11_Security Electronics.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24125R0077Solicitation
About this file
These documents are detailed design drawings for security electronics systems at the West Roxbury VA Medical Center, part of a project to replace boilers and upgrade controls. The comprehensive set of drawings covers physical access control, intercom systems, and security surveillance television across multiple buildings and levels, including Building 1, an existing tunnel, a new emergency generator building, and a fire pump building.
The security system design includes multiple components such as electric strikes, magnetic locks, card readers, intercom/video stations, cameras with various mounting options (wall, ceiling, parapet, pedestal), and integrated access control panels. Key technical specifications include using Category 6A UTP cabling, singlemode fiber optic connections, and networked systems with ethernet switches and network video recorders. The system will feature panoramic and fixed cameras with motion detection and analytics capabilities, covering both interior and exterior areas, with centralized monitoring in Security Room 205. The project is scheduled for bid documents issued on 11/14/2025, with a focus on comprehensive security integration across the VA Medical Center's facilities.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVER T-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
SYMBOLS
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
M
T
M
T
T
M
M
M
T
T
M
T
M
T
M
T
M
M
T
M
T
M
T
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH CLOSED CIRCUIT TELEVISION
CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, MULTI-SENSOR/PANORAMIC VIEW, ANGLE OF VIEW
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
360°
40°
X
M PTZ
M
T
AP
SECURITY ACCESS, DOOR PROP/EXIT ALARMDA
SECURITY ACCESS, INTERFACE RELAY SWITCH
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR
ARMORED CABLE
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BFF BELOW FINISH FLOOR
BLDG BUILDING
BMS BALANCED MAGNETIC SWITCH
BPIP BOILER PLANT INSTRUMENTATION PANEL
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONT CONTINUE
CONTR CONTRACTOR
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG DEGREES
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DRSW DOOR SWITCH
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EXIST EXISTING
FLEX FLEXIBLE METALLIC CONDUIT
FT FEET OR FOOT
ABBREVIATIONS
GND GROUND
GEN GENERATOR
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HZ HERTZ
IC INTERCOM
IDS INTRUSION DETECTION SYSTEM
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
LF LINEAR FEET (FOOT)
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MT MOUNT
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
N NEUTRAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PACS PHYSICAL ACCESS CONTROL SYSTEM
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
REQD REQUIRED
SF SQUARE FOOT (FEET)
SI INTERNATIONAL SYSTEM OF UNITS
SSTV SECURITY SURVEILLANCE TELEVISION
SW SWITCH
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VASS VIDEO ASSESSMENT AND SURVEILLANCE SYSTEM
WP WEATHERPROOF
A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
B. THE MINIMUM STANDARD FOR ALL WORK SHALL BE THE APPLICABLE CODES REFERENCED ON THE LIFE SAFETY PLANS ON SHEET LS101 INCLUDING THE NATIONAL
ELECTRICAL CODE. WHENEVER THE ENGINEERS DESIGN REQUIRES A HIGHER STANDARD, THE HIGHER STANDARD DESIGN SHOWN SHALL BE FOLLOWED.
C. ALL WORK SHALL BE PERFORMED BY AN ELECTRICIAN LICENSED BY THE STATE OF MASSACHUSETTS. AT COMPLETION OF THE PROJECT, A CERTIFICATE OF
COMPLIANCE SHALL BE FURNISHED BY THE ELECTRICAL INSPECTION AGENCY HAVING JURISDICTION OVER ELECTRICAL WORK PERFORMED.
D. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, AND TOOLS TO EXECUTE WORK DETAILED BY THE DRAWINGS AND PROJECT SPECIFICATIONS, AND SHALL PROVIDE A COMPLETELY OPERATIONAL VIDEO SURVEILLANCE/ELECTRICAL SYSTEM UPON COMPLETION OF THE PROJECT.
E. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE ELECTRICAL WORK WITH THAT OF OTHER TRADES. THE ELECTRICIAN IS RESPONSIBLE FOR MAKING ALL
ELECTRICAL CONNECTIONS TO THE EQUIPMENT REQUIRING ELECTRICAL POWER, REGARDLESS OF WHO FURNISHED OR INSTALLED IT.
F. THE CONTRACTOR IS RESPONSIBLE FOR DAILY CLEANUP OF ALL WORK AREAS DURING TERM PROJECT; AND FOR RETURNING TO ORIGINAL CONDITION UPON
COMPLETION OF ALL WORK INDICATED.
G. ALL ELECTRICAL WORK SHALL BE WARRANTED FOR ONE YEAR FROM THE DATE OF INSPECTION PUNCHLIST COMPLETION.
H. ALL MATERIALS USED SHALL BE NEW AND UL LISTED WHERE A LISTING EXISTS FOR THE PRODUCT.
I. CONDUIT CONCEALED IN WALLS OR CEILINGS SHALL BE EMT WITH TAMPER PROOF SCREWS, AND EXPOSED CONDUITS SHALL BE EMT WITH TAMPER PROOF SCREWS.
ALL CONDUITS SHALL HAVE AN EXTRA CONDUCTOR PULLED FOR GROUNDING. ALL CONDUIT SHALL BE CONCEALED, UNLESS SPECIFICALLY NOTED OTHERWISE. ALL
CONDUIT FITTINGS SHALL BE COMPRESSION TYPE. THE LAST PIECE OF CONDUIT INSTALLED TO EQUIPMENT SHALL BE FLEXIBLE METAL CONDUIT. MINIMUM CONDUIT
SIZE SHALL BE 3/4 INCH. CONDUITS SHALL BE INSTALLED AT RIGHT ANGLES TO CEILINGS, WALLS, AND STRUCTURAL MEMBERS. CONDUIT SHALL BE SUPPORTED BY
PIPE STRAPS, WALL BRACKETS, OR HANGERS. SPACER BACK CLAMPS SHALL BE UTILIZED IN MOIST OR WET AREAS.
