866-B710-01_REV 1_AC LOAD ANALYSIS_07-05-21.pdf

PDF 880 KB Posted

Attached to
New Crane Barge Federal contract opportunity
Solicitation number
W912BU22B0018
Issued by
Department of the Army Corps of Engineers Engineering District Philadeplhia

About this file

This document provides details for an invitation for bid for a new crane barge. The U.S. Army Corps of Engineers Marine Design Center is soliciting bids to procure a crane barge to replace an existing vessel currently in operation by the Detroit District. The new barge is to be built and classed by the American Bureau of Shipping as a Maltese Cross A-1 Steel Barge for Great Lakes service. Key specifications include a length of 150 feet, beam of 50 feet, depth of 10 feet, and design waterline of 5 feet. Bidders must fabricate and deliver the barge to the St. Mary's Falls Canal in Sault Sainte Marie, Michigan, and liquidated damages are associated with the procurement. The solicitation requires bid guarantees, payment and performance bonding. Bids are due by email to Amanda.Bellnier@usace.army.mil on August 29th at 10:00am EDT.

View the file

Other files for this federal contract opportunity

Other files attached to New Crane Barge, newest first.
File Type Posted
W912BU22B0018 Amendment 3.pdf PDF
W912BU22B0018 Amendment 1 SF30.pdf PDF
Amendment 2 TAI 1240_866-B522-02_Rev 3_SPUD HANDLING SYSTEM ARRANGEMENT_05-23-22 (Redlined for Amendment).pdf PDF
W912BU22B0018 Amendment 1.pdf PDF
T1716010 KEEN Stability Letter - signed with Load Charts_106379386.pdf PDF
866-B685-01_REV 3_HEATING AND VENTILATION SYSTEM CALCULATIONS_04-26-22.pdf PDF
866-B330-07_Rev 1_BOOM REST DESIGN CALCULATIONS_02-28-22.pdf PDF
866-B406-01 MDC STANDARD FLOATING PLANT PAINT SCHEDULE.pdf PDF
866-B601-01 PIPE MARKING GUIDE.pdf PDF
866-B125-01_Rev 1_HYDROSTATICS_05-26-21.pdf PDF
866-B301-01 Rev 5 MIDSHIP SECTION.pdf PDF
866-B320-01_Rev 2_INDEPENDENT TANKS.pdf PDF
866-B330-05_Rev 4_CRANE REINFORCED DECK AREA.pdf PDF
866-B330-01_Rev 2_DECK DUNNAGE PLAN.pdf PDF
866-B310-01 REV 4 WELDING SCHEDULE.pdf PDF
866-B425-01_Rev 0_WALKWAYS PLATFORMS RAILINGS AND GRATINGS.pdf PDF
866-B415-01_Rev 2_DOORS WINDOWS HATCHES AND MANHOLES.pdf PDF
866-B730-04_REV 3_ELECTRICAL POWER PLANT.pdf PDF
866-B330-04_Rev 2_CRANE TRACKING AREA.pdf PDF
866-B667-01_REV 1_SANITARY AND BLACK WATER SYSTEM.pdf PDF
866-B730-01_Rev 1_LIGHTING PLAN.pdf PDF
W912BU22B0018.pdf PDF
866-B170-01_Rev 1_DRY DOCKING PLAN.pdf PDF
866-B105-01_Rev 0_HULL LINES AND OFFSETS.pdf PDF
866-B309-01 Rev 6 TRANSVERSE STRUCTURE.pdf PDF
866-B307-03 Rev 5 RAKE STRUCTURE.pdf PDF
866-B330-03_Rev 1_MACHINERY AND WINCH FOUNDATIONS CALCULATIONS pdf.pdf PDF
866-B552_01_Rev 3_SPUD WELL STRUCTURAL ARRANGEMENT.pdf PDF
866-B685-02_Rev 4_HEATING AND VENTILATION SYSTEM DRAWING.pdf PDF
866-B677-01_Rev 2_FIXED FIRE EXTINGUISHING SYSTEM.pdf PDF
866-B640-01_Rev 2_ENGINE COOLING SYSTEM.pdf PDF
866-B630-01_Rev 2_FUEL OIL SYSTEM ARRANGEMENT.pdf PDF
866-B635-01_Rev 2_LUBE OIL STORAGE ARRANGEMENT.pdf PDF
866-B637-01_Rev 2_WASTE OIL SYSTEM.pdf PDF
866-B690-01_Rev 1_COMPRESSED AIR SYSTEM.pdf PDF
866-B660-03_Rev 2_DECK WASHDOWN SYSTEM.pdf PDF
TAI 1240_866-B115-01_Rev 4_WEIGHT ESTIMATE_06-08-22.pdf PDF
866-B215-01_Rev 3_GENERAL ARRANGEMENT.pdf PDF
866-B330-02_Rev 2_MACHINERY AND WINCH FOUNDATION.pdf PDF
866-B311-01 Rev 6 LONGITUDINAL STRUCTURE.pdf PDF
866-B307-01 Rev 6 DECK AND BOTTOM PLATING.pdf PDF
866-B330-06_Rev 1_BOOM REST.pdf PDF
866-B315-01_Rev 3_DECKHOUSE STRUCTURE.pdf PDF
866-B307-02_Rev 3_SHELL PLATING.pdf PDF
866-B325-01_Rev 2_SEA CHEST DETAILS.pdf PDF
866-B436-01_Rev 1_INSULATION AND SHEATHING.pdf PDF
866-B410-01 Rev 5 SKEG STRUCTURE.pdf PDF
866-B550-01_Rev 2_SPUD STRUCTURAL ARRANGEMENT_02-04-22.pdf PDF
TAI 1240_866-B522-02_Rev 3_SPUD HANDLING SYSTEM ARRANGEMENT_05-23-22.pdf PDF
866-B650-01_Rev 1_ENGINE EXHAUST SYSTEM.pdf PDF
Show all 50

