7 - Electrical.pdf
PDF 13 MB Posted
- Attached to
- Construct Corrosion Control Hangar Federal contract opportunity
- Solicitation number
- W50S8Z20B0001
About this file
This document provides details for a federal solicitation seeking construction services. The Oregon Air National Guard is soliciting bids for a firm fixed-price contract to construct a corrosion control hangar and support facilities at Kingsley Field in Klamath Falls, Oregon. The project scope includes construction of a pre-engineered metal hangar and adjacent support spaces totaling approximately 16,000 square feet as well as an aircraft tow-lane. The solicitation will include a base bid and four options. The performance period is 365 calendar days from notice to proceed. This opportunity is set aside exclusively for small businesses with a NAICS code of 236210 and size standard of $36.5 million. Bids are due on January 6, 2020. The pre-bid conference will be held on December 12, 2019 and site visits will follow. The Department of the Army is the contracting agency.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch #3 Revised Specs -Steel Sliding Doors -RFI 047.pdf | ||
| Attch # 2 - Sheet T-011 -RFI 040-41 Response.pdf | ||
| Attch #4 - Revised - Door hardware.pdf | ||
| SF30 Amendment #4.pdf | ||
| Corrosion Control Pre-Bid Minutes 12 Dec.pdf | ||
| SF30 Amendment #3.pdf | ||
| SF30 Amendment #2.pdf | ||
| SF30.pdf | ||
| Sign-In Sheet.pdf | ||
| JA Brand Name - Automated Logic_Redacted.pdf | ||
| 8 - Technology Systems.pdf | ||
| 6 - Mechanical.pdf | ||
| 2 - Structural.pdf | ||
| W50S8Z20B0001.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 3.pdf | ||
| 1 - General and Civil.pdf | ||
| 4 - Fire Alarm and Fire Sprinkler.pdf | ||
| 5 - Plumbing.pdf | ||
| JA Brand Name - Advantor (1)_Redacted.pdf | ||
| 3 - Architectural.pdf | ||
| JA Brand Name - Monaco Fire Alarm_Redacted.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 1.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 2.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LUMINAIRE SYMBOLS MeadELECTRICAL ABBREVIATIONS GENERAL NOTES:GENERAL SYMBOLS COPPER FEEDER SCHEDULE 0 RECESSED LUMINAIRE CONDUCTOR SIZES (AWG or KCMIL)NO. OF
SETS
CONDUIT lunt#/E-### DETAIL NUMBER / SHEET NUMBER
KEYED NOTE, USED TO DESCRIBE ADDITIONAL
INFORMATION OF WORK REQUIRED, SPECIFIC TO
THE SHEET AND/OR DETAIL IT IS SHOWN WITH.
NEMA 3R RATING
NEMA 4X RATING
AMPERES
ARCHITECT/ENGINEER
ABOVE ACCESSIBLE CEILING
AIR COOLED CONDENSING UNIT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
ALTERNATE
AIRCRAFT PROCESS EQUIPMENT
AUTOMATIC TRANSFER SWITCH
BUILDING
BREAKER
CONDUIT
CIRCUIT BREAKER
CIRCULATION FAN
CHILLER
CHILLED WATER PUMP
CIRCUIT
CIRCULATION PUMP
COMPUTER ROOM AIR CONDITIONER
CONDENSATION RETURN
CABINET UNIT HEATER
DROP CORD
DIGITAL CONTROL PANEL
DUCT HEATER
DISCONNECT
DOOR OPERATOR
DRAWING
ELECTRICAL-TO-OPTICAL CONVERTER
ELECTRICAL CONTRACTOR
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
EMERGENCY
ELECTRICAL METALLIC TUBING
EQUIPMENT SUPPLIER
EXISTING TO REMAIN
ELECTRICAL WATER COOLER
ELECTRICAL WATER HEATER
FUSED
FIRE ALARM
FAN COIL UNIT
GENERAL CONTRACTOR
GARBAGE DISPOSAL
GROUND FAULT INTERRUPTER
GROUND
GAS WATER HEATER
HAND DRYER
HORSEPOWER
HEATING, VENTILATION, AIR CONDITIONING
HOT WATER BOILER
HOT WATER PUMP
INSTANTANEOUS ELECTRIC WATER HEATER
INFRARED HEATER
INTERMEDIATE METALLIC CONDUIT
INSTANTANEOUS WATER HEATER
JUNCTION BOX
MAKE-UP AIR UNIT
MAXIMUM
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MAIN DISTRIBUTION FRAME
MAIN DISTRIBUTION PANEL
MINIMUM
MASS NOTIFICATION SYSTEM
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
NOT IN CONTRACT
NIGHT LIGHT
NIGHT LIGHT AND EMERGENCY LIGHT
NOT TO SCALE
ON CENTER
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
PHASE
PANEL
POLYVINYLCHLORIDE
RADIANT CEILING PANEL
RECEPTACLE
REFRIGERATOR
REQUIRED
RETURN FAN
RIGID GALVANIZED STEEL CONDUIT
MAY ALSO BE REFERENCED AS RMC OR GRC
RIGID METAL CONDUIT
ROOF TOP UNIT
SOLID NEUTRAL
SERVICE ENTRANCE
SECURITY PANEL
SUPPLY FAN
SUMP PUMP
STAINLESS STEEL
SWITCH
TO BE REMOVED
TEMPERATURE CONTROL PANEL
TO FLOOR ABOVE
TO FLOOR BELOW
TYPICAL
UNIT COOLER
UNDERGROUND
UNIT HEATER
UNLESS NOTED OTHERWISE
UNIT VENTILATER
VOLTS
VARIABLE FREQUENCY DRIVE
VERSUS
WATTS
WATER COOLED CONDENSER
WATER HEATER
WET LOCATION LISTED
WEATHERPROOF
TRANSFORMER
EXPLOSION PROOF
REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS
PLANS, INFORMATION AND NOTES.
3R 1. MARK AMPACITY0 SIZEPHASE NEUTRAL EQ GND ISO GND4XRECESSED TROFFER
9.111111 A 3-# 12 1 -# 1220 20 1 1/2'RECESSED LINEAR THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE
DETAILS OF WORK, VERIFY DIMENSIONS IN THE FIELD,
AND ADVISE THE ARCHITECT/ENGINEER OF ANY
DISCREPANCY BEFORE PERFORMING ANY WORK.
2.A/E Mead & Hunt, Inc.
9600 NE Cascades Parkway
Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
20Y 1 3-# 12 1 -# 12 1 -# 12 1/2'20O SURFACE ROUND LUMINAIRE AAC
3-# 10 1 -# 10 1/2'25 25 1ACCUh 1 SURFACE INDUSTRIAL LINE TYPE KEY 25Y 1 3-# 10 1 -# 10 1 -# 10 1/2'25AFFh 1 PENDANT INDUSTRIAL THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE
WITH THE ABA (AMERICANS WITH BARRIERS ACT).
3.AFG 1 3-# 10 1 -# 10 3/4'30 302 NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
WALL BRACKET AHU 3-# 10 1 -# 10 1 -# 1030Y 30 1 3/4'
ALT REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED
WALLS AND FLOORS. MAKE RATED PENETRATIONS AS
REQUIRED. SEAL ALL RATED PENETRATIONS AS
IDENTIFIED IN DIVISION 1 REQUIREMENTS.
4.CEILING MOUNTED EXIT SIGN 1 3 - # 8 1 -# 10 3/4'35 35APE
3 - # 8 1 - # 8 1 -# 1035Y 35 1 3/4'ATSWALL MOUNTED EXIT SIGN
BLDG
BRKR
TETRATECHIt40 40 1 3 - # 8 1 -# 10 3/4'ONE-LINE EQUIPMENT ENCLOSURE<- ARROW DENOTES EXIT SIGN CHEVRON
1 - # 8 1 -# 1040Y 40 1 3 - # 8 1FLUSH MOUNT ALL TOGGLE SWITCHES AND
RECEPTACLES AT HEIGHTS ABOVE FINISHED FLOOR AS
SHOWN IN THE DEVICE MOUNTING HEIGHT DETAIL,
EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE
SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED
EXPOSED.
5.
EMERGENCY BATTERY UNIT C www. tetratech. comPANEL DIVISION LINES
1 -# 1045 45 1 3 - # 6 3/4'CB 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
EEMERGENCY SHADING MODIFIER
LUMINAIRE CIRCUITRY & CONTROL KEY:
LUMINAIRE TYPE
SITE UNDERGROUND ELECTRIC 45Y 45 1 3 - # 6 1 - # 6 1 -# 10 1CF
3 - # 6 1 -# 1050 50 1 1CH
CHWP 50Y 1 3 - # 6 1 - # 6 1 -# 10 1-1/4'50
CKTSERVICE & DISTRIBUTION SYMBOLS CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT
IDENTIFICATION. CIRCUITING SHALL AGREE WITH
NUMBERING ON THE PANEL SCHEDULES PROVIDED.
BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE
BETWEEN EACH PHASE. COMMON NEUTRALS MAY NOT BE
USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON
PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.
6. 1 -# 1060 60 1 3 - # 4 1
CP
60Y 1 3 - # 4 1 - # 4 1 -# 10 1-1/4'60LOWER CASE LETTER INDICATES SWITCHLEG CONTROL
"R" INDICATES LIGHTING CONTROL PANEL
REFER TO LIGHTING CONTROL PANEL SCHEDULE
CRAC
1 3 - # 4 1 - # 8 1-1/4'70 70CRPGROUND ACCESS WELL
CUH 1 - # 4 1 - # 870 Y 70 1 3 - # 4 1-1/4'GROUND ROD
DCNUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER 1 3 - # 3 1 - # 8 1-1/4'80 80STATIC GROUND RECEPTACLE DDC
1 - # 3 1 - # 880Y 80 1 3 - # 3 1-1/4'LUMINAIRE CONTROL SYMBOLS DH 7. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES
WILL BE RUN IN SEPARATE RACEWAY FROM ALL OTHER
CIRCUITS.
