18038.02-01-440-02_Machinery Control System Points List_Rev A_signed.pdf
PDF 721 KB Posted
- Attached to
- NOAA Ship Ronald H. Brown: Mid-Life Refit Federal contract opportunity
- Solicitation number
- 1305M221RNMAN01155
About this file
This document outlines the requirements for a mid-life refit of the NOAA Ship Ronald H. Brown. The National Oceanic and Atmospheric Administration is seeking a firm fixed price contract to provide all labor, materials, and equipment necessary to upgrade or overhaul many of the ship's systems, including repowering, bow thruster, Z-drive, potable water, chilled water, sewage, science refrigeration, uncontaminated seawater, air handling, HVAC, tank level indicator, navigational equipment, radar, lighting, and exterior ballast and fuel tank vent renewals. Much of the ship's piping will also be replaced along with identified steelwork. Offerors must submit inquiries by June 28, 2021 and proposals by August 6, 2021. The refit work will ensure the continued operation of this research vessel.
View the file
Other files for this federal contract opportunity
Show all 50
NOAA Ship Ronald H. Brown: Mid-Life Refit has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BY:
CHECKED:
APPROVED:
FILE:
DOCUMENT:
REVISION:
DATE:
REV. SECTION DESCRIPTION
- ALL Initial Release A Page 8 MG Set 1 and 2 items removed. ID NO. 02-252E126 and 02-252E127.
R/V Atlantis Midlife Refit Alarm and Monitoring System (AMS) Points List Vessel Repower Project
Woods Hole Oceanographic Institution Woods Hole, Massachusetts
JS
JMW
DWL
18038.02 18038.02-01-440-02 A 6/5/2019
REFERENCED NOTES
GENERAL NOTES REFERENCES
REVISIONS
1. This list includes all data points that shall, at a minimum, be incorporated into the Alarm and Monitoring System (AMS). The Contractor shall verify this list with certified drawings of provided equipment. Any additional data points required to support installed systems and/or meet applicable flag and class requirements shall also be included in the final system points list.
2. AMS system shall recieve all data points from field devices and vessel systems, and provide control, alarm, and indication in accordance with the 'Function' columns of this spreadsheet.
3. The Contractor shall confirm all monitoring and alarm points. Where [TBD] is noted in the table, the Contractor shall interface with the system designer to provide appropriate information to complete the design.
4. Where alarm setpoints and alarm delays are noted, these reflect the best information available at the time of design.
Deviations to these values must be approved by the Owner.
5. Regulatory references to Part 4, Chapter 9 of the ABS Rules refer to the Steel Vessel Rules in accordance with 4-7-1/1 of the ABS Rules for Steel Vessel <90m in length.
6. To minimize operator distraction and enhance response to abnormal situations, audible alarms at the Pilothouse AMS operator station shall be limited to propulsion, steering, vital machinery, personnel, fire, and flooding alarms that are required by ABS and USCG. All alarm conditions should be available for view at the Pilothouse OS. Non-vital alarms should not sound in the bridge. If an alarm goes unacknowledged at the Main Control Station, the Engineer Assistance Needed alarm shall activate.
1. R/V Atlantis Midlife Refit, Shipyard Contract Technical Specification, Glosten, Inc., Document No. 16101.02- S01
2. R/V Atlantis Midlife Refit, WP-01 – Work Package Specification, Repower, Glosten, Inc.
3. R/V Atlantis Electrical One Line Diagram, Glosten Inc., Drawing No. 01-300-01
4. R/V Atlantis Integrated Control and Monitoring Block Diagram System One-Line, Glosten Inc., Drawing No. 01- 440-01
5. Not Used
6. Electrical One-Line Diagram, Dept. of the Naval Sea Systems Command, 300-6932-781 Rev D, 16 January 1996
7. Electrical Load Analysis, Dept. of the Naval Sea Systems Command, 300-6932-780 Rev B, 16 January 1996
8. Panelboards/Lighting One-Line Diagram, Dept. of the Naval Sea Systems Command, 300-6932-741 Rev E, 10 February 1994
9. Machinery Control System Block Diagram, Dept. of the Naval Sea Systems Command, 202-6932-730 Rev F, 7 September 1993
10. Clean Power System Elementary Wiring Diagram, Dept. of the Naval Sea Systems Command, 300-6932-740 Rev C, 17 September 1993
11. Lighting System Deck Plan, Dept. of the Naval Sea Systems Command, 300-6932-744 Rev D, 10 February
12. H.V.A.C. Fan List, Dept. of the Naval Sea Systems Command, 514-6932-963 Rev F, 30 August 1993
13. AGOR 24 Mid Life Overhaul Option 1 Siemens Blue Drive PlusC, Siemens Industry Inc., 20 January 2017.
PREPARED FOR
A. All Marcon tank level indicators are to be protected by 0.1A fuses. The Marcon TLI are configured to output a 4-20mA signal.
B. The Contractor is responsible for calibration of TLI and correlation with tank tables for volume calculations, values shown are developed from T&S booklet and existing AMS calibration sheets.
C. Serial communications link between generator local panel and AMS.
D. Machinery space bilge alarms: retain bilge float switches.
E. Alarms shall be inhibited during normal starting and stopping sequences, see 46 CFR 62.25-20(e)(iv).
F. Alarms associated with EAS system shall be developed by the Contractor to meet applicable requirements.
G. Shutdown control function performed by engine safety system, integral to main engine local panel.
H. Field device is part of Siemens supply.
I. Existing indication lights and pushbuttons shall be replaced.
J. Field device to be retained. Contractor shall confirm device characteristics and provide new cabling to device.
K. Integration with the work scope of other work packages (in addition to WP-01) is required.
L. Existing analog panel meter shall be replaced.
M. The Engineer Assistance Needed alarm shall sound at the pilothouse and the EAS when manually activated at the MCSC, if an power supply fails, or if an AMS alarm goes unacknowledged for 2 minutes.
PREPARED FOR
R/V Atlantis Midlife Refit AMS Points List, Rev. A Page 1 of 19
Glosten, Inc.
File No. 18038.02
5 June 2019
ID NO.