New Crane Barge has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Est. Est. Est. Est. Est. Est. Est. Est. Est. Est.

V HP KW D.F KW D.F KW D.F KW D.F KW D.F KW D.F KW D.F KW D.F KW D.F KW D.F KW

1 DECK WINCH NO. 1 480V 7.50 5.59 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.00 0.00 0.00 0.00

2 DECK WINCH NO. 2 480V 7.50 5.59 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.20 1.12 0.00 0.00 0.00 0.00

3 DECK WINCH NO. 3 480V 7.50 5.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

4 DECK WINCH NO. 4 480V 7.50 5.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

5 SPUD WINCHES NO.1 480V 50.00 37.25 0.00 0.00 0.00 0.00 0.80 29.80 0.70 26.08 0.00 0.00 0.00 0.00 0.80 29.80 0.80 29.80 0.00 0.00 0.00 0.00

6 SPUD WINCHES NO.2 480V 50.00 37.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

7 SPUD WINCHES NO.3 480V 50.00 37.25 0.00 0.00 0.00 0.00 0.90 33.53 0.80 29.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

8 SPUD WINCHES NO.4 480V 50.00 37.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

9 DECK WASH DOWN PUMP 480V 25.00 18.63 0.20 3.73 0.20 3.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

10 GENERATOR NO. 1 RADIATOR FAN 480V 10.30 7.67 0.05 0.38 0.20 1.53 0.20 1.53 0.20 1.53 0.05 0.38 0.20 1.53 0.20 1.53 0.20 1.53 0.00 0.00 0.00 0.00

11 GENERATOR NO. 2 RADIATOR FAN 480V 10.30 7.67 0.05 0.38 0.20 1.53 0.20 1.53 0.20 1.53 0.05 0.38 0.20 1.53 0.20 1.53 0.20 1.53 0.00 0.00 0.00 0.00