A LIGHTNING AIR TERMINAL © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
100 100 1 3 - # 1 1 - # 8 1-1/2'DISC
DO 1 -# 1 1 - # 8100Y 100 1 3-# 1 1-1/2'GROUNDING CONDUCTOROCCUPANCY SENSOR CEILING MOUNT (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
ELECTRONIC TIME CLOCK
PHOTO ELECTRIC CONTROL (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
LOW VOLTAGE SWITCH
* DENOTES SWITCH NAME, SEE LIGHTING
CONTROL PANEL & SWITCH SCHEDULE.
SINGLE POLE SWITCH
SWITCH NOTATIONS:
DENOTES 3-WAY SWITCH
DENOTES 4-WAY SWITCH
DENOTES WALL BOX DIMMER SWITCH
WSX DENOTES OCCUPANCY SENSOR
(X REPRESENTS SCHEDULE DESIGNATION)
DENOTES PILOT SWITCH
DENOTES TIMER SWITCH
DWG 1 - # 6110 110 1 3-# 1 1-1/2'8. A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE
INSTALLED WITH CIRCUIT CONDUCTORS TO ALL
RECEPTACLES.
PANELBOARD E/O
110Y 110 1 3 - # 1 1 -# 1 1 - # 6 2EC
3-# 1/0 1 - # 6I~pe1 125 125 1 1-1/2'ECB
9. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE
CEILING, ETC. UNLESS OTHERWISE INDICATED ON THE
PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS, AND STORAGE ROOMS WITHOUT
CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.
EF 125Y 125 1 3-# 1/0 1 - # 1/0 1 - # 6 2
EM 1 - # 6150 150 1 3-# 1/0 1-1/2'
EMT
3-# 1/0 1 - # 1/0 1 - # 6150Y 150 1 2
ESs 175 175 1 3 - # 2/0 1 - # 6 2ETR
10. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED
WALLS SHALL BE OFFSET A MINIMUM OF 6"
HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED.
3 - # 2/0 1 - # 2/0 1 - # 6175Y 175 1 2EWC
EWH
1 3 - # 3/0 1 - # 6200 200 24
FD 3 - # 3/0 1 - # 3/0 1 - # 6200Y 200 1 2-1/2'
FA
1 3 - # 4/0 1 - # 4225 225 2FCU 11. COORDINATE AND CO-LOCATE WALL MOUNTED
RECEPTACLE LOCATIONS WITH TECHNOLOGY
(VOICE/DATA, ETC) OUTLETS SHOWN ON THE T-SERIES
DRAWINGS UNLESS OTHERWISE NOTED, EACH
TECHNOLOGY OUTLET SHALL BE LOCATED WITHIN 24"OF
ITS ASSOCIATED RECEPTACLE. ASSOCIATED RECEPTACLE
SHALL BE DEFINED AS THE RECEPTACLE NEAREST THE
LOCATION OF, AND AT THE SAME HEIGHT AS,THE
TECHNOLOGY OUTLET WHEN MULTIPLE RECEPTACLES
ARE SHOWN ON A WALL.
P 225Y 1 3 - # 4/0 1 - # 4/0 1 - # 4 2-1/2'225GC
T
GD 1 - #4250 250 1 3-250 2-1/2'
GFI 250Y 1 1 -250 1 - #4250 3-250 3'
GND
1 - # 4300 300 1 3-350 3'GWH
300Y 1 1 -350 1 - # 4 3-1/2'300 3-350HDRECEPTACLE SYMBOLS HP 1 - # 3350 350 1 3-500 3'
HVAC 1 - # 3350Y 350 1 3-500 1 -500 3-1/2’
HWBDUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT 12. DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS
(EWC) SHALL BE CONCEALED BEHIND WATER COOLER
ACCESS PLATE OR BE DIRECTLY BELOW AND CENTERED
ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
1 1 - # 3380 380 3-500 3'HWP
IEWHDOUBLE DUPLEX RECEPTACLE 1 - # 3380Y 380 1 3-500 1 -500 3-1/2’ o400 1 1 - # 3IH 400 3-500 3'ABOVE COUNTER DUPLEX RECEPTACLE IMC 1 - # 3400Y 400 1 3-500 1 -500 3-1/2’-e COSIMPLEX RECEPTACLE IWH CO13. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR
FURNITURE AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS AND REVIEWED
SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL
ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR
EQUIPMENT.
450 3 - # 4/0 1 - # 2450 2 2 oJ-BOX O450Y 3 - # 4/0 1 - # 4/0 1 - # 2 2-1/2'450 2 CDMAURECEPTACLE NOTATIONS:
DENOTES DEDICATED OUTLETS
DENOTES ELECTRIC WATER COOLER OUTLETS
DENOTES GROUND FAULT INTERRUPTER OUTLETS
1 - # 2500 500 2 3-250 2-1/2'MAX a:a: <j>
MC 500Y 1 -250 1 - # 2500 2 3-250 3’EWC
GFCI
O'a: <
MCC 1 -# 1600 600 2 3-350 3’ oMDF
600Y 1 -350 1 -# 1600 2 3-350 3’ O CDWP DENOTES WEATHER PROOF OUTLETS MDP
CO1 - # 1/0700 700 2 3-500 3’14. ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT
SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND
MECHANICAL EQUIPMENT. ALL MOUNTING OF
ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON
EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL
BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
MIN.X1 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 OUTLETS
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 OUTLETS o Ct3MNS 1 - # 1/0700Y 700 2 3-500 1 -500 3-1/2'X2
MTD
1 - # 1/0800 800 2 3-500 3’
MTG
1 - # 1/0800Y 800 2 3-500 1 -500 3-1/2'MTS COo1000 1000 1 - # 2/03 3-400 3’NIC EMOTOR & EQUIPMENT CONNECTION
SYMBOLS
1 - # 2/0NL 1000Y 1000 3 3-400 1 -400 3-1/2' CO15. CONTRACTOR TO PROVIDE SUITABLE MECHANICAL
PROTECTION AROUND ALL CONDUITS STUBBED OUT
FROM FLOORS, WALLS OR CEILINGS DURING
CONSTRUCTION TO PREVENT BENDING OR DAMAGING OF
STUB OUTS DUE TO CARELESSNESS WITH
CONSTRUCTION EQUIPMENT.
NL/EL 1200 1200 4 1 - # 3/03-350 3’ oa:NTS 1200Y 1200 4 1 -350 1 - # 3/03-350 3’
OC "OCD orELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS, SIZED
PER NEC. COORDINATE REQUIREMENTS WITH CONTRACTOR
FURNISHING MOTOR OR EQUIPMENT. REFER TO
SPECIFICATIONS AND EQUIPMENT WIRING SCHEDULE FOR
ADDITIONAL WORK ASSOCIATED WITH MOTOR OR EQUIPMENT.
2500 2500 7 3-500 1 -350 3-1/2'OFCI
OFOI
CD
2500Y 1 - 500 1 -350 4’2500 7 3-500 COPH 16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE
REPAIRED TO MATCH EXISTING BY A QUALIFIED
CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR.
ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
FEEDER SCHEDULE NOTES:
THE SCHEDULE IS A SCHEDULE OF TYPICAL FEEDERS AND SOME OF THE SIZES
MAY NOT APPLY TO THIS PROJECT.
PNL CD
PVC 1. COVFD o oDdVARIABLE FREQUENCY MOTOR CONTROLLER RCP O)
RECPTNON-FUSIBLE DISCONNECT SWITCH o o oALL THE CONDUCTOR AMPACITIES ARE BASED ON TABLE 310.15(B)(16) OF THE
2017 NEC FOR COPPER CONDUCTOR TYPE THHN/THWN-2
2.REF
FUSIBLE DISCONNECT SWITCH REQ’D 17. DRAWINGS INDICATE THE EXTENT OF HAZARDOUS
LOCATIONS. INSTALLATION MEANS AND METHODS SHALL
BE SUITABLY RATED FOR THE ENVIRONMENT INDICATED
ON THE DRAWINGS.
s RF FEEDER SIZES SHOWN ON THE RISER DIAGRAM INDICATE FEEDER AMPACITIES
AND DO NOT NECESSARILY CORRESPOND TO THE CIRCUIT BREAKER AMPACITIES.
CERTAIN FEEDERS MAY BE SIZED FOR DERATION FACTORS AND/OR OVERSIZED
FOR VOLTAGE DROP PER NEC REQUIREMENTS.
3.MOTOR STARTING SWITCH WITH OVERLOADS ISSUEDMS RGSs 10/04/19 REVISED BID
DOCUMENTS
MOTOR STARTING SWITCH WITHOUT OVERLOADSMX RMC£ 18. ALL INTERLOCKING REQUIRED BY THE DRIVE
MANUFACTURER BETWEEN THE VARIABLE FREQUENCY
DRIVE AND THE DISCONNECT SWITCHES SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
RTUMTS MANUAL TRANSFER SWITCHEo S/No l?bl PR0fiENCLOSED CIRCUIT BREAKERc SE=3
SEC-PT3
CD 19. SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM
REQUIREMENTS FOR BUS BRACING AND DEVICE RATING.
ALL EQUIPMENT SHALL BE FULLY RATED UNLESS
SPECIFICALLY NOTED AS SERIES RATED.
SFE
SP
IC&ITssoo T3 sw=3 OREGON so/v/sf
EXPIRES:
x
TBR 20. EC SHALL REFER TO T-SERIES AND FA-SERIES SET OF
DOCUMENTS INCLUDED IN THIS BID PACKAGE FOR ALL
TELECOMMUNICATION AND FIRE ALARM WORK
ASSOCIATED WITH THIS PROJECT. EC SHALL INCLUDE IN
THIS BID ALL LABOR AND MATERIALS REQUIRED FOR THE
COMPLETE BOXES AND RACEWAY SYSTEMS FOR BOTH
TELECOMMUNICATION AND FIRE ALARM SYSTEMS (BOTH
NEW AND FUTURE). ALL CABLE TRAY, CONDUITS, BOXES
AND OUTLETS REQUIRED FOR TELECOMMUNICATION AND
FIRE ALARM SYSTEM INSTALLATION SHALL BE
COORDINATED WITH THE ASSOCIATED DRAWING SET AND
VERIFIED IN FIELD WITH TELECOMMUNICATION AND FIRE
ALARM CONTRACTORS PRIOR TO ROUGH-IN.
