEEL PROTECTION

TL-1

WOOD STOVE W/

48"X48" HEARTH PAD

1'-4" MIN CLR

S

H E

LF

/R

O D

A610D B1

2'-2"

2' -8

S

H E

LF

/R

O D

MECH/STORAGE

BATH 2

LVP-1

DW1

1 SHELF/ROD

1 SHELF/ROD

CONTROLS

ABA SHOWER DOOR

ABA SHOWER HEAD

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

INCLUDE BLOCKING FOR

TV MOUNT ABOVE

RECEPTICAL

(5) SHELVES

1 SHELF/ROD

D104B

D

6B

D

D107B

D111A

D

D114

GARAGE

MIN

5'-7"

MAX

9"

MIN

5'-7"

M

IN

5' -0

MIN

5'-0"

MIN

5'-7"

MAX

9"

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:3

:4

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

3BR ABA FLOOR PLAN

326141A101D

06/12/2026

1/4" = 1'-0"A101D

A1 ABA FLOOR PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 ALL DIFFUSERS / GRILLS IN GYP. CEILING TO BE PAINTED TO MATCH ADJACENT FINISH. ALL COVE HEATERS

TO MATCH CEILING FINISH.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECIEVE UNDER COUNTER LIGHTING.

10 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL

SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS AND ALL APPLICABLE CODES AND AHJ

REQUIREMENTS.

SD

SD

SD/CO

SD

SD/CO

A

B

C

2 31

2'-0"

'-8

"CEILING

ACCESS

PANEL

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GWB 9' - 0"

GWB 9' - 0"

GWB 9' - 0"

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 8"

GWB 9' - 0"GWB 9' - 0" GWB 9' - 0"

GWB 8' - 0"

GWB 9' - 0"

GWB 8' - 0"

'-0

'-2

2'-0" 6" 3'-6" 6" 4'-3 1/8" 6" 3'-6" 6"

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GARAGE

MECH/STORAGE

BEDROOM 02

LAUNDRY

HALL

DINING KITCHENBATH 02BEDROOM 03

LIVING ROOM

BEDROOM 1

WIC 01

BATH 01

GWB 9' - 0"

FIRE SUPPRESSION SYSTEM TO BE PROVIDED.

DELEGATED DESIGN. PROVIDE UPONOR AQUASAFE

SYSTEM OR APPROVED EQUAL. PROVIDE FIRE

SUPPRESSION SYSTEM DRAWINGS, HYDRAULIC

CALCULATIONS, AND MANUFACTURER'S PRODUCT

DATA SHEETS FOR REVIEW AND APPROVAL BY THE

NPS FIRE CODE OFFICIAL/AHJ OR DESIGNEE, PRIOR

TO INSTALLATION.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:2

:1

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

3BR REFLECTED CEILING

PLAN

326141A102C

06/12/2026

1/4" = 1'-0"A102C

A1 REFLECTED CEILING PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE

NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED

GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION

CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR

BUILDING MANUFACTURER; ALL COVE HEATERS TO MATCH CEILING FINISH. ALL ENGINEERING SHOWN IS

SCHEMATIC AND FOR REFERENCE ONLY. ALL SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS

AND ALL APPLICABLE CODES AND AHJ REQUIREMENTS.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O.

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECEIVE UNDER COUNTER LIGHTING.