12 STANDALONE GENERATOR RADIATOR FAN 480V 8.80 6.56 0.20 1.31 0.05 0.33 0.05 0.33 0.05 0.33 0.20 1.31 0.05 0.33 0.05 0.33 0.05 0.33 0.00 0.00 0.00 0.00

13 MACHINERY ROOM SUPPLY FAN 480V 3.00 2.24 0.50 1.12 0.40 0.89 0.50 1.12 0.40 0.89 0.50 1.12 0.40 0.89 0.50 1.12 0.40 0.89 0.00 0.00 0.00 0.00

14 MACHINERY ROOM RETURN FAN 480V 5.00 3.73 0.50 1.86 0.40 1.49 0.50 1.86 0.40 1.49 0.50 1.86 0.40 1.49 0.50 1.86 0.40 1.49 0.00 0.00 0.00 0.00

15 CRANE SERVICE LOAD 480V 54.00 40.23 0.09 3.62 0.20 8.05 0.09 3.62 0.20 8.05 0.16 6.44 0.50 20.12 0.09 3.62 0.20 8.05 0.00 0.00 0.00 0.00

16 175KVA ISOLATION TRANSFORMER NO.1 (SHORE POWER) 480V - 140.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

17 EQUIPMENT POWER PANEL - P1 - - 27.02 - 0.00 - 18.61 - 0.00 - 18.61 - 0.00 - 18.61 - 0.00 - 18.61 - 0.00 - 18.61

18 EQUIPMENT POWER PANEL - P2 - - 95.01 - 8.00 - 20.01 - 20.00 - 32.01 - 8.00 - 20.01 - 20.00 - 32.01 - 10.00 - 22.01

19 EQUIPMENT POWER PANEL - L1 - - 48.75 - 5.40 - 14.89 - 4.98 - 17.48 - 5.10 - 16.67 - 3.59 - 14.89 - 1.58 - 6.18

20 GEN.LIGHTING/RECEP. PANEL - L2 - - 21.04 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69 - 9.69

21 GEN.LIGHTING/RECEP. PANEL - L3 - - 37.94 - 13.82 - 13.34 - 13.82 - 13.34 - 13.82 - 13.34 - 13.82 - 13.34 - 13.82 - 13.34

22 HVAC POWER PANEL - L4 - - 7.13 - 4.31 - 3.57 - 5.20 - 2.67 - 4.31 - 3.57 - 5.20 - 3.49 - 5.20 - 3.49

23 DECK LOAD PANEL - L5 - - 64.44 - 4.68 - 4.68 - 2.92 - 2.92 - 4.68 - 9.36 - 3.07 - 3.07 - 3.07 - 3.07

TOTAL 699.40 60.53 104.58 132.16 168.65 59.32 119.38 97.39 140.95 43.35 76.38

24 HOT WATER UNIT HEATER NO.1 - MACHINERY ROOM 480V 4.03 3.00 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80

25 HOT WATER UNIT HEATER NO.2 - MACHINERY ROOM 480V 4.03 3.00 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50

26 HOT WATER UNIT HEATER NO.3 - MACHINERY ROOM 480V 4.03 3.00 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80 0.00 0.00 0.60 1.80

27 HOT WATER UNIT HEATER NO.4 - MACHINERY ROOM 480V 4.03 3.00 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50 0.00 0.00 0.50 1.50

28 HOT WATER UNIT HEATER - GENERATOR ROOM 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

29 HOT WATER UNIT HEATER - BOILER ROOM 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

30 HOT WATER UNIT HEATER - FWD WINCH ROOM 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

31 HOT WATER UNIT HEATER - AFT WINCH ROOM 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

32 HOT WATER UNIT HEATER - STORAGE SPACE (FR.9-FR.17) 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

TOTAL 27.02 0.00 18.61 0.00 18.61 0.00 18.61 0.00 18.61 0.00 18.61

33 SPACE HEATER - GALLEY/MESS 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

34 SPACE HEATER - DAY ROOM 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

35 SPACE HEATER - 6 CREW 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

36 SPACE HEATER - DECK OPERATOR CONTROL HOUSE 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

37 SPACE HEATER - CONTROL HOUSE/OFFICE 480V 4.03 3.00 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40 0.00 0.00 0.80 2.40