COORDINATE CONDUIT BETWEEN ALL SYSTEMS FORA
CLEAN INSTALLATION.
C
TCPo
I TFA
TFBo
CM
TYP
UCcr
UG
LU
UHo
I 3142200-121252.01 10/04/19
M&H NO.:
LU UNO DATE:
DESIGNED BY: JRH
KAS
o UV
CM
LO VCM DRAWN BY:
VFDCM IMRCHECKED BY:VSo o DO NOT SCALE DRAWINGSCM wCM wcc SHEET CONTENTS
CO NOTES, SYMBOLS &
ABBREVIATIONS
WH03
O WLo
WP>CD XFMR¥
XPo
SHEET NO.:
CL
CM
CO
E-001CO
o
CM
O
E o o c =5
"O E oo ■O =5 X c o
Ih» o
CM
LU
O i
LU
O
CM
LO
CM
CM
i O o
CM
CM
CO
O o
O
CL
CM
CD
CO
O
MeadPOWER GENERAL NOTES:
lunt1. ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL BE
SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND OUTSIDE OF
THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE ROUTED
BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT SHALL NOT BE
ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL BE ATTACHED TO
HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL SUPPORTS AS
REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN HANGAR 123
SHALL BE NEMA4X. COORDINATE ROUTING WITH OTHER TRADES. ALL
CONDUIT IN HANGAR 123 SHALL BE RMC.
PANEL 1/LB ^ PANEL 1/LC
UNLESS NOTED OTHERWISE
PANEL 1/LD ^x PANEL 1/LD
UNLESS NOTED OTHERWISE
x PANEL 1/LF
UNLESS NOTED OTHERWISE
<T Mead & Hunt, Inc.
9600 NE Cascades Parkway
Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
IUNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE
OFFICEI
@ CU-1 @ CU-219 9.304) 19
ft r112GFCI/WP GFCI/WP
€fftr5s 2. SEE DRAWINGS E-151 AND E-152 FOR AREA CLASSIFICATION ZONES.VES □<H>oooooooo29 1 111 REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU
LEAD-LINED WALLS.
3.□ ^25
9.301) TYP OF 4SW CUH72" TETRATECHIt1 1 "l
1 REFER TO E-603 FOR ELECTRICAL EQUIPMENT WIRING SCHEDULE.1 ' 4.u u u 27 2/LB-16.18
HP-3
25 31SW www. tetratech. com
BREAK ROOM KEYED NOTES29 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
(9.312)1‘113 3n n n ft l27 SW GFCI/WP
■ TT10 EC□ 9.301 ROUTE MECHANICAL EQUIPMENT BRANCH CIRCUITS UNDERGROUND
BETWEEN EQUIPMENT AND DISCONNECTS.
CU-1
CU-21 I UP OFFICE1HP-1
(9.337) 1/LF-23,251 3109|ft IGFCI/WP GFCI/WPftPANEL 1/LD 31 PROVIDE 200A, 3-POLE, 4-WIRE GENERATOR RECEPTACLE. COORDINATE
EXACT NEMA REQUIREMENTS WITH BASE PRIOR TO ORDERING.
9.302IIpar Viol i=<n>l'°r 11
<U>7(0) OHD
oT 1/LC-9 <u> til rrsf(0)
2/LE-9
OHD I GFCI46' 1 9 11i/lb-8 □i 391 /LB-1,3,5
BEAD
9.304 ELECTRICAL MAIN SERVICE CHASE. ELECTRICAL CHASE CONTINUES UP TO
BOTTOM OF ELECTRICAL ROOM ON THE EQUIPMENT FLOOR. CONDUITS TO
ENTER THE BOTTOM OF SERVICE SWITCHBOARD. COORDINATE
INSTALLATION WITH TELECOM SERVICE CONDUITS AND FOUNDATION WALL
OPENING.
I GFCIi SWPFT
EQUIPMENT
ROOM
1/LD-3939 1 1
^7 i 7^46 1 1
HD@MEN’S 91/LC-5
EEWS-1
/ 11 OIL ANALYSIS
ROOM
SW1107 PANEL 1/LB 1/LD-33 © Copyright 2018
This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
(9.312) 1 9X1I ft•fLi ft/ 108SW7!46' \ XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL
THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL
INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO
WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH
THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX
IN CMU WALL.
9.307 3 O tt>3. A
GFCI/WP^ EEWS-1
1/LF-28
GFCI 46’■ P/^INT MIXING
HibOM/STOR
6 22JAN Il 46"MEN'S
LOCKER
ROOM
37 ft9\/\ 1/LD-39
____ I I I GFCI 116 y PANEL 1/LF(ON ROOF) 126 G@PFT <H>\. A 13STORAGE115 3146”
4 , 9.312 RECEPTACLES DESIGNATED WITH 'SW' ARE CONTROLLED VIA OCCUPANCY
SENSOR. PROVIDE PLUG LOAD POWER PACK(S) ASSOCIATED WITH CEILING
MOUNTED OCCUPANCY SENSOR(S). REFER TO ASSOCIATED LIGHTING
PLANS FOR OCCUPANCY SENSOR TYPE AND LOCATION.
^6 n 115A W
II A Igfci , 2 —Ll-l'Q/ r * L 46" 13 1324 ^GFCI m WOMEN'SWOMEN'S
LOCKER
ROOM
1/LB-2 _
EEWS-1 (Ql
_ 1/LC-7
IQ) EEWS-1
22° d1 INSPECTION 1/LF-14.16 (3#10, 3/4"C.)
-0 L6-30R
^ PL-1
3 PL-2
9.313 PROVIDE 4” SQUARE BOX WITH 1" CONDUIT INSTALLED BETWEEN JUNCTION
BOX AND PANEL 1/LD FOR FUTURE. PROVIDE PULL STRING. JUNCTION BOX
INSTALLED AT 18”AFF. COORDINATE WITH MILLWORK CONTRACTOR.
1/LD-41 BAY
HALLWAYHDGFCI GFCI□ 10311813(§) BLAST @
1024 4PAINT 1 GFCI/WPGFCI FILM VIEWING
ROOM 5 9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER
FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS
REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR
WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE
ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.
46' 4 tBEAD BOOTH
ROOM
I □\GFCIPAINT BOOTH
GFCI^tr™r <H><
17 107 17 46"<H>e125 LAUNDRY
ROOM
PANEL PPE CLEAN
ROOM/
CIRCULAT.
127 6 20 1 /
15 15@CR119 tI gjGFCI^ ^ GFCI REFER TO DETAIL 2/E-501 FOR SCHEMATIC DIAGRAM OF X-RAY INTERLOCK
SYSTEM.
9.320PL-1 1/LF-10120
1/LF-2,4,6 <U> 1/LF-18
XRAY
I
19PANEL 1/LB
UNLESS NOTED OTHERWISE
X-RAY CR 6I____ I <u> 9.321 PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED
WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).
PROVIDE WALL MOUNT BRACKET LWMB2.
10524 i i® 1/LF-8■24 oBEACON LIGHT
@ 7-6"STENCIL
ROOM @CR31 V21FIRE
PROTECTION
ROOM
ALL DISCONNECT SWITCHES IN HANGAR 123 SHALL BE NEMA4X.9.332
H 1/LF-12 320) •AIR LOCKI 9.320 CO9.I GFCI/WP 18 COb 121 ■H h rI 6 9.321 o9.337 PROVIDE A TOTAL OF TEN (10) - 1" SPARE CONDUITS WITH PULL STRING
FROM PANEL 1/LD (SECOND TUB) TO ABOVE ACCESSIBLE CEILING AND CAP
FOR FUTURE USE.
I 24 oI V^ST. CD122 I m a: a: UiI 21MPM■CUH O'PANEL 1/LA
UNLESS NOTED OTHERWISE a:1©24
□ ofl X-RAY VAULT ROOM(9.332) lI O CDGFCI/WP COL1
5 104TTP-3 REM-1 oSMS 26 [26\ COGFCI/WP
1/LD-26
1/LA-33 1/LA-27 □ft ft1/LA-37 46" 46' 2vBAP-1
1/LA-25
tL I rl /z z zII BEACON LIGHTn A \<U)I @ 7'-6"GFCI/WP COo5I E9.320
CO9.321I rTO ELEC ROOM GROUND BUS oI a:1/LD-38,40 "OI ^ PANEL 1/LF
UNLESS NOTED OTHERWISE CD q:HP-2 CDI CO13
46' GFCI/WP
GFCI/WP CD1
COO ODdPANEL 1/HA O) FIRST FLOOR POWER PLANF o o oLCP i 1 1/8" = r-o"(9.316
OHD@
1/LA-17
ISSUED
(0) DOOR-1
1/LE-1,3,5
(0) DOOR-2
1/LE-2,4,6
10/04/19 REVISED BID
DOCUMENTSa£
E o o c =5
"O
CO
CD
E □ I
\$\T,o 13o ■o
46=5 OREGON
so/v/sf
EXPIRES:
GFCI/WP^
PANEL 1/LA^
x c L 1 1 . vZ o 4 45 DC/1LEl I GFCI GFCI
10 10o JICM cnPANEL H MTS/1 LE < Icr
L GENERATOR
PLUG
GFCI/WP
-o (9.302)ILU LAUNDRY
ROOM
GFCIo I 3142200-121252.01
10/04/19
M&H NO.:
II42 MOUNT UNDER SINK FOR
FUTURE GARBAGE DISPOSAL
ILU
12 DATE:1 119o I JRHDESIGNED BY:CM
— DOOR-1
DOOR-2
10 11 fUIL3
64" 64' KAS7ICM DRAWN BY:.31346" EF-1 1GFCI3K(f)>42 (J)21 ^ GFCI <n>42" 11 13CM 1/LA-39 IMRGFCI/WPGFCI/WPGFCI/WP 1/HA-1,3,5 DRY(C
1/LD-14.16
\ 46 CHECKED BY:
SMS 1o ■^>■9 ftGFCI 17a 15O DO NOT SCALE DRAWINGSJCN ECN
<U> <u> SHEET CONTENTSi r 1 i^-nGFCI/WPCO GFCI/WP FIRST FLOOR
POWER PLAN
rCD 3 3o GFCI/WPo
CD
ENLARGED LAUNDRY - ROOM 111 ENLARGED KITCHEN AREA - ROOM 113o 3 2______ PANEL 1/LA y
(9.332) UNLESS NOTED OTHERWISE “
1/4" = 1-0" 1/4" = 1-0"H h
SHEET NO.:
CL
c» NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS OTHERWISE NOTED. NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS
OTHERWISE NOTED.