J. HUBS SHALL BE USED ON BOXES WHERE CONDUIT ENTERS THE TOP AND IS EXPOSED TO WEATHER. SEALING LOCKNUTS MAY BE USED FOR SIDE ENTRY CONDUITS
IN THIS APPLICATION.
K. CONDUITS SHALL BE SEALED WHERE THEY ENTER THE BUILDING TO PREVENT GROUNDWATER ENTRY.
L. BOXES SHALL BE INSTALLED SUCH THAT THEY ARE SUPPORTED BY THE STRUCTURE. BOXES MAY NOT BE SUPPORTED BY CONDUIT.
M. IN THE ABSENCE OF DETAILS HEREIN ON USE OR INSTALLATION OF A PARTICULAR MATERIAL OR DEVICE, CODES AND MANUFACTURERS RECOMMENDATIONS SHALL BE
USED AS GUIDANCE.
N. IT IS HIGHLY RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE PRIOR TO BIDDING, TO BECOME FAMILIAR WITH EXISTING CONDITIONS TO BE ENCOUNTERED
DURING CONSTRUCTION.
O. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. COORDINATE WORK ACCORDINGLY. COMPLY WITH
SPECIFICATIONS AND GENERAL NOTES AS APPLICABLE.
P. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS.
Q. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRESTOPPING/SEALANT MATERIAL TO MAINTAIN THE
EXISTING FIRE RATING FOR THE ASSEMBLY.
R. PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND TERMINATION POINTS. LABELS SHALL BE SELF ADHESIVE OR
HEAT SHRINK TYPE AND BE PERMANENTLY AFFIXED TO THE WIRE BEING LABELED.
S. NO LIVE WORK WILL BE ALLOWED. EVERY CIRCUIT SHALL BE LOCKED-OUT AND TAGGED-OUT BEFORE COMMENCING WORK.
T. NO "J" HOOKS. (OR ANY OTHER TYPE OF WIRE "HANGING" SYSTEM IS PERMITTED WITHIN THE SCOPE OF THIS WORK FOR THE ENTIRE LENGTH OF WIRING RUNS
INDICATED.)
U. NEW CONDUIT RUNS SHOWN BY PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL INSTALL NEW CONDUITS IN CONCEALED LOCATIONS UNLESS SPECIFICALLY
NOTED OTHERWISE.
V. TOTAL CONDUIT LENGTHS MAY NOT EXCEED 295'-0" FROM CAMERA LOCATION TO I.T. ROOM CONNECTION POINT.
W. NEW CONDUITS SHALL BE SECURED TO EXISTING WALL CONSTRUCTION, EXISTING STRUCTURAL SYSTEM OR EXISTING PLASTER FINISHES CONCEALED FROM VIEW (ABOVE
SAT).
X. CONTRACTOR SHALL TAKE MEASURES NECESSARY TO AVOID CONFLICTS WITH EXISTING MECHANICAL, ELECTRICAL AND PLUMBING (MEP) INFRASTRUCTURE AT NO
ADDITIONAL COST TO VAMC.
Y. VA INFORMATION TECHNOLOGY/SYSTEMS PERSONNEL WILL USE THE CONTRACTOR'S COMPLETED, LABELED AND INDEX LISTED CABLING TO PHYSICALLY MAKE THE FINAL
CONNECTION TO VAMC OWNED SWITCHES INSIDE OF IT ROOMS.
Z. INTRUSION DETECTION SYSTEMS (IDS), DURESS/PANIC SYSTEMS, PHYSICAL ACCESS CONTROL SYSTEMS (PACS), AND SECURITY SURVEILLANCE TELEVISION (SSTV)
DESIGN TO FOLLOW VA PSRDM - CHAPTER 10, VA TDM 2016, AND NEC.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t
523A4-20-208
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
Physical Security:
FORCE PROTECT
/1 /2
:5
:5
P M
TY001
SECURITY ELECTRONICS
SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012NO. DESCRIPTION DATE
D8
C501
S P
S P
F A
SI
GN
D
E
E
G M
H H
H H
H H
H
Y D
H
Y D
M H
M H
M H
M H
M H
M H
M H
S
S
S
T R
O
W S
O
W S
O
W S
O
W S
O
W S
O
W S
W
W
D
D
H H
E
E
E
E
E
E
O
S G
H
Y D
S
S
S
S
T
T
O
W S
O
W S
O
W S
O
W S
O
W S
O
W S
O
W S
W
O
W S
S
H H
E
S
S
S
DD
S
O S
G
S
S
D
D
BUILDING
NO. 10
CONCRETE BLOCK
(AREA INACC.)
BU
ILD
ING
NO
. 2
ME
TA
L
BU
ILD
ING
BUILDING
NO. 7
BUILDING
NO. 3
G A S
TA
N K
SH
ED
BUILDING
NO. 17
BUILDING
NO. 5
BUILDING
NO. 1
BUILDING
NO. 8
TY502
HE1
IE1
IE3
LE1 ME1
TY502
HE2
ME2
LE2
5 6
7 6
FIRE PUMP
BUILDING
12 1314
TYP. OF 2
TYP. OF 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTHACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
Physical Security:
FORCE PROTECT
/1 /2
:5
:5
P M
TY100
SECURITY ELECTRONICS
SITE PLAN
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1" = 20'-0"
SITE PLAN
SHEET KEYNOTES:
1 PEDESTRIAN GATE WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO
POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO
DETAIL 3 ON SHEET TY502.