38 480V, 3P, OUTLET NO.1 (Appleton ACP603BC) 480V 53.69 40.00 0.20 8.00 0.20 8.00 0.50 20.00 0.50 20.00 0.20 8.00 0.20 8.00 0.50 20.00 0.50 20.00 0.25 10.00 0.25 10.00

39 480V, 3P, OUTLET NO.2 (Appleton ACP603BC) 480V 53.69 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

TOTAL 95.01 8.00 20.01 20.00 32.01 8.00 20.01 20.00 32.01 10.00 22.01

CONNECTED LOAD

LOAD DESCRIPTION SUMMER SUMMER SUMMERWINTER WINTER

EQUIPMENT POWER PANEL - P2 (480VAC, 3PH, 3W)

WINTER

MAIN SWITCHBOARD (480VAC, 3PH, 3W)

USACE 3265 150FT CELRE CRANE BARGE AC LOAD ANALYSIS

EQUIPMENT POWER PANEL - P1 (480VAC, 3PH, 3W)

OPERATION CONDITION 1 OPERATION CONDITION 2

SUMMER WINTER

OPERATION CONDITION 5OPERATION CONDITION 3

Operating Condition 2: Lifting two spuds simultaneously, barge service loads and crane general service loads except crane diesel heater loads.

Operating Condition 3: Crane general service, crane heating and barge service loads.

Operating Condition 5: Shore Power Connection loads.

Operating Condition 4: Lifting one spud, barge service loads and crane general service loads except crane diesel heater loads.

ITEM NO.

OPERATION CONDITION 4

SUMMER WINTER

LEGEND:

Operating Condition 1: Barge service loads and crane general service loads except crane diesel heater loads.

TAI-1240 USACE_150'x50'x10' CELRE CRANE BARGE MDC Project: 3265, Hull No: 866

07/05/2021 Rev 1

CONNECTED LOAD

LOAD DESCRIPTION SUMMER SUMMER SUMMERWINTER WINTERWINTER

USACE 3265 150FT CELRE CRANE BARGE AC LOAD ANALYSIS

OPERATION CONDITION 1 OPERATION CONDITION 2

SUMMER WINTER

OPERATION CONDITION 5OPERATION CONDITION 3

ITEM NO.

OPERATION CONDITION 4

SUMMER WINTER

40 GENERATOR NO.1 BATTERY CHARGER 120V - 0.50 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30

41 GENERATOR NO.2 BATTERY CHARGER 120V - 0.50 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30 0.60 0.30

42 24VDC BATTERY CHARGER NO.1 120V - 0.75 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08

43 24VDC BATTERY CHARGER NO.2 120V - 0.75 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08 0.10 0.08

44 STANDALONE GENERATOR BATTERY CHARGER 120V - 0.50 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15 0.30 0.15

45 GENERAL ALARM BATTERY CHARGER 120V - 0.25 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08 0.30 0.08

46 CRANE HEATER 120V - 1.00 0.00 0.00 0.90 0.90 0.00 0.00 0.90 0.90 0.00 0.00 0.90 0.90 0.00 0.00 0.90 0.90 0.00 0.00 0.20 0.20

47 GENSETS NO.1 BLOCK HEATER 120V - 1.50 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.20 0.30

48 GENSETS NO.2 BLOCK HEATER 120V - 1.50 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.50 0.75 0.00 0.00 0.20 0.30

49 SWITCHBOARD SPACE HEATERS 120V - 1.50 0.20 0.30 0.90 1.35 0.00 0.00 0.90 1.35 0.00 0.00 0.90 1.35 0.00 0.00 0.90 1.35 0.00 0.00 0.20 0.30