-H-
CO
E-101CO
a) o
CN
Mead l luntKEYED NOTES I
9.202 MOUNT FIXTURE AT 9'-0" AFF MEASURED FROM BOTTOM OF FIXTURE. Mead & Hunt, Inc.
9600 NE Cascades Parkway
Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
9.203 MOUNT FIXTURE AT 8'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
4.
9.204 MOUNT FIXTURE AT 8'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.
MOUNT FIXTURE AT 7'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.9.205
MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM
OF FIXTURE.
9.212 TETRATECHIt
9.314 FIRE PUMP CONTROLLER www. tetratech. com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
9.315 JOCKEY PUMP CONTROLLER
Il=l@ <H)46"AP 9.317 INSTALL L5-20 SIMPLEX RECEPTACLE TO SIDE OF CABLE TRAY (TYPICAL OF 4). REFER TO DETAIL 8/E-501.2/LB-11 1 (9.330)XFMR T-1MSB/HA PANEL MDP/LA PANEL 2/LE a PROVIDE SURGE PROTECTIVE DEVICES (SPD) ON ALL 120VAC CIRCUITS
ASSOCIATED WITH EQUIPMENT FED FROM PANEL 2/LE. PROVIDE HINGED
TERMINAL BOX ADJACENT TO PANEL 2/LE FOR ALL SPD(S). SPD MUST HAVE
BOTH UL 1449 AND UL 1283 LISTING.
9.330
PANEL 2/LA
(9.331 )(9.317}1
ELEC.
IT 9.331 HOUSEKEEPING PAD BY OTHERS. COORDINATE SIZE AND LOCATION WITH
GENERAL CONTRACTOR PRIOR TO INSTALLATION.
1 202PANEL 2/LB PANEL MP/HA
203 2/LA-1
$46'' iGNDlGNDl
2/LA-11 © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
(JP 46" 46'
& I M.La t n ni—1
ENLARGED FIRE PROTECTION ROOM 122 ENLARGED PLAN - ELEC 2034 31/4" = r-o’ i/4n = r-o"
NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LB, UNLESS NOTED OTHERWISE.
o CO COtr o_ ................... ...................__ o CDIT N
♦ [ ] 2/LA-2[-(9.203) N1ET I203 J a:ELEC.N1 N1 IT ELEC. a: a> (TYP.)( 9.204} 202 I 203 202 O'a: <
2/LA-2 2/LA-2 92/LA-2t In oGFCI/WP46'NE l__3 3g 2/LA-2 s s O CD17t'1 4 CO2/LA-2 PANEL 2/LA- 7 o Ct31/LD-36
OCEN .N {^2} DM
[ 1 I 1 1/HA-12Ra
* VIA LCP FOR PE ON /
“TIMECLOCK OFF
2/LA-2 2/LA-2
COo E=□ ERU-1
CO/
oa:NEN N / [ 1 I I 1 h ■O46" CD or2/LA-2 2/LA-22/LA-2 2/LA-2 17 CD/
CO/
< CD
COO ODd/ O)N
I 1 O o o/2/LA-2 2/LA-2N N @AHU-2t 1 I I
2/LA-2 2/LA-2 /
EQUIPMENT
ROOM
ISSUED
10/04/19 REVISED BID
DOCUMENTS201 EF-2 (0)
2/LA-35
E o NE NEo N N
[ 1 ] 1 PRO/,c =3 2/LA-2 2/LA-2 2/LA-2/LA-2 2/LA-2 46'T3 17to
CD
E
IC&IT,oo ■O
=5 OREGON
so/v/sf tyfj. HUO^
EXPIRES:
x C o I
N N N N1 I 1 \ ] 1O
2/LA-2 2/LA-2 2/LA-2 2/LA-2CM □ □
LU
O
I 3142200-121252.01 10/04/19
(§) MAU-1 M&H NO.:
LU
DATE:
o
JRHDESIGNED BY:CM
LO
KASCM NE NEN N DRAWN BY:
I- ] [ ]CM IMR2/LA-2 2/LA-2 CHECKED BY:2/LA-2 2/LA-2oo DO NOT SCALE DRAWINGSHPW-2 HPW-1CM
CM @ O SHEET CONTENTS
CO EQUIPMENT FLOOR
ELECTRICAL PLANS
COoo ilrr? mn r>
CD
EQUIPMENT FLOOR LIGHTING REFLECTED CEILING PLAN EQUIPMENT FLOOR POWER PLANo
12 1/8" = 1 '-O' 1/8" = 1'-0' SHEET NO.:
CL
O
LO
CD NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LA, UNLESS NOTED OTHERWISE.
E-102CO
a) o
MeadLIGHTNING PROTECTION AND
GROUNDING GENERAL NOTES: lunt
1. THE LIGHTNING PROTECTION SHALL REQUIRE AN INSPECTION PRIOR TO
ACCEPTANCE PER UFC 3-575-01. THE SYSTEM SHALL BE INSPECTED BY A
COMMERCIAL, 3RD PARTY INSPECTOR WHOSE SOLE WORK IS LIGHTNING
PROTECTION AND SHALL BE CERTIFIED BY THIS 3RD PARTY INSPECTOR AS
COMPLIANT WITH AFI 32-1065 AND NFPA 780.
Mead & Hunt, Inc.
9600 NE Cascades Parkway
Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
THE USE OF BUILDING STEEL AS DOWN CONDUCTORS IS NOT PERMITTED.2.G G
INSTALLATION OF THE LIGHTNING PROTECTION SYSTEM SHALL NOT VOID
THE WARRANTY OF THE ROOF.
3.
4. ANY EXHAUST AND VENTS SHALL BE PROTECTED BY ADDITIONAL AIR
TERMINALS. REFER TO MECHANICAL AND PLUMBING PLANS. TETRATECHIt www. tetratech. com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254KEYED NOTES
322}9.
A PROVIDE BIMETALLIC CONNECTOR BETWEEN #1/0 AL AND #2 AWG CU DOWN
CONDUCTOR. PROVIDE #2 AWG CU "DOWN CONDUCTOR" FROM ROOF TO
GROUND TERMINAL AS INDICATED. "DOWN CONDUCTOR" SHALL BE
ROUTED IN CONDUIT INTERIOR TO THE BUILDING AND WITHIN CMU/STUD
CAVITY WHEREVER POSSIBLE.
9.322VA A
G
G
LIGHTNING PROTECTION SYSTEM GROUND TERMINALS SHALL BE MINIMUM
3/4" X 10'-0" COPPER-CLAD STEEL GROUND ROD BURIED INTO EARTH 1'-6"
TO TOP OF GROUND ROD. CONDUCTORS SHALL BE PERMANENTLY
CONNECTED TO GROUND TERMINAL WITH EXOTHERMIC WELD. PROVIDE
MINIMUM ONE (1) GROUND TERMINAL IN A GROUND ACCESS WELL FOR
TESTING REQUIREMENTS. REFER TO PLANS FOR EXACT QUANTITY OF
ACCESS WELLS.
9.323
G © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
A A G
A A PROVIDE #1/0 AL "MAIN-SIZE LIGHTNING CONDUCTOR" FOR INTERCONNECT
OF ALL AIR TERMINALS ON ROOF.
9.324
G
CONNECT LIGHTNING PROTECTION SYSTEM / GROUND RING TO BUILDING
GROUND VIA MAIN GROUND BAR IN ELECTRICAL ROOM. REFER TO DETAIL
1/E-503 FOR ADDITIONAL REQUIREMENTS.
9.325
G
PROVIDE #1/0 BARE COPPER COUNTERPOISE GROUND RING SYSTEM
INSTALLED A MINIMUM OF 3'-8" AWAY FROM STRUCTURE. GROUND RING
SHALL BE BURIED AT LEAST 30" BELOW GRADE.
9.326
GA A
20'-0" MAXIMUM SEPARATION BETWEEN AIR TERMINALS ALONG ROOF
PERIMETER AND AS INDICATED (TYPICAL).
9.327
A A
BOND STRIKE TERMINATION DEVICE DIRECTLY TO TOP OF MECHANICAL
UNIT.
9.328
G
BOND TO BOTTOM OF MECHANICAL UNIT METALLIC ENCLOSURE.9.329
G
A A G oGA A CO CO ooG CD cccc<j>A o'G cc< =a= o
O CD co O Ct3
<LIGHTNING PROTECTION
AND GROUNDING SYMBOLS coo E
CO
<§> GROUND ROD ooc ~oCD orGROUND ACCESS WELL CD
COA LIGHTNING AIR TERMINAL
< CDSTATIC GROUND RECEPTACLE
COO ODC O)
o O OG GROUNDING CONDUCTOR
ISSUED
10/04/19 REVISED BID
DOCUMENTS(9.323
E o o c =5
"O
CO
E
IC&IToo ■O
=5 OREGON
so/v/sf
EXPIRES:
x C o I i*-o
CM
LU
O
I 3142200-121252.01 10/04/19
M&H NO.:
LU
DATE:
O
JRHDESIGNED BY:CM
LO
KASCM DRAWN BY:
CM IMRCHECKED BY:
O o DO NOT SCALE DRAWINGSCM
CM
SHEET CONTENTS
CO
LIGHTNING
PROTECTION AND
GROUNDING PLAN
CO
O o
QC
O
LIGHTNING PROTECTION AND GROUNDING PLAN SHEET NO.:1CL
i/8n = r-o1
LO
CO
E-103CO
CD
o
MeadLIGHTING GENERAL NOTES:
PANEL 1/LB ^ PANEL 1/LC
UNLESS NOTED OTHERWISE
PANEL 1/LD y
UNLESS NOTED OTHERWISE “
x PANEL 1/LD
UNLESS NOTED OTHERWISE
x PANEL 1/LF
UNLESS NOTED OTHERWISE<TI luntUNLESS NOTED OTHERWISE
1. REFER TO SHEET E-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.
OB OAEVIA LCP FOR PE ON /
TIMECLOCK OFF
1/HA-14Rb
VIA LCP FOR
PE ON/OFF
(MTD ON ROOF)
2. REFER TO SHEET E-601 FOR LUMINAIRE SCHEDULE.1/HA-12Ra
VIA LCP FOR PEON/®
TIMECLOCK OFF
Mead & Hunt, Inc.
