Attch #3 Revised Specs -Steel Sliding Doors -RFI 047.pdf
PDF 37 KB Posted
- Attached to
- Construct Corrosion Control Hangar Federal contract opportunity
- Solicitation number
- W50S8Z20B0001
About this file
This document provides details for a federal solicitation to award a firm fixed-price construction contract. The scope of work involves building a 16,000 square foot corrosion control hangar and concrete aircraft tow-lane at Kingsley Field Air National Guard Base in Klamath Falls, Oregon. Interested contractors must register in the System for Award Management and attend a pre-bid conference on December 12, 2019, with questions due by December 19, 2019. The bid opening is January 6, 2020, and contract duration is 365 calendar days from notice to proceed. The project is set aside 100% for small businesses under NAICS code 236210 with a $36.5 million size standard. Attention is directed to the limitations on subcontracting clause requiring the awardee to perform 15% of the contract cost with its own employees. Three brand-name items are specified as sole source procurements. The solicitation and plans will be available on the Federal Business Opportunities website requiring a Marketing Partner ID Number for access.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch # 2 - Sheet T-011 -RFI 040-41 Response.pdf | ||
| Attch #4 - Revised - Door hardware.pdf | ||
| SF30 Amendment #4.pdf | ||
| Corrosion Control Pre-Bid Minutes 12 Dec.pdf | ||
| SF30 Amendment #3.pdf | ||
| SF30 Amendment #2.pdf | ||
| SF30.pdf | ||
| Sign-In Sheet.pdf | ||
| JA Brand Name - Automated Logic_Redacted.pdf | ||
| 8 - Technology Systems.pdf | ||
| 7 - Electrical.pdf | ||
| 6 - Mechanical.pdf | ||
| 2 - Structural.pdf | ||
| W50S8Z20B0001.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 3.pdf | ||
| 1 - General and Civil.pdf | ||
| 4 - Fire Alarm and Fire Sprinkler.pdf | ||
| 5 - Plumbing.pdf | ||
| JA Brand Name - Advantor (1)_Redacted.pdf | ||
| 3 - Architectural.pdf | ||
| JA Brand Name - Monaco Fire Alarm_Redacted.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 1.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 2.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Kingsley Field ANG Base, Klamath Falls Type B3 Revised Bid Submittal Construct Corrosion Control Hangar 04 October 2019
SECTION 08 34 16.10
STEEL SLIDING HANGAR DOORS
05/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 325 (2017) Steel Construction Manual
AISC 360 (2016) Specification for Structural Steel Buildings
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI SG03-3 (2002; Suppl 2001-2004; R 2008) Cold-Formed Steel Design Manual Set
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2017) Minimum Design Loads for Buildings and Other Structures
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2019) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A1011/A1011M (2018a) Standard Specification for Steel Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, SECTION 08 34 16.10 Page 1
High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA MG 1 (2018) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
NFPA 220 (2018) Standard on Types of Building Construction
NFPA 409 (2016; ERTA 2016) Standard on Aircraft Hangars
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 1-200-01 (2016; with Change 2, 2018) DoD Building Code (General Building Requirements)
UFC 3-301-01 (2013; with Change 4, 2018) Structural Engineering
UNDERWRITERS LABORATORIES (UL)
UL 506 (2017) UL Standard for Safety Specialty Transformers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval.for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability
SECTION 08 34 16.10 Page 2 eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Manufacturer's Qualifications; G Installer's Qualifications; G
SD-02 Shop Drawings sealed by the Door Manufacturer's Registered Professional Engineer
Hangar doors; G
Submit the door manufacturer's complete schematic wiring diagram, field wiring diagram, and a complete physical location drawing showing the location of controls with the runs of conduit, size of conduit, number and size of wires in each conduit, location of junction boxes, and full details of control mountings.
Submit drawings showing details of construction, installation, and operation; size, shapes, and thickness of materials; joints and connections; reinforcing; hardware; mechanical devices;
electrical devices; and design and detail data for work of other trades affected by hangar doors.
SD-05 Design Data sealed by the Door Manufacturer's Registered Professional Engineer
Hangar doors; G
Submit design drawings and structural, mechanical, and "U" value calculations.
SD-10 Operation and Maintenance Data
Hangar doors, Data Package 2; G
Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Include wiring and control diagrams.
1.3 DESIGN REQUIREMENTS
1.3.1 Door Design and Components
The Steel sliding hangar doors and components dictated in the construction documents are representative of a commercially-available door. Design and fabricate the door to fit within the space allocated and in accordance with the criteria specified herein. Design doors to operate properly without binding, interference, or damage to weather stripping or the adjacent structure. Door must be of limited combustible construction in accordance with NFPA 220 and NFPA 409.
