B09_Amd_02_Attach_08_26_28_00_Overcurrent_and_Short_Circuit_Protective_Devices_Rev_1_0002.pdf

PDF 355 KB Posted

Attached to
NOCA 156728 Stehekin WWTP
Solicitation number
140P2023R0131
Issued by

About this file

This technical specification document outlines requirements for overcurrent and short circuit protective devices for a federal contract to replace an obsolete wastewater treatment plant. Key details include specifications for low voltage circuit breakers and fuses to provide overcurrent and short circuit protection. Device types include molded case, thermal magnetic, ground fault, and motor circuit protector breakers. Submittal requirements cover product data, fabrication drawings, and control wiring diagrams. Testing requirements specify acceptance testing per Section 26 08 13 and testing of load shedding and automatic reclosing functions for remotely operated circuit breakers. Installation instructions provide guidance on current and interrupting ratings, series ratings, ambient temperature compensation, and frame size and trip settings for circuit breakers and fuse classes for different applications.

View the file

Other files

File Type Posted
Sol_140P2023R0131_Amd_0004.pdf PDF
B09_Amd_03_Attach_02_Solit_Clauses_Construction_REVISED_20230828_0003.docx DOCX document
Sol_140P2023R0131_Amd_0003.pdf PDF
B09_Amd_03_Attach_04_32_62_17_Driven_Steel_Sheet_Piling_Rev_1_0003.pdf PDF
B09_Amd_03_Attach_01_140P2023R0131_QA3_0003.xlsx XLSX spreadsheet
B09_Amd_03_Attach_05_NOCA_STEHEKIN_Drawings_for_Rev_2_Structural_Updates_08-25-23_0003.pdf PDF
B09_Amd_03_Attach_03_01_27_00_Definition_of_Contract_Line_Items_Rev_1_0003.pdf PDF
B09_Amd_03_SF30_NOCA_156728_140P2023R0131_0003.pdf PDF
Sol_140P2023R0131_Amd_0002.pdf PDF
B09_Amd_02_Attach_04_Specification_40_61_96_correction_0002.pdf PDF
B09_Amd_02_Attach_10_Site_Visit_Tri_Fold_NOCA_156728_0002.docx DOCX document
B09_Amd_02_Attach_11_Site_Visit_Sign-in_0002.pdf PDF
B09_Amd_02_Attach_01_140P2023R0131_QA2_0002.xlsx XLSX spreadsheet
B09_Amd_02_Attach_07_26_09_13_Electrical_Metering_Devices_Rev_1_0002.pdf PDF
B09_Amd_02_SF30_NOCA_156728_140P2023R0131_0002.pdf PDF
B09_Amd_02_Attach_05_Specification__40_66_40_correction_0002.pdf PDF
B09_Amd_02_Attach_03_Specification_03_31_30_correction_0002.pdf PDF
B09_Amd_02_Attach_06_Specification__46_53_25_correction_0002.pdf PDF
B09_Amd_02_Attach_02_Specification_01_73_20_correction_0002.pdf PDF
B09_Amd_02_Attach_09_NOCA_STEHEKIN_Drawings_for_Rev_1_Electrical_Updates_08-10-2023_0002.pdf PDF
Sol_140P2023R0131_Amd_0001.pdf PDF
B09_Amd_01_SF30_NOCA_156728_140P2023R0131_0001.pdf PDF
B09_Amd_01_140P2023R0131_QA1s_0001.xlsx XLSX spreadsheet
B08_Attach_3_22_07_26_-_Final_Geo-tech_Report.pdf PDF
B08_Attach_9_Solit_PSP_Vol_II_GenRefs.doc DOC document
B08_Attach_2c_NOCA_156728_100__CD_Drawings_Part3.pdf PDF
B08_Attach_8_Solit_PSP_Vol_I_PastPerf_REQD.docx DOCX document
B08_Attach_2b_NOCA_156728_100__CD_Drawings_Part2.pdf PDF
B08_Attach_2a_NOCA_156728_100__CD_Drawings_Part1.pdf PDF
B08_SF_1442_140P2023R0131.pdf PDF
B08_Attach_7_Deliverables_LmtOnSubconRpt_REQ.xlsx XLSX spreadsheet
B08_Attach_6_Construction_Contract_Administration.docx DOCX document
Sol_140P2023R0131.pdf PDF
B08_Attach_4_22_10_06_-_Geotech_Report_for_Disposal_Field_Test_Pits_-r1.pdf PDF
B08_Attach_1_NOCA_156728_100___CD_Specifications.pdf PDF
B08_Attach_5_Const_WD_DBA_WA20230065.pdf PDF
B08_Attach_2d_NOCA_156728_100__CD_Drawings_Part4.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10350902 National Park Service Replace Obsolete Stehekin Wastewater Treatment Plant - 100% Complete Contract Documents

