B09_Amd_02_Attach_06_Specification__46_53_25_correction_0002.pdf

PDF 130 KB Posted

Attached to
NOCA 156728 Stehekin WWTP Federal contract opportunity
Solicitation number
140P2023R0131
Issued by
Department of the Interior National Park Service National Office

About this file

This document amends specifications for a recirculating textile filter system for the Stehekin Wastewater Treatment Plant. The specifications outline seasonal scenarios for limiting equipment operation to reduce the overall electric load at the plant. For summer operation from April 1 to October 31, no more than one feed pump, one small recirculation pump, two large recirculation pumps, one discharge pump, and one anoxic return pump can operate at a time, with a total of four pumps. The fan inlet heater cannot operate. For winter operation from November 1 to May 31, the same limits apply except large recirculation pumps cannot operate and the fan inlet heater cannot operate during pump operation. The amended specifications relate to solicitation number 140P2023R0131 from the National Park Service National Office for the Stehekin Wastewater Treatment Plant.

View the file

Other files for this federal contract opportunity

Other files attached to NOCA 156728 Stehekin WWTP, newest first.
File Type Posted
Sol_140P2023R0131_Amd_0004.pdf PDF
B09_Amd_03_Attach_01_140P2023R0131_QA3_0003.xlsx XLSX spreadsheet
B09_Amd_03_Attach_05_NOCA_STEHEKIN_Drawings_for_Rev_2_Structural_Updates_08-25-23_0003.pdf PDF
B09_Amd_03_Attach_04_32_62_17_Driven_Steel_Sheet_Piling_Rev_1_0003.pdf PDF
B09_Amd_03_Attach_03_01_27_00_Definition_of_Contract_Line_Items_Rev_1_0003.pdf PDF
Sol_140P2023R0131_Amd_0003.pdf PDF
B09_Amd_03_SF30_NOCA_156728_140P2023R0131_0003.pdf PDF
B09_Amd_03_Attach_02_Solit_Clauses_Construction_REVISED_20230828_0003.docx DOCX document
B09_Amd_02_Attach_08_26_28_00_Overcurrent_and_Short_Circuit_Protective_Devices_Rev_1_0002.pdf PDF
B09_Amd_02_Attach_04_Specification_40_61_96_correction_0002.pdf PDF
B09_Amd_02_Attach_01_140P2023R0131_QA2_0002.xlsx XLSX spreadsheet
B09_Amd_02_Attach_02_Specification_01_73_20_correction_0002.pdf PDF
B09_Amd_02_Attach_09_NOCA_STEHEKIN_Drawings_for_Rev_1_Electrical_Updates_08-10-2023_0002.pdf PDF
Sol_140P2023R0131_Amd_0002.pdf PDF
B09_Amd_02_Attach_03_Specification_03_31_30_correction_0002.pdf PDF
B09_Amd_02_SF30_NOCA_156728_140P2023R0131_0002.pdf PDF
B09_Amd_02_Attach_11_Site_Visit_Sign-in_0002.pdf PDF
B09_Amd_02_Attach_10_Site_Visit_Tri_Fold_NOCA_156728_0002.docx DOCX document
B09_Amd_02_Attach_05_Specification__40_66_40_correction_0002.pdf PDF
B09_Amd_02_Attach_07_26_09_13_Electrical_Metering_Devices_Rev_1_0002.pdf PDF
B09_Amd_01_SF30_NOCA_156728_140P2023R0131_0001.pdf PDF
Sol_140P2023R0131_Amd_0001.pdf PDF
B09_Amd_01_140P2023R0131_QA1s_0001.xlsx XLSX spreadsheet
B08_Attach_2c_NOCA_156728_100__CD_Drawings_Part3.pdf PDF
B08_Attach_2b_NOCA_156728_100__CD_Drawings_Part2.pdf PDF
B08_Attach_3_22_07_26_-_Final_Geo-tech_Report.pdf PDF
B08_Attach_6_Construction_Contract_Administration.docx DOCX document
B08_Attach_9_Solit_PSP_Vol_II_GenRefs.doc DOC document
B08_Attach_2a_NOCA_156728_100__CD_Drawings_Part1.pdf PDF
B08_Attach_1_NOCA_156728_100___CD_Specifications.pdf PDF
B08_Attach_8_Solit_PSP_Vol_I_PastPerf_REQD.docx DOCX document
B08_Attach_7_Deliverables_LmtOnSubconRpt_REQ.xlsx XLSX spreadsheet
B08_Attach_4_22_10_06_-_Geotech_Report_for_Disposal_Field_Test_Pits_-r1.pdf PDF
Sol_140P2023R0131.pdf PDF
B08_Attach_2d_NOCA_156728_100__CD_Drawings_Part4.pdf PDF
B08_Attach_5_Const_WD_DBA_WA20230065.pdf PDF
B08_SF_1442_140P2023R0131.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADD the following to Specification Section 46 53 25 – Recirculating Textile Filter System Article 2.8.D.

10. Limiting equipment operation to reduce the overall WWTP electric load per the following operator defined seasonal scenarios:

a. Summer Operation to be operator adjustable with a default of April 1 – October 31.

b. Winter Operation to be operator adjustable with a default of November 1 – May 31.

c. Summer Operation

1) Operation of no more than one RTF Feed Pump (PMP‐4411 and PMP‐4412) at any given time.

2) Operation of no more than one Small Recirculation Pump (PMP‐5111 and PMP‐ 5112) at any given time.

3) Operation of no more than two Large Recirculation Pumps (PMP‐5211, PMP‐5311, PMP‐5411, and PMP‐5511) at any given time.

4) Operation of no more than one RTF Discharge Pump (PMP‐5613 and PMP‐5614) at any given time.

5) Operation of no more than one Anoxic Return Pump (PMP‐5611 and PMP‐5612) at any given time.

6) Operation of no more than 4 pumps total at any given time. The order of priority is:

a) RTF Feed Pumps (PMP‐4411 and PMP‐4412)

b) RTF Discharge Pumps (PMP‐5613 and PMP‐5614)

c) Large Recirculation Pumps (PMP‐5211, PMP‐5311, PMP‐5411, and PMP‐5511)

d) Small Recirculation Pumps (PMP‐5111 and PMP‐5112

e) Anoxic Return Pumps (PMP‐5611 and PMP‐5612)

7) No operation of fan inlet heater (HTR‐5142).

d. Winter Operation

1) Operation of no more than one RTF Feed Pump (PMP‐4411 and PMP‐4412 at any given time.

2) Operation of no more than one Small Recirculation Pump (PMP‐5111 and PMP‐ 5112) at any given time.

3) No Operation of Large Recirculation Pumps (PMP‐5211, PMP‐5311, PMP‐5411, and

PMP‐5511).

4) Operation of no more than one RTF Discharge Pump (PMP‐5613 and PMP‐5614) at any given time.

5) Operation of no more than one Anoxic Return Pump (PMP‐5611 and PMP‐5612) at any given time.

6) No operation of fan inlet heater (HTR‐5142) during pump operation.