LIGHT FIXTURE SCHEDULE

FIXTURE COUNT

LED WALL MOUNTED SCONCE 2

CEILING FAN WITH LED LIGHT FIXTURE 3

BATH FAN WITH LED LIGHT FIXTURE 2

RECESSED CANNED LIGHTING 29

LED PENDANT LIGHT 3

EXTERIOR DOWNLIGHT; COMPLY WITH EXTERIOR LIGHT REGULATIONS 1

SD

SD/CO

SD

SD/CO

A

B

C

2 31

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GWB 9' - 0"

GWB 9' - 0"

GWB 8' - 8"

GWB 9' - 0"GWB 9' - 0" GWB 9' - 0"

GWB 8' - 0"

GWB 9' - 0"

'-0

'-2

2'-0" 6" 3'-6" 6" 4'-3 1/8" 6" 3'-6" 6"

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

CEILING

ACCESS

PANEL

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GWB 8' - 0"

GARAGE

LAUNDRY

MECH/STORAGE

BEDROOM 02

FOYER

LIVING ROOM

DINING KITCHEN

BEDROOM 03

BATH 2

WIC 01

BATH 01

BEDROOM 01

GWB 9' - 0"

FIRE SUPPRESSION SYSTEM TO BE PROVIDED.

DELEGATED DESIGN. PROVIDE UPONOR AQUASAFE

SYSTEM OR APPROVED EQUAL. PROVIDE FIRE

SUPPRESSION SYSTEM DRAWINGS, HYDRAULIC

CALCULATIONS, AND MANUFACTURER'S PRODUCT

DATA SHEETS FOR REVIEW AND APPROVAL BY THE

NPS FIRE CODE OFFICIAL/AHJ OR DESIGNEE, PRIOR

TO INSTALLATION.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:3

:4

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

3BR ABA REFLECTED

CEILING PLAN

326141A102D

06/12/2026

1/4" = 1'-0"A102D

A1 REFLECTED CEILING PLAN

NOTES PLAN

1 REFERENCE ALL GENERAL NOTES ON SHEET A001

2 NIGHT SKY: PROJECT SHALL COMPLY WITH NPS AND PARK LIGHTING GUIDLINES TO REDUCE IMPACTS TO THE

NIGHT SKY AND WILDLIFE. THIS WILL INCLUDE, BUT IS NOT LIMITED TO, LOW-LEVEL LIGHTING, MINIMIZED

GLARE, DOWNWARD FOCUSED LIGHT FIXTURES, AND ENERGY EFFICIENT LIGHT SOURCES SUCH AS

LOW-PRESSURE SODIUM LAMPS.

3 REFERENCE ALL FIRE-SUPPRESSION SPRINKLER SYSTEM REQUIREMENTS ON SHEET A001. FIRE PROTECTION

CONTRACTOR TO PROVIDE SPRINKLER SHOP DRAWINGS FOR ARCHITECT'S REVIEW AND APPROVAL.

4 REFER TO ELECTRICAL DRAWINGS FOR LIGHT SWITCH LOCATIONS.

5 ALL DIFFUSERS / GRILLS IN GYP. CEILING TO BE PAINTED TO MATCH ADJACENT FINISH. ALL COVE HEATERS

TO MATCH CEILING FINISH.

6 ALL CEILING HEIGHTS TO BE 8' U.N.O

7 ALL GYP. BD. CEILINGS SHALL BE FINISHED TO LEVEL 5 FINISH AND PAINTED P-1 FLAT SHEEN, U.N.O.

8 LIGHT/FAN COMBO TO BE SATIN NICKEL U.N.O.

9 ALL CABINETS LOCATED IN THE KITCHEN TO RECIEVE UNDER COUNTER LIGHTING.

10 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS TO BE ENGINEERED BY RESIDENTIAL MODULAR

BUILDING MANUFACTURER. ALL ENGINEERING SHOWN IS SCHEMATIC AND FOR REFERENCE ONLY. ALL

SYSTEMS MUST MEET MANUFACTURER RECOMMENDATIONS AND ALL APPLICABLE CODES AND AHJ

REQUIREMENTS.