9600 NE Cascades Parkway Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
OCE
REFER TO SHEET E-602 FOR OCCUPANCY SENSOR, LIGHTING CONTROL
PANELAND SWITCH STATION SCHEDULES.
3.1/HA-12Ra
X
IB1E
34 •-
VEST. 4. EC SHALL ALLOW TIME AND EFFORT FOR ALL OCCUPANCY SENSOR AND
PHOTO SENSOR CALIBRATION.
D1 D1E D1E0 0 0 11130a 30a 30a a DiA3OCE—
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
OFFICEI LOCATION OF CEILING OCCUPANCY SENSORS ON THIS PLAN ARE SHOWN
DIAGRAMMATICALLY AND DOESN'T SUGGEST ACUTAL LOCATIONS. EC SHALL
COORDINATE EXACT PLACEMENT IN FIELD BASED ON THIE INSTALLED
DUCTWORK, PIPING AND DIFFUSERS TO PREVENT OCCUPANCY SENSOR
NUISANCE TRIPPING. DO NOT INSTALL SENSORS WITHIN 3'-0" OF DIFFUSERS.
5.TRAINI MG /
BREAK ROOM
30 mD3 D3 '□ (
- OC11230b 30b uJ 30c OSI l-01/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
-(9.216)
112 ®3SDc ( 9.211)—| u X1 TETRATECHIts-D |©303 bO D3o ® Dba,b,c,d
■a,b,c,d 30b 0BEOC1 OC1 OCE OAESS 05- (9.212PANEL 1/LD(9.211 6. ALL EMERGENCY BATTERY OPERATED EXIT LIGHTS AND EBU'S SHALL BE
WIRED FROM SAME LIGHTING BRANCH CIRCUIT AS ROOM BEING SERVED.
Da www. tetratech. com341/LA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF '
1/LA-12Ra VIA LCP FOR PE ON / f
TIMECLOCK OFFQ
1/HA-12Ra
^«VIA LCP FOR PE ON/
1/HA-12Ra 'OSl)0DD1 D1E D1 D1E 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
D1® VIA LCP FOR PE ON /
TIMECLOCK OFF
0 0 0 0 03430a 30a 30a 30a TIMECLOCK OFF30a ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL
BE SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND
OUTSIDE OF THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE
ROUTED BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT
SHALL NOT BE ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL
BE ATTACHED TO HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL
SUPPORTS AS REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN
HANGAR 123 SHALL BE NEMA4X. COORDINATE ROUTING WITH OTHER
TRADES. ALL CONDUIT IN HANGAR 123 SHALL BE RMC.
7.■3 - z z z
=FD1\J MEN'S
$ S3 \(9.209 Sa30a OFFICE[—(9.21o) X1 X1r^. EQUIPMENT
ROOM
(0S10-" a/4T4-4 ]N3 U 30d U 30d AE A0 [X1 D1Es 19C 30aC 30bOCE 0 19B
I® ”QE 2 110A AEQ Q QE 3bCO 30a1/HA-12Ra'~'
VIA LCP FOR PE ON /
TIMECLOCK OFF
L 34
SJ3 d
.osi OIL ANALYSIS
ROOM
(TYP.
30b 30a® ®a
T k _D2
19 19D1E -D1 D1E D1 D1<RB€JT MIXING
ROOM/STOR
OSUb •0 0 030b 30b 30b 30a (OS3) r D 108PANEL 1/LB- TYP. /T REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU
LEAD-LINED WALLS.
8.126 , A AI7 7 2 D2 .OSI3DC 30a 0BE 19 1930 w30 IN3
|-( 9.206) /n? C 30C^^l
30a 340D1 3b 30b
C CI
© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
KEYED NOTES2 (osi)b N2E N2JAND2- [ ] hs /.----- N1N1-P.0S2 30 21b30b MEN'S 30b
LOCKER CE
ROOM
21a116s 30Q Q Q PANEL 1/LF4 C
L30
0 ws a C03bws- 9.206 OCCUPANCY SENSORS SHALL BE PENDANT MOUNTED BELOW ALL
STRUCTURAL BEAMS, PLUMBING AND MECHANICAL PIPING AND DUCTWORK
TO ALLOW FOR CLEAN VIEWING ANGLE.
INSPECTIONI CO D0 BE YCOL WSN1 30 \
/ \ C 32a
PD2'- D2
32 32
-SI® ©a
BAY♦(9.210)
(TYP.)
//. D30b30b 3a AI \ Aco34 ] 103□ ,N2 N2Bs ■ \ \ \ \□ C 32a 34T- 9.207 REFER TO DETAIL 1/E-501. TYPICAL FOR ALL WALL MOUNTED EXIT SIGNS
SHOWN ON THIS PLAN.
3CO C03 21a 21br 197 7 2 2 19WOMEN'S.
0D1 32b
3bCO C 32b
D1D1E0 (0Sl)b 0LAUNDRY
ROOM .
11732a .0S232b FILM VIEWING
ROOM
WS /a,b 9.208 MOUNT FIXTURE AT 32'-0” AFF MEASURED FROM BOTTOM OF FIXTURE.A .OSI.0: CO aBEAD BOOTH
ROOM
32119 BPAINT BOOTH 107N2 N2E /u BE 9.209 MOUNT FIXTURE AT 10'-O" AFF MEASURED FROM BOTTOM OF FIXTURE.I-125 D1 D1 3434 21a127 0 0 32a 21b3b 32bPANEL 1/LC-
HALLWAY A A 9.210 MOUNT FIXTURE AT 13'-0" AFF MEASURED FROM BOTTOM OF FIXTURE OR
ON NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL TYPE F FIXTURES
SHALL BE MOUNTED AT SAME HEIGHT.
II SQE 102
PE-CLEAN ROOM/
CIRCULAT.
WOMEN'S
LOCKER!
B
F xi® 19I 19X1 0S3 N2 N2BE BEB BBE L120 .0S3 9.211 MOUNT FIXTURE AT 13'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.t hCO34 34 34 34 340 34 21a 21bT18 03 B4CO, X-RAY CRI
342 MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM
OF FIXTURE.
9.212•-s 105PANEL 1/LB
UNLESS NOTED OTHERWISE
3 AE
cf=b 19AIR LOCK cEBUT 9.214 MOUNT FIXTURE AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.N1 N1 N2E N2I
21b9.209.0S2 21a32 32 9.215 PROVIDE WITH NEMA 4X ENCLOSURE./
Q FIRE I
PROTECTION
,ROOM |
(TYP.)( 9.206)-—(0S2)OB STENCIL
ROOM .
I 9.216 MOUNT FIXTURE BELOW MEZZANINE STAIR LANDING AT 9'-6" AFG
MEASURED FROM BOTTOM OF FIXTURE.
a,b /1/HA-14Rb
VIA LCP FOR
PE ON/OFF
(MTD ON PARAPET)
I o/9.307 W121122 N2 N2 / X-RAY VAULT
ROOM
[ h 19 C 19 9.217 FIXTURE SHALL BE TRAPEZE MOUNTED BELOW MECHANICAL DUCTWORK AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE. CO/21a 21bN1 N1 CO9.223 0-I2PANEL 1/HA
UNLESS NOTED OTHERWISE
o: 104VEST.MOUNT ON ROOF
AIM NORTH. I o<>>♦(9 32 32I CD.224 101l 9.220 MOUNT FIXTURE AT ROUGHLY 8'-6” AFF TO BOTTOM OF FIXTURE OR ON
NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL EBUS SHALL BE
MOUNTED AROUND HANGAR AT SAME HEIGHT.
sa a: a: o>. - N2 N2E C 19 C 19“ tLT PE O'WP 21aOC 21b 0£f510Re I__B c/*b 5f a
EBU1 I 1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
F [-(9.209) J ® 3aSS o3b 3SX1EBU1 EBU1 EBU1 10Re (9.209
VIA LCP FOR PE ON /
TIMECLOCK OFF
1/HA-12Ra
X30)‘ l-O OCE
10Re 9.221 PROVIDE ADDITIONAL NEMA 4X STRUT SUPPORTS OFF OF STRUCTURAL
GIRDER TO ALLOW FOR EXIT SIGN MOUNTING. TYPICAL OF EXIT SIGNS IN
HANGAR 123. O CDm -+-EBU1WP OL COOAE SOCE f 1/HA-12Ra f VIA LCP FOR PE ON /
TIMECLOCK OFF
OC2Ra 1/HA-12Ra o1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
CO
(9.209 (9.209VIA LCP FOR PE ON /
TIMECLOCK OFF 9.222 MOUNT TO COLUMN.
(9.208°2l <A1
PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED
WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).
PROVIDE WALL MOUNT BRACKET LWMB2. MOUNT BEACON LIGHT AT 7'-6".
BEACON LIGHTS (TYPICAL OF 3 WITH THIS NOTE) CONTROLLED BY SWITCH
IN AIR LOCK 124. BEACON LIGHTS SHALL BE CIRCUITED TO PANEL 1/LA-41.
