26_2500_-_ENCLOSED_BUS_ASSEMBLIES.PDF

PDF 114 KB Posted

Attached to
Renovate Hangar 885 Federal contract opportunity
Solicitation number
W9136418B5000
Issued by
Department of the Army Ohio Army National Guard

About this file

262500

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Hangar 885, newest first.
File Type Posted
Bid_Opening_Sign_In_W91364-18-B-5000.pdf PDF
Final_Bid_Opening_DOC_Abstract_of_offers_18B5000.pdf PDF
Amendment_6_RFI_Questions-Answers-July_20_2018.pdf PDF
Amendment_6_Drawings.pdf PDF
W91364-18-B-5000-0006.pdf PDF
W91364-18-B-5000-0005.pdf PDF
Amendment_4_ELEC_-_7.17.2018.pdf PDF
ANGETL_15-01-03,_Fire_Prot_Design_Policy.pdf PDF
Amendment_4_drawing_narrative.pdf PDF
Amendment_4_RFI_Questions-Answers-July_17_2018.pdf PDF
Amendment_4_Civil_-_C300_Site_Plan.pdf PDF
Amendment_4_ARCH_-_7.17.2018.pdf PDF
Amendment_4_HVAC_-_7.17.2018.pdf PDF
W91364-18-B-5000-0004.pdf PDF
321216_-_ASPHALT_PAVING.pdf PDF
323113_-_CHAIN_LINK_FENCES_AND_GATES.pdf PDF
OH1180099_7-06-2018_Franklin_County.pdf PDF
W9136418B5000-Amendment_0003.pdf PDF
RFI_Questions-Answers-July_13,_2018.pdf PDF
885S_1981Reno.pdf PDF
W9136418B5000-Amendment_0002.pdf PDF
885A_1981Reno.pdf PDF
RFI__Answer-July_10,_2018.pdf PDF
Pre-Bid_Conference_Renovate_Hangar_-6_Jul_18-_18B5000.pdf PDF
885F_1981Reno.pdf PDF
6JUL18_885_Site_Visit_Sign_In_Sheet.pdf PDF
885H_1981Reno.pdf PDF
885S_1953.pdf PDF
885E__1981Reno.pdf PDF
W9136418B5000_Hangar_885_Survey_Reports_and_Sampling_Data.pdf PDF
OH118_6-15-2018-Franklin.pdf PDF
RFI_Answers-July_7,_2018.pdf PDF
W91364-18-B-5000_Amendment_0001_RENOVATE_BLDG_885.pdf PDF
27JUN18_Site_Visit_Docs.pdf PDF
NLZG102008_RenovateHangar885_Full_Drawing_Set_Vol_02-IFB_Part_3_of_3.pdf PDF
NLZG102008_RenovateHangar885_specifications_Vol_01-IFB.pdf PDF
SECTION_013100_Govt_Specific_Addendum.pdf PDF
W91364-18-B-5000_RENOVATE_BLDG_885.pdf PDF
18B5000_-_JA_Manaco_Fire_Alarm_System.pdf PDF
18B5000_JA_Project_Mates.pdf PDF
NLZG102008_RenovateHangar885_Full_Drawing_Set_Vol_02-IFB_Part_1_of_3_.pdf PDF
W9136418B5000-_RFI_template.pdf PDF
NLZG102008_RenovateHangar885_specifications_Vol_02-IFB.pdf PDF
NLZG102008_RenovateHangar885_Full_Drawing_Set_Vol_02-IFB_Part_2_of_3.pdf PDF
NLZG102008_RenovateHangar885_Full_Drawing_Set_Vol_01-IFB.pdf PDF
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Rickenbacker ANG Base

Renovate Hanger 885

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 1

December 19, 2017

100% DESIGN SET

SECTION 262500 - ENCLOSED BUS ASSEMBLIES

PART 1 - GENERAL

1.1

A.

RELATED DOCUMENTS

Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2

SUMMARY

A. Section Includes:

1. Feeder-bus assemblies.

2. Plug-in bus assemblies.

3. Bus plug-in devices.

1.3

DEFINITIONS

A. kAIC: kiloampere interrupting capacity.

B. SPD: Surge protective device.

1.4

ACTION SUBMITTALS

A. Shop Drawings: For each type of product.

1. Show fabrication and installation details for enclosed bus assemblies. Include plans, elevations, and sections of components. Designate components and accessories, including clamps, brackets, hanger rods, connectors, straight lengths, and fittings.