50 STANDALONE GENERATOR BLOCK HEATER 120V - 1.50 0.00 0.00 0.00 0.00 0.00 0.00 0.20 0.30 0.00 0.00 0.90 1.35 0.00 0.00 0.20 0.30 0.00 0.00 0.20 0.30

51 WINCH ROOM NO. 1 HEATER 120V - 1.00 0.00 0.00 0.20 0.20 0.00 0.00 0.80 0.80 0.00 0.00 0.20 0.20 0.00 0.00 0.50 0.50 0.00 0.00 0.20 0.20

52 WINCH ROOM NO. 2 HEATER 120V - 1.00 0.00 0.00 0.20 0.20 0.00 0.00 0.80 0.80 0.00 0.00 0.20 0.20 0.00 0.00 0.50 0.50 0.00 0.00 0.20 0.20

53 WINCH ROOM NO. 3 HEATER 120V - 1.00 0.00 0.00 0.20 0.20 0.00 0.00 0.80 0.80 0.00 0.00 0.20 0.20 0.00 0.00 0.50 0.50 0.00 0.00 0.20 0.20

54 WINCH ROOM NO. 4 HEATER 120V - 1.00 0.00 0.00 0.20 0.20 0.00 0.00 0.80 0.80 0.00 0.00 0.20 0.20 0.00 0.00 0.50 0.50 0.00 0.00 0.20 0.20

55 FUEL OIL BOILER NO.1 208V - 5.96 0.10 0.60 0.35 2.09 0.10 0.60 0.35 2.09 0.10 0.60 0.35 2.09 0.10 0.60 0.35 2.09 0.00 0.00 0.00 0.00

56 FUEL OIL BOILER NO.2 208V - 5.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

57 PRESSURE SET PUMP 120V - 0.56 0.30 0.17 0.30 0.17 0.10 0.06 0.10 0.06 0.30 0.17 0.30 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

58 SANITARY/BLACK WATER TRANSFER PUMP 208V 5.00 3.73 0.20 0.75 0.10 0.37 0.20 0.75 0.10 0.37 0.20 0.75 0.20 0.75 0.20 0.75 0.10 0.37 0.00 0.00 0.00 0.00

59 LUBE OIL TRANSFER PUMP 120V 0.75 0.56 0.20 0.11 0.10 0.06 0.20 0.11 0.10 0.06 0.20 0.11 0.20 0.11 0.20 0.11 0.10 0.06 0.00 0.00 0.00 0.00

60 FUEL OIL TRANSFER PUMP 120V 0.75 0.56 0.20 0.11 0.20 0.11 0.20 0.11 0.20 0.11 0.20 0.11 0.20 0.11 0.20 0.11 0.20 0.11 0.00 0.00 0.00 0.00

61 BILGE PUMP (POTABLE) 120V 1.00 0.75 0.20 0.15 0.20 0.15 0.20 0.15 0.20 0.15 0.20 0.15 0.20 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

62 BALLAST PUMP (POTABLE) 208V 8.00 5.96 0.20 1.19 0.20 1.19 0.20 1.19 0.20 1.19 0.20 1.19 0.20 1.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

63 HEATING WATER CIRCULATING PUMP NO.1 208V 3.00 2.24 0.20 0.45 0.50 1.12 0.20 0.45 0.50 1.12 0.20 0.45 0.50 1.12 0.20 0.45 0.50 1.12 0.00 0.00 0.00 0.00

64 HEATING WATER CIRCULATING PUMP NO.2 208V 3.00 2.24 0.00 0.00 0.50 1.12 0.00 0.00 0.50 1.12 0.00 0.00 0.50 1.12 0.00 0.00 0.50 1.12 0.00 0.00 0.00 0.00

65 WATER HEATER 120V 6.00 0.10 0.60 0.50 3.00 0.10 0.60 0.50 3.00 0.10 0.60 0.50 3.00 0.10 0.60 0.50 3.00 0.10 0.60 0.50 3.00