WP 9.223o
HD-< 9.223)
O COJ o1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
(9.316) Ex PANEL 1/LF UNLESS NOTED OTHERWISEfcm! CO10Rf oa: u9.224 PROVIDE SWITCH WITH ENGRAVED NAMEPLATE "XRAY BEACON LIGHTS". CDH or
— PANEL 1/HA
LCP 9.215)
EBU?g|
CD
C/)O^Rb O^Rb O^Rb oL 9.307 XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL
THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL
INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO
WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH
THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX
IN CMU WALL.
4Rb
< CD
COO ODdHANGAR O)
(9.208 9.211)123 o o o9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER
FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS
REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR
WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE
ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.
obOOC2 OC111/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
1/LA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
1/HA-14Rb
VIA LCP FOR
PE ON/OFF
(MTD ON ROOF)
ISSUED
10/04/19 REVISED BID
DOCUMENTS
E
O EBuii o Lo
6Rcc =5
"O
03 B1□9.222CD
E WP
IC&IToo (9.208
■o F=5 OREGON so/v/sf
EXPIRES: blio/fl lORf0^*x C
OC2o 1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
l i*-o
CM
9.221< OsRd (9.222) o 8Rd O EBU?fl
LL WP9.207 9.316)
F
QlORg
8Rd 8RdB2ir 10Rg2[^C^pEBU1
LU
O
I 3142200-121252.01 10/04/19
M&H NO.:EBU1 FX3 EBUIC^p ^lORgLU C^pEBUIA2 DATE:
UWPo
JRHDESIGNED BY:CM
LO
OCE O
1/HA-12Ra -
VIA LCP FOR PE ON /
TIMECLOCK OFF
□ □ KASCM DRAWN BY:1
CM IMRCHECKED BY:
9.223)
{9.209)
O
O DO NOT SCALE DRAWINGSCM
CM
SHEET CONTENTS
CO
FIRST FLOOR
LIGHTING PLAN
CD
O O PANEL 1/HA y
UNLESS NOTED OTHERWISE To i-
OB>
CD 1/HA-14Rb
VIA LCP FOR
PE ON/OFF
(MTD ON PARAPET)
x o
FIRST FLOOR LIGHTING PLAN SHEET NO.:1CL 1/8" = r-o"
LO
CO
E-121CO
o
Eoo c =5 "O
CD
E oo ■O=5 X c o
Ih» o
CM
LU
O iLU O
CM
LO
CM
CM
iOo
CM
CM
CO
03Oo
>cd¥ O
CL
O Is-
CO
o c =5 "O
CD
E oo ■O=5 X c o
Ih» o
CM
LU
O iLU O
CM
LO
CM
CM
iOo
CM
CM
CO
03Oo cd¥ O
CL
CM
O Is-
CO
o c =5 "O E oo ■O=5 X c o
Ih» o
CM
LU
O iLU O
CM
LO
CM
CM
iOo
CM
CM
CO
03Oo
>0¥ O
CL
CM
O Is-
CO
o c =5 "O E oo ■O=5 X c o
Ih» o
CM
LU
O iLU O
CM
LO
CM
CM
iOo
CM
CM
CO
03Oo
>0¥ O
CL
coo Is-
CO
o
Mead lunt
#2 GRD CABLE TRAY Mead & Hunt, Inc.
9600 NE Cascades Parkway
Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
TYPICAL: DRY-TYPE TRANSFORMER IN ELECTRICAL ROOMS.
SEE PLANS FOR EXACT LOCATIONS AND ROOM NUMBERS.
#3/0 GRD #6 GRD TELECOM EQUIPMENT RACK(S)
W
EQUIPMENT GROUNDING
CONDUCTOR
PER NEC 250.122. SEE
FEEDER SCHEDULE
MAIN TELECOM ROOM
MAIN GROUNDING BUSBAR (TMGB) TETRATECHIt
STREET SIDE OF BUILDING
WATER METER. CONNECT TO
METALLIC WATER MAIN
WITHIN 5'-0" OF WATER
SERVICE ENTRANCE. PROVIDE
JUMPER ACROSS WATER METER.
A www. tetratech. com ww #3/0 GRD 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
t
AAAALEAD-LINED SIDE OF HANGAR
123 OR XRAY ROOM 104.LEAD WRAP CONDUIT
ELBOW. PROVIDE ELBOW
ADJACENT TO WALL ---------
Y PANELBOARD(S) GROUND BUS
REBAR STUBBED THROUGH FLOOR BY FOUNDATION
CONTRACTOR.
15KVA-#8 AWG
30KVA-#6 AWG
45KVA-#4 AWG
75KVA-#3 AWG
112.5KVA-#2 AWG
150KVA - #1/0 AWG
225KVA - #3/0 AWG
300KVA-#4/0 AWG
J
CONDUIT PENETRATING LEAD WALL UL LISTED FITTINGS FOR THE
PURPOSE (TYP)#3/0 GRD
L © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
FOUNDATION REBAR
LEAD LINING. SEE ARCHITECTURAL PLANS. CONCRETE FOOTING
GROUND RING♦SWITCHBOARD
NEUTRAL BUS
GROUND BUS LOCATED IN
ELECTRICAL ROOM.
GROUND BUS
SWITCHBOARD
REMOVABLE LINK MAIN BONDING JUMPER -
SIZED PER NEC 250.28(D). @----- ©------®v GR GR GR
\NOTES:
GROUNDING ELECTRODE CONDUCTOR
SIZED PER NEC 250.66.
1. ALL GROUND CONDUCTORS TO BE ROUTED IN PVC CONDUIT.
2. ALL GROUND CONDUCTORS ON THIS DIAGRAM SHALL BE COPPER.
3. REFER TO SHEET E-103 FOR CONNECTIONS OF LIGHTNING PROTECTION SYSTEM TO GROUND RING.
® © GROUNDING SYSTEM DETAIL (TYP)CONDUIT THRU LEAD-LINED WALL DETAIL
NO SCALE NO SCALE
o
CO CO
oo CD a: a: <j> o'a: < o O CD co O Ct3
RED PLASTIC WARNING TAPE;
12" BELOW GRADE
CAST-IN PLACE CONCRETE
ENCASEMENT. COo E
CO
SECURE TOP SPACER TO PREVENT
CONDUITS FROM FLOATING DURING
CONCRETE POUR. oa:1" ABOVE SIDES OF DUCT.
CROWN DUCT TO A PEAK ■OCD orcdDUCTBANKS CONDUITS. SEE DIV.
26 SECTIONS FOR SIZES AND
QUANTITIES. CO
CD
(?) POWER
2) POWER SPARE
EPOXY COATED #4 REBAR;
CONTINUOUS ALONG
DUCTBANK (TYP)
COO ODd O) o O OPLASTIC CONDUIT
SPACERS/SUPPORTS
CONCRETE PAVERS FOR
LEVELING
ISSUED
10/04/19 REVISED BID
DOCUMENTS
E ' II- :| I l=l I :| I l=l I 111=11 11=1 I 1=1oo c ----- 3’ 3’ 3’ 3" UNDISTURBED EARTH=3
T3 DETAIL NOTES:to
CD
E
CONCRETE COVER DIMENSIONS SHOWN ARE MINIMUM.
IC&IToo
DUCT BANK SHALL BE A MINIMUM OF 36” BELOW GRADE.■o
=5 OREGON
so/v/sf
EXPIRES:
x C o I © ELECTRICAL DUCTBANK TYPICAL SECTION - 2 X 4i*-o
CM NO SCALE
<cr
LU
O
I 3142200-121252.01 10/04/19
M&H NO.:
LU
DATE:
DESIGNED BY: JRH
KAS
o
CM
LO
CM DRAWN BY:
CM IMRCHECKED BY:
Oo DO NOT SCALE DRAWINGSCM
CM
SHEET CONTENTS
CO
DETAILS©
Oo
><d
QC
O
SHEET NO.:
CL
o Is-
E-503CO
a) o
MeadOPTIONS/ACCESSORIES CODE LISTING: LUMINAIRE SCHEDULE 01 AIR HANDLING CAPABILITY - RETURN AIR luntSEE SPECIFICATION FOR ADDITIONAL INFORMATION REGARDING LUMINAIRE AND INSTALLATION REQUIREMENTS. PROVIDE OPTIONS AND ACCESSORIES REFERENCED BY THE COLUMN TITLED " OPTIONS/ACCESSORIES". MANUFACTURERS LISTED ACCEPTABLE SHALL MEET ALL
REQUIREMENTS AND FEATURES INDICATED. ACCEPTABLE MANUFACTURERS MUST MEET THE PHOTOMETRIC PERFORMANCE OF THE LISTED UNIT.NOTE:
3" DEEP PARABOLIC LOUVERS02
ABBREVIATIONS: GWB = GYPSUM WALL BOARD
ES = EXPOSED STRUCTURE
LG = LAY-IN GRID
R = RECESSED V = VARIES
S = SURFACE W = WALL MOUNTED
UNV = UNIVERSAL VOLTAGE
P = PENDANT
PLAS = PLASTER
PL = POLE MOUNTED
4" DEEP PARABOLIC LOUVERS03
Mead & Hunt, Inc.