Submit Calculations sealed by the door manufacturer's registered professional engineer for review.
1.3.1.1 Steel Door Components
Design all supporting, steel bracing and framing steel members in
SECTION 08 34 16.10 Page 3 accordance with the specified loads and the requirements of AISC 325 and AISC 360. Design all cold formed steel in accordance with AISI SG03-3.
Weld steel in accordance with the AWS D1.1/D1.1M Standards.
1.3.2 Loads
Design the door for the loads in accordance with UFC 1-200-01, UFC 3-301-01 and all other applicable criteria.
1.3.2.1 Wind Loads
In the closed position, design doors and all components to withstand the wind pressures indicated by the Engineer of Record. Design all door components to withstand both the highest positive and negative pressures based on actual tributary area from the wind load indicated. In addition, design doors and all components to be operational during wind events which cause a positive or negative service load pressure of 15 psf psf on the surface of the door.
1.3.3 Deflections
For any door member, the deflection due to design wind load shall not exceed the member's length divided by 120.
Design Doors as a system to withstand the upward and downward deflections of the door header structure.
1.3.4 Connections
Design connections at top and bottom guide rails to withstand both the positive and negative design wind pressures. Design for an inward and outward seismic force according to the requirements for exterior nonstructural wall elements and connections in ASCE 7. The governing force (wind or seismic) must be concurrent with the door self-weight and must be factored according to ASCE 7 load combinations.
1.3.5 Cold-Formed Steel Members
Cold-formed steel main members and girts shall be not less than 1/4 inch thick.
1.4 QUALITY ASSURANCE
1.4.1 Manufacturer's Qualifications
Use a steel sliding hangar door product from a manufacturer who is regularly engaged in the design, fabrication, erection, and service of steel sliding hangar doors of type and size required for this project. The manufacturer shall have at least 5 years of similar steel sliding hangar door design experience. Similar doors must have comparable function and design including size, configuration, type of use, retractable or moving elements, safety features, controls, and other key engineering elements as the door being specified. It is acceptable to show that a series of similar doors collectively meet all comparable elements to the door being specified, although not necessarily individually. Manufacturer must submit written evidence on similar past door designs and installations listing the name, location, contact information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation. Only manufacturers who can submit this evidence
SECTION 08 34 16.10 Page 4 of actual installations where the products have proven practical, durable, and require a minimum of maintenance, will be qualified under this specification.
1.4.2 Installer's Qualifications
Installation of the door(s) shall be supervised by a manufacturer's representative and shall be in accordance with approved shop drawings.
Installers shall be skilled and experienced in the erection of steel sliding hangar doors of the type specified herein. Installers must submit written evidence of similar past door installations listing the name, locations, contact information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation.
1.4.3 Warranty
The door manufacturer shall provide a three-year warranty for all mechanical and electrical components against defects in material and workmanship beginning on the date of Project Acceptance.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials which are not shop installed on the doors in original rolls, packages, containers, boxes, or crates bearing the manufacturer's name, brand, and model number. Store materials and equipment in dry locations with adequate ventilation, free from dust and water, and so as to permit access for inspection and handling. Handle doors carefully to prevent damage. Remove damaged items that cannot be restored to like-new condition and provide new items.
PART 2 PRODUCTS
2.1 HANGAR DOORS
2.1.1 Structural Steel
AISC 360 and ASTM A36/A36M.
2.1.2 Formed Steel
AISI SG03-3.
2.1.3 Galvanized Steel
Hot dipped galvanized frames in accordance with ASTM A123/A123M.
2.1.4 Sheet Steel
ASTM A1011/A1011M hot-rolled steel sheet, commercial quality, ASTM A1008/A1008M cold-rolled steel sheet, commercial quality.
2.1.5 Galvanized Sheet Steel
ASTM A653/A653M, coating designation G 90 galvanized steel sheet, commercial quality.
SECTION 08 34 16.10 Page 5
2.1.6 Exterior Covering
2.1.7 Interior Covering
Flat liner sheets, not thinner than 16 gage.
Preformed metal siding is specified in Section 07 42 63 FABRICATED WALL PANEL ASSEMBLIES with factory finish equal to Kynar 500 PVDF fluoropolymer.
