BUILDING INSULATION

View the file

Other files

File Type Posted
QUESTIONS AND ANSWERS LA PORTE as of 21 JUL 09.doc DOC document
QUESTIONS AND ANSWERS LA PORTE AS OF 20 JUL 09.doc DOC document
QUESTIONS AND ANSWERS as of 8 Jul 09.doc DOC document
QUESTIONS AND ANSWERS as of 7 Jul 09.doc DOC document
QUESTIONS AND ANSWERS as of 6 JUL 09.doc DOC document
Addendum 2 Dimensioned Floor Plans 20090701.pdf PDF
QUESTIONS AND ANSWERS LA PORTE AS OF 29 JUN 09 —
9- Exhibit C 12-05.doc DOC document
Exhibit D-E-F Jan 08.doc DOC document
8 -Exhibit B 1205.doc DOC document
QUESTIONS AND ANSWERS as of 1 JUL 09.doc DOC document
08110-Steel Doors Frames.DOC DOC document
09651 - Resilient Tile Flooring and Accesories.DOC DOC document
ATTENDANCE ROSTER.pdf PDF
PREPROPOSAL MEETING MINUTES - LA PORTE FACILITIES.doc DOC document
PHOTOS.doc DOC document
Hurricane IKE B 1359 Drawings 20090506.pdf PDF
09512-Accoustical Ceiling.doc DOC document
09680 - Carpet.DOC DOC document
01001-00-General_Requirements.doc DOC document
01731-00-Cutting_ _Patching.DOC DOC document
01019-00-Contract_Considerations.DOC DOC document
AF Form 3052 Construction Cost Estimate Breakdown.xls XLS spreadsheet
Form WH-347-Wage report Form-BlanK.xls XLS spreadsheet
07620-Sheet Metal Flashing and Trim.DOC DOC document
01420-00-Environmental_Protection.doc DOC document
01700-00-Contract_Closeout.DOC DOC document
01300-00-Submittals 20090302.doc DOC document
09900 - Painting.doc DOC document
07591-Preparation for Reroofing 20090227 .doc DOC document
Contractor_Security_Policy_Letter.doc DOC document
Form 3065-Contract Progress Report.xls XLS spreadsheet
07550-Modified Bitumin Roofing 20090226.doc DOC document
Form 3064- Progress Schedule.xls XLS spreadsheet
09255-Gypsum Board Assemblies.DOC DOC document
07560-Cold Coal Tar Modified 20090227.doc DOC document
01105-00-Haz_Mat_Procedures.doc DOC document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ellington Field ANGB

Houston, Texas

MASTERSPEC text, Copyright 1995, AIA, The American Institute of Architects

Paragraph number formatting method, Copyright 1988, ARCOM, Architectural Computer Services, Inc.

SECTION 07210

BUILDING INSULATION

PART 1 - GENERAL

1.1

RELATED DOCUMENTS

A.

Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2

SUMMARY

A.

This Section includes the following:

ADJUST LIST BELOW TO SUIT PROJECT. DELETE APPLICATIONS SUCH AS CAVITY WALL INSULATION AND SAFING INSULATION THAT ARE SPECIFIED IN OTHER SECTIONS.

1. Cavity wall insulation.

2. Concealed building insulation.

3. Exposed building insulation.

B.

Related Sections: The following Sections contain requirements that relate to this Section:

LIST BELOW ONLY PRODUCTS, CONSTRUCTION, AND EQUIPMENT FOR THIS PROJECT THAT THE READER MIGHT EXPECT TO FIND IN THIS SECTION BUT ARE SPECIFIED ELSEWHERE. VERIFY THAT THE SECTION TITLES LISTED BELOW ARE CORRECT FOR THIS PROJECT'S SPECIFICATIONS.

1. Division 3 Section “Cast-in-Place Concrete.”

2. Division 7 Section "Firestopping" for safing insulation.

3. Division 9 Section “Gypsum Board Assemblies” for insulation installed as part of metal-framed wall and partition assemblies.

RETAIN APPLICABLE SECTION TITLE BELOW.

1.3

SUBMITTALS

A.

General: Submit each item in this Article according to the Conditions of the Contract and Division 1 Specification Sections.

B.

Provide product Data for each type of insulation product specified.

C.

Samples of exposed insulation for initial selection in the form of actual units or sections of units showing the full range of colors available for each type of exposed insulation indicated.

DELETE ABOVE IF COLORS ARE PRESELECTED AND SPECIFIED OR SCHEDULED. RETAIN BELOW WITH OR WITHOUT ABOVE. DELETE BOTH IF NO EXPOSED INSULATION OR SAMPLES ARE REQUIRED.

DELETE BELOW WHERE SECTION HAS BEEN EDITED TO RETAIN ONLY PRODUCTS WITH WELL-KNOWN NONVARYING VALUES.