2 HANDHOLE SIZE ACCORDING TO NEC 314.28 AND 314.30. EHH (OR CHH) =
ELECTRICAL (OR COMMUNICATIONS) HANDHOLE. PROVIDE WITH LOCKABLE COVER.
REFER TO DETAIL 5, SHEET TY503.
3 PROVIDE SIX (6) 2-STRAND SINGLMODE (OS2) OPTICAL FIBERS IN 2"C FROM
INTERCOM/VIDEO STATIONS AND CAMERAS BACK TO SECURITY 205 (SHEET
TY121.3B). PROVIDE 2-STRAND SINGLEMODE (OS2) OPTICAL FIBER TO SURVILLANCE
CABINETS AT EACH CAMERA LOCATION AND INTERCOM/VIDEO STATIONS.
4 ELECTRICAL POWER FOR SLIDE GATE OPERATOR AND POE INJECTORS (CAMERAS AND
INTERCOM/VIDEO STATIONS). REFER TO ELECTRICAL SITE PLAN, SHEET ES101.3
FOR ADDITIONAL INFORMATION.
5 ENTRANCE SLIDE GATE OPERATOR CONTROL (ACCESS CONTROL) - 4#12, 1#12 GND
IN 1"C AND CONNECT TO ASSOCIATED ACCESS CONTROL PANEL (SECURITY 205 -
SHEET TY121.3B).
6 PEDESTRIAN GATE CONTROL AND MONITORING (ACCESS CONTROL) - 2C#14 AND
TWO (2) 2C#18 CABLES IN 1"C. CONNECT TO ASSOCIATED POWER SUPPLY AND
ACCESS CONTROL PANEL (SECURITY 205 - SHEET TY121.3B).
7 INTERCOM/VIDEO STATION AND CAMERA - TWO (2) 2-STRAND SINGLEMODE (OS)
OPTICAL CABLES IN 1"C FROM SURVEILLANCE CABINET (AT PUSHBUTTON PEDESTAL)
TO INDICATED HANDHOLE.
8 PROVIDE TWO (2) SPARE 2" CONDUITS FROM SECURITY 205 (SHEET TY121.3B) TO
INDICATED HANDHOLE.
9 CARD READERS (ACCESS CONTROL) - TWO (2) 6C/#18AWG SHIELDED CABLE,
1-1/4"C. ROUTE ONE (1) 6C/#18 AWG SHIELDED CABLE FROM EACH CARD
READER TO ASSOCIATED ACCESS CONTROL PANEL (SECURITY 205 - SHEET
TY121.3B).
10 CARD READER (ACCESS CONTROL) - ONE (1) 6C/#18AWG SHIELDED CABLE, 1"C.
ROUTE PEDESTRIAN GATE CARD READER TO ASSOCIATED ACCESS CONTROL PANEL
(SECURITY 205 - SHEET TY121.3B).
11 PROVIDE ACCESS CONTROL AND SSTV FOR FIRE PUMP BUILDING. REFER TO SHEET
TY401.3 FOR ADDITONAL INFORMATION.
12 FIRE PUMP BUILDING CONTROL AND MONITORING (ACCESS CONTROL) -TWO (2)
4C/#20 (1-PR SHIELDED) AND THREE (3) 2C/#18 NON-SHIELDED CABLES IN
1-1/4"C. CONNECT TO ASSOCIATED POWER SUPPLY AND ACCESS CONTROL PANEL
(SECURITY 205 - SHEET TY121.3B).
13 FIRE PUMP BUILDING CARD READER (ACCESS CONTROL) - ONE (1) 6C/#18AWG
SHIELDED CABLE, 1"C. CONNECT TO ASSOCIATED ACCESS CONTROL PANEL
(SECURITY 205 - SHEET TY121.3B).
14 FIRE PUMP BUILDING CAMERA - ONE (1) CAT 6A, 1"C. CONNECT TO SECURITY
205 (SHEET TY121.3B).
15 ELECTRICAL POWER FOR POE INJECTORS (CAMERAS AND INTERCOM/VIDEO
STATIONS). REFER TO ELECTRICAL SITE PLAN, SHEET ES101.3 FOR ADDITIONAL
INFORMATION.
GENERAL NOTES:
1 LOCATE ALL EXISTING UNDERGROUND UTILITIES FOR ALL UNDERGROUND WORK PRIOR
TO EXCAVATION OR TRENCHING. HAND DIG WITHIN 10' OF AN UTILITY CROSSING
WITH NEW WORK.
2 MINIMUM BURY FOR ALL SITE CONDUITS SHALL BE 30", UNLESS OTHEWISE NOTED.
CONTRACTOR IS RESPONSIBLE FOR ALL SITE TRENCHING AND BACKFILL.
3 REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION.
4 EQUIPMENT/DEVICES SHOWN ON THIS SHEET SHALL BE COORDINATED WITH GATE
LOCATIONS AND GENERAL CONTRACTOR PRIOR TO ROUGH-IN.
5 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
6 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
7 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
8 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
9 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
10 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
NO. DESCRIPTION DATE
90° M
90° M
EXISTING TUNNEL
EXT
BUILDING 1
BASEMENT
MER
TY
.3
TY
.3
EXISTING TUNNEL
EXT
TY
.3
TY
.3
PUMP ROOM
TY
1.
5D
TY101.5D
EXISTING TUNNEL
EXT
NEW TUNNEL
T
A0011
A0012
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
KEYPLAN
PLAN
NORTH
ACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
TUNNEL
BLDG 1
Physical Security:
FORCE PROTECT
/1 /2
:5
:5
P M
TY101.3
SECURITY ELECTRONICS
EXISTING TUNNEL
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1/4" = 1'-0"
EXISTING TUNNEL LEFT
SCALE: 1/4" = 1'-0"
EXISTING TUNNEL RIGHT
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER FROM EXISTING BUILDING
1 (DATA CLOSET GB-100A - SHEET TY201.3) TO BOILER PLANT (SECURITY 205 -
SHEET TY121.3B). HOLD TIGHT TO BOTTOM OF STRUCTURE, COORDINATE ROUTING
WITH OTHER TRADES.