Description
General Note Regulatory Citation Regulatory Existing Preference Display (HMI) Trend
Alarm Control
Signal Type
Cabinet Alarm Group
Range Units Signal Range/ Units
(AI/AO)
or Signal Sense
(DI/DO)
Engineering Range/Units Manufacturer Model / Part Location Hi / On
Hi Delay(on/off) HiHi
HiHiDelay(on/off Low / OFF
Lo Delay(on/off) LoLo
LoLo Delay(on/o Ref. Dwg Comment
COLUMN DESCRIPTIONS
Authority
Function
Signal
HMI
Instrument
Instrument Manufacturer or equipment manufacturer if available.
instrument or equipment model number or part number if available.
Alarms
The signal is required to initiate an AMS alarm. The alarm shall show on the AMS OS in text and colorized indication.
The signal initiates, or is part of a controlled equipment.
Description of the signal A reference to a note from Sheet 1 of this document.
A reference to a section of the USCG regulations (46 CFR), ABS Steel Vessel Rules, and/or ABS Steel Vessel Rules <90 meters in length.
The signal is interpreted to be required by one or more regulatory authorities.
The signal is from or to an existing piece of equipment.
Additional comments associated with signal.
ID number associate with the signal. Number is a reference to existing instrument numbers for retained instruments, or to Instrument IDs from new P&IDs.
Low or Off alarm activation setpoint.
Low or Off alarm on delay, and/or off delay.
Low-Low alarm activation setpoint.
Low-Low alarm on delay, and/or off delay.
Reference drawing associated with signal.
Location of instrument associated with the signal.
High or On alarm activation setpoint.
High or On alarm on delay, and/or off delay.
High-High alarm activation setpoint.
High-High alarm on delay, and/or off delay.
The signal is not required by regulatory authority, but is included as part of the design.
The signal is required to be shown on the AMS operator stations on one of the system screens.
The signal is required to be shown as a trend line built into the AMS OS.
Units of the range to be use on the operator station screens.
Signal range and units of the instrument (e.g. 4-20mA)
Engineering range associated with the instrument signal range (e.g. 0 to 100 psi)
Type of signal:
AI: Analog Input AO: Analog Output DI: Digital Input DO: Digital Output INT: Calculated or derived signal internal to the AMS RTD: Resistance Temperature Device (e.g. Pt100) SAI: Analog Input Signal via Serial Interface SAO: Analog Output Signal via Serial Interface SDI: Digital Input Signal via Serial Interface SDO: Digital Output Signal via Serial Interface TC: Thermocouple RIO or processing cabinet associated with the signal.
Alarm grouping associated with the signal.
Range of the display to be used on the operator station screens.
R/V Atlantis Midlife Refit AMS Points List, Rev. A Page 2 of 19
Glosten, Inc.
ID NO. Description Note Ref.
Regulatory Citation R eg ul at or y
E xi st in g
Pr ef er en ce
D is pl ay
(H
M I)
Tr en d
A la rm
C on tr ol
Signal Type Cabinet Alarm Group Range Units
Signal Range/Units
(AI/AO)
or Signal Sense (DI/DO)
Engineering Range/Units Manufacturer Model / Part Location Hi / On
Hi Delay (On/Off) HiHi
HiHiDelay (On/Off) Low / OFF
Lo Delay (On/Off) LoLo
LoLo Delay
(On/Off) Ref. Dwg(s) Comment AMS System Points List
Port Z-Drive
AZP-100 Port Z-Drive Azimuth Defective J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-101 Port Z-Drive Hydraulic Oil Tank Level Low J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-103 Port Z-Drive Hydraulic Pressure Low E, J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-105 Port Z-Drive Hydraulic Oil Temperature High J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/High [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-106 Port Z-Drive Lube Oil Pressure Low E, J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-107 Port Z-Drive Lube Oil Temperature High J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/High [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-108 Port Z-Drive Lube Oil Tank Level Low J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-109 Port Z-Drive Hydraulic Pump Overload J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-111 Port Z-Drive Hydraulic Pump Phase Failure J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-113 Port Z-Drive Hydraulic Pump Power Failure J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-115 Port Z-Drive Control Power Normal J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZP-130 Port Z-Drive Hydraulic Pump Run J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - Motor Cont. existing Prop Motor Rm - - - - - - - - 339P0207-0021, SHTS 33CA-DB AZP-132 Port Z-Drive Lube Oil Pump Run J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - Motor Cont. existing Prop Motor Rm - - - - - - - - 339P0207-0021, SHTS 33CA-DB PMP-153 MCSC - Port Z-Drive Healthy Relay I X X X DO PCU 1 Propulsion - - [TBD] - [TBD] existing MCSC - - - - - - - - 339P0207-0021, SHTS 21AR, 21CB
PMP-154
MCSC - Port Propulsion Motor Lube Oil Pump Running Indicator Lamp I X X X DO PCU 1 Propulsion - - Energized = pump running - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CB
PMP-155
MCSC - Port Propulsion Motor Azimuth Pump Running Indicator Lamp I X X X DO PCU 1 Propulsion - - Energized = pump running - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CB
PMP-165 PHC - Port Z-Drive Azimuth Pump Running Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CC
PMP-164 PHC - Port Z-Drive Lube Oil Pump Running Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZP-121 PHC - Port Z-Drive Azimuth Pump Overload Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CC
AZP-125
PHC - Port Z-Drive Azimuth Pump Power Failure Indicator Lamp I X X X DO RIO 5 Propulsion - -
IR, NO contacts Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CC
AZP-127 PHC - Port Z-Drive Normal Power Failure Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CC
AZP-120
PHC - Port Z-Drive Hydraulic Oil Tank Level Low Indicator Lamp I X X X DO RIO 5 Propulsion - -