2.1.8 Insulation
Provide insulation that: a) Contains no asbestos; b) Is permanently secured in place behind the exterior covering; and c) Has a flame spread rating of 75 or less and a smoke-developed rating of 100 or less when tested in accordance with ASTM E84. Do not use cellular plastics as exposed finish material. The doors shall have an air-to-air "U" value matching the insulate panels of the PEMB and a sound transmission class (STC) of not less than 35db.
2.1.9 Hardware
Provide hangar door hardware to accommodate actual dead loads plus wind loads specified. Provide top guide rollers, bottom wheels, interleaf bumpers, tractor pulls, track cleaners, and top bumpers as required for a complete and operational installation.
2.1.9.1 Wheel Assemblies
Bottom wheels shall be of steel plate or cast steel, having a minimum tread diameter as required for the actual wheel loading. Where the height-to-width ratio of the door leaf exceeds three, wheel assemblies shall be vertically adjustable. Construct wheel assemblies to permit removal of the wheel without removing the door leaf from its position on the rail.
a. Treads: Machine wheel treads concentric with bearing seats. The clear distance between flanges shall not exceed the width of the rail by more than 1/8 inch at the tread nor more than 1/4 inch at the edge of the flange. Machine internal bearing seats accurately for a press fit.
Heat treat wheels 18 inches or greater in diameter to obtain a rim hardness of 320 Brinnel.
b. Wheel bearings: Provide tapered roller or spherical bearings, either internal or cartridge type, arranged so that both horizontal and vertical loads shall be transferred to the rail only through the bearing. Bearings shall be tightly sealed and equipped with high-pressure grease fittings.
2.1.9.2 Fixed Pancake Top Guide Rollers
Horizontal type; each with single or double steel rollers of a suitable diameter and thickness for satisfactory performance under the designated load conditions and top guide system used. Provide permanently lubricated bearings. Rollers shall be stainless steel.
2.1.9.3 Vertical Floating Head Top Guide Rollers
Provide top-roller assemblies to:
SECTION 08 34 16.10 Page 6
a. Move up and down within the specified live load positive and negative deflection of the roof in the vicinity of the door opening;
b. Allow easy removal through the top of the guide system; and
c. Include both horizontal and vertical rollers built into a frame which is connected in such a manner as to transmit the specified wind loads from the door to the hangar structure and to prevent disengagement of the door from the top guide.
Rollers shall be stainless steel.
2.1.10 Personnel Doors
The hangar door manufacturer shall provide structural frames and electrical interlock for personnel doors.
2.1.10.1 Doors and Frames
Specified in Section 08 11 13 STEEL DOORS AND FRAMES.
2.1.10.2 Hardware for Personnel Doors
Specified in Section 08 71 00 DOOR HARDWARE.
2.1.10.3 Electrical Interlock
Provide each personnel door with an electrical interlock switch to prevent motor operation of the leaf or group in which it is located when the personnel door is open. Provide an identified indicator light at each door leaf control station indicating when the personnel door is in the open position.
2.1.11 Weather Stripping
Provide adjustable and readily replaceable material. Provide as indicated on vertical edges, sills, and heads to afford a weathertight installation.
2.1.11.1 Neoprene
Use flap-type, two-ply, cloth-inserted neoprene or extruded, double flap, single or dual opposed solid neoprene material on vertical edges and sills. The two-ply material shall have a minimum thickness of 1/8 inch and shall be retained continuously for its full length and secured with rust-resistant fasteners 12 inches o.c. Extruded weather stripping with heavy center section shall be attached at 12 inches o.c., but continuous bar may be omitted. Clearance between metal parts on vertical edges of leaves and between leaves and jambs which are to be weather-stripped shall be as indicated.
2.1.11.2 Metallic
Form head weather stripping material between each leaf and the top guide system of not thinner than 18 gage galvanized sheet steel or flap-type, cloth-inserted neoprene, as indicated.
2.1.11.3 Hanging Head Flashing
Provide with the top guide system specified in Section 05 12 00 STRUCTURAL
SECTION 08 34 16.10 Page 7
STEEL. Provide cloth-inserted neoprene weathering fastened to top of door leaves to engage the head flashing when doors are closed.
2.1.12 Fasteners
Hot dipped galvanized.
2.1.13 Sealant
Single-component or multicomponent elastomeric type conforming to ASTM C920, Type S or M, Grade NS, Class 12.5, Use NT. Provide a sealant that has been tested on the types of substrate to which it will be applied.
2.1.14 Primer
Zinc-Rich Epoxy Primer per Section 09 90 00 PAINTS AND COATINGS.