D.

Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for insulation products.

INSERT SPECIFIC MODEL CODE ORGANIZATION BELOW OR REVISE IF REPORT MUST BE FROM ANOTHER SOURCE.

E.

Research or evaluation reports of the model code organization acceptable to authorities having jurisdiction that evidence compliance of foam-plastic insulations with building code in effect for Project.

1.4

QUALITY ASSURANCE

A.

Single-Source Responsibility for Insulation Products: Obtain each type of building insulation from a single source with resources to provide products complying with requirements indicated without delaying the Work.

B.

Fire-Test-Response Characteristics: Provide insulation and related materials with the fire-test-response characteristics indicated on Drawings or specified elsewhere in this Section as determined by testing identical products per test method indicated below by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. Identify materials with appropriate markings of applicable testing and inspecting agency.

RETAIN BELOW WHERE TEST RESULTS ARE INDICATED WITH OTHER PRODUCT REQUIREMENTS IN PART 2. RETAIN ONLY TEST METHODS APPLICABLE TO TYPES OF CHARACTERISTICS SPECIFIED.

1.

Surface-Burning Characteristics: ASTM E 84.

RETAIN BELOW ONLY IF PRODUCTS SPECIFIED IN PART 2 ARE PART OF A FIRE-RESISTANCE-RATED ASSEMBLY.

2.

Fire-Resistance Ratings: ASTM E 119.

BELOW IS A PASS-FAIL TEST FOR MEASURING COMBUSTIBILITY THAT IS REFERENCED IN CODES TO DETERMINE IF ELEMENTARY PRODUCTS ARE NONCOMBUSTIBLE. ONLY SELECTED UNFACED MINERAL-FIBER INSULATIONS WITHOUT FACINGS AND UNFACED CELLULAR GLASS INSULATION PASS THIS TEST. SEE EVALUATIONS.

3.

Combustion Characteristics: ASTM E 136.

1.5

DELIVERY, STORAGE, AND HANDLING

A.

Protect insulation materials from physical damage and from deterioration by moisture, soiling, and other sources. Store inside and in a dry location. Comply with manufacturer's written instructions for handling, storing, and protecting during installation.

DELETE PARA AND SUBPARAS BELOW IF NO PLASTIC INSULATION.

B.

Protect plastic insulation as follows:

1.

Do not expose to sunlight, except to extent necessary for period of installation and concealment.

2.

Protect against ignition at all times. Do not deliver plastic insulating materials to Project site before installation time.

3.

Complete installation and concealment of plastic materials as rapidly as possible in each area of construction.

PART 2 - PRODUCTS

2.1

MANUFACTURERS

A.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering insulation products that may be incorporated in the work include, but are not limited to, the following:

RETAIN ABOVE FOR NONPROPRIETARY OR BELOW FOR SEMIPROPRIETARY SPECIFICATION. REFER TO DIVISION 1 SECTION "MATERIALS AND EQUIPMENT."

SEE EDITING INSTRUCTION NO. 1 IN THE EVALUATIONS FOR CAUTIONS ABOUT NAMING PRODUCTS AND MFRS. SEE EVALUATIONS FOR PRODUCT LISTS.

1.

Extruded-Polystyrene Board Insulation:

a.

Amoco Foam Products Company.

b.

DiversiFoam Products.

c.

Dow Chemical Co.

d.

UC Industries, Inc.; Owens-Corning Co.

2.

Polyisocyanurate Board Insulation:

a.

Celotex Corporation (The).

b.

NRG Barriers, Inc.

3.

Glass-Fiber Insulation:

a.

CertainTeed Corporation.

b.

Knauf Fiber Glass GmbH.

c.

Owens-Corning Fiberglas Corporation.

2.2

INSULATING MATERIALS

A.

General: Provide insulating materials that comply with requirements and with referenced standards.

DELETE BELOW IF ONLY LOOSE-FILL INSULATION IS RETAINED. REVISE IF SPECIAL SIZES ARE REQUIRED AND AVAILABILITY IS VERIFIED.

1.

Provide in sizes to fit applications indicated, selected from manufacturer's standard thicknesses, widths, and lengths.

DELETE TYPES OF INSULATION NOT REQUIRED. COORDINATE SELECTIONS WITH THICKNESSES INDICATED ON DRAWINGS AND WITH HVAC DESIGN AND ENERGY PROGRAM. WHERE INSULATION IS EXPOSED OR OPEN TO AIR SPACES IN PLENUMS, CAVITIES, OR SIMILAR VOIDS, TAKE CARE TO COMPLY WITH CODES FOR FIRE-TEST-RESPONSE CHARACTERISTICS.

B.