IR, NO contacts Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZP-123 PHC - Port Z-Drive Azimuth Pump Phase Fail Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD PT-302A Port Steering Lube Oil Pressure X X AI RIO 3 Propulsion 0 - 100 psi [TBD] 0 - 100 psi [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3 PT-302B Port Steering Hydraulic Pressure X X AI RIO 3 Propulsion 0 - 4000 psi [TBD] 0 - 4000 psi [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3
RTD-302A Port Steering Lube Oil Temperature X X RTD RIO 3 Propulsion -180 - 850 deg C RTD - 100ohm, Platinum a = 0.00385 -180 - 850 deg C [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3
RTD-302B Port Steering Hydraulic Oil Temp X X RTD RIO 3 Propulsion -180 - 850 deg C RTD - 100ohm, Platinum a = 0.00385 -180 - 850 deg C [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3 Stbd Z-Drive
AZS-100 Stbd Z-Drive Azimuth Defective J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-101 Stbd Z-Drive Hydraulic Oil Tank Level Low J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-103 Stbd Z-Drive Hydraulic Pressure Low E, J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-105 Stbd Z-Drive Hydraulic Oil Temperature High J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/High [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-106 Stbd Z-Drive Lube Oil Pressure Low E, J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-107 Stbd Z-Drive Lube Oil Temperature High J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/High [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-108 Stbd Z-Drive Lube Oil Tank Level Low J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Low [TBD] [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-109 Stbd Z-Drive Hydraulic Pump Overload J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-111 Stbd Z-Drive Hydraulic Pump Phase Failure J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-113 Stbd Z-Drive Hydraulic Pump Power Failure J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion OK/Fault - [TBD] - Motor Cont. existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-115 Stbd Z-Drive Control Power Normal J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - LIPS controls existing Prop Motor Rm alm on fault 1 sec - - - - - - 339P0207-0021, SHTS 33CA-DB
AZS-130 Stbd Z-Drive Hydraulic Pump Run J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - Motor Cont. existing Prop Motor Rm - - - - - - - - 339P0207-0021, SHTS 33CA-DB AZS-132 Stbd Z-Drive Lube Oil Pump Run J 46 CFR 62, 4-3-3/11.9 X X X DI RIO 3 Propulsion On/Off - [TBD] - Motor Cont. existing Prop Motor Rm - - - - - - - - 339P0207-0021, SHT 21CB PMS-153 MCSC - Stbd Z-Drive Healthy Relay I X X X DO PCU 2 - - [TBD] - [TBD] existing MCSC - - - - - - - - 339P0207-0021, SHTS 21AR, 21CC
PMS-154
MCSC - Stbd Propulsion Motor Primary Lube Oil Pump Running Indicator Lamp I X X X DO PCU 2 Propulsion - - Energized = pump running - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CC
PMS-155
MCSC - Stbd Propulsion Motor Azimuth Pump Running Indicator Lamp I X X X DO PCU 2 Propulsion - - Energized = pump running - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CC
PMS-165 PHC - Stbd Z-Drive Azimuth Pump Running Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
PMS-164 PHC - Stbd Z-Drive Lube Oil Pump Running Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZS-121 PHC - Stbd Z-Drive Azimuth Pump Overload Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZS-125
PHC - Stbd Z-Drive Azimuth Pump Power Failure Indicator Lamp I X X X DO RIO 5 Propulsion - -
IR, NO contacts Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZS-127 PHC - Stbd Z-Drive Normal Power Failure Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZS-120
PHC - Stbd Z-Drive Hydraulic Oil Tank Level Low Indicator Lamp I X X X DO RIO 5 Propulsion - -
IR, NO contacts Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
AZS-123 PHC - Stbd Z-Drive Azimuth Phase Failure Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD PT-301A Stbd Steering Lube Oil Pressure X X AI RIO 3 Propulsion 0 - 100 psi [TBD] 0 - 100 psi [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3 PT-301B Stbd Steering Hydraulic Pressure X X AI RIO 3 Propulsion 0 - 4000 psi [TBD] 0 - 4000 psi [TBD] [TBD] Prop Motor Rm - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3
RTD-301A Stbd Steering Lube Oil Temperature X X RTD RIO 3 Propulsion -180 - 850 deg C RTD - 100ohm, Platinum a = 0.00385 -180 - 850 deg C [TBD] [TBD] - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3
RTD-301B Stbd Steering Hydraulic Oil Temp X X RTD RIO 3 Propulsion -180 - 850 deg C RTD - 100ohm, Platinum a = 0.00385 -180 - 850 deg C [TBD] [TBD] - - - - - - - - 01-440-01, WH01101-E-001 Was part of GE AMS system annex to RIO 3 Port Propulsion Motor
[TBD] Port Propulsion Motor Bearing Temp DE H Table 4A-B1 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 [TBD] Port Propulsion Motor Bearing Temp NDE H Table 4A-B1 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 [TBD] Port Propulsion Motor Winding Temperature - Phase A H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Port Propulsion Motor Winding Temperature - Phase B H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Port Propulsion Motor Winding Temperature - Phase C H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Port Propulsion Motor Cooling Water Outlet Temperature H Table 4A-B13 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Port Propulsion Motor Cooling Air Temperature - Cold Side H Table 4A-B13 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
PMP-151 MCSC - Port Propulsion Motor Fault Indicator Lamp I X X X DO PCU 1 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CB Change existing IDEC Window Lettering, illuminate on any alarm condition of propulsion motor
PMP-161 PHC - Port Propulsion Motor Fault Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CB Change existing IDEC Window Lettering, illuminate on any alarm condition of propulsion motor
PMP-200 PHC - Port Propulsion Motor CB Open Indicator Lamp I Table 4A-B9 X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD Illuminate if Stbd motor CB is open or tripped
Authority AlarmsSignal HMI InstrumentFunction
R/V Atlantis Midlife Refit AMS Points List, Rev. A Page 3 of 19
Glosten, Inc.
Ref.