LIGHT FIXTURE SCHEDULE

FIXTURE COUNT

LED WALL MOUNTED SCONCE 2

UNDER CABINET LIGHTING 2

CEILING FAN WITH LED LIGHT FIXTURE 3

BATH FAN WITH LED LIGHT FIXTURE 2

RECESSED CANNED LIGHTING 29

LED PENDANT LIGHT 3

EXTERIOR DOWNLIGHT; COMPLY WITH EXTERIOR LIGHT REGULATIONS 1

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

AC B

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

EXTERIOR DOOR

HANDRAIL

STROBE

EXTERIOR ELECTRICAL OUTLET

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

A CB

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

ELECTRICAL PANEL

FIBERGLASS WINDOW

MODULAR BUILDINGS MANUFACTURER TO PROVIDE DECORATIVE, NON-

FUNCTIONAL SHUTTERS AT ALL WINDOWS. WOOD SHUTTERS ARE NOT

ALLOWED. ALIGN TOP OF SHUTTER WITH TOP OF WINDOW TRIM AND

BOTTOM OF SHUTTER WITH TOP OF WINDOW SILL. STYLE AND COLOR

OPTIONS SHALL BE INCLUDED IN MODULAR BUILDING SHOP DRAWINGS.

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

/2

'-0

'-4

/4

'-0

/4

METAL STANDING SEAM

ROOF PANEL

EXTERIOR DOOR

HANDRAIL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET EXTERIOR

ELECTRICAL OUTLET

HANDRAIL

EXTERIOR HOSE BIB

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

1 2 3

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

HANDRAIL

FIBERGLASS WINDOW

CEMENT FIBER SIDING

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:4

:1

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

2BR ELEVATIONS

326141A200A

06/12/2026

1/4" = 1'-0"A200A

A2 FRONT ELEVATION

1/4" = 1'-0"A200A

B2 REAR ELEVATION

1/4" = 1'-0"A200A

A1 RIGHT ELEVATION 2 BEDROOM

1/4" = 1'-0"A200A

B1 LEFT ELEVATION

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

ABC

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

EXTERIOR DOOR

HANDRAIL

STROBE

EXTERIOR ELECTRICAL OUTLET

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

A B C

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

ELECTRICAL PANEL

FIBERGLASS WINDOW

MODULAR BUILDINGS MANUFACTURER TO PROVIDE DECORATIVE, NON-

FUNCTIONAL SHUTTERS AT ALL WINDOWS. WOOD SHUTTERS ARE NOT

ALLOWED. ALIGN TOP OF SHUTTER WITH TOP OF WINDOW TRIM AND

BOTTOM OF SHUTTER WITH TOP OF WINDOW SILL. STYLE AND COLOR

OPTIONS SHALL BE INCLUDED IN MODULAR BUILDING SHOP DRAWINGS.

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

/2

'-0

'-4

/4

'-0

/4

METAL STANDING SEAM

ROOF PANEL

EXTERIOR DOOR

HANDRAIL

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET EXTERIOR

ELECTRICAL OUTLET

HANDRAIL

EXTERIOR HOSE BIB

LEVEL 01

100'-0"

LEVEL 02

108'-0"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

1 2 3

'-4

/4

'-0

/2

'-0

/4

METAL STANDING SEAM

ROOF PANEL

HANDRAIL

FIBERGLASS WINDOW

CEMENT FIBER SIDING

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:0

:1

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

2BR ABA ELEVATIONS

326141A/326104A200B

05/28/25

1/4" = 1'-0"A200B

A2 FRONT ELEVATION

1/4" = 1'-0"A200B

B2 REAR ELEVATION

1/4" = 1'-0"A200B

A1 RIGHT ELEVATION

1/4" = 1'-0"A200B

LEVEL 02

108'-11 1/2"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

ABC

CEMENT FIBER SIDING

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOW

LEVEL 01

100'-0"