TOTAL 48.75 5.40 14.89 4.98 17.48 5.10 16.67 3.59 14.89 1.58 6.18

66 DECK OPERATOR CONTROL HOUSE LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

67 CONTROL HOUSE/OFFICE LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

68 DECK OPERATOR CONTROL HOUSE RECEPTACLES NO.1 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

69 DECK OPERATOR CONTROL HOUSE RECEPTACLES NO.2 120V - 1.80 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36 0.20 0.36

70 CONTROL HOUSE/OFFICE RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

71 MAIN DECK AFT PORT FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

72 MAIN DECK AFT PORT FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

73 MAIN DECK AFT STBD FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

74 MAIN DECK AFT STBD FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

75 AFT WINCH ROOM LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

76 GENERATOR ROOM LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

77 MACHINERY ROOM LIGHTING NO.1 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

78 MACHINERY ROOM LIGHTING NO.2 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

79 BOILER ROOM LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

80 STORAGE (P) LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

81 STORAGE (C) LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

82 AFT WINCH ROOM RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

83 GENERATOR ROOM RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

84 MACHINERY ROOM RECEPTACLES NO.1 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

85 MACHINERY ROOM RECEPTACLES NO.2 120V - 1.80 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54

86 BOILER ROOM RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

87 STORAGE (P) RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

88 STORAGE (S) RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

89 STORAGE (C) RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

90 FWD WINCH ROOM LIGHTING 120V - 0.10 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05 0.50 0.05

TOTAL 21.04 9.69 9.69 9.69 9.69 9.69 9.69 9.69 9.69 9.69 9.69

EQUIPMENT POWER PANEL - L1 (208/120VAC, 3PH, 4W)

GEN. LIGHTING/RECEP. PANEL - L2 (208/120VAC, 3PH, 4W)

TAI-1240 USACE_150'x50'x10' CELRE CRANE BARGE MDC Project: 3265, Hull No: 866

07/05/2021

CONNECTED LOAD

LOAD DESCRIPTION SUMMER SUMMER SUMMERWINTER WINTERWINTER

USACE 3265 150FT CELRE CRANE BARGE AC LOAD ANALYSIS

OPERATION CONDITION 1 OPERATION CONDITION 2

SUMMER WINTER

OPERATION CONDITION 5OPERATION CONDITION 3

ITEM NO.

OPERATION CONDITION 4

SUMMER WINTER

91 GALLEY/MESS LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

92 GALLEY REFRIGERATOR RECEPTACLE 120V - 2.40 0.30 0.72 0.10 0.24 0.30 0.72 0.10 0.24 0.30 0.72 0.10 0.24 0.30 0.72 0.10 0.24 0.30 0.72 0.10 0.24