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES

26 28 00 - 1

SECTION 26 28 00

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Low voltage circuit breakers.

2. Low voltage fuses.

B. Related Specification Sections include but are not necessarily limited to:

1. Section 26 05 00 - Electrical - Basic Requirements.

2. Section 26 08 13 - Acceptance Testing.

3. Section 26 09 13 – Electrical Metering Devices

1.2 QUALITY ASSURANCE

A. Referenced Standards:

1. Institute of Electrical and Electronics Engineers, Inc. (IEEE):

a. C37.13, Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures.

b. C37.16, Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors -

Preferred Ratings, Related Requirements, and Application Recommendations.

c. C37.17, Trip Devices for AC and General Purpose DC Low Voltage Power Circuit

Breakers.

2. National Fire Protection Association (NFPA):

a. 70, National Electrical Code (NEC).

3. Underwriters Laboratories, Inc. (UL):

a. 248-1, Low-Voltage Fuses - Part 1: General Requirements.

b. 248-8, Low-Voltage Fuses - Part 8: Class J Fuses.

c. 489, Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches, and

Circuit-Breaker Enclosures.

d. 943, Standard for Safety for Ground-Fault Circuit-Interrupters.

e. 1066, Standard for Low-Voltage AC and DC Power Circuit Breakers Used in

Enclosures.

1.3 SUBMITTALS

A. Shop Drawings:

1. Product technical data including:

a. Provide submittal data for all products specified in PART 2 of this Specification Section.

b. See Specification Section 26 05 00 for additional requirements.

2. Fabrication and/or layout drawings.

3. Control wiring diagram and programing for load shedding.

B. Contract Closeout Information:

1. Operation and Maintenance Data:

a. See Specification Section 01 78 23 for requirements for the mechanics, administration, and the content of Operation and Maintenance Manual submittals.

C. Informational Submittals:

1. Reports:

a. As-left condition of all circuit breakers that have adjustable settings.

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES

26 28 00 - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Subject to compliance with the Contract Documents, the following manufacturers are acceptable:

1. Circuit breakers:

a. Eaton.

b. GE by ABB.

c. Square D Company.

d. Siemens.

2. Fuses:

a. Eaton Bussmann, Inc.

b. Littelfuse, Inc.

c. Mersen

2.2 CIRCUIT BREAKERS

A. Molded Case Type:

1. General:

a. Standards: UL 489.

b. Unit construction.

c. Over-center, toggle handle operated.

d. Quick-make, quick-break, independent of toggle handle operation.

e. Manual and automatic operation.

f. All poles open and close simultaneously.

g. Three position handle: On, off and tripped.

h. Molded-in ON and OFF markings on breaker cover.

i. One-, two- or three-pole as indicated on the Drawings.

j. Current and interrupting ratings as indicated on the Drawings.