Regulatory Citation R eg ul at or y
E xi st in g
Pr ef er en ce
D is
I)
Tr en d
A la rm
C on tr ol
Signal Type Cabinet Alarm Group Range Units
Signal Range/Units
(AI/AO)
or Signal Sense (DI/DO)
Engineering Range/Units Manufacturer Model / Part Location Hi / On
Hi Delay (On/Off) HiHi
HiHiDelay (On/Off) Low / OFF
Lo Delay (On/Off) LoLo
LoLo Delay
(On/Off) Ref. Dwg(s) Comment
Authority AlarmsSignal HMI InstrumentFunction
Stbd Propulsion Motor [TBD] Stbd Propulsion Motor Bearing Temp DE H Table 4A-B1 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 [TBD] Stbd Propulsion Motor Bearing Temp NDE H Table 4A-B1 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 [TBD] Stbd Propulsion Motor Winding Temperature - Phase A H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Stbd Propulsion Motor Winding Temperature - Phase B H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Stbd Propulsion Motor Winding Temperature - Phase C H Table 4A-B8 X X X RTD RIO 3 Propulsion 40 - 300 deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01 RTDs in motor [TBD] Stbd Propulsion Motor Cooling Water Outlet Temperature H Table 4A-B13 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Stbd Propulsion Motor Cooling Air Temperature - Cold Side H Table 4A-B13 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - [TBD] - Siemens - Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
PMS-151 MCSC - Stbd Propulsion Motor Fault Indicator Lamp I X X X DO PCU 2 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CC Change existing IDEC Window Lettering, illuminate on any alarm condition of propulsion motor
PMS-161 PHC - Stbd Propulsion Motor Fault Indicator Lamp I X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD Change existing IDEC Window Lettering, illuminate on any alarm condition of propulsion motor
PMS-200 PHC - Stbd Propulsion Motor CB Open Indicator Lamp I Table 4A-B9 X X X DO RIO 5 Propulsion - - IR, NO contacts
Energized = Lamp Illuminated - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD Illuminate if Stbd motor CB is open or tripped Port Propulsion Motor Drive
-- Additional Serial I/O to be included per Siemens standard -- Serial PCU 1 - - - - - Siemens Bluedrive Prop Motor Rm - - - - - - - - [TBD] Port Propulsion Motor Drive Cooling Water Temperature H Table 4A-D5 X X X SAI PCU 1 Propulsion [TBD] deg F [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Port Propulsion Motor Drive Supply Voltage H,E Table 4A-D1 X X X SAI PCU 1 Propulsion [TBD] Volts [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - [TBD] [TBD] - - 01-440-01
[TBD] Port Propulsion Motor Drive Input Current H Table 4A-D2 Table 4A-D3 X X X SAI PCU 1 Propulsion 0 - [TBD] Amps [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD] Port Propulsion Motor Drive Cooling Water Running H X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - see note [TBD] - - 01-440-01 Alarm if drive running and cooling water not running
[TBD] Port Propulsion Motor Drive Water Leakage H X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alarm on leak
5 sec on & off - - - - - - 01-440-01
[TBD] Port Propulsion Motor Drive Cooling Fault H,E Table 4A-D6 X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alm on fault
5 sec on & off - - - - - - 01-440-01
[TBD] Port Propulsion Motor Running H Table 4A-B10 X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - - - - - 01-440-01 [TBD] Port Propulsion Motor Voltage H,E Table 4A-B2 X X X SAI PCU 1 Propulsion [TBD] Volts [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Port Propulsion Motor Frequency H,E Table 4A-B4 X X X SAI PCU 1 Propulsion 0 - 65 Hertz [TBD] [TBD] Siemens Bluedrive Prop Motor Rm - - - - - - - - 01-440-01 [TBD] Port Propulsion Motor Current H,E Table 4A-B5 X X X SAI PCU 1 Propulsion 0 - [TBD] Amps [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 PMP-115 Port Propulsion Motor Drive - Power Limit H Table 4A-D3 X X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm see note [TBD] - - - - - - 01-440-01 Alarm on power limit
[TBD] Port Propulsion Motor Ground Fault H Table 4A-B7 X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alarm on fault [TBD] - - - - - - 01-440-01
PMP-150 MCSC - Port Propulsion Motor Power Limit Indication Lamp I X X X DO PCU 1 Propulsion - - Energized = pwr limited - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CB PMP-152 MCSC - Port Propulsion Motor Drive Fault Indicator Lamp I X X DO PCU 1 Propulsion - - Energized = drive failure - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CB PMP-160 PHC - Port Propulsion Motor Power Limit Indication Lamp I X X X DO RIO 5 Propulsion - - Energized = pwr limited - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CC PMP-162 PHC - Port Propulsion Motor Drive Fault Indicator Lamp I X X DO RIO 5 Propulsion - - Energized = drive failure - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
PMP-180
PMP-185
PBW/SBW - Port Propulsion Motor Power Limit Indicator Lamps (2 total) I X X X DO RIO 5 Propulsion - -
IR,NO contacts Energized = power limit - IDEC SLC-30
BWCS
BWCP - - - - - - - - 339P0207-0022, SHT 22CB
Stbd Propulsion Motor Drive
-- Additional Serial I/O to be included per Siemens standard -- Serial PCU 2 - - - - - Siemens Bluedrive Prop Motor Rm - - - - - - - - [TBD] Stbd Propulsion Motor Drive Cooling Water Temperature H Table 4A-D5 X X X SAI PCU 2 Propulsion [TBD] deg F [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Stbd Propulsion Motor Drive Supply Voltage H,E Table 4A-D1 X X X SAI PCU 2 Propulsion [TBD] Volts [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - [TBD] [TBD] - - 01-440-01
[TBD] Stbd Propulsion Motor Drive Input Current H Table 4A-D2 Table 4A-D3 X X X SAI PCU 2 Propulsion 0 - [TBD] Amps [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD] Stbd Propulsion Motor Drive Cooling Water Running H X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - see note [TBD] - - 01-440-01 Alarm if drive running and cooling water not running
[TBD] Stbd Propulsion Motor Drive Water Leakage H X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alarm on leak
5 sec on & off - - - - - - 01-440-01
[TBD] Stbd Propulsion Motor Drive Cooling Fault H,E Table 4A-D6 X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alm on fault
5 sec on & off - - - - - - 01-440-01
[TBD] Stbd Propulsion Motor Running H Table 4A-B10 X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - - - - - 01-440-01 [TBD] Stbd Propulsion Motor Voltage H,E Table 4A-B2 X X X SAI PCU 2 Propulsion [TBD] Volts [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 [TBD] Stbd Propulsion Motor Frequency H,E Table 4A-B4 X X X SAI PCU 2 Propulsion 0 - 65 Hertz [TBD] [TBD] Siemens Bluedrive Prop Motor Rm - - - - - - - - 01-440-01 [TBD] Stbd Propulsion Motor Current H,E Table 4A-B5 X X X SAI PCU 2 Propulsion 0 - [TBD] Amps [TBD] [TBD] Siemens Bluedrive Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01 PMS-115 Stbd Propulsion Motor Drive - Power Limit H Table 4A-D3 X X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm see note [TBD] - - - - - - 01-440-01 Alarm on power limit