2. Show fittings, materials, fabrication, and installation methods for listed firestop barriers.

3. Indicate required clearances, method of field assembly, and location and size of each field connection.

4. Detail connections to switchgear, switchboards, transformers, and panelboards.

5. Cable and conductor terminal sizes for bus and plug-in device terminations.

6. Wiring Diagrams: Power wiring.

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Floor plans and sections, drawn to scale. Include scaled bus-assembly layouts and relationships between components and adjacent structural, mechanical, and electrical elements. Show the following:

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 2

1. Vertical and horizontal enclosed bus-assembly runs, offsets, and transitions.

2. Clearances for access above and to the side of enclosed bus assemblies.

3. Vertical elevation of enclosed bus assemblies above the floor or bottom of structure.

4. Support locations, type of support, and weight on each support.

5. Location of adjacent construction elements including luminaires, HVAC and plumbing equipment, fire sprinklers and piping, signal and control devices, and other equipment.

B. Qualification Data: For testing agency.

C. Field quality-control reports.

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For enclosed bus assemblies to include in emergency, operation, and maintenance manuals.

1.7 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Plug-in Units: 10 percent of amount installed for each size indicated, but no fewer than 2 unit(s).

1.8 QUALITY ASSURANCE

A. Testing Agency Qualifications: Member company of NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

1.9 DELIVERY, STORAGE, AND HANDLING

A. Deliver, store, and handle enclosed bus assemblies according to NEMA BU 1.1, "General

Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less."

PART 2 - PRODUCTS

2.1 ASSEMBLY DESCRIPTIONS

A. Source Limitations: Obtain enclosed bus assemblies and plug-in devices from single source from single manufacturer.

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 3

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

C. Comply with UL 857.

2.2 PERFORMANCE REQUIREMENTS

A. Derate enclosed bus assemblies for continuous operation at indicated ampere ratings for ambient temperature not exceeding 122 deg F (50 deg C).

2.3 ENCLOSED BUS ASSEMBLIES

A. Feeder-Bus Assemblies: Low-impedance bus assemblies in totally enclosed, nonventilated housing; single-bolt joints; ratings as indicated.

1. Recommended Manufacturers:

a. Eaton

b. Schneider Electric

c. Siemens

d. General Electric

e. ABB

2. Electrical Characteristics:

a. Voltage: 120/208, 480, 277/480 V.

b. Phase: Three; 3 wire, 4 wire.

c. Percent of Neutral Capacity: 100, unless noted otherwise on drawings.

3. Short-Circuit Interrupting Rating:

a. For Bus Amperage of 200: 65 symmetrical kAIC.

b. For Bus Amperage of 800: 85 symmetrical kAIC.

c. For Bus Amperage of 1200: 100 symmetrical kAIC.

d. For Bus Amperage of 1600: 125 symmetrical kAIC.

e. For Bus Amperage of 2500: 150 symmetrical kAIC.

f. For Bus Amperage of 5000: 200 symmetrical kAIC.

4. Temperature Rise: 55 deg C above 40 deg C ambient maximum for continuous rated current.

5. Bus Materials: Current-carrying copper conductors, fully insulated with Class 130C insulation except at joints; plated surface at joints.

6. Voltage Drop:

a. Measure voltage drop at 30 deg C ambient with bus thermally stabilized at full

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 4 rated load.

b. Three-phase, line-to-line voltage drop less than 3.1 V per 100 feet (30.5 m) at 40 percent power factor.

7. Ground: 50 percent capacity, internal bus bar of material matching bus material.

8. Ground: 50 percent capacity, isolated, internal bus bar of material matching bus material.

9. Enclosure: Steel with manufacturer's standard finish.

10. Fittings and Accessories: Manufacturer's standard.

11. Firestop: Comply with UL 1479 firestop system, listed and labeled by an NRTL acceptable to authorities having jurisdiction for penetrations of fire-rated walls, ceilings, and floors.

12. Mounting: Arranged flat, edgewise, or vertically without derating. Rated for hanger spacing of up to 10 feet (3 m) for horizontally mounted runs and up to 16 feet (5 m) for vertically mounted runs.