2 PROVIDE PULL BOX - SIZE ACCORDING TO NEC 314.28.
3 EXTEND 2'C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER UP TO LEVEL
ABOVE (MECHANICAL ROOM GD117 - SHEET TY201.3).
4 PENDANT MOUNTED CAMERA WITH MOTION DETECTION (REFER TO DETAIL 5, SHEET
TY504). MOUNT AS HIGH AS POSSIBLE WHILE PROVIDING COVERAGE OF PIPING
TUNNEL, FIELD COORDINATE EXACT LOCATION WITH PIPE ROUTING.
M
M
M
M
0°
0°
270°
A
9 8 7 6 5 4
C
D
B.3
B
8.7 8.4 7.6
A.7
A.6
A.4
C.7
C.9
120B 101I
101H
101E101D 101F 101G
101C
102A
102B
DA DA
TY
.3 B
TY
.3 B
DA
DA
DA
9 9 9 9 DADADADA
10 10 1011111111
DE1
DE2
DE5
C1021
B1011
B1013
14 14 14
S S
S
M
S
M
S
M
S
M
SM S
X
S
M
S
S
S
M
MS
S
S
R S
S
S
S
X
S
M
S
S
R S
R S
M S
X
SR S
S
S
S
X
SM
X
SS
104A
SX
SS
X
S
S
M
D
DA
S X
M
X
S
S
S
S
X
M
X
SSS
105A
CONTROL ROOM
STAIR
BOILER ROOM
101A
101B
DA
DA
S X M
X
S
S S 1
S X
M
XS
S
S
1 15
R S
R S
R S
R S X
S
DE4
S S
B1012
E S
E S
120A
E S
E S E S
E S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
NEW
EMERGENCY
GENERATOR
BLDG.
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW BOILER
PLANT
TUNNEL
BLDG 1
Physical Security:
FORCE PROTECT
/1 /2
:5
:5
P M
TY111.3A
SECURITY ELECTRONICS
MAIN LEVEL - PHASE 3, AREA A
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1/4" = 1'-0"
MAIN LEVEL - PHASE 3, AREA A
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 SINGLE DOOR WITH ELECTRIC STRIKE AND MAGNETIC LOCK. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 2 ON SHEET TY501.
2 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
3 EXTERIOR-MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AT 8'-0" AFG.
4 SINGLE DOOR WITH ELECTRIC STRIKE. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO DETAIL
1 ON SHEET TY501.
5 CEILING-MOUNTED CAMERA. REFER TO DETAIL 4, SHEET TY504.
6 REMOTE VASS/SSTV WORKSTATION.
7 43" LED SECURITY SURVEILLANCE TELEVISION MONITOR. COORDINATE LOCATION
AND MOUNTING HEIGHT WITH OWNER.
8 IP VIDEO MASTER STATION - DESK MOUNTED.
9 COILING DOOR WITH MAGNETIC LOCK AND SECURITY GRILLE. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 6 ON SHEET TY501.
10 COILING DOOR CONTROLLER.
11 SECURITY GRILLE CONTROLLER. PROVIDE A TIMER-TO-CLOSE EXPANSION MODULE
FOR THE CONTROLLER.
12 TWO (2) UP/DOWN/STOP CONTROL STATIONS FOR THE COILING DOOR AND SECURITY
GRILLE CONTROLLERS. LOCATE CONTROL STATIONS ADJACENT TO ASSOCIATED CARD
READER/KEYPAD.
13 CORNER-MOUNTED CAMERA (REFER TO DETAIL 2, SHEET TY504). MOUNT AT
12'-0"AFF AND PROVIDE COVERAGE OF BOILER PANEL.
14 BOILER CONTROL PANEL.
15 AS PART OF PHASE 5, CONTRACTOR SHALL REMOVE PHYSICAL ACCESS CONTROL
DEVICES AT INDICATED DOOR AND TURN OVER DEVICES TO OWNER. PROVIDE
BLANK COVERPLATES FOR BACKBOXES WITH REMOVED PAC DEVICES.
16 PROVIDE CONNECTION FROM FIRE ALARM CONTROL MODULE TO PHYSICAL ACCESS
CONTROL SYSTEM. CONTROLLED DOORS SHALL ALLOW FREE EXIST UPON ACTIVATON
OF THE FIRE ALARM SYSTEM AS REQUIRED BY NFPA 72. COORDINATE WITH FIRE
ALARM SYSTEM CONTRACTOR.
17 SINGLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO DETAIL 5 ON SHEET
TY501.
M
M
90° M
M
M
A
4 1
C
D
B.3
B
3 2
A.7
A.6
A.4
C.7
C.9
TY
.3 A
TY
.3 A
104B
105B
DA
DA
104A
105A
DA
DA
E1042
E1052
E1051
E1041
S
M
X
M S
S
S
X S
S X
M
X
M
S
S
S
S
X
M
X
M
S
S
S
S
S
S
S
S
X
M
X
M
GENERATOR
ROOM
SUBSTATION
ROOM
121B
DA
X
M X
S
S
S
S
DE3
STAIR
REFER TO CONTINUATION ON
SECURITY ELECTRONICS SITE PLAN
(SHEET TY100)
121A6 E
S
EH
EH
E H
E H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW
EMERGENCY
GENERATOR
BLDG.