93 GALLEY MICROWAVE RECEPTACLE 120V - 2.40 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72

94 GALLEY COFFEE MAKERS RECEPTACLE 120V - 2.40 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72

95 GALLEY COOKING RANGE RECEPTACLE 120V - 2.40 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72 0.30 0.72

96 GALLEY COUNTERTOP RECEPTACLE#1 120V - 3.60 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08

97 GALLEY RECEPTACLES 120V - 1.80 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54

98 WORK SHOP/STORAGE LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

99 DAY ROOM LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

100 6 CREW LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

101 HEAD PORT LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

102 HEAD STBD LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

103 FWD WINCH ROOM LIGHTING 120V - 0.10 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06 0.60 0.06

104 WORK SHOP/STORAGE RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

105 DAY ROOM RECEPTACLES NO.1 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

106 DAY ROOM RECEPTACLES NO.2 120V - 1.80 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54

107 CREW RECEPTACLES NO. 1 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

108 CREW RECEPTACLES NO. 2 120V - 1.80 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54 0.30 0.54

109 HEAD PORT RECEPTACLE 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

110 HEAD STBD RECEPTACLE 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

111 FWD WINCH ROOM RECEPTACLES 120V - 1.80 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90 0.50 0.90

112 MAIN DECK EXTERIOR LIGHTING (PORT) 120V - 0.10 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04

113 MAIN DECK EXTERIOR LIGHTING (STBD) 120V - 0.10 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04

114 MAIN DECK FWD PORT FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

115 MAIN DECK FWD STBD FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

116 MAIN DECK FWD PORT FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

117 MAIN DECK FWD STBD FLOOD LIGHT 120V - 0.06 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02 0.40 0.02

118 MAIN DECK EXTERIOR LIGHTING (PORT CENTER) 120V - 0.10 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04

119 GALLEY COUNTERTOP RECEPTACLE#2 120V - 3.60 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08

120 GALLEY COUNTERTOP RECEPTACLE#3 120V - 3.60 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08 0.30 1.08

121 MAIN DECK EXTERIOR LIGHTING (STBD CENTER) 120V - 0.10 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04 0.40 0.04

TOTAL 37.94 13.82 13.34 13.82 13.34 13.82 13.34 13.82 13.34 13.82 13.34

122 FWD WINCH ROOM EXHAUST FAN 208V 0.75 0.56 0.60 0.34 0.50 0.28 0.90 0.50 0.50 0.28 0.60 0.34 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

123 AIR HANDLER UNIT 208V 2.50 1.86 0.50 0.93 0.50 0.93 0.50 0.93 0.20 0.37 0.50 0.93 0.50 0.93 0.50 0.93 0.20 0.37 0.50 0.93 0.20 0.37

124 WORKSHOP/STORAGE SUPPLY FAN 208V 0.75 0.56 0.60 0.34 0.50 0.28 0.90 0.50 0.50 0.28 0.60 0.34 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

125 WORKSHOP/STORAGE EXHAUST FAN 208V 0.75 0.56 0.60 0.34 0.50 0.28 0.90 0.50 0.50 0.28 0.60 0.34 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

126 BOILER ROOM SUPPLY FAN 208V 1.00 0.75 0.60 0.45 0.50 0.37 0.90 0.67 0.50 0.37 0.60 0.45 0.50 0.37 0.90 0.67 0.70 0.52 0.90 0.67 0.70 0.52

127 GENERATOR ROOM SUPPLY FAN 208V 0.75 0.56 0.90 0.50 0.50 0.28 0.90 0.50 0.50 0.28 0.90 0.50 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

128 GENERATOR ROOM EXHAUST FAN 208V 0.75 0.56 0.90 0.50 0.50 0.28 0.90 0.50 0.50 0.28 0.90 0.50 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

129 AFT WINCH ROOM EXHAUST FAN 208V 0.75 0.56 0.60 0.34 0.50 0.28 0.90 0.50 0.50 0.28 0.60 0.34 0.50 0.28 0.90 0.50 0.70 0.39 0.90 0.50 0.70 0.39

130 HEAD EXHAUST FAN (BELOW DECK) 120V 0.03 0.02 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01

131 HEAD EXHAUST FAN (DECK) 120V 0.03 0.02 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01 0.50 0.01 0.60 0.01

132 GALLEY EXHAUST FAN 120V 1.27 0.95 0.50 0.47 0.50 0.47 0.50 0.47 0.20 0.19 0.50 0.47 0.50 0.47 0.50 0.47 0.20 0.19 0.50 0.47 0.20 0.19

133 CONDENSER UNIT 120V 0.25 0.19 0.50 0.09 0.50 0.09 0.50 0.09 0.20 0.04 0.50 0.09 0.50 0.09 0.50 0.09 0.20 0.04 0.50 0.09 0.20 0.04

TOTAL 7.13 4.31 3.57 5.20 2.67 4.31 3.57 5.20 3.49 5.20 3.49

134 WELDING RECEPTACLES - STERN 60 AMPS 120/240V - 11.52 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15 0.20 2.30 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15

135 DECK RECEPTACLE - 60 AMPS #1 (GFCI) 120/240V - 11.50 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15 0.20 2.30 0.10 1.15 0.10 1.15 0.10 1.15 0.10 1.15