2. Remotely operated breakers:

a. Basis of design for remotely operated breakers Square D. Solutions by other manufactures listed in Part 1 are acceptable:

1) Powerlink ECB-G3 Breakers

2) NF-G3 POWERLINK control busses attached to interior rails in a panelboard

3) POWERLINK G3 power supply

4) Modem Kit 6382G3MODEM for use with POWERLINK G3 Controllers

b. Title 24 and ASHRAE 90.1 compliant.

c. Remotely monitor and control circuits.

d. Ability to control breakers remotely – ON, OFF

e. Integral branch circuit overcurrent protection as required by the NEC. Circuit breakers shall have a UL-listed interrupting rating sufficient for the application or UL-listed series connected ratings for the maximum available fault current at that point in the system. Submittals reflecting the use of relays or contactors to perform remote switching shall show evidence in writing that the relays or contactors are listed to withstand the available fault current.

f. UL-listed SWD ratings for 15 ampere, 20 ampere, and 30 ampere 1-pole, 2-pole, and 3-pole branch devices, HID ratings, and HACR ratings.

g. Handle operator that shall mechanically open the power switching device contacts when moved to the OFF position and disable the contacts from being remotely closed.

Handle operator shall accept field-installable handle tie to allow application where a handle tie is required by the NEC.

h. Manual override switch to enable or disable the remote operation of the device and allow circuit breaker handle to fully control the on/off state of the circuit breaker.

Override shall fully disengage remote operation of the circuit breaker mechanism.

Device utilizing one-shot or temporary overrides shall not be accepted.

i. Visible flag that clearly indicates the status of the circuit breaker contacts with the panel trim installed. Flag shall indicate ON, OFF, and TRIPPED circuit breaker states. The

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES

26 28 00 - 3 visible flag shall be mechanical in nature, directly tied to the circuit breaker mechanism, and shall be provided in addition to any status indicator supplied by the system electronics.

j. Voltage status signal to indicate the presence or absence of voltage at the load terminal as a true indication of the on/off status of the connected circuit to aid in identifying wiring errors, such as a back-feed or disconnected neutral conductor.

k. Circuit to indicate the number of poles of the remotely operable circuit breaker.

l. Integral control connector to simplify and speed installation and eliminate wiring errors such that the control connection is made automatically when installing the breaker in the panelboard. Connection to the breaker shall not introduce control wiring into the panelboard gutter space. Control connections shall be rated NEC Class 1 to eliminate the requirement for barriers in the gutter space such that control connections may reside with electrical power circuit conductors.

m. Switching full load endurance rating of 200,000 open/close/open remote operations.

3. Thermal magnetic type:

a. Inverse time overload and instantaneous short circuit protection by means of a thermal magnetic element.

b. Frame size 150 amp and below:

1) Non-interchangeable, non-adjustable thermal magnetic trip units.

c. Ground Fault Circuit Interrupter (GFCI) Listed:

1) Standard: UL 943.

2) One- or two-pole as indicated on the Drawings.

3) Class A ground fault circuit.

4) Trip on 5 mA ground fault (4-6 mA range).

d. Switching Duty (SWD) Listed:

1) 15 and 20 amp rated at 347 V and less.

2) Suitable for switching loads on a regular basis

e. Title 24 and ASHRAE 90.1 compliant.

f. Remotely monitor and control circuits.

g. Ability to control breakers remotely – ON, OFF

4. Motor circuit protector:

a. Adjustable instantaneous short circuit protection by means of a magnetic or solid state trip element.

b. Sized for the connected motor.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Current and interrupting ratings as indicated on the Drawings.

B. Series rated systems not acceptable.

C. Devices shall be ambient temperature compensated.

D. Circuit Breakers:

1. Molded case circuit breakers shall incorporate the following, unless indicated otherwise on the Drawings:

a. Frame sizes 400 amp and less with trip setting less than 400A shall be thermal magnetic type.

b. Motor circuit protectors sized for the connected motor.

2. Insulated case circuit breakers shall incorporate the following, unless indicated otherwise on the Drawings:

a. Set current sensor or rating plugs long time pick-up setting so that the indicated trip level is near the 75% trip point.

E. Fuses:

1. UL Class RK-1 (fast acting): Use where indicated.

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES

26 28 00 - 4

2. UL Class RK-1 (dual element): Use for motor feeder and branch circuit devices.

3. UL Class RK-5: Use for motor feeder and branch circuit devices.

3.2 FIELD QUALITY CONTROL

A. Testing:

1. Acceptance testing: See Specification Section 26 08 13.

2. Remotely Operated Circuit Breakers:

a. Testing automatic load shedding operation.

b. Testing automatic reclosing operation.

END OF SECTION