NEW BOILER
PLANT
Physical Security:
FORCE PROTECT
TUNNEL
BLDG 1
/1 /2
:5
:5
P M
TY111.3B
SECURITY ELECTRONICS
MAIN LEVEL - PHASE 3, AREA B
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 DOUBLE DOOR WITH ELECTRIC STRIKE AND (2) MAGNETIC LOCKS. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 4 ON SHEET TY501.
2 CORNER-MOUNTED CAMERA (REFER TO DETAIL 3, SHEET TY504). MOUNT AT
11'-0"AFF.
3 SINGLE DOOR WITH ELECTRIC STRIKE AND MAGNETIC LOCK. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 2 ON SHEET TY501.
4 EXTERIOR-MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AT 8'-0" AFG.
5 PROVIDE TWO (2) SPARE 2" CONDUITS DOWN TO BELOW GRADE AND EXTEND TO
SITE.
6 SINGLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO DETAIL 5 ON SHEET
TY501.
SCALE: 1/4" = 1'-0"
MAIN LEVEL - PHASE 3, AREA B
D W
FEC
FEC
M
360°360°
M
M
M
A
9 8 7 6 5
C
D
B.3
B
8.7 8.4 7.6
A.7
A.6
A.4
C.7
C.9
LOUNGE
I.T.
BEDROOM
TLT
SHOWER
LOCKERS
TLT/SHOWER
STORAGE
STAIR
CORRIDOR
BOILER ROOM
CATWALKS
DA
DA
TY
.3 B
TY
.3 B
E2061
F1011 F1012
S
S
H X
S L
X H
L S
ELEC
JAN.
G2031
E2201
STAIR
8.7 8.49 8
E3201
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
NEW
EMERGENCY
GENERATOR
BLDG.
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW BOILER
PLANT
TUNNEL
BLDG 1
Physical Security:
FORCE PROTECT
/1 /2
:5
:0
P M
TY121.3A
SECURITY ELECTRONICS
MEZZANINE LEVEL - PHASE 3, AREA A
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 WALL-MOUNTED CAMERA WITH MOTION DETECTION (REFER TO DETAIL 3, SHEET
TY504). MOUNT AS HIGH AS POSSIBLE, COORDINATE MOUNTING HEIGHT WITH
OTHER TRADES.
2 SINGLE DOOR WITH ELECTRIFIED MORTISE LOCK. PROVIDE CONDUIT/WIRING BACK
TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER
TO DETAIL 3 ON SHEET TY501.
3 PENDANT MOUNTED 360-DEGREE FISHEYE PANORAMIC CAMERA (REFER TO DETAIL 5,
SHEET TY504). MOUNT AT 12'-0" AFF; HOWEVER, FIELD COORDINATE EXACT
MOUNTING FOR OPTIMAL COVERAGE.
4 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER FROM EXISTING BUILDING
1 (DATA CLOSET GB-100A - SHEET TY201.3) TO BOILER PLANT (SECURITY 205 -
SHEET TY121.3B). HOLD TIGHT TO BOTTOM OF STRUCTURE, COORDINATE ROUTING
WITH OTHER TRADES.
5 PROVIDE PULL BOX - SIZE ACCORDING TO NEC 314.28.
6 EXTEND 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER UP TO LEVEL
ABOVE AND INTO THE CHILLER PLANT (SHEET TY111.5C).
7 SURFACE-MOUNTED CAMERA. MOUNT SIMILAR TO DETAIL 4, SHEET TY504, EXCEPT
WITH SURFACE MOUNT BACKBOX.
8 SINGLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO DETAIL 5 ON SHEET
TY501.
SCALE: 1/4" = 1'-0"
MEZZANINE LEVEL - PHASE 3, AREA A
NO. DESCRIPTION DATE
SCALE: 1/4" = 1'-0"
UPPER MEZZANINE LEVEL - PHASE 3, AREA A
FEC
M
M
M M
A
4 1
C
D
B.3
B
3 2
A.7
A.6
A.4
C.7
C.9
STAIR
CORRIDOR
STORAGE
GENERATOR
ROOM
MEZZANINE
SECURITY
TY
.3 A
TY
.3 A
DA
S
X M X
S S S
STORAGE
H X
S
S L
DA
E2051
G2032
OFFICE
MECH
E2171
E2211
H X
S
S L
DA
22113 321
STAIR
C
C.9 D
E3211
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW
EMERGENCY
GENERATOR
BLDG.
NEW BOILER
PLANT
Physical Security:
FORCE PROTECT
TUNNEL
BLDG 1
/1 /2
:5
:0
P M
TY121.3B
SECURITY ELECTRONICS
MEZZANINE LEVEL - PHASE 3, AREA B
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 SECURITY ELECTRONICS EQUIPMENT RACK. REFER TO DETAIL 3 ON SHEET TY605
FOR ADDITIONAL INFORMATION.
2 3/4" PLYWOOD TREATED WITH FLAME RETARDANT PAINT - SEE SPECIFICATIONS FOR
FURTHER DETAILS. TYPICAL ON ALL WALLS.
3 TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). REFER TO DETAILS 6 AND 7 ON
SHEET E-503 FOR ADDITIONAL REQUIREMENTS.
4 WALL-MOUNTED EQUIPMENT RACK TO HOUSE INTERCOM SYSTEM HEADEND
EQUIPMENT. REFER TO DETAIL 1, SHEET TY605 FOR ADDITIONAL INFORMATION.
5 PHYSICAL ACCESS CONTROL PANELS AND DOOR POWER SUPPLIES - QUANTITY AS
REQUIRED. REFER TO SPECIFICATION SECTION 281300.