[TBD] Stbd Propulsion Motor Ground Fault H Table 4A-B7 X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm alarm on fault [TBD] - - - - - - 01-440-01
PMS-150 MCSC - Stbd Propulsion Motor Power Limit Indicator Lamp I X X X DO PCU 2 Propulsion - - Energized = pwr limited - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CC PMS-152 MCSC - Stbd Propulsion Motor Drive Fault Indicator Lamp I X X DO PCU 2 Propulsion - - Energized = drive failure - IDEC SLC-30 MCSC - - - - - - - - 339P0207-0021, SHT 21CC PMS-160 PHC - Stbd Propulsion Motor Power Limit Indicator Lamp I X X X DO RIO 5 Propulsion - - Energized = pwr limited - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD PMS-162 PHC - Stbd Propulsion Motor Drive Fault Indicator Lamp I X X DO RIO 5 Propulsion - - Energized = drive failure - IDEC SLC-30 PHC - - - - - - - - 339P0207-0022, SHT 22CD
PMS-180
PMS-185
PBW/SBW - Stbd Propulsion Motor Power Limit Indicator Lamps (2 total) I X X X DO RIO 5 Propulsion - -
IR,NO contacts Energized = power limit - IDEC SLC-30
BWCS
BWCP - - - - - - - - 339P0207-0022, SHT 22CB
Port Propulsion Motor Transformer
[TBD] Port Propulsion Motor Transformer - Winding A Temperature H Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Port Propulsion Motor Transformer - Winding B Temperature H Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Port Propulsion Motor Transformer - Winding C Temperature H Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Port Propulsion Motor Transformer - Water Leakage Detected H X X X DI RIO 3 Propulsion On/Off - [TBD] - Trafotek/Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Port Propulsion Motor Transformer - Cooling Water Inlet Temperature H X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] - - [TBD] [TBD] - - 01-440-01
[TBD]
Port Propulsion Motor Transformer - Cooling Water Outlet Temperature H X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Port Propulsion Motor Transformer - Heat Exchanger Cold Air Temperature H X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Port Propulsion Motor Transformer - Air flow detected H, E X X X DI RIO 3 Propulsion On/Off - [TBD] - Trafotek/Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Port Propulsion Motor Transformer - #1 Fan Motor - Running Feedback H X X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemen Bluedrive Prop Motor Rm - - - - see note 3 sec - - 01-300-01, 01-440-01 Prop motor transformer blowers to be controlled by motor drive.
[TBD]
Port Propulsion Motor Transformer - #2 Fan Motor - Running Feedback H X X X SDI PCU 1 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - see note 3 sec - - 01-300-01, 01-440-01 Prop motor transformer blowers to be controlled by motor drive.
Stbd Propulsion Motor Transformer
[TBD] Stbd Propulsion Motor Transformer - Winding A Temperature Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Stbd Propulsion Motor Transformer - Winding B Temperature Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Stbd Propulsion Motor Transformer - Winding C Temperature Table 4A-E1 X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100 Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Stbd Propulsion Motor Transformer - Water Leakage Detected X X X DI RIO 3 Propulsion On/Off - [TBD] - Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Stbd Propulsion Motor Transformer - Cooling Water Inlet Temperature X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100
Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] - - [TBD] [TBD] - - 01-440-01
[TBD]
Stbd Propulsion Motor Transformer - Cooling Water Outlet Temperature X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100
Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Stbd Propulsion Motor Transformer - Heat Exchanger Cold Air Temperature X X X RTD RIO 3 Propulsion [TBD] deg F RTD - Pt100
Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] [TBD] [TBD] - - - - 01-440-01
[TBD] Stbd Propulsion Motor Transformer - Air flow detected E X X X DI RIO 3 Propulsion On/Off - [TBD] - Trafotek/ Siemens Prop Motor Rm [TBD] [TBD] - - - - - - 01-440-01
[TBD]
Stbd Propulsion Motor Transformer - #1 Fan Motor - Running Feedback H X X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - see note 3 sec - - 01-300-01, 01-440-01 Prop motor transformer blowers to be controlled by motor drive.
[TBD]
Stbd Propulsion Motor Transformer - #2 Fan Motor - Running Feedback H X X X SDI PCU 2 Propulsion On/Off - [TBD] - Siemens Bluedrive Prop Motor Rm - - - - see note 3 sec - - 01-300-01, 01-440-01 Prop motor transformer blowers to be controlled by motor drive.
Propulsion Control EOT-100 MCSC - EOT Power Failure Indicator Lamp X X DO RIO 5 Propulsion - - - - - - MCSC - - - - - - - - 01-438-01
EOT-101 EOT Power Failure 46 CFR 113.3-5 X X X DI RIO 4 Propulsion OK/Fault - [TBD] - PMC 8201 Telegraph PHC alm 1 sec On/Off - - - - - - 01-438-01 Power failure of any of the EOT units (two in bridge, two in MCS)
EOT-120 PHC - EOT Power Failure Indicator Lamp X X DO RIO 5 Propulsion - - - - - - PHC - - - - - - - - 01-438-01
R/V Atlantis Midlife Refit AMS Points List, Rev. A Page 4 of 19
Glosten, Inc.
Ref.
Regulatory Citation R eg ul at or y
E xi st in g
Pr ef er en ce
D is
I)
Tr en d
A la rm
C on tr ol
Signal Type Cabinet Alarm Group Range Units
Signal Range/Units
(AI/AO)
or Signal Sense (DI/DO)
Engineering Range/Units Manufacturer Model / Part Location Hi / On
Hi Delay (On/Off) HiHi
HiHiDelay (On/Off) Low / OFF
Lo Delay (On/Off) LoLo
LoLo Delay
(On/Off) Ref. Dwg(s) Comment
Authority AlarmsSignal HMI InstrumentFunction
Bow Thruster
[TBD] Bow Thruster Control System Fault K X DI RIO 7 Non-Vital Mach. OK/Fault - Open circuit to alarm - [TBD] [TBD] [TBD] - - - - - - ZF Dwg. No. 52170483 Rev. 6, page 59
[TBD] Bow Thruster Power Supply Fault K X DI RIO 7 Non-Vital Mach. OK/Fault - Open circuit to alarm - [TBD] [TBD] [TBD] - - - - - - ZF Dwg. No. 52170483 Rev. 6, page 59
[TBD] Bow Thruster Command Bridge Alarm Buzzer Accept K X DO RIO 7 Non-Vital Mach. - - NO, momentary closed to accept alarm [TBD] - - - - - - - - ZF Dwg. No. 52170483 Rev. 6, page 59 output is from RIO to ZF
Bow Thruster Fresh Water Cooling Pump 1 Running K X X DI RIO 7 - Running/ Stopped - Closed = Running - [TBD] [TBD] [TBD] - - - - - - 01-536-01
Motor Controller for pump 536P005, AMS should alarm if bow thruster running and pump is not running.