9600 NE Cascades Parkway Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
04 SEMI-SPECULAR PARABOLIC LOUVER
LOW IRIDESCENT PARABOLIC LOUVER05 LED SYSTEM
INPUT
WATTAGE
LEDBALLAST/
DRIVER
CEILING
TYPE
FIXTURE
DEPTH
OPTIONS /
ACCESSORIES
KEYED
NOTEDELIVERED
LUMENS
DES. MANUFACTURER CATALOG SERIES DESCRIPTION LAMP DATA VOLTAGE MOUNT ACCEPTABLE MANUFACTURERSFLAT ALUMINUM DOOR FRAME06
REGRESSED ALUMINUM DOOR FRAME07
HE WILLIAMS 50 SERIES
3-1/4'A METALUX 24GR-LD5-34-A125-UNV-L840-CD1-U 2’ X 4' RECESSED LENSED TROFFER LED, 4000K UNV D R LG 26.7 3,51408 FLAT STEEL DOOR FRAME DAYBRITE LT LED SERIES SINGLE GASKETED DOOR FRAME09 TETRATECHItHE WILLIAMS 50 SERIES24GR-LD5-34-A125-UNV-EL14W-L840-
CD1-UAE METALUX SAME AS ’A' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV LG 3-1/4'D R 26.7 3,514 DAYBRITE LT LED SERIES10 DOUBLE GASKETED DOOR FRAME www. tetratech. com
CREE ZR SERIES
A2 METALUX 24CZ-LD5-35-S-UNV-L840-CD1-U 2' X 4' RECESSED VOLUMETRIC TROFFER LED, 4000K UNV LG 3-1/4'D R 25.3 3,63511 TRIPLE GASKETED DOOR FRAM, LENS & BODY 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
HE WILLIAMS AT SERIES
ANTIMIRCOBIAL PROTECTION PAINTED FINISH12 CREE ZR SERIES24CZ-LD5-35-S-UNV-EL14W-L840-CD1 SAME AS 'A2' EXCEPT WITH EMERGENCY BATTERY OPTION 3-1/4'A2E METALUX LED, 4000K UNV D R LG 25.3 3,635-U HE WILLIAMS AT SERIES13 DAMP LOCATION LISTED CREE ZR SERIES14 STAINLESS STEEL TRIM & DOOR FRAME A3 METALUX 24CZ-LD5-50-S-UNV-L840-CD1-U 2' X 4' RECESSED VOLUMETRIC TROFFER LED, 4000K UNV LG 3-1/4' 40.7D R 5,190
HE WILLIAMS AT SERIES
MATTE DIFFUSE CLEAR REFLECTOR15 PHILIPS GUTH SERIESCLMF-24-4-ALH-INA-A19156-LD4-2LO- 40-UNV-EDD1-EL14WA4E FAIL-SAFE 2' X 4' RECESSED LENSED TROFFER WITH EMERGENCY BATTERY OPTION LED, 4000K UNV GWB 3-1/2' 52.4 5,461D R
16 REFLECTOR COLOR OTHER THAN CLEAR KURTZON
HE WILLIAMS AT SERIES17 WHITE MILLIGROOVE BAFFLE 2’ X 2' RECESSED VOLUMETRIC TROFFER 2-3/4'B METALUX 22CZ-LD5-24-S-UNV-L840-CD1-U LED, 4000K UNV D R LG 19.6 2,570
CREE ZR SERIES
BLACK MILLIGROOVE BAFFLE18 HE WILLIAMS AT SERIES22CZ-LD5-24-S-UNV-E14W-L840-CD1- © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
BE METALUX SAME AS 'B' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV LG 2-3/4' 19.6D R 2,570UADA COMPLIANT19 CREE ZR SERIES
HE WILLIAMS AT SERIES22CZ-LD5-24-S-U N V-E14 W-L840-CD1 -
U-DF-22-W
FURNISH WITH SYMMETRIC REFLECTOR20 B1E METALUX SAME AS 'BE' EXCEPT CEILING TYPE LED, 4000K UNV DW 2-3/4' 19.6D R 2,570
CREE ZR SERIES
FURNISH WITH ASYMMETRIC REFLECTOR21
HE WILLIAMS AT SERIES
2’ X 2' RECESSED VOLUMETRIC TROFFER 2-3/4'B2 METALUX 22CZ-LD5-34-S-UNV-L840-CD1-U LED, 4000K UNV D R LG 29.4 3,638FURNISH WITH SLOPE ADAPTER - VERIFY SLOPE22 CREE ZR SERIES
DAYBRITE LT LED SERIESFURNISH WITH AUXILIARY EMERGENCY BATTERY PACK23 14GR-LD5-20-A125-UNV-L840-CD1-U- DF-14-WUC METALUX 1' X 4' RECESSED LENSED TROFFER LED, 4000K UNV GWB 5-5/8' 17.2D R 2,062
HE WILLIAMS 50 SERIES24 FURNISH WITH WIRE GUARD
DAYBRITE LT LED SERIES14GR-LD5-20-A125-UNV-EL14 W-L840-
CD1-U-DF-14-WU SAME AS ’C EXCEPT WITH EMERGENCY BATTERY OPTION 5-5/8'CE METALUX LED, 4000K UNV D R GWB 17.2 2,062FURNISH WITH CHAIN MOUNTING ACCESSORIES25 HE WILLIAMS 50 SERIES
FURNISH WITH RIGID PENDANT STEMS26 DAYBRITE LT LED SERIES
5-5/8'C1 METALUX 14GR-LD5-32-A125-UNV-L840-CD1 -U 1’ X 4' RECESSED LENSED TROFFER LED, 4000K UNV D R LG 29.8 3,310
HE WILLIAMS 50 SERIESFURNISH WITH SWIVEL CANOPY27
PORTFOLIO LD6A SERIES
D GOTHAM EVO-40/15-6AR-MD-LSS-MVOLT-EZ10 6" DIAMETER DOWNLIGHT LED, 4000K UNV V 7-9/16' 19 1,572PATTERN 12 ACRYLIC LENS - 0.125" MIN. THICKNESS D R28
PHILIPS CALCULITE SERIES
PATTERN 12 ACRYLIC LENS - 0.156" MIN. THICKNESS29 PORTFOLIO LD4A SERIES
EVO-40/10-4AR-MD-LSS-MVOLT-EZ10 4" DIAMETER DOWNLIGHT 7-9/16'D1 GOTHAM LED, 4000K UNV D R V 13 1,189
PHILIPS CALCULITE SERIESPATTERN 12 ACRYLIC LENS - 0.187" MIN. THICKNESS30
PORTFOLIO LD4A SERIESEVO-40/10-4AR-MD-LSS-MVOLT-EZ10FURNISH WITH SOLID FRONT31 SAME AS ’D1’ EXCEPT WITH EMERGENCY BATTERY OPTION 7-9/16'D1E GOTHAM LED, 4000K UNV D R V 13 1,189-EL PHILIPS CALCULITE SERIES
FURNISH WITH PHOTO CELL32 PHILIPS CAPRI SERIESH457-ICAT-1E-EL406-940-TL402HS-TR
M400SND2 HALO 4" DIAMETER DOWNLIGHT (SHOWER LUMINAIRE) LED, 4000K UNV D GWB 5-3/8' 13R 900
1/2" X 1/2" X 1/2" SILVER PARACUBE LOUVER33 ACUITY JUNO SERIES
PINNACLE FINA SERIESFSDEP-2-FL-3000DN-0UP-940K-1C-UN
V-L11-SM-WH
34 WHITE STRAIGHT BLADE LOUVERS FOCAL POINT 24" DIAMETER SURFACE MOUNTED DOWNLIGHTD3 LED, 4000K UNV D S LG 3' 27 3,000
FURNISH TRIM SUITABLE FOR USE WITH NARROW TEE CLG SYSTEM35 PINNACLE FINA SERIESFSDEP-2-FL-7000DN-0UP-940K-1C-UN V-L11-SM-WH oFOCAL POINT 48" DIAMETER SURFACE MOUNTED DOWNLIGHTD4 LED, 4000K UNV D S LG 3.7' 63 7,000CUSTOM PAINTED FINISH - COLOR AS SELECTED BY ARCHITECT36
KIM LIGHTING CFL SERIESDSXF2LED-P2-40K-WFL-277-THK-DM
G-DNAXD
FROSTED LENS REFLECTOR, SATIN LENS DIFFUSER37 COF LITHONIA 8" X 12" LED FLOOD LUMINAIRE LED, 4000K W 12'277 D 78 10,678 COINVUE VFS SERIES oWET LOCATION LISTED38 oMETALUX VISIUM SERIES CDPHZL-70L-4K-80CRI-27-P-W-W-D-UPH -35-277V-WH-PF-122-A 28-1/2" DIAMETER INDUSTRIAL ROUND PENDANTL HOLOPHANE LED, 4000K 277 D P ES 24.34' 589 63,851 1BALLAST/DRIVER CODE LISTING: (SEE SPECIFICATIONS)
LED DIMMABLE POWER SUPPLY (0-10V).
DIALIGHT VIGILANT SERIES cccc<j>
COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8
0CRI-WH-EC36
D O'N LITHONIA 4’ X 10" INDUSTRIAL LOW BAY LUMINAIRE LED, 4000K UNV V 3-1/4'D P 29 3,636 cc< oGENERAL NOTES: COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8
0CRI-E7W-WH-EC36 O CDNE LITHONIA SAME AS 'N' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV V 3-1/4'D P 29 3,636 CO1. EC SHALL VERIFY AND COORDINATE ALL LUMINAIRE TRIMS/FLANGES WITH RESPECTIVE CEILING TYPES SCHEDULED AND/OR SUBMITTED BY THE GC PRIOR TO ORDERING OF THE LUMINAIRES. SCHEDULE INDICATES TRIM TYPES BASED ON THE GENERIC CEILING INFORMATION AVAILABLE AT THE TIME BIDDING DOCUMENTS WERE ISSUED AND DOES NOT REFLECT ACTUAL THICKNESS OF GYPSUM WALL BOARD OR PLASTER CEILING OR EXACT GRID TYPE SPECIFIED BY
THE ARCHITECT.
oCOLUMBIA LCR SERIES Ct3MSL-4000LM-SBL-MVOLT-GZ10-40K-8 0CRI-WHLITHONIA 3-1/4'N1 SAME AS 'N' EXCEPT SURFACE MOUNTED LED, 4000K UNV D S V 29 3,636
<COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8
0CRI-E7W-WHN1E LITHONIA SAME AS 'N1' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV S V 3-1/4'D 29 3,636 COo EKEYED NOTES: COLUMBIA LCR SERIES8ILED-LD5-W-CL-UNV-L840-CD1-U-AY C-CHAIN/SET/U CON2 METALUX 8' X 11" INDUSTRIAL LOW BAY LUMINAIRE LED, 4000K UNV ES 4-15/16'D P 65 10,052
EC TO VERIFY AND COORINDATE ALL MOUNTING ACCESSORIES REQUIRED FOR ALTERNATE MANUFACTURER.1. oocCOLUMBIA LCR SERIES8ILED-LD5-W-CL-UNV-L840-EL14W-C D1-U-AYC-CHAIN/SET/U SAME AS ’N2’ EXCEPT WITH EMERGENCY BATTERY OPTION 4-15/16'N2E METALUX LED, 4000K UNV D P ES 65 10,052CONFIRM FILTERS REQUIRED WITH COR PRIOR TO ORDERING.2. "OCD ocCDHOLOPHANE HXPL SERIESFIELD VERIFY EXACT LENGTH OF FIXTURE REQUIRED TO ACCOMMODATE THE DESIGNATED LOCATION AND LENGTH
SHOWN ON LIGHTING PLANS. PROVIDE ALL ACCESSORIES REQUIRED TO CREATE A COMPLETE AND OPERATIONAL
SYSTEM.