6 WALL-MOUNTED CAMERA WITH MOTION DETECTION (REFER TO DETAIL 3, SHEET
TY504). MOUNT AS HIGH AS POSSIBLE, COORDINATE MOUNTING HEIGHT WITH
OTHER TRADES.
7 SINGLE DOOR WITH ELECTRIFIED MORTISE LOCK. PROVIDE CONDUIT/WIRING BACK
TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER
TO DETAIL 3 ON SHEET TY501.
8 SINGLE DOOR WITH ELECTRIC STRIKE AND MAGNETIC LOCK. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 2 ON SHEET TY501.
9 PROVIDE PULL BOX - SIZE ACCORDING TO NEC 314.28.
10 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER FROM EXISTING BUILDING
1 (DATA CLOSET GB-100A - SHEET TY201.3) TO BOILER PLANT (SECURITY 205 -
SHEET TY121.3B). HOLD TIGHT TO BOTTOM OF STRUCTURE, COORDINATE ROUTING
WITH OTHER TRADES.
11 PROVIDE TWO (2) SPARE 2" CONDUITS DOWN TO LEVEL BELOW AND EXTEND TO
SITE.
12 SURFACE-MOUNTED CAMERA. MOUNT SIMILAR TO DETAIL 4, SHEET TY504, EXCEPT
WITH SURFACE MOUNT BACKBOX.
13 SINGLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL PANEL. REFER TO DETAIL 5 ON SHEET
TY501.
SCALE: 1/4" = 1'-0"
MEZZANINE LEVEL - PHASE 3, AREA B
NO. DESCRIPTION DATE
SCALE: 1/4" = 1'-0"
UPPER MEZZANINE LEVEL - PHASE 3, AREA B
A
9 8 7 6 5 4
C
D
B.3
B
8.7 8.4 7.6
A.7
A.6
A.4
E
F
KE1
KE2
TY
.3 B
TY
.3 B
M
M
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
NEW
EMERGENCY
GENERATOR
BLDG.
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW BOILER
PLANT
TUNNEL
BLDG 1
Physical Security:
FORCE PROTECT
/1 /2
:5
:0
P M
TY141.3A
SECURITY ELECTRONICS
ROOF LEVEL - PHASE 3, AREA A
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 PENDANT MOUNTED 180-DEG PANORAMIC CAMERA WITH PARAPET MOUNT. REFER
TO DETAIL 1, SHEET TY504.
SCALE: 1/4" = 1'-0"
ROOF LEVEL - PHASE 3, AREA A
0°
270°
M
A
4 1
C
D
B.3
B
3 2
A.7
A.6
A.4
C.7
C.9
TY
.3 A
TY
.3 A
M
M
JE1
JE2
S
DA
X
M
X
S
S
S
E4211
STAIR
E S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
EXISTING
BOILER
PLANT
NEW
EMERGENCY
GENERATOR
BLDG.
NEW BOILER
PLANT
Physical Security:
FORCE PROTECT
TUNNEL
BLDG 1
/1 /2
:5
:0
P M
TY141.3B
SECURITY ELECTRONICS
ROOF LEVEL - PHASE 3, AREA B
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1/4" = 1'-0"
ROOF LEVEL - PHASE 3, AREA B
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 PENDANT MOUNTED 270-DEG PANORAMIC CAMERA WITH PARAPET MOUNT. REFER
TO DETAIL 1, SHEET TY504.
2 SINGLE DOOR WITH ELECTRIC STRIKE AND MAGNETIC LOCK. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 2 ON SHEET TY501.
3 WALL-MOUNTED CAMERA WITH MOTION DETECTION (REFER TO DETAIL 3, SHEET
TY504). MOUNT AS HIGH AS POSSIBLE, COORDINATE MOUNTING HEIGHT WITH
OTHER TRADES.
BLDG.
TO
#3
FEC
ST2-G ST7-G
CG-5
CG-11
CG-10
CG8A
CG-9
# 5
GB-112GB-113GB-114 GB-111
GB-110
GB-115
GB-115B
GB-115A
GB-117
GB-116A
GB-116
GB-118B
GB-118A
GB-142
GB-118D
GB-118C
GB-118E
GB-119
GB-119A
GB-119B
GB-146
GB-145
GB-144
GB-143A
GB-143B
GB-120
GB-122
GC-108A
GD-125
GD-122
GD-126
GD-126A
GD-129
GD-130
GD-121
GD-121A
GD-121B
GD-112
GD-112A
GD-100
GD-101
GD-113
GD-114
GD-119
GD-115
GD-118B
GD-118C
GD-118A
GD-116
GD-117
GB-135
GB-108B GB-108A GB-108
GB-137
GB-138
GB-139
GB-140
GB-141A GB-141B
GB-136
GB-103 GB-104
GB-107GB-106GB-105
GB-105B
GB-102C
GB-100
GB-100A
GC-112
GC-113
GC-100
GC-100A
GC-101
GC-102
GC-103
GC-103A
GC-104
GC-110
GC-109
GC-109A
GC-111
GC-108
GC-106
GC-104A
GC-106A GC-106B
GC-107A
GC-107
GC-105
GC-105A
GB-100B
GD-129A
GD-122A
CG-1
CG-2
CG-3
CG-4B
CG-4
CG-4A
CG-5
CG-5A
GB-160
GB-159
GB-158
GB-178
GB-162
GD-123A
GB-102
GB-107A
GB-115C
GB-119C
GD-129B
GD-123
GD-126B
GB-167
GB-149
GB-165 GB-166
GB-163
GB-164
GB-161
GC-107B
GB-105A
GB-150
CG-14
GD-118
GC-115 GC-116
GD-101C
GC-122 GC-137 CG-24GB-147
GB-100C
CG-13
STAIR STAIR
STAIR NO.5A
ELEV. #3
CORRIDOR
CORRIDOR
CORRIDOR
LOBBY
ELEV. #2
ELEV. #1
STAIR #4
ELEV. #5
ELEV. #4
STAIR
ENGINEERING
CLINICAL
ENGINEERING
CLINICAL
ENGINEERING
CLINICAL
UNION
CREDIT
OFFICE
CHIEF I.V. TEAM
ENGINEERING
CLINICAL
ENGINEERING
CLINICAL
ENGINEERING
CLINICAL
DOCTORS OFFICE
PULMONARY
TOILET &
FEMALE
LOCKERS
FEMALE
SHOWER
OFFICE
PULMONARY
RESPIRATORY
CHIEF
THERAPIST
ROOM
MECHANICAL
TESTING
RESPIRATORY
THERAPIST
RESPIRATORY
OFFICE
RESPIRATORY
WHEELCHAIR STORAGE
ESCORT
OFFICE
ESCORT
OFFICE
I.V. TEAM
CONFERENCE RM
PULMONARY
OFFICE
PULMONARY/
LAB
PFT
SUPPLY ROOM
RESPIRATORY
CYLINDER
GAS
STORAGE
ROOM
CHAPLAIN
OFFICE
CHAPEL
MAIN
ELECTRIC
VAULT
PUMP
ROOM
FIRE
ALCOVE
ELECTRIC CLOSET
CLOSET
ELECTRICCLOSET
TEL.