13. Expansion Section: Manufacturer's standard expansion fitting for the provided busway with expansion capability to accommodate thermal expansion of bus and enclosure, and to accommodate movement across building expansion joints.

B. Plug-in Bus Assemblies: Low-impedance bus assemblies in totally enclosed, nonventilated housing; single-bolt joints; ratings as indicated.

1. Recommended Manufacturers:

a. Eaton

b. Schneider Electric

c. Siemens

2. Electrical Characteristics:

a. Voltage: 120/208, 480, 277/480 V.

b. Phase: Three; 3 wire, 4 wire.

c. Percent of Neutral Capacity: 100, unless indicated otherwise on drawings.

3. Short-Circuit Interrupting Rating:

a. For Bus Amperage of 800: 85 symmetrical kAIC.

b. For Bus Amperage of 1200: 100 symmetrical kAIC.

c. For Bus Amperage of 1600: 125 symmetrical kAIC.

d. For Bus Amperage of 2500: 150 symmetrical kAIC.

e. For Bus Amperage of 5000: 200 symmetrical kAIC.

4. Temperature Rise: 55 deg C above 40 deg C ambient maximum for continuous rated current.

5. Bus Materials: Current-carrying copper conductors, fully insulated with Class 130C insulation except at stabs and joints; plated surface at stabs and joints.

6. Ground: 50 percent capacity, internal bus bar of material matching bus material.

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 5

7. Enclosure: Steel, with manufacturer's standard finish.

8. Plug-in Openings: 24 inches (600 mm) o.c. on each side of bus, and hinged covers over unused openings. Plug-in openings shall be finger-safe with covers open or closed.

9. Fittings and Accessories: Manufacturer's standard.

10. Firestop: Comply with UL 1479 firestop system, listed and labeled by an NRTL acceptable to authorities having jurisdiction for penetrations of fire-rated walls, ceilings, and floors.

11. Mounting: Arranged flat, edgewise, or vertically without derating. Rated for hanger spacing of up to 10 feet (3 m) for horizontally mounted runs and up to 16 feet (5 m) for vertically mounted runs.

12. Expansion Section: Manufacturer's standard expansion fitting for the provided busway with expansion capability to accommodate thermal expansion of bus and enclosure, and to accommodate movement across building expansion joints.

C. Joints:

1. Busway joints shall use one high-strength steel bolt with Belleville washers.

2. Bolts shall be torque indicating type and at ground potential.

3. Bolts shall be two-headed design to indicate when proper torque has been applied and require only a standard long handle wrench to be properly activated.

4. Access shall be required to only one side of the busway for tightening joint bolts.

5. Joint connection assemblies shall be removable without disturbing adjacent busway lengths.

6. Joint connection assemblies that rely on the joint cover to provide ground continuity are unacceptable.

2.4 PLUG-IN DEVICES

A. Molded-Case Circuit Breakers: UL 489; hookstick-operated handle, lockable with two padlocks, and interlocked with cover in closed position. Interlocked to prevent plug-in device insertion into or removal from bus with switch in closed position.

1. Recommended Manufacturers:

a. Eaton

b. Schneider Electric

c. Siemens

B. Accessories: Hookstick operator, adjustable to maximum extension of 14 feet (4.3 m).

PART 3 - EXECUTION

3.1 INSTALLATION

A. Coordinate layout and installation of enclosed bus assemblies and suspension system with other

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 6 construction that penetrates ceilings or floors or is supported by them, including luminaires, HVAC equipment, fire-suppression system, and partition assemblies.

B. Equipment Mounting:

1. Install enclosed bus assemblies on cast-in-place concrete equipment base(s). Comply with requirements for equipment bases and foundations specified in Section 033000

"Cast-in-Place Concrete." or Section 033053 "Miscellaneous Cast-in-Place Concrete."

2. Coordinate size and location of concrete curbs around openings for vertical bus.

Concrete, reinforcement, and formwork requirements are specified with concrete.

C. Support bus assemblies independent of supports for other elements such as equipment enclosures at connections to panelboards and switchboards, pipes, conduits, ceilings, and ducts.

1. Design each fastener and support to carry load indicated by seismic requirements and to comply with seismic-restraint details according to Section 260548.16 "Seismic Controls for Electrical Systems."