LEVEL 02

108'-11 1/2"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

A B C

CEMENT FIBER SIDING ELECTRICAL PANEL

23 1

METAL STANDING SEAM

ROOF PANEL

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOWCEMENT FIBER SIDING

FIBERGLASS WINDOW

VENTILATION CODE

REQUIREMENT TO BE MET

2 31

METAL STANDING SEAM

ROOF PANELSTROBE

CEMENT FIBER SIDING FIBERGLASS WINDOWGARAGE DOOR VENTILATION CODE

REQUIREMENT TO BE MET

MODULAR BUILDINGS MANUFACTURER TO PROVIDE DECORATIVE, NON-

FUNCTIONAL SHUTTERS AT ALL WINDOWS. WOOD SHUTTERS ARE NOT

ALLOWED. ALIGN TOP OF SHUTTER WITH TOP OF WINDOW TRIM AND

BOTTOM OF SHUTTER WITH TOP OF WINDOW SILL. STYLE AND COLOR

OPTIONS SHALL BE INCLUDED IN MODULAR BUILDING SHOP DRAWINGS.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:2

:3

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

3BR ELEVATIONS

326141A200C

06/12/2026

1/4" = 1'-0"A200C

A2 FRONT ELEVATION

1/4" = 1'-0"A200C

B2 REAR ELEVATION

1/4" = 1'-0"A200C

A1 RIGHT ELEVATION

1/4" = 1'-0"A200C

LEVEL 02

108'-11 1/2"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

ABC

CEMENT FIBER SIDING

METAL STANDING SEAM

ROOF PANEL

FIBERGLASS WINDOWVENTILATION CODE

REQUIREMENT TO BE MET

LEVEL 01

100'-0"

LEVEL 02

108'-11 1/2"

TO FOUNDATION

99'-0 1/2"

GRADE

98'-4 1/2"

RIDGE

115'-4 3/4"

A B C

CEMENT FIBER SIDING ELECTRICAL PANEL

23 1

METAL STANDING SEAM

ROOF PANEL

ELECTRICAL OUTLET CEMENT FIBER SIDINGFIBERGLASS WINDOW VENTILATION CODE

REQUIREMENT TO BE MET

2 31

METAL STANDING SEAM

ROOF PANEL

STROBE

CEMENT FIBER SIDINGEXTERIOR DOOR

FIBERGLASS WINDOW

CEMENT FIBER SIDINGGARAGE DOOR VENTILATION CODE

REQUIREMENT TO BE MET MODULAR BUILDINGS MANUFACTURER TO PROVIDE DECORATIVE, NON-

FUNCTIONAL SHUTTERS AT ALL WINDOWS. WOOD SHUTTERS ARE NOT

ALLOWED. ALIGN TOP OF SHUTTER WITH TOP OF WINDOW TRIM AND

BOTTOM OF SHUTTER WITH TOP OF WINDOW SILL. STYLE AND COLOR

OPTIONS SHALL BE INCLUDED IN MODULAR BUILDING SHOP DRAWINGS.

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:3

:4

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

3BR ABA ELEVATIONS

326141A200D

06/12/2026

1/4" = 1'-0"A200D

A2 FRONT ELEVATION

1/4" = 1'-0"A200D

B2 REAR ELEVATION

1/4" = 1'-0"A200D

A1 RIGHT ELEVATION

1/4" = 1'-0"A200D

1'-9"1'-9"

3'-6"

1 1/4" 1 1/4"

**TOEKICK

**CABINETS

**PULL

/8

**FLOATING SHELVES

3'-7" 3'-0"

**UPPER CABINETS

**SHELVES

**PULL

**COUNTERTOP & BACKSPLASH

**DISHWASHER

**CABINET

**TOE KICK

**BASE CABINETS

2'-0" 2'-0" 4'-0" 2'-0" 1'-0"

2'-0"

1'-0"

1'-0"1'-6"3'-0"2'-0"2'-6"3'-0"5"

3'-0"5"

**FILLER PANEL

3'-6 3/4" 2'-6" 2'-1 1/4" 2'-6"

10'-8"

**BATHTUB

**COUNTERTOP & BACKSPLASH

**CABINETS

**PULL

**MIRROR

**SHOWER HEAD

**FAUCET CONTROLS

**FAUCET

**TOWEL BAR

**ROBE HOOK

5'-0 1/8"