SUPERVISOR OFFICE
PROSTHETICS
PROSTHETICS
OFFICE /
FITTING
ROOM
SUPERVISORS
OFFICE
FITTING
ROOM
RECEPTION
OVEN ROOM
PROSTHETICS
PROSTHETICS
LAB
PROSTHETICS
CASTING ROOM
PROSTHETICS
STORAGE
MECHANICAL
ROOM
ORTHO/LAB
PULMONARY
OFFICE
TELEPHONE
CLOSET CLOSET
ELECTRIC
CLOSET
H.A.C.
CHIEF PULMONARY
MEDICINE
STAFF
PHYSICIAN
STAFF
PHYSICIAN
PFT
LAB
BATH-
ROOM
ROOM
LOCKER
OFFICE
CT SCANNER
ROOM
STORAGE
ROOM
CT SCAN
WAITING AREA
OFFICE
CT SCAN
HOLDING
PATIENT
TOILET
CONTROL
ROOM
ELECTRIC
CLOSET
CLOSET
DATA
CLOSET
ELECTRIC
TELEPHONE
CLOSET
AFGE
UNION
UNION (JP)
NURSES
HOSPITAL IN HOME
MEDICAL
SECRETARY
EMS
SERVICE CHIEF
EMS
SUPERVISOR
EMS
VESTIBULE
RECEIVING
OFFICE
ANESTHESIOLOGY
MECHANICAL
ROOM
STORAGE
EMS
TRASH ROOM
MEDICAL WASTE
TOILET
MALE
EMS LINEN
STORAGE
SPACE
TO CRAWL TO CRAWL
SPACE
TO CRAWL
SPACE
TO CRAWL
SPACE
HATCHWAY
TO CRAWL
SPACE
ELECTRIC
CLOSET
EMS
STORAGE
STORAGE
EMS
STORAGE
EMS
ROOM
ASSISTANT CHIEF
EMS
SECRETARY
EMS
TELEPHONE
CLOSET
ELECTRIC VAULT
UPS ROOM
ENTRANCE
PLATFORM
RAISED
SACRISTY
PULMONARY
PROGRAM ASST.
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
PULMONARY
CORRIDOR
ALCOVE
ELECTRIC
CLOSET
ROOM
BREAK
VIEWING
ROOM
ROOM
DRESSING
WAITING
ROOM
EEG
CT SCANNER
ROOM
STORAGE
ROOM
ENGINEERING
CLINICAL
STORAGE
I.V. TEAM
OFFICE
ELECTRIC VAULT
AUTOMATIC TRANSFER SWITCHES
NEUROLOGY
RESIDENTS OFFICE
OIT OFFICE
OIT STORAGE
AC-031
AIR HANDLER
AC-051
AIR HANDLER
STORAGE
ROOM
DRESSING
ROOM
OFFICE OFFICE
ELECTRICAL
ROOM
SCREENING
AREA
RECEPTION
ROOM
PROGRAM OFFICE
EMS BREAK
ROOM
CHECK-IN
EQUIP. STOR.
TECHNICIAN
OFFICE
DRESSING
ROOM
HANDICAP
OIT SUPERVISOR
OFFICE
WAITING ROOM
PROSTHETICS
WAITING ROOM
WHEELCHAIR
TOILET
FEMALE
TOILET
MALE
ELECTRICAL
GROUP ROOM TEL/DATA CORRIDORUNASSIGNED
CLOSET
CORRIDOR
U P
UP
U P
UP
UP
DN
UP
UP
UP
DN
1 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
Physical Security:
FORCE PROTECT
/1 /2
:5
:0
P M
TY201.3
SECURITY ELECTRONICS
BUILDING 1
GROUND LEVEL
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 3/32" = 1'-0"
BUILDING 1 GROUND LEVEL
GENERAL NOTES:
1 ALL WORK WITHIN THIS BUILDING SHALL BE PERFORMED AFTER HOURS.
COORDINATE WITH THE VA.
2 CONTRACTOR SHALL PROPERLY SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE
RATED WALLS.
3 ALL SECURITY ELECTRONICS CABLING SHALL BE INSTALLED IN CONDUIT WITH
CONDUIT ROUTED ABOVE CEILING.
