FH - CDC - ELECTRICAL - SITE PLAN - LIGHTING_Amendment1-ES-102.pdf
PDF 292 KB Posted
- Solicitation number
- W912DS26RA018
About this file
This is an Electrical Lighting Site Plan (Sheet ES102) for the Child Development Center at Fort Hamilton, New York, prepared under Solicitation No. W912DS23F0031 and Contract No. W912DS19D0007 by the US Army Corps of Engineers, New York District.
The document specifies site lighting requirements for the facility, including a detailed Site Lighting Fixtures Schedule that outlines five pole-mounted LED lighting fixture types (P-1 through P-4). Fixtures range from single luminaires rated at 38W to four-way configurations at 152W, all operating at 277V with 3000K color temperature. All fixtures feature Type III medium distribution, dark bronze mounting on 20-foot aluminum poles with 6-inch shafts, and include photocells and dimming drivers with motion sensors. The fixture count totals 14 units distributed across the site. General notes require the contractor to submit lighting calculations with fixture cutsheets; verify all fixtures are energy-efficient LED types compliant with the Buy American Act; coordinate utility locations with other disciplines and the facility manager; maintain minimum burial depths and clearances per applicable codes; provide 2-inch Schedule 40 PVC conduit (concrete-encased under roads and asphalt) and 2-inch Schedule 80 PVC direct-buried conduit in other areas; and size wiring considering voltage drop and load balancing. The plan also requires demolition of all existing pole lighting, poles, pathways, and wiring back to their power supply within designated areas. The document was issued August 29, 2025, with a corrected scale noted for 07/2026.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XXXXXXXX
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X
UGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGE
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHT
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE
UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT UGT
UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UE
UE
UE
UE
UE
UE
U E
U E
U E
U E
U E
U E
T
M G UE
UE
E
MH
E
MH
CHILD DEVELOPMENT CENTER
( SMALL: 0-5 years old )
PLAYGROUND
AREA 'B'
PLAYGROUND
AREA 'C'
PLAYGROUND
AREA 'A'
FFL 39.75
UE
UE
PC
A1 ELECTRICAL - LIGHTING - SITE PLAN
1" = 20'
SHEET KEYNOTES
GENERAL NOTES
1. REFER TO E001 FOR SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
2. REFER TO EL100 SERIES, EL601 FOR INTERIOR, ENTRANCE/EXIT,
AND CANOPY LIGHTING LAYOUT AND SCHEDULE, AND TO EL602
FOR LIGHTING CONTROLS INFORMATION.
3. REFER TO SITE CIVIL DRAWINGS FOR COMPLETE UTILITIES
PLANS.
4. LIGHTING FIXTURE PLACEMENT IS DIAGRAMMATIC.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH
OTHER DISCIPLINES TO VERIFY UTILITY LOCATIONS. REFER TO
CIVIL DRAWINGS FOR LOCATION OF UTILITIES.
5. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR
TO VERIFY THE ACCURACY AND COMPLETENESS OF UTILITIES
SHOWN ON THIS DRAWING WITH THE FACILITY MANAGER PRIOR
TO ANY CONSTRUCTION ACTIVITY AND REPORT DISCREPANCIES
TO THE COR.
6. MINIMUM BURIAL DEPTHS AND SUFFICIENT CLEARANCES
BETWEEN NEW AND EXISTING UTILITIES AND/OR STRUCTURES
SHALL BE COORDINATED WITH THE RESPECTIVE DISCIPLINES
AND MAINTAINED IN ACCORDANCE WITH APPLICABLE CODES
AND AUTHORITY HAVING JURISDICTION. NEW UTILITIES SHALL BE
PLACED ABOVE OR BELOW EXISTING UTILITIES/STRUCTURES AT
CROSSINGS IN ACCORDANCE WITH REQUIRED DEPTHS AND
CLEARANCES.
5. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH PULL STRINGS.
6. REFER TO STRUCTURAL DRAWINGS AND EARTHWORK
SPECIFICATIONS FOR ADDITIONAL DUCT BANK REQUIREMENTS.
7. FOR SITE LIGHTS, PROVIDE 2'' SCHEDULE 40 PVC CONCRETE
ENCASED UNDER ROADS AND ASPHALT AND 2'' SCHEDULE 80
PVC DIRECT BURIED CONDUIT IN ALL OTHER AREAS. PROVIDE
HANDHOLES AS REQUIRED.
8. CONTRACTOR SHALL SUBMIT LIGHTING CALCULATIONS ALONG
WITH LIGHT FIXTURE CUTSHEETS. ALL LIGHT FIXTURES WILL BE
ENERGY EFFICIENT, LED TYPE, AND MUST MEET THE BUY
AMERICAN ACT.