4 1/2"

1'-8"

**TOE KICK

**BATHTUB

**CABINETS

**PULL7

**SPOUT

**SHOWERHEAD

**FAUCET

**TOWEL BAR

1'-8" 1'-8" 1'-8" 1'-8" 1'-8" 3"

**TOEKICK

**CABINETS

**PULL

**COUNTERTOP

/2

3"

**UPPER CABINETS

**REFRIGERATOR

**MICROWAVE

**SHELVES

**COUNTERTOP & BACKSPLASH

**PULL

**LOWER CABINETS

**OVEN/RANGE

**TOE KICK

2'-0" 2'-0" 2'-6" 1'-9" 3'-3" 1'-6" 2"

1'-0" 1'-0" 2'-6" 1'-9"

1 1/2"

3'-0"

1 1/2"

1'-8" 2"

2'-6"

2'-10" 6'-0"

8'-10"

**COUNTERTOP & BACKSPLASH

**PULL

**DRAWERS

**BATHTUB

**TOILET

**CABINETS

**TOE KICK

**MIRROR

**LIGHT

**SHOWER HEAD & FAUCET

**TOWEL BAR

**ROBE HOOK

**TISSUE HOLDER

**TOILET

**DOOR

**SHOWER HEAD

**CONTROLS

**FAUCET

**TUB

5'-0"

**TOWEL BAR

**ROBE HOOK

**TOWEL BAR

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:4

:1

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

2BR INTERIOR

ELEVATIONS

326141A610A

06/12/2026

1/4" = 1'-0"A610A

A6 HALLWAY - LEFT

1/4" = 1'-0"A610A

A7 LAUNDRY/UTILITY - LEFT

1/4" = 1'-0"A610A

A1 KITCHEN - LEFT

1/4" = 1'-0"A610A

A9 BATH 02 - RIGHT

1/4" = 1'-0"A610A

A8 BATH 02 - FRONT

1/4" = 1'-0"A610A

A3 MUDROOM - FRONT

1/4" = 1'-0"A610A

A2 KITCHEN - REAR

1/4" = 1'-0"A610A

A4 BATH 01 - FRONT 2 BEDROOM

1/4" = 1'-0"A610A

A10 BATH 02 - BACK

1/4" = 1'-0"A610A

A5 BATH 01 - RIGHT

9"

**UPPER CABINETS

**FLOATING SHELVES

**PULL

**TOE KICK

**COUNTERTOP & BACKSPLASH

**BASE CABINETS

**DISHWASHER

**REFRIGERATOR

8' -0

M A

X

2' -1

0" 1'

-8

3' -4

2"

1" 2'-10" 2'-0" 2'-0" 4'-0" 2'-0" 2'-0"

1"

2'-10" 3'-0"2'-0" 1'-6"

REMOVABLE CABINET FACE

FOR ADA ACCESS @ SINK

9"1'-0"

**UNDER CABINET LIGHTING

2'-6"

11'-4"

**ABA BATHTUB/SHOWER

**GRAB BARS INSTALLED

PER ABA REQUIREMENTS;

PROVIDE BLOCKING

**COUNTERTOP & BACKSPLASH

1'

-2

5'-0"

7' -6

2' -7

**MIRROR PER ABA REQUIREMENTS

6"

** ABA SPOUT

** ABA FAUCET

** ABA SHOWERHEAD

**TOWEL BAR PER ABA REQUIREMENTS

1' -2

6'

-1 0"

1' -8

3' -1

/2

1'

-6

**DOOR

**GRAB BARS

**BATHTUB

** ABA SPOUT

** ABA FAUCET

** ABA SHOWERHEAD

5'-4" 3'-6"

8'-10"

1' -2

"2' -1

0"

4"