Extruded-Polystyrene Board Insulation: Rigid, cellular polystyrene thermal insulation formed from polystyrene base resin by an extrusion process using hydrochlorofluorocarbons as blowing agent to comply with ASTM C 578 for type and with other requirements indicated below:

1.

Type VII, 2.20-lb/cu. ft. minimum density.

RATINGS IN SUBPARA BELOW ARE EXAMPLES ONLY AND GENERALLY REPRESENT MAXIMUMS ALLOWED BY MODEL BUILDING CODES FOR FOAM-PLASTIC INSULATION. REVISE TO SUIT PRODUCTS REQUIRED AND CODE IN EFFECT FOR PROJECT. SEE EVALUATIONS.

2.

Surface-Burning Characteristics: Maximum flame-spread and smoke-developed indices of 75 and 450, respectively.

RETAIN SUBPARA BELOW ONLY AFTER VERIFYING AVAILABILITY IN TYPE, FORM, AND SIZE REQUIRED FOR PROJECT.

3.

Recycled Content: Not less than 50 percent blend of post-consumer and recovered polystyrene resins.

PARA BELOW DESCRIBES "STYROFOAM THERMADRY DRAINAGE PANELS" BY DOW CHEMICAL AND "INSUL-DRAIN" BY UC INDUSTRIES. THEY ARE INTENDED FOR BELOW-GRADE APPLICATIONS. VERIFY WHETHER MFR'S STANDARD FABRIC AND INSULATION BOARD IS SUITABLE FOR SOIL CONDITIONS AND SOIL PRESSURES TO WHICH IT WILL BE EXPOSED. SEE PRODUCT LIST IN EVALUATIONS. DELETE IF THIS PRODUCT IS SPECIFIED IN OTHER SECTIONS, SUCH AS DIVISION 2 SECTION "FOUNDATION DRAINAGE SYSTEMS" AND DIVISION 7 SECTIONS FOR WATERPROOFING.

C. Foil-Faced, Polyisocyanurate Board Insulation: ASTM C 1289, Type I, Class 1 or 2, with maximum flame-spread and smoke-developed indices of 75 and 450, respectively, based on tests performed on unfaced core on thicknesses up to 4 inches (101 mm).

D.

Faced Mineral-Fiber Blanket Insulation: Thermal insulation combining mineral fibers of type described below with thermosetting resins to comply with ASTM C 665, Type III, Class A (blankets with reflective vapor-retarder membrane facing and flame spread of 25 or less); with foil-scrim-kraft, foil-scrim, or foil-scrim-polyethylene vapor-retarder membrane on one face. Provide 6-1/4” thick R-value 19 for metal studs at 16”.

RETAIN 1 OF 3 BELOW.

1.

Mineral-Fiber Type: Fibers manufactured from glass.

BELOW DESCRIBES "PANEL DECK THERMAL-SHIELD" INSULATION AVAILABLE FROM SCHULLER INTERNATIONAL. DELETE IF NOT REQUIRED.

2.

Flanged Units: Provide blankets fabricated with facing incorporating 5-inch-wide flanges along edges for attachment to framing members.

2.3

AUXILIARY INSULATING MATERIALS

A.

Adhesive for Bonding Insulation: Product with demonstrated capability to bond insulation securely to substrates indicated without damaging insulation and substrates.

BELOW CAN BE USED TO PROTECT WALL OR UNDER-SLAB INSULATION FROM DAMAGE DURING BACKFILLING OR CONCRETE/REINFORCING PLACEMENT.

B.

Protection Board: Premolded, semirigid asphalt/fiber composition board, 1/4 inch thick, formed under heat and pressure, standard sizes.

2.4

INSULATION FASTENERS

BELOW IS AN EXAMPLE OF A MECHANICAL FASTENER. PRONG ANCHORS, WELDING PINS, POINTED RODS, ETC., ARE ALSO AVAILABLE. INSERT AS REQUIRED.

REVISE SIZE BELOW IF REQUIRED.

A.

Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch-thick galvanized steel sheet, with beveled edge for increased stiffness, sized as required to hold insulation securely in place, but not less than 1-1/2 inches square or in diameter.

RETAIN SUBPARA BELOW IF ANCHORS ARE USED IN CRAWLSPACES, CEILING PLENUMS, ATTIC SPACES, ETC., WHERE SHARP ENDS OF SPINDLES WOULD BE EXPOSED TO HUMAN CONTACT.

1.

Where spindles will be exposed to human contact after installation, protect ends with capped self-locking washers incorporating a spring steel insert to ensure permanent retention of cap.

B.

Anchor Adhesive: Product with demonstrated capability to bond insulation anchors securely to substrates indicated without damaging insulation, fasteners, and substrates.

PART 3 - EXECUTION

3.1

EXAMINATION

A.

Examine substrates and conditions, with Installer present, for compliance with requirements of Sections in which substrates and related work are specified and to determine if other conditions affecting performance of insulation are satisfactory. Do not proceed with installation until unsatisfactory conditions have been corrected.