136 DECK RECEPTACLE - 60 AMPS #2 (GFCI) 120/240V - 11.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

137 DECK RECEPTACLE - 60 AMPS #3 (GFCI) 120/240V - 11.50 0.10 1.15 0.10 1.15 0.00 0.00 0.00 0.00 0.10 1.15 0.20 2.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

138 DECK RECEPTACLE - 32 AMPS #1 (GFCI) 120/240V - 6.14 0.10 0.61 0.10 0.61 0.10 0.61 0.10 0.61 0.10 0.61 0.20 1.23 0.13 0.77 0.13 0.77 0.13 0.77 0.13 0.77

139 DECK RECEPTACLE - 32 AMPS #2 (GFCI) 120/240V - 6.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

140 DECK RECEPTACLE - 32 AMPS #3 (GFCI) 120/240V - 6.14 0.10 0.61 0.10 0.61 0.00 0.00 0.00 0.00 0.10 0.61 0.20 1.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

TOTAL 64.44 4.68 4.68 2.92 2.92 4.68 9.36 3.07 3.07 3.07 3.07

DECK LOAD PANEL - L5 (208/120VAC, 3PH, 4W)

HVAC POWER PANEL - L4 (208/120VAC, 3PH, 4W)

GEN. LIGHTING/RECEP. PANEL - L3 (208/120VAC, 3PH, 4W)

TAI-1240 USACE_150'x50'x10' CELRE CRANE BARGE MDC Project: 3265, Hull No: 866

07/05/2021

CONNECTED LOAD

LOAD DESCRIPTION SUMMER SUMMER SUMMERWINTER WINTERWINTER

USACE 3265 150FT CELRE CRANE BARGE AC LOAD ANALYSIS

OPERATION CONDITION 1 OPERATION CONDITION 2

SUMMER WINTER

OPERATION CONDITION 5OPERATION CONDITION 3

ITEM NO.

OPERATION CONDITION 4

SUMMER WINTER

141 Design & Service Margin (Exc. Spuds) 55.04 6.05 10.46 6.88 11.28 5.93 11.94 6.76 11.12 4.34 7.64

142 Total Load (Inc. Margin) 754.44 66.58 115.03 139.05 179.93 65.25 131.32 104.15 152.07 47.69 84.02

143 100 0 0.00 1 100.00 1 100.00 1 100.00 0 0.00 1 100.00 1 100.00 1 100.00 0 0.00 0 0.00

144 100 0 0.00 1 100.00 1 100.00 1 100.00 0 0.00 1 100.00 1 100.00 1 100.00 0 0.00 0 0.00

145 75 1 75.00 0 0.00 0 0.00 0 0.00 1 75.00 0 0.00 0 0.00 0 0.00 0 0.00 0 0.00

146 133 0 0.00 0 0.00 0 0.00 0 0.00 0 0.00 0 0.00 0 0.00 0 0.00 1 133.00 1 133.00

% 88.77% 57.52% 69.52% 89.97% 87.00% 65.66% 52.08% 76.03% 35.85% 63.17%

- 1 2 2 2 1 2 2 2 1 1

WINTER

Item No.

SUMMER WINTERWINTER

OPERATING CONDITION - 04

eKW

SUMMER WINTER WINTERSUMMER

OPERATING CONDITION - 03

SUMMER

SUMMARY

MARGIN SECTION

ELECTRIC LOAD PER GENSET

NO OF GENSET ON LOAD

10.0%

Power Source

GENSET # 1

GENSET # 2

Standalone Generator

Shore Power (Thomas & Betts DS2404MP000)

OPERATING CONDITION - 01 OPERATING CONDITION - 02 OPERATING CONDITION - 04

SUMMER

TAI-1240 USACE_150'x50'x10' CELRE CRANE BARGE MDC Project: 3265, Hull No: 866

07/05/2021