Bow Thruster Fresh Water Cooling Pump 2 Running K X X DI RIO 7 - Running/ Stopped - Closed = Running - [TBD] [TBD] [TBD] - - - - - - 01-536-01
Motor Controller for pump 536P006, AMS should alarm if bow thruster running and pump is not running.
Bow Thruster Sea Water Cooling Pump 1 Running K X X DI RIO 7 - Running/ Stopped - Closed = Running - [TBD] [TBD] [TBD] - - - - - - 01-532-01
Motor Controller for pump 532P005, AMS should alarm if bow thruster running and pump is not running.
Bow Thruster Sea Water Cooling Pump 2 Running K X X DI RIO 7 - Running/ Stopped - Closed = Running - [TBD] [TBD] [TBD] - - - - - - 01-532-01
Motor Controller for pump 532P006, AMS should alarm if bow thruster running and pump is not running.
Bow Thruster Fresh Water Cooling Pump 1 Standby Start K X X DI RIO 7 - OK/Fault - Closed = Standby Unit Started - Bow Thruster Room - - - - - - - - 01-536-01 Motor Controller for pump 536P005 Bow Thruster Fresh Water Cooling Pump 2 Standby Start K X X DI RIO 7 - OK/Fault - Closed = Standby Unit Started - Bow Thruster Room - - - - - - - - 01-536-01 Motor Controller for pump 536P006 Bow Thruster Sea Water Cooling Pump 1 Standby Start K X X DI RIO 7 - OK/Fault - Closed = Standby Unit Started - Bow Thruster Room - - - - - - - - 01-532-01 Motor Controller for pump 532P005 Bow Thruster Sea Water Cooling Pump 2 Standby Start K X X DI RIO 7 - OK/Fault - Closed = Standby Unit Started - Bow Thruster Room - - - - - - - - 01-532-01 Motor Controller for pump 532P006
536I070 Bow Thruster Fresh Water Cooling Pressure K X X X AI RIO 7 - 0 - 60 PSI 4-20mA - Bow Thruster Room - - - - 26 PSI [TBD] - - 01-536-01 26 PSI nominal 536I069 Bow Thruster Fresh Water Cooling Temperature K X X X AI RIO 7 - [TBD] Deg F 4-20mA - Bow Thruster Room 32 F [TBD] - - - - - - 01-536-01 532I043 Bow Thruster Sea Water Cooling Pressure K X X X AI RIO 7 - 0 - 8 PSI 4-20mA - Bow Thruster Room - - - - 3 PSI [TBD] - - 01-532-01 5.2 PSI nominal
02-252E122 MCSC Bow Thruster RPM Indication Gauge X X AO RIO 4 - -1200 - 1200 RPM
4mA = max reversed rpm 12mA = 0 rpm
20mA = max prop rpm 0 - 1200 RPM MCSC - - - - - - - - 01-438-01, 01-440-01 signals to be verified by contractor
02-252E123 MCSC Bow Thruster Azimuth Position Gauge X X AO RIO 4 - 0-360 Deg
4mA/20mA = 180 deg 8mA = 90 deg port
12mA = 0 deg 16mA = 90 deg stbd 0-360 Degrees MCSC - - - - - - - - 01-438-01, 01-440-01 signals to be verified by contractor
01-438E003 MCSC Bow Thruster Fault Indicator Lamp X X X DO RIO 4 Non-Vital Mach. - - - - IDEC SLC-30 MCSC - - - - - - - - 01-438-01, 01-440-01 01-438E003 MCSC Bow Thruster Raised Indicator Lamp X X DO RIO 4 - - - - - IDEC SLC-30 MCSC - - - - - - - - 01-438-01, 01-440-01 01-438E003 MCSC Bow Thruster Lowered Indicator Lamp X X DO RIO 4 - - - - - IDEC SLC-30 MCSC - - - - - - - - 01-438-01, 01-440-01
Bow Thruster RPM Indication K X X SAI PCU 2 - [TBD] [TBD] AMS = Master TCU = Slave 0 - 1200 RPM ZF
Motor Generator Room - - - - - - - - 01-440-01 signals via Modbus to be verified by contractor. AMS = Master, TCU = Slave
Bow Thruster Azimuth Position Indication K X X SAI PCU 2 - [TBD] [TBD] AMS = Master TCU = Slave 0-360 Degrees ZF
Motor Generator Room - - - - - - - - 01-440-01 signals via Modbus to be verified by contractor. AMS = Master, TCU = Slave
Bow Thruster Fault K X X X SDI PCU 2 Non-Vital Mach. OK/Fault - AMS = Master TCU = Slave - ZF
Motor Generator Room - - - - - - - - 01-440-01 signals via Modbus to be verified by contractor. AMS = Master, TCU = Slave
Bow Thruster Raised K X X SDI PCU 2 - Raised/ Lowered -
AMS = Master TCU = Slave - ZF
Motor Generator Room - - - - - - - - 01-440-01 signals via Modbus to be verified by contractor. AMS = Master, TCU = Slave
Bow Thruster Lowered K X X SDI PCU 2 - Raised/ Lowered -
AMS = Master TCU = Slave - ZF
Motor Generator Room - - - - - - - - 01-440-01 signals via Modbus to be verified by contractor. AMS = Master, TCU = Slave
Vital Service Systems AIR-220 Pilothouse Start Air Pressure Low Indicator Lamp I X X DO RIO 5 Non-Vital Mach. - - [TBD] [TBD] PHC - - - - - - - - 339P0207-0022, SHT 22CC
551I001 Aft Start Air Reciever Inlet Pressure Table 1A-G1 X X X AI RIO 1 Vital Mach.