2.1.15 Starters
Provide magnetic reversing starters in NEMA ICS 6, Type 12 enclosures equipped with access door-controlled, fused safety disconnect switches.
Starters shall be factory wired with overload and undervoltage protection, mechanical and electrical interlocks, auxiliary contacts, relays and timing devices as required, control circuit transformers, and a numbered terminal strip. The control circuit transformer shall reduce the voltage in the control circuits to 120 volts or less, and shall conform to UL 506.
2.1.16 Electrical
Provide conduit, wire, flexible cables, boxes, devices, and accessories under Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. If permanent electrical power is not available when door installation is complete, provide temporary power in accordance with distribution system requirements in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM, for testing and adjusting the doors.
2.2 FABRICATION
2.2.1 Doors
2.2.1.1 Frames and Framing
Door leaves shall be of welded or bolted construction. Joints shall develop 100 percent of the strength of the framing members. Vertical members shall be continuous throughout the height of the door. When required, prepare splices to facilitate field assembly in accordance with standard practice. Frames and framing members shall be true to dimensions and square in all directions; no leaf shall be bowed, warped, or out of line in the vertical or horizontal plane of the door opening by more than 1/8 inch in 20 feet. Provide diagonal bracing so that the completed leaf assembly will be braced to withstand shipping, assembly, and operational loads. Exposed welds and welds which interfere with the installation of various parts such as cover sheets shall be ground smooth. Prepare, prime, and coat structural framing and miscellaneous steel as specified in paragraph FINISHES.
2.2.1.2 Exterior Covering and Interior Liner Sheets
Flat sheets shall be fastened to the frame either by edge welding, plug
SECTION 08 34 16.10 Page 8 welding, or threaded fasteners 12 inches o.c. Where flat sheets are attached as either exterior covering or interior liner sheets, the clear unsupported area shall not exceed 25 square feet. Make edges of exterior sheets weathertight with sealant.
2.2.2 Locking Devices
Do not provide locking devices on motor-operated hangar doors.
2.2.3 Tractor Pulls
Provide tractor pulls so that leaves can be towed by a tractor or similar equipment in the event of power failure. The tractor pull shall be designed for drive force to tow door or 5000 pounds whichever is greater.
Minimum thickness steel plate shall be 3/8 inch.
2.2.4 Track Cleaners
Provide a device to clear debris from the rail head and wheel flange grooves as the leaf is moved.
2.2.5 Insulation
Secure insulation to doors with clips, studs, or adhesive. Protect insulation within 8 feet of floor with steel liner sheets secured to framing 12 inches o.c.. at edges with hot dipped galvanized, self-tapping screws.
2.2.6 Cable System for Group Doors
The minimum size for the cable which interconnects the leaves shall be 3/8 inch; the cables shall be improved plow steel with lubricated hemp centers or wire rope cores. Sheaves over which the cables operate shall have a diameter of at least 18 cable diameters and either sealed ball-or roller-type bearings or graphite bronze bearings of a sufficient capacity for the operating loads. Grease fittings shall be provided for the sheave bearings unless permanently lubricated bearings are used.
2.3 OPERATION
2.3.1 Hangar Door Types
Hangar doors shall be unidirectional biparting as indicated.
2.3.1.1 Individually Operated Doors
Each door leaf shall have a separate, traction-drive operating unit driving one or more of the bottom wheels. Each leaf shall have a motor-mounted, spring-set, solenoid-released motor brake. Each leaf shall move independently of the other leaves. Provide doors that require operating personnel to walk with the leaf as it moves.
2.3.1.2 Floating Group Doors
Each group of three or more leaves shall have a separate, traction-drive operating unit located in each end leaf of the floating group doors, which drives one or more wheels of the end leaf, and a wraparound cable system on the intermediate leaves coupled to each end leaf; or an interleaf pickup system. Movement of either end leaf shall allow stacking and unstacking of the other end and shall also allow intermediate leaves to move in concert.
SECTION 08 34 16.10 Page 9
The group of leaves traveling abreast may then be positioned as desired in the opening. Provide necessary cables, fittings, cable sheaves, housings, guards, pickups, brackets, anchors, and miscellaneous hardware.
2.3.1.3 Anchored Group Doors
Each group of leaves shall have a traction-drive operating unit located in the lead leaf of the group and driving one or more wheels of the lead leaf.
The leaves in each group shall start to move at the same time and arrive at their fully open or fully closed positions simultaneously. Provide necessary cables, fittings, sheaves, housings, guards, pickups, brackets, anchors, and miscellaneous hardware.