3. 2’ LED HAZARDOUS LOCATION LINEAR FIXTURE WITH CLEAR
POLYCARBONATE LENS AND IP66 & CLASS I DIV II RATED.N3 EATON DLL-2-UNV1-S903-TF-WH LED, 4000K UNV S GWB 34.3D 2.7' 3,958 CO
HE WILLIAMS
8VT2-LD4-9-DR-UNV-L840-CD1-WL-U-
VT2-CHAIN/SET-U CD8' X 7" INDUSTRIAL VAPORTITE LUMINAIRE 5-7/8'Q METALUX LED, 4000K UNV D P ES 105 9,000
(/)o oDC O)HE WILLIAMS8VT2-LD4-9-DR-UNV-L840-EL10W-CD 1 -W L-U-VT2-CHAIN/SET-U SAME AS ’Q’ EXCEPT WITH EMERGENCY BATTERY OPTION 5-7/8'QE METALUX LED, 4000K UNV D P ES 105 9,000 o o oCOOPER LIGHTING
U PHILIPS CONTINUOUS UNDERCABINET LIGHT LED, 4000K 120 S 1.7' 25 / 4FT 1,079/4FT523-000027.77 D 3
LITHONIA LIGHTING
ISSUEDPORTFOLIO LD6A SERIESEVO-40/10-6AR-MD-LSS-MVOLT-EZ10 6" DIAMETER DOWNLIGHT 7-9/16'OAE GOTHAM LED, 4000K UNV D R V 12 1,059 10/04/19 REVISED BID
DOCUMENTS
-EL PHILIPS CALCULITE SERIES
£ FEDERAL SIGNALE RED OBSTRUCTION LIGHTOB ADB SAFEGATE OBSL-L-1-1-1-0-0-0-1-0-0 LED UNV S 10.8' 12o EATON ERL SERIESo
PR Qfic CREE EDGE SERIES=3 oc LITHONIA DSXW1 LED-10C-350-40K-T3M-MVOLT 14" X 6-1/2" WALL PACK LED, 4000K UNV W 10' 14 1,488DT3 PHILIPS 122 SCONCE SERIEScd
CD
E CREE EDGE SERIESSAME AS ’OC’ EXCEPT WITH EMERGENCY BATTERY AND BACK BOX
OPTIONS
DSXW1 LED-10C-350-40K-T3M-MVOLT
-BBW-ELCWLITHONIAOCE LED, 4000K UNV D W 14' 14 1,488
PHILIPS 122 SCONCE SERIES IC&IToo
■O CREE EDGE SERIES=5
OREGON
so/v/sf
EXPIRES:
LITHONIA 14" X 6-1/2" WALL PACKOC1 DSXW1 LED-10C-530-40K-T3M-MVOLT LED, 4000K UNV D W 10’ 20 2,159x
PHILIPS 122 SCONCE SERIESC
o CREE EDGE SERIES OC2 LITHONIA DSXW1LED-20C-530-40K-T3M-MVOLT 14" X 6-1/2" WALL PACK LED, 4000K UNV W 10'D 36 4,288i
PHILIPS 122 SCONCE SERIES
o
CM LITHONIA, DUAL-LITE, PHILIPS
ISOLITE EMERGENCY BATTERY UNIT LED W/UNIT 2-3/16'EBU RL2-LED-WH-SD UNV W 4 125<oc LITHONIA, DUAL-LITE, PHILIPSLU EBU1 ISOLITE RL2LEDWP-2-WH-SD EMERGENCY BATTERY UNIT LED W/UNIT UNV W 3.4' 4 125o i 3142200-121252.01 10/04/19
M&H NO.:
LU
DATE:
DESIGNED BY: JRH
KAS
SURE-LITE CAX SERIESo X1 LITHONIA LE-S-1-R-ELN-SD SINGLE FACE LED EXIT SIGN LED W/UNIT UNV V V 7-7/8' 2.5CM PHILIPS 46 SERIESLO CM DRAWN BY:SURE-LITE CAX SERIESCM IMRLITHONIA DOUBLE FACE LED EXIT SIGN LED W/UNIT 7-7/8'X2 LE-S-2-R-ELN-SD UNV V V 2.5 CHECKED BY:PHILIPS 46 SERIESoo DO NOT SCALE DRAWINGSCM SURE-LITE UX SERIESCM -H- X3 LITHONIA WLTE-W-1-R-EL-SD SINGLE FACE LED EXIT SIGN (WET LOCATION) LED W/UNIT UNV W 2-1/2' 2.7 SHEET CONTENTS
DUAL-LITE EVE4X SERIESCO
SCHEDULESCD
O o
CD
o
SHEET NO.:
CL
■sl-o h-
E-601CO
CD
o
MeadLIGHTING CONTROL PANEL SCHEDULE (LCP) OCCUPANCY/VACANCY/PHOTO SENSOR SCHEDULE luntOVERRIDE
DEVICE
RELAY
NUMBER
RELAY TYPE AREA
CONTROLLED
KEYED
NOTE
TECHNOLOGYSENSOR COVERAGE
AREA
CIRCUIT DESCRIPTIONVOLTAGE PATTERN MOUNTING KEYED NOTEIDPOLES VOLTAGE SIZE PIR MICRO Mead & Hunt, Inc.
9600 NE Cascades Parkway Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
1/HA-2Ra1 1 277V 20A LV A, A1, A2 HANGAR 123
SINGLE-POLE, WALL MOUNT SWITCH TYPE OCCUPANCY SENSOR. CAT# WSX PDT AUTO-ON OR
VACANCY120/277WS X X 180 UP TO 800 SF WALL 1,31 277V 20A 1/HA-4Rb LV A, A1, A2 HANGAR 1232
1/HA-6RC3 1 277V 20A LV A, A1, A2 HANGAR 123
SINGLE-POLE, WALL MOUNT SWITCH TYPE DIMMING OCCUPANCY SENSOR. CAT# WSX D; 0-10
VOLT,1% ELDO DRIVER COMPATIBLE
4 1 277V 20A 1/HA-8Rd LV A, A1, A2 HANGAR 123 120/277WS1 X X 180 UP TO 800 SF WALL 1,2 1 277V 20A 1/HA-10 Re LVA, B, B1, B2 HANGAR 1235
CEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY; CAT# CM PDT, SMALL
MOTION
1/HA-10Rf6 1 277V 20A LVA, B, B1, B2 HANGAR 123 OS1 12-24V X X UP TO 500 SF CEILING 4, 5,6360 1 277V 20A 1/HA-10Rg LVA, B, B1, B2 HANGAR 1237
1/HA-12Ra PE ON / TS OFF BUILDING EXTERIOR8 1 277V 20A TETRATECHItCEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY; CAT# CM PDT, LARGE MOTIONOS2 12-24V X X 360 UP TO 2000 SF CEILING 4, 5,61 277V 20A 1/HA-14Rb PE ON / OFF OBSTRUCTION9 www. tetratech. com
10 1 277V 20A SPARE UP TO 28' @9' MH ;
UP TO 36'@ 15'
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
OS3 12-24V X X CEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY, CAT#CM PDT, HALLWAYS CEILING360 2,611 1 277V 20A SPARE
MH
12 1 277V 20A SPARE
SINGLE ZONE DAYLIGHT SENSOR WITH SELECTABLE ON/OFF OR DIMMING APPLICATION; CAT # CM
PC ADCGENERAL NOTES: DS 12-24V N/A N/A N/A CEILING 7
SITE LIGHTING TO TURN ON AT 5:00 PM AND OFF AT MIDNIGHT.
BUILDING PHOTO EYE WILL OVERRIDE THE SITE LIGHTING DURING DAYTIME HOURS.
INTERIOR BUILDING LIGHTING TO TURN OFF AT 1:00 AM. LIGHTS SHALL BLINK 5 MINUTES PRIOR TO SHUTOFF. AUTO
OFF 1:00 AM; 1:00 AM TO 7:00 AM - LV SWITCH OVERRIDE ON FOR 2 HRS.
1.
0 FC (MIN) TO 50-750 FC (MAX) OUTDOOR PHOTOCELL INSTALLED IN APPROPRIATELY RATED
ENCLOSURE
2. N/A N/A N/APE 12-24V ROOF 8
3.
GENERAL NOTES:
1. COLOR OF DEVICES SHALL BE COORDINATED/MATCHING COLOR OF RECEPTACLES AND SWITCHES AS IDENTIFIED IN SPECIFICATION SECTION 26 27 26
PROVIDE ADEQUATE SUPPORT FOR CONTROL WIRING, REFER TO WIRING DIAGRAMS SUPPLIED WITH SELECTED DEVICES. FOLLOW MANUFACTURER INSTRUCTIONS
FOR ADDITIONAL INFORMATION REFER TO SPECIFICATION SECTION 26 51 00.
ALL LOW VOLTAGE SENSORS SHALL BE PROVIDED WITH 20A RATED POWER PACKS WITH ZERO CROSS SWITCHING TECHNOLOGY AND MANUAL ON MODE
PROVIDE 8’ OF ADDITIONAL WIRING ABOVE ACCESSIBLE CEILING.
ALL POWER PACKS AND SLAVE PACKS SHALL BE INSTALLED IN APPROVED ENCLOSURES RATED FOR THE ENVIROMENTAL SPACES WHERE THEY ARE INSTALLED
WHERE OCCUPANCY SENSORS CONTROLLING LIGHTS OF A DIFFERENT VOLTAGES A SEPARATE POWER/SLAVE PACK…