0-300
Nominal = 250 psi 4-20mA [TBD] [TBD] [TBD] Generator Room - - - - [TBD] [TBD] - - 01-551-01
Reciever supplied from existing air compressors 1 and 2. This reciever supplies generator start air, ship service air, as well as air for the MSD/BWTS air reciever
551I013 Ship Service Air Inlet Pressure Table 1A-G1 X X X AI RIO 1 Vital Mach.
0-300
Nominal = 250 psi 4-20mA [TBD] [TBD] [TBD] Generator Room - - - - [TBD] [TBD] - - 01-551-01
551I002 Forward Start Air Reciever Inlet Pressure Table 1A-G1 X X X AI RIO 1 Vital Mach.
0-300
Nominal = 250 psi 4-20mA [TBD] [TBD] [TBD] Generator Room - - - - [TBD] [TBD] - - 01-551-01
Reciever supplied from existing air compressors 1 and 2. This reciever supplies generator start air, ship service air, as well as air for the MSD/BWTS air reciever
551E002 Air Compressor Fault X X DI RIO 1 Vital Mach. OK/Fault - - - - - - - - - - - - - - 01-551-02
551E002 Air Compressor Running X X DI RIO 1 Running/ Stopped - - - - - - - - - - - - - - 01-551-02
AIR-300 Fuel Oil Valve Control Air Low Pressure J X X DI RIO 2 Vital Mach. On/Off - [TBD] - Omega PSW-113 Pump Room - - - - alm 1 sec on/off - - Halter Dwg 6932730
440E032 Motor Generator Room Temperature X X X RTD RIO 7 Vital Mach. 40 - 125 deg F RTD - Pt100 Omega EWSE-Pt100 Motor Generator Room 100 F
5 sec on & off 110 F
5 sec on & off - - - - 01-440-01 Contractor to provide new field device
440E032 Incinerator Room Temperature X X X X RTD RIO 2 Vital Mach. 40 - 125 deg F RTD - Pt100 Omega EWSE-Pt100 Incinerator Room 100 F 5 sec on & off 110 F
5 sec on & off - - - - 01-440-01 Contractor to provide new field device
440E032 Generator Room Temperature X X X X RTD RIO 2 Vital Mach. 40 - 125 deg F RTD - Pt100 Omega EWSE-Pt100 Generator Room 100 F 5 sec on & off 110 F
5 sec on & off - - - - 01-440-01 Contractor to provide new field device
440E032 Switchboard Room Temperature X X X X RTD RIO 6 Vital Mach. 40 - 125 deg F RTD - Pt100 Omega EWSE-Pt100 Switchboard Room 100 F 5 sec on & off 110 F
5 sec on & off - - - - 01-440-01 Contractor to provide new field device
440E032 Propulsion Room Air Temperature X X X X RTD RIO 3 Vital Mach. 40 - 125 deg F RTD - Pt100 Omega EWSE-Pt100 Prop Motor Rm 100 F 5 sec on & off 110 F
5 sec on & off - - - - 01-440-01 Contractor to provide new field device
SWA-300 Z-Drive SW Cooling Pump - Standby Unit Started J 46 CFR Table 62.35-50 4-9-5/13.13 X X X DI PCU 2 Vital Mach.
Running/ Stopped - Closed = Standby Unit Started - MCS Motor Control alm
1 sec On/Off - - - - - -
01-300-01 339P0207-0022, SHT 21CA existing signal to be modified, signal from relay box in MCC bucket
SWP-300 Propulsion Sea Water Cooling Pump - Standby Unit Started 46 CFR Table 62.35-50 4-9-5/13.13 X X DI PCU 2 Vital Mach.
Running/ Stopped - Closed = Standby Unit Started - MCS Motor Control alm
1 sec On/Off - - - - - -
01-300-01 339P0207-0022, SHT 21CA existing signal to be modified, signal from relay box in MCC bucket
[TBD] Generator Sea Water Cooling System - Standby Unit Started 46 CFR Table 62.35-50 4-9-5/13.13 X X DI RIO 2 Vital Mach.
Running/ Stopped - Closed = Standby Unit Started - [TBD] [TBD] [TBD] - - - - - - 01-300-01 & 01-532-01 signal from MCSC
[TBD] Generator Sea Water Cooling Pump 1 Running X X DI RIO 2 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-532-01
[TBD] Generator Sea Water Cooling Pump 2 Running X X DI RIO 2 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-532-01
536I045 Propulsion Fresh Water Cooling Water Temperature Table 4A-A11 Table 4A-D5 X X X X RTD RIO 3 Vital Mach.
30-130 nominal = 108 deg F RTD - Pt100 Omega PRTF-11 Lower Gen Rm 107.6 F
5 sec on & off 115 F
2 sec on & off 68 F
5 sec on & off - - 01-536-01 inhibit alarm when pump is off
536I043 Propulsion Fresh Water Cooling Water Pressure E X X X AI RIO 3 Vital Mach.
0-60 nominal = 30 psi 4-20mA [TBD] Danfoss MBS 5150 Winch Room - - - - 5 PSI [TBD] - - 01-536-01 AMS to start standby unit upon low pressure alarm
[TBD] Propulsion Fresh Water Cooling System - Standby Unit Started 46 CFR Table 62.35-50 4-9-5/13.13 X X INT PCU 1/2 Vital Mach. - - Closed = Standby Unit Started [TBD] [TBD] [TBD] - - - - - - 01-300-01 & 01-536-01 signal from relay box in Motor Controller
536P001 Propulsion Fresh Water Cooling Pump 1 Running X X DI RIO 3 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-536-01
536P001 Propulsion Fresh Water Cooling Pump 1 in Remote X X DI RIO 3 - Local/Remote - Closed = Remote - [TBD] - - - - - - - - 01-536-01 536P001 Propulsion Fresh Water Cooling Pump 1 Start X X DO RIO 3 - - - NO, Close to Start (momentary) [TBD] - - - - - - - - 01-536-01 536P001 Propulsion Fresh Water Cooling Pump 1 Stop X X DO RIO 3 - - - NO, Close to Stop (momentary) [TBD] - - - - - - - - 01-536-01
300E033 Propulsion Fresh Water Cooling Pump 1 Insulation Resistance X X DI RIO 3 Non-Vital Mach. OK/Low [TBD]
NC - Open to Alarm, Controlled by automatic insulation resistance monitor - MEG Alert GP500-M-AS Winch Room [TBD] [TBD] - - - - - - 01-536-01, 01-300-01 Signals from device inside motor controller (01-536P001)
536P002 Propulsion Fresh Water Cooling Pump 2 Running X X DI RIO 3 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-536-01
R/V Atlantis Midlife Refit AMS Points List, Rev. A Page 5 of 19
Glosten, Inc.