5' -2

**TOE KICK

**CABINETS

**PULL

**DRAWERS

**COUNTERTOP & BACKPLASH

**TOILET

**BATHTUB

1'-4 3/4"

7' -6

**MIRROR

6"

**TOWEL BAR

8'-10"

**TOE KICK

**CABINETS/DRAWERS

**PULL

**COUNTERTOP

3"

2" 1'-8" 1'-8"

M A

X

1' -7

1' -2

6'

-1 0"

**BATHTUB

**SPOUT

**FAUCET

**FAUCET

9" 2'

-1

**UPPER CABINETS

**REFRIGERATOR; PROVIDE MANUF.

RECOMMENDED CLEARANCE

**OVEN/RANGE

**LOWER CABINETS

**TOE KICK

**PULL

**COUNTERTOP & BACKSPLASH

**FLOATING SHELVING

0"

8' -0

1'-0" 1'-0" 2'-0" 2'-6" 1'-9" 3'-3" 1'-6" 2 1/2"

2'-0" 2'-6" 1'-9"

1 1/2"

3'-0"

1 1/2"

1'-6"

2 1/2"

2' -1

0" 1'

-8

3' -6

1' -8

1'

-3

2' -3

RANGE HOOD

9"

FALSE DRAWER

SWITCHES FOR RANGE HOOD & LIGHT

**FILLER PANEL

**GRAB BARS INSTALLED

PER ABA REQUIREMENTS;

PROVIDE BLOCKING

**TOILET

**DOOR

**TISSUE HOLDER

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:0

:1

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

2BR ABA INTERIOR

ELEVATIONS

326141A/326104A610B

05/28/25

1/4" = 1'-0"A610B

B1 ABA KITCHEN - LEFT

1/4" = 1'-0"A610B

B7 ABA BATH 02 - RIGHT

1/4" = 1'-0"A610B

B6 ABA BATH 02 - FRONT

1/4" = 1'-0"A610B

B4 BATH 01 - FRONT

1/4" = 1'-0"A610B

B3 ABA MUDROOM - FRONT

1/4" = 1'-0"A610B

B5 BATH 01 - RIGHT

1/4" = 1'-0"A610B

B2 ABA KITCHEN - REAR

1/4" = 1'-0"A610B

B8 ABA BATH 02 - BACK

4'-1" 1'-4" 3'-4" 1'-4" 3'-0" 1"

**CABINETS/DRAWERS

**PULL

**COUNTERTOP & BACKSPLASH

**CABINET

**MIRROR

3'-6"

8 1/2"

4'-6"

2"

2'-3" 1 9/16"

**WASHER/DRIER

**COUNTERTOP & BACKSPLASH

**PULL

**CABINETS

**TOE KICK

**UPPER CABINETS

1'-0" 2'-0" 3'-0" 1'-6" 1'-6"

**COUNTERTOP

**DRAWER

**PULL

**TOE KICK

**CABINETS

**DISHWASHER

OPEN TO

BEYOND

3'-0" 3'-0" 3'-0"

**COUNTERTOP

**PULL

**CABINETS

**TOE KICK

OPEN TO

BEYOND

2'-7" 2'-6" 2'-6" 5'-7"

**UPPER CABINETS

**REFRIGERATOR

**MICROWAVE

**COUNTERTOP & BACKSPLASH

**PULL

**LOWER DRAWERS

**OVEN/RANGE

**LOWER CABINETS

**TOE KICK

5'-4"

**SHELVES8

**MIRROR

**SHOWERHEAD

**SHOWER ROD

**HAND TOWEL

**FAUCET

**DRAWERS

**PULL

**SPOUT

**BATHTUB

**TOE KICK

**CABINET

**TOILET PAPER HOLDER

1'-9" 1'-9"

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:2

:3

P M

A u to d e sk

D o c s:

Y

E L L N

P S /0 a rc h b d r.