3.2

PREPARATION

A.

Clean substrates of substances harmful to insulations or vapor retarders, including removing projections capable of puncturing vapor retarders or that interfere with insulation attachment.

DELETE BELOW IF NO POURED-IN-PLACE TYPES.

3.3

INSTALLATION, GENERAL

A.

General: Comply with insulation manufacturer's written instructions applicable to products and application indicated.

B.

Install insulation that is undamaged, dry, unsoiled, and has not been exposed at any time to ice and snow.

C.

Extend insulation in thickness indicated to envelop entire area to be insulated. Cut and fit tightly around obstructions and fill voids with insulation. Remove projections that interfere with placement.

D.

Apply single layer of insulation to produce thickness indicated.

DELETE ABOVE OR BELOW. RETAIN BELOW ONLY IF PROJECT CONDITIONS ARE KNOWN TO EXIST WHERE MULTIPLE LAYERS ARE REQUIRED.

3.4

INSTALLATION OF GENERAL BUILDING INSULATION

A.

General: Apply insulation units to substrates by method indicated, complying with manufacturer's written instructions. If no specific method is indicated, bond units to substrate with adhesive or use mechanical anchorage to provide permanent placement and support of units.

B.

Set vapor-retarder-faced units with vapor retarder to warm side of construction, unless otherwise indicated. Do not obstruct ventilation spaces, except for firestopping.

DELETE ABOVE AND BELOW IF NO UNITS ARE FURNISHED WITH VAPOR-RETARDER FACES.

1. Tape joints and ruptures in vapor retarder, and seal each continuous area of insulation to surrounding construction to ensure airtight installation.

DELETE BELOW IF NO FOIL-FACED UNITS; ALSO, IF AIR SPACE IS NOT POSSIBLE.

DELETE PARA AND SUBPARAS BELOW IF NO MINERAL-FIBER BLANKET INSULATION IS USED IN CAVITIES OF FRAMING MEMBERS.

C.

Install mineral-fiber blankets in cavities formed by framing members according to the following requirements:

1.

Use blanket widths and lengths that fill cavities formed by framing members. Where more than one length is required to fill cavity, provide lengths that will produce a snug fit between ends.

2.

Place blankets in cavities formed by framing members to produce a friction fit between edges of insulation and adjoining framing members.

3.

For metal stud-framed construction with faced blankets having stapling flanges, position insulation to produce 1/2-inch continuous air space between insulation facing and inner surface of concealing finish material, unless otherwise indicated. Secure insulation by inset, tapping flanges to sides of framing members.

REVISE BELOW TO INDICATE TYPE OF CONCRETE SUBSTRATE, SUCH AS ARCHITECTURAL PRECAST CONCRETE PANELS OR CAST-IN-PLACE CONCRETE WALLS.

D.

Install board insulation on concrete substrates by adhesively attached, spindle-type insulation anchors as follows:

1.

Fasten insulation anchors to concrete substrates with insulation anchor adhesive according to anchor manufacturer's written instructions. Space anchors according to insulation manufacturer's written instructions for insulation type, thickness, and application indicated.

2.

After adhesive has dried, install board insulation by pressing insulation into position over spindles and securing it tightly in place with insulation-retaining washers, taking care not to compress insulation below indicated thickness.

3.

Where insulation will not be covered by other building materials, apply capped washers to tips of spindles.

E. Install in concealed spaces behind glass spandrels in accordance with glass and curtain wall manufacturers recommendations.

DELETE BELOW IF NO VOIDS OR IF NOT NEEDED FOR SOUND DEADENING, SOUND ABSORPTION, THERMAL PROTECTION, OR AIR-INFILTRATION REDUCTION.

F.

Stuff glass-fiber insulation into miscellaneous voids and caviaty spaces where shown. Compact to approximately 40 percent of normal maximum volume equaling a density of approximately 2.5 lb/cu. ft.

3.6

PROTECTION

A. General: Protect installed insulation from damage due to harmful weather exposures, physical abuse, and other causes. Provide temporary coverings or enclosures where insulation is subject to abuse and cannot be concealed and protected by permanent construction immediately after installation.

3.7 SCHEDULE OF INSULATIONS

A. Roof Insulation:

1.

Polyisocyanurate Board Insulation: R = 19 nominal

B. Wall Insulation:

1. Extruded-Polystyrene Board Insulation: R = 11 (nominal).).

2. Faced Mineral Fiber Insulation: R = 11 (nominal).

C.

Sound Insulation: 3-1/2” x 16” x 96”.

D.

Spandrel Insulation:

1.

Extruded-Polystyrene Board Insulation: R = 11 (nominal).

END OF SECTION 07210

Building Insulation

07210-5