Ref.
Regulatory Citation R eg ul at or y
E xi st in g
Pr ef er en ce
D is
I)
Tr en d
A la rm
C on tr ol
Signal Type Cabinet Alarm Group Range Units
Signal Range/Units
(AI/AO)
or Signal Sense (DI/DO)
Engineering Range/Units Manufacturer Model / Part Location Hi / On
Hi Delay (On/Off) HiHi
HiHiDelay (On/Off) Low / OFF
Lo Delay (On/Off) LoLo
LoLo Delay
(On/Off) Ref. Dwg(s) Comment
Authority AlarmsSignal HMI InstrumentFunction
536P002 Propulsion Fresh Water Cooling Pump 2 in Remote X X DI RIO 3 - Local/Remote - Closed = Remote - [TBD] - - - - - - - - 01-536-01 536P002 Propulsion Fresh Water Cooling Pump 2 Start X X DO RIO 3 - - - NO, Close to Start (momentary) [TBD] - - - - - - - - 01-536-01 536P002 Propulsion Fresh Water Cooling Pump 2 Stop X X DO RIO 3 - - - NO, Close to Stop (momentary) [TBD] - - - - - - - - 01-536-01
300E033 Propulsion Fresh Water Cooling Pump 2 Insulation Resistance X X DI RIO 3 Non-Vital Mach. OK/Low [TBD]
NC - Open to Alarm, Controlled by automatic insulation resistance monitor - MEG Alert GP500-M-AS Winch Room [TBD] [TBD] - - - - - - 01-536-01, 01-300-01 Signals from device inside motor controller (01-536P002)
536I006 Propulsion Fresh Water Cooling Expansion Tank Low Level X X DI RIO 3 Vital Mach. OK/Low [TBD] Closed = level low - [TBD] Winch Room - - - - see note 5 sec on & off - - 01-536-01 Alarm on 10%, to be calibrated upon installation
LAL = 536I006
536I055 Generator Room Fresh Water Cooling Water Temperature X X X X RTD RIO 2 Vital Mach.
30-130 nominal = 107.6 deg F RTD - Pt100 Omega PRTF-11 Lower Gen Rm 111.2 F 5 sec on & off - - - - - - 01-536-01 TAH = 536I055A
536I053 Generator Room Fresh Water Cooling Water Pressure E X X X AI RIO 2 Vital Mach.
0-60 nominal = 26 psi 4-20mA [TBD] Danfoss MBS 5150 Lower Gen Rm - - - - 5 PSI [TBD] - - 01-536-01 PAL = 536I053A
[TBD]
Generator Room Fresh Water Cooling System - Standby Unit Started
Table 4A-A11 46 CFR Table 62.35-50 4-9-5/13.13 X INT PCU 1/2 Vital Mach. - - Closed = Standby Unit Started [TBD] [TBD] [TBD] - - - - - - 01-300-01, 01-440-01
[TBD] Generator Room Fresh Water Cooling Pump 1 Running X X DI RIO 2 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-536-01
[TBD] Generator Room Fresh Water Cooling Pump 1 in Remote X X DI RIO 2 - Local/Remote - Closed = Remote - [TBD] - - - - - - - - 01-536-01 [TBD] Generator Room Fresh Water Cooling Pump 1 Start X X DO RIO 2 - - - NO, Close to Start (momentary) [TBD] - - - - - - - - 01-536-01 Primary/Standby with auto start of standby on low pressure.
[TBD] Generator Room Fresh Water Cooling Pump 1 Stop X X DO RIO 2 - - - NO, Close to Stop (momentary) [TBD] - - - - - - - - 01-536-01 Primary/Standby with auto start of standby on low pressure.
[TBD] Generator Room Fresh Water Cooling Pump 2 Running X X DI RIO 2 - Running/ Stopped - Closed = Running - [TBD] - - - - - - - - 01-536-01
[TBD] Generator Room Fresh Water Cooling Pump 2 in Remote X X DI RIO 2 - Local/Remote - Closed = Remote - [TBD] - - - - - - - - 01-536-01 [TBD] Generator Room Fresh Water Cooling Pump 2 Start X X DO RIO 2 - - - NO, Close to Start (momentary) [TBD] - - - - - - - - 01-536-01 Primary/Standby with auto start of standby on low pressure.
[TBD] Generator Room Fresh Water Cooling Pump 2 Stop X X DO RIO 2 - - - NO, Close to Stop (momentary) [TBD] - - - - - - - - 01-536-01 Primary/Standby with auto start of standby on low pressure.
536I058 Generator Room Fresh Water Cooling Expansion Tank Low Level X X DI RIO 1 Vital Mach. OK/Low [TBD] Closed = level low - [TBD] Generator Room - - - - see note
5 sec on & off - - 01-536-01 Alarm on 10%, to be calibrated upon installation
[TBD] Generator Room Ventilation Fan Controller - Fault X X DI RIO 1 Vital Mach. OK/Fault - [TBD] - Delta T MCE [TBD] alm on fault
1 sec On/Off - - - - - - 01-514-01
[TBD] Engineers Assistance Needed - to Paging System X X DO RIO 1 AMS - - - - Zenitel [TBD] [TBD] - - - - - - - - 01-440-01 See Reference 2 for more details
[TBD] Fire Alarm - Vital - to Paging System X X DO RIO 1 Fire - - - - Zenitel [TBD] [TBD] alm on fault - - - - - - - 01-440-01 See Reference 2 for more details
[TBD] Vital Alarm - to Paging System X X DO RIO 1 Vital Mach. - - - - Zenitel [TBD] [TBD] alm on fault - - - - - - - 01-440-01 See Reference 2 for more details
[TBD] Non-Vital Alarm - to Paging System X X DO RIO…