2.3.2 Operating Units
Each operating unit shall move its lead leaf at a speed of approximately 60 feet per minute at zero wind load conditions and to be operable up to and including a maximum wind load of 15 pounds per square foot. The operating units shall consist of either a separate motor and gear reducer or a gearhead motor, high-speed shaft brake, and necessary roller chains and sprockets. The systems shall be provided with overload protection for the drive units and a means for emergency tractor towing operation.
a. Motors shall be NEMA MG 1, high-starting torque, reversible type with sufficient horsepower and torque output to operate the leaves in either direction from any position under zero wind load conditions at not more than 75 percent of their rated capacity. Motors shall operate on current voltage of the characteristics indicated at not more that 3600 1800 rpm. Motor enclosures shall be drip-proof type or NEMA totally-enclosed, fan-cooled (TEFC) totally-enclosed, wash-down (TEWD) type. Motors shall have a minimum service factor of 1.2.
b. Gear reduction units shall allow a reversal of effort through the gears without damage to the units.
c. Operating mechanisms shall be covered on the interior of the leaf by a hinged 16 gage flat steel cover.
2.3.3 Braking Systems
Braking systems shall be designed to ensure stoppage of the leaves under normal, dry rail conditions within the safety edge overtravel limit. The braking systems shall be either a magnetic, spring-set, solenoid-released brake or hydraulic type. Provide a hand release to release the brake when it becomes necessary to move the leaf with an outside force. The hand release shall be an automatic reset type so that the brake will be operable during subsequent electrical operation of the door.
2.3.4 Controls
Doors shall be controlled by constant pressure push buttons mounted on the door leaves. Removing pressure from the button shall stop the movement of the leaves. The control equipment shall conform to NEMA ICS 1 and NEMA ICS 2. Interior push buttons shall be mushroom head type, mounted in heavy-duty, oil-tight enclosures conforming to NEMA ICS 6, Type 13, except that enclosure for reversing starter with disconnect switch shall be Type 12.
SECTION 08 34 16.10 Page 10
2.3.4.1 Push Buttons for Individually Operated Doors
The leaves mounted on the outer rails shall have the push buttons mounted on the exterior face; the leaves on the inner rails shall have the buttons mounted on the interior face; and the leaves on the middle rails shall have the buttons mounted on both the exterior and interior faces. The button at each edge of a leaf shall allow the leaf to travel with that edge as the leading edge only. The controls shall not be reversible. Location of each control button shall be as indicated.
2.3.4.2 Push Buttons for Floating Group Doors
Each group shall be controlled by push button stations mounted at each end of each group of leaves. Stations shall contain one button for stacking the leaves, one button for unstacking the leaves, and a third button for moving the leaves in a group. The leaves mounted on the outer rail shall have the push buttons mounted on the exterior face. The leaves mounted on the inner rail shall have the push buttons mounted on the interior face.
Location of each control station shall be shown on manufacturer's drawings.
2.3.4.3 Push Buttons for Anchored Group Doors
Each group shall be controlled by a two-button push button station marked "OPEN" and "CLOSE" mounted near the inside leading edge of the lead leaf.
2.3.5 Limit Switches
Provide limit switches to prevent overtravel and bumping. Safety edges shall not be used as limit switches.
2.3.5.1 Lever Arm Type Limit Switches
Provide for anchored group doors to stop the travel of each group in the fully open and fully closed positions. The limit switches shall be:
a. Positive acting, snap action, lever arm type with actuating cams designed with sufficient overtravel to permit the group to come to a complete stop without overtraveling the limit switches.
b. Mounted on the leaves, and the actuating cams mounted either on the top guides or on adjacent door leaves.
2.3.6 Safety Edges
Provide fail-safe safety edges on each edge of each leaf of individually operated doors each leading and trailing edge of drive leaves for floating group doors the leading edge of the drive leaf of anchored group doors from one inch above the floor to the top of the door leaf. For leaves 12 inches thick (including siding) or less, provide a single run of safety edge the full width of door. For leaves over 12 inches thick (including siding,) provide a double run of safety edge spaced to provide the maximum degree of safety in stopping the leaves. For leaves over 12 inches thick (including siding) provide a double run of safety edges on the outer edge of each side of door leaf covering no less than 80 percent of leaf.
a. Design: Provide safety edges to provide a minimum of 3-1/2 inches of overtravel after actuation until solid resistance is met and door motion comes to a complete stop. If door requires more than 3-1/2 inches to come to a complete stop, provide additional overtravel built
SECTION 08 34 16.10 Page 11