4 ALL CEILING TILES REMOVED SHALL BE REINSTALLED AND ALL DEBRIS SHALL BE
REMOVED PRIOR TO NORMAL WORKING HOURS. ANY DAMAGED TILES SHALL BE
REPLACED WITH NEW.
5 REFER TO SHEET TY605 FOR THE SECURITY LAN FUNCTIONAL SCHEMATIC.
SHEET KEYNOTES:
1 TERMINATE THE SINGLEMODE (OS2) OPTICAL FIBER AT A PATCH PANEL INSTALLED IN
AN EXISTING EQUIPMENT RACK.
2 PROVIDE AN ADDITIONAL 50' OF CONDUIT/FIBER TO ACCOMMODATE FINAL LOCATION
OF THE EXISTING EQUIPMENT RACK LOCATION. CONTRACTOR SHALL VERIFY FINAL
LOCATION WITH VA'S COR.
3 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER FROM EXISTING BUILDING
1 (DATA CLOSET GB-100A - SHEET TY201.3) TO BOILER PLANT (SECURITY 205 -
SHEET TY121.3B). ROUTE CONDUIT ABOVE CEILING.
4 PROVIDE PULL BOX - SIZE ACCORDING TO NEC 314.28.
5 EXTEND 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER DOWN TO LEVEL
BELOW (BASEMENT - SHEET TY003.3).
6 PROVIDE PULL BOX ABOVE CEILING - SIZE ACCORDING TO NEC 314.28.
S
X
S
X
S
X
S
X
S
DA
FIRE PUMP HOUSE
H
E
M 2
DE-8
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTHACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
Physical Security:
FORCE PROTECT
/1 /2
:5
:0
P M
TY401.3
SECURITY ELECTRONICS
FIRE PUMP BUILDING - PHASE 3
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012NO. DESCRIPTION DATE
SCALE: 1/2" = 1'-0"
FIRE PUMP BUILDING - PHASE 3
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 DOUBLE DOOR WITH ELECTRIC STRIKE AND (2) MAGNETIC LOCKS. PROVIDE
CONDUIT/WIRING BACK TO POWER SUPPLIES AND ASSOCIATED PHYSICAL ACCESS
CONTROL PANEL. REFER TO DETAIL 4 ON SHEET TY501.
2 EXTERIOR-MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AT 8'-0" AFG.
D
C.7
C.9
PUMP ROOM
TY
.3
/2 TY101.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
Physical Security:
FORCE PROTECT
A R
E A
D
NEW
EMERGENCY
GENERATOR
BLDG.
NEW BOILER
PLANT
NEW
CHILLER
PLANT
TUNNEL
BLDG 1
/1 /2
:5
:5
P M
TY101.5D
SECURITY ELECTRONICS
BASEMENT LEVEL - PHASE 5, AREA D
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1/4" = 1'-0"
BASEMENT LEVEL - PHASE 5, AREA D
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
5 REFER TO SHEET TY605 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET TY606 FOR SECURITY SURVEILLANCE TELEVISION DIAGRAM.
7 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, SECURITY
SURVEILLANCE TELEVISION, AND INTERCOM SYSTEMS ARE LOCATED IN SECURITY 205
(SHEET TY121.3B).
SHEET KEYNOTES:
1 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER FROM EXISTING BUILDING
1 (DATA CLOSET GB-100A - SHEET TY201.3) TO BOILER PLANT (SECURITY 205 -
SHEET TY121.3B). HOLD TIGHT TO BOTTOM OF STRUCTURE, COORDINATE ROUTING
WITH OTHER TRADES.
2 PROVIDE PULL BOX - SIZE ACCORDING TO NEC 314.28.
3 EXTEND 2"C WITH 12-STRAND SINGLEMODE (OS2) OPTICAL FIBER UP TO LEVEL
ABOVE (SHEET TY111.5C).
A
13 12 11 10
C
D
10.5
B.3
B
8.7
A.7
A.6
A.4
C.7
C.9
106B
DA
106F
106E106D106C
DA
4 DA4 DA
4 DA
TY
.3 A
TY
.3 A
BACK ROOM
S
S S
M S
XS
XS
S
S
S
X
M
X
SSS
SSS
M M M M M M
SSSS S S
R S
RR
106D
S
S
DE6
DE7
FUTURE PHASE
R S
R S
R S
E S
E S
106A
DA
SX
S
E S
SX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD GRW
PROFESSIONAL ENGINEERCONSULTANTS
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
KEYPLAN
ACTUAL
NORTH
NEW
CHILLER
PLANT
MR PROJECT NO:
Hazardous Materials:
MABBETT & ASSOCIATES
Architect & Civil Engineering:
WBRC
Fire & Life Safety:
KOFFEL ASSOCIATES
Electronic Security:
GRW
Tunnel Structural & Civil Engineering:
PEC
NEW
EMERGENCY
GENERATOR
BLDG.
NEW BOILER
PLANT
Physical Security:
FORCE PROTECT
TUNNEL
BLDG 1
/1 /2
:5
:0
P M
TY111.5C
SECURITY ELECTRONICS
MAIN LEVEL - PHASE 5, AREA C
REPLACE BOILERS AND
UPGRADE CONTROLS
WEST ROXBURY VA MEDICAL CENTER
WEST ROXBURY, MA
11/14/2025 PJB PJB
BID DOCUMENTS
ISSUED FOR CONSTRUCTION
0506-0012
SCALE: 1/4" = 1'-0"
MAIN LEVEL - PHASE 5, AREA C
GENERAL NOTES:
1 REFER TO SHEETS TY501 - TY503 FOR PHYSICAL ACCESS CONTROL SYSTEM
DETAILS.
2 REFER TO SHEET TY504 FOR CAMERA MOUNTING DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEETS TY601 - TY604 FOR PHYSICAL ACCESS…