rv t

3BR INTERIOR

ELEVATIONS

326141A610C

06/12/2026

1/4" = 1'-0"A610C

A1 BATH 01 - FRONT

1/4" = 1'-0"A610C

B2 LAUNDRY - FRONT

1/4" = 1'-0"A610C

C2 KITCHEN - REAR

1/4" = 1'-0"A610C

C3 DINING - FRONT

1/4" = 1'-0"A610C

C1 KITCHEN - FRONT

1/4" = 1'-0"A610C

B3 HALL CLOSET - LEFT

1/4" = 1'-0"A610C

B1 BATH 02

5'-5" 3'-4" 1'-4" 3'-0" 1"

**CABINETS/DRAWERS

**PULL

**COUNTERTOP & BACKSPLASH

**ABA TOE KICK

**GRAB BARS INSTALLED PER ABA

REQUIREMENTS; PROVIDE BLOCKING

**ABA FAUCET

**MIRROR

'-1

'-2

8 1/2"

2'-3" 4'-10"

M A

X

'-1

'-6

'-6

**COUNTERTOP & BACKSPLASH

**PULL

**CABINETS

**TOE KICK

**UPPER CABINETS

'-1

1'-0" 2'-0" 3'-0"

1'-6"

1'-6"

**COUNTERTOP

**DRAWER

**PULL

**TOE KICK

**CABINETS

**DISHWASHER

1'-0" 2'-0" 3'-0" 1'-6" 1'-6"

OPEN TO

BEYOND

M A

X

'-1

3'-1" 3'-0" 3'-0"

M A

X

'-1

**COUNTERTOP

**PULL

**CABINETS

**TOE KICK

3'-0" 3'-0" 3'-0"

OPEN TO

BEYOND

'-1

M A

X

'-1

'-8

'-6

'-0

2'-7" 2'-6" 2'-6" 2'-6" 3'-1" 4"

4"

**UPPER CABINETS

**REFRIGERATOR

**COUNTERTOP & BACKSPLASH

**PULL

**LOWER DRAWERS

**OVEN/RANGE

**TOE KICK

'-0

**RANGE HOOD

**FALSE DRAWER

**SWITCHES FOR RANGE HOOD & LIGHT

'-6

'-0

'-0

'-0

'-0

'-6

5'-4"

**SHELVES8

'-0

**MIRROR

**SHOWERHEAD

**SHOWER ROD

**HAND TOWEL

**FAUCET

**DRAWERS

**PULL

**SPOUT

**BATHTUB

**TOE KICK

**CABINET

**TOILET PAPER HOLDER

1'-9" 1'-9"

'-6

A

B

C

PRELIMINARY

NOT FOR

CONSTRUCTION

Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only.

YELLOWSTONE NATIONAL PARK

TITLE OF SHEET

PMIS/PKG NO.

DRAWING NO.SUB SHEET NO.DESIGNED:

JC

CADD:

BB/PS/AS

TECH. REVIEW:

LF

DATE:

A/E: FIRM

PRIME:

STANTEC

CHEYENNE, WY

SHEET

OF

P

LO

T D

A

TE

R

E V

IT

V

E R

SI

O

N

198433

:3

:4

P M

A u to d e sk

D o c s:

/1

Y

E L L N

P S a rc h b d r_ a d a .r v t

3BR ABA INTERIOR

ELEVATIONS

326141A610D

06/12/2026

1/4" = 1'-0"A610D

A1 ABA BATH 01 - FRONT

1/4" = 1'-0"A610D

B2 ABA LAUNDRY - FRONT

1/4" = 1'-0"A610D

C2 ABA KITCHEN - REAR

1/4" = 1'-0"A610D

C3 ABA DINING - FRONT

1/4" = 1'-0"A610D

C1 ABA KITCHEN - FRONT

1/4" = 1'-0"A610D

B3 ABA HALL CLOSET - LEFT

1/4" = 1'-0"A610D

B1 BATH 02 - RIGHT

File details come from the government source that posted it. Updated .