2. Design each fastener and support to carry 200 lb (90 kg) or 4 times the weight of bus assembly, whichever is greater.

3. Support bus assembly to prevent twisting from eccentric loading.

4. Support bus assembly with not less than 3/8-inch (10-mm) steel rods. Install side bracing to prevent swaying or movement of bus assembly. Modify supports after completion to eliminate strains and stresses on bus bars and housings.

5. Fasten supports securely to building structure according to Section 260529 "Hangers and

Supports for Electrical Systems."

6. Bolts and nuts that are loosened for any reason after tightening to manufacturer's recommended torque setting shall be discarded and replaced with new bolts and nuts.

D. Install expansion fittings at locations where bus assemblies cross building expansion joints.

Install at other locations so distance between expansion fittings does not exceed manufacturer's recommended distance between fittings.

E. Construct rated firestop assemblies where bus assemblies penetrate fire-rated elements such as walls, floors, and ceilings. Seal around penetrations according to Section 078413 "Penetration

Firestopping."

F. Install weatherseal fittings and flanges where bus assemblies penetrate exterior elements such as walls or roofs. Seal around openings to make weathertight. See Section 079200 "Joint Sealants" for materials and application.

G. Coordinate bus-assembly terminations to equipment enclosures to ensure proper phasing, connection, and closure.

H. Tighten bus-assembly joints with torque wrench or similar tool recommended by bus-assembly manufacturer. Tighten joints again after bus assemblies have been energized for 30 days.

I. Install bus-assembly, plug-in units. Support connecting conduit independent of plug-in unit.

J. Comply with NECA 1.

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 7

3.2 CONNECTIONS

A. Ground equipment according to Section 260526 "Grounding and Bonding for Electrical

Systems."

B. Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and

Cables."

C. Terminate to transformer enclosures with matching bus assemblies according to Section 262200

"Low-Voltage Transformers."

D. Terminate to switchgear enclosures with matching bus assemblies according to Section 262300

"Low-Voltage Switchgear."

E. Terminate to switchboard enclosures with matching bus assemblies according to Section 262413 "Switchboards."

F. Terminate to panelboard enclosures with matching bus assemblies according to Section 262416

"Panelboards."

G. Terminate to motor-control centers enclosures with matching bus assemblies according to

Section 262419 "Motor-Control Centers."

3.3 FIELD QUALITY CONTROL

A. Perform the following tests and inspections with the assistance of a factory-authorized service representative:

1. After installing equipment test, for compliance with requirements according to

NETA ATS.

2. Visual and Mechanical Inspection:

a. Compare equipment nameplate data with Drawings and Specifications.

b. Inspect physical and mechanical condition.

c. Inspect anchorage, alignment, and grounding.

d. Verify correct connection according to single-line diagram.

e. Inspect bolted electrical connections for high resistance using one or more of the following methods:

1) Use of low-resistance ohmmeter.

2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method according to manufacturer's published data.

3) Perform thermographic survey.

3. Electrical Tests:

Project No. NLZG102008

SECTION 262800

CIRCUIT AND MOTOR DISCONNECTS

Page No. 8

a. Perform insulation resistance measurements through bolted connections and bus joints with low-resistance ohmmeter.

b. Perform insulation resistance tests of each busway, phase to phase, and phase to ground.

c. Perform a dielectric withstand voltage test on each busway, phase to ground with phases not under test grounded for one minute.

d. Measure resistance of assembled busway sections on insulated busway and compare values with adjacent phases.

e. Perform phasing test on each busway tie section energized by separate sources.

f. Verify operation of busway space heaters.

B. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final

Acceptance, perform an infrared scan of each switch. Remove all access panels so joints and connections are accessible to portable scanner.

1. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

2. Record of Infrared Scanning: Prepare a certified report that identifies switches checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

3. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each switch 11 months after date of Substantial Completion.

C. Test Labeling: On completion of satisfactory testing of each unit, attach a dated and signed

"Satisfactory Test" label to tested component.

D. Enclosed bus assemblies will be considered defective if they do not pass tests and inspections.

E. Prepare test and inspection reports.

3.4 ADJUSTING

A. Set field-adjustable, circuit-breaker trip ranges as indicated.

3.5 CLEANING

A. Vacuum dirt and debris; do not use compressed air to assist in cleaning.

3.6 PROTECTION

A. Provide final protection to ensure that moisture does not enter bus assembly.

END OF SECTION 262500