9. CONTRACTOR RESPONSIBLE FOR SIZING THE WIRING IN
CONSIDERATION OF VOLTAGE DROP AND LOAD BALANCING.
10. LIGHT FIXTURES SHOWN ON PLAN ARE NTS AND FOR
DIAGRAMMATIC LOCATION ONLY.
1. ALL EXISTING POLE LIGHTING, INCLUDING POLES, SHALL BE
DEMOLISHED WITHIN THIS AREA. DEMOLISH LIGHTS, POLES,
PATHWAYS, AND WIRING BACK TO ITS POWER SUPPLY.
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
FO
R T
H
AM
IL
TO
N , N
EW
Y
O R
K
PR
O
JE
C T
N O
. 7
US Army Corps of Engineers ®
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
K.
S
C H
N
ED
LE
R
K.
S
C H
N
ED
LE
R
Y.
B
AR
R
ET
T
M . G
IU
R
G
IU
AU
G
U
ST
9, W
2D S2
3F
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
W
2D S1
9D
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S N
EW
Y
O R
K D
IS
TR
IC
T
F
ED
ER
AL
P
LA
ZA
, N
EW
Y O
R K
N Y
N
EL
EC
TR
IC
AL
LI
G
H
TI
N G
SI
TE
P
LA
N
ES102
SITE LIGHTING FIXTURES SCHEDULE
TYPE
MARK
DESCRIPTION LAMP INITIAL
COLOR
TEMP.
MOUNTING NOTESVOLTAGE WATTAGE COUNT
P-1 LED AREA SINGLE
LUMINAIRE WITH
PHOTOCELL AND 20FT
ALUMINUM POST
LED POLE38 W 3 FIXTURE: 4,376 LUMENS, TYPE III MEDIUM
DISTRIBUTION, ROUND POLE MOUNTING,
DARK BRONZE COLOR, 7-PIN RECEPTACLE.
POLE: 20 FT ROUND POLE, 6 IN. SHAFT,
SINGLE FIXTURE MOUNTING, DARK
BRONZE COLOR.
277 V 3000 K
B-U-G
RATING
B1-U0-G1
P-2 LED POLE76 W 7277 V 3000 K FIXTURE: 8,752 LUMENS, TYPE III MEDIUM
DISTRIBUTION, ROUND POLE MOUNTING,
DARK BRONZE COLOR, 7-PIN RECEPTACLE.
POLE: 20FT ROUND POLE, 6 IN. SHAFT,
TWO FIXTURES SEPARATED BY 90
DEGREES MOUNTING, DARK BRONZE
COLOR.
B1-U0-G1
P-3 LED POLE144 W 3277 V 3000 K FIXTURE: 13,128 LUMENS, TYPE III
MEDIUM DISTRIBUTION, ROUND POLE
MOUNTING, DARK BRONZE COLOR, 7-PIN
POLE: 20FT ROUND POLE, 6 IN. SHAFT,
THREE FIXTURES SEPARATED BY 90
DEGREES MOUNTING, DARK BRONZE
COLOR
B1-U0-G1
P-4 LED AREA FOUR-WAY
LUMINAIRES WITH
PHOTOCELL AND 20FT
ALUMINUM POST
LED POLE152 W 1277 V 3000 K FIXTURE: 17,504 LUMENS, TYPE III
MEDIUM DISTRIBUTION, ROUND POLE
MOUNTING, DARK BRONZE COLOR, 7-PIN
POLE: 20FT ROUND POLE, 6 IN. SHAFT,
FOUR FIXTURES SEPARATED BY 90
DEGREES MOUNTING, DARK BRONZE
COLOR
B1-U0-G1
LED AREA
THREE-WAY
LUMINAIRES WITH
PHOTOCELL AND 20FT
ALUMINUM POST
LED AREA TWO-WAY
LUMINAIRE WITH
PHOTOCELL AND 20FT
ALUMINUM POST
RECEPTACLE.
RECEPTACLE.
P-1
P-1
P-2
P-1 P-2
P-2
P-2
P-2
P-2
P-2
P-3 P-3
P-4
1 (TYP.)
P-3
LP1-16
LP1-16
LP1-16
LP1-16
LP1-16
LP1-16
LP1-16
LP1-19
LP1-19
LP1-19
LP1-19
LP1-19
LP1-19
LP1-19
DIMMING DRIVER, MOTION SENSOR.
DIMMING DRIVER, MOTION SENSOR.
DIMMING DRIVER, MOTION SENSOR.
DIMMING DRIVER, MOTION SENSOR.
10' 20' 40'0
SCALE: 1" = 20'1
C
O R
R
EC
TE
D
S C
AL
E
/2
AutoCAD SHX Text 221'-1.25"
AutoCAD SHX Text 74'-7.25"
AutoCAD SHX Text 221'-1.25"
AutoCAD SHX Text 74'-7.25"