This document provides details for a federal solicitation seeking construction services. The Oregon Air National Guard is soliciting bids for a firm fixed-price contract to construct a corrosion control hangar and support facilities at Kingsley Field in Klamath Falls, Oregon. The project scope includes construction of a pre-engineered metal hangar and adjacent support spaces totaling approximately 16,000 square feet as well as an aircraft tow-lane. The solicitation will include a base bid and four options. The performance period is 365 calendar days from notice to proceed. This opportunity is set aside exclusively for small businesses with a NAICS code of 236210 and size standard of $36.5 million. Bids are due on January 6, 2020. The pre-bid conference will be held on December 12, 2019 and site visits will follow. The Department of the Army is the contracting agency.

View the file

Other files for this federal contract opportunity

Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LUMINAIRE SYMBOLS MeadELECTRICAL ABBREVIATIONS GENERAL NOTES:GENERAL SYMBOLS COPPER FEEDER SCHEDULE 0 RECESSED LUMINAIRE CONDUCTOR SIZES (AWG or KCMIL)NO. OF

SETS

CONDUIT lunt#/E-### DETAIL NUMBER / SHEET NUMBER

KEYED NOTE, USED TO DESCRIBE ADDITIONAL

INFORMATION OF WORK REQUIRED, SPECIFIC TO

THE SHEET AND/OR DETAIL IT IS SHOWN WITH.

NEMA 3R RATING

NEMA 4X RATING

AMPERES

ARCHITECT/ENGINEER

ABOVE ACCESSIBLE CEILING

AIR COOLED CONDENSING UNIT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

ALTERNATE

AIRCRAFT PROCESS EQUIPMENT

AUTOMATIC TRANSFER SWITCH

BUILDING

BREAKER

CONDUIT

CIRCUIT BREAKER

CIRCULATION FAN

CHILLER

CHILLED WATER PUMP

CIRCUIT

CIRCULATION PUMP

COMPUTER ROOM AIR CONDITIONER

CONDENSATION RETURN

CABINET UNIT HEATER

DROP CORD

DIGITAL CONTROL PANEL

DUCT HEATER

DISCONNECT

DOOR OPERATOR

DRAWING

ELECTRICAL-TO-OPTICAL CONVERTER

ELECTRICAL CONTRACTOR

ENCLOSED CIRCUIT BREAKER

EXHAUST FAN

EMERGENCY

ELECTRICAL METALLIC TUBING

EQUIPMENT SUPPLIER

EXISTING TO REMAIN

ELECTRICAL WATER COOLER

ELECTRICAL WATER HEATER

FUSED

FIRE ALARM

FAN COIL UNIT

GENERAL CONTRACTOR

GARBAGE DISPOSAL

GROUND FAULT INTERRUPTER

GROUND

GAS WATER HEATER

HAND DRYER

HORSEPOWER

HEATING, VENTILATION, AIR CONDITIONING

HOT WATER BOILER

HOT WATER PUMP

INSTANTANEOUS ELECTRIC WATER HEATER

INFRARED HEATER

INTERMEDIATE METALLIC CONDUIT

INSTANTANEOUS WATER HEATER

JUNCTION BOX

MAKE-UP AIR UNIT

MAXIMUM

MECHANICAL CONTRACTOR

MOTOR CONTROL CENTER

MAIN DISTRIBUTION FRAME

MAIN DISTRIBUTION PANEL

MINIMUM

MASS NOTIFICATION SYSTEM

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

NOT IN CONTRACT

NIGHT LIGHT

NIGHT LIGHT AND EMERGENCY LIGHT

NOT TO SCALE

ON CENTER

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

PHASE

PANEL

POLYVINYLCHLORIDE

RADIANT CEILING PANEL

RECEPTACLE

REFRIGERATOR

REQUIRED

RETURN FAN

RIGID GALVANIZED STEEL CONDUIT

MAY ALSO BE REFERENCED AS RMC OR GRC

RIGID METAL CONDUIT

ROOF TOP UNIT

SOLID NEUTRAL

SERVICE ENTRANCE

SECURITY PANEL

SUPPLY FAN

SUMP PUMP

STAINLESS STEEL

SWITCH

TO BE REMOVED

TEMPERATURE CONTROL PANEL

TO FLOOR ABOVE

TO FLOOR BELOW

TYPICAL

UNIT COOLER

UNDERGROUND

UNIT HEATER

UNLESS NOTED OTHERWISE

UNIT VENTILATER

VOLTS

VARIABLE FREQUENCY DRIVE

VERSUS

WATTS

WATER COOLED CONDENSER

WATER HEATER

WET LOCATION LISTED

WEATHERPROOF

TRANSFORMER

EXPLOSION PROOF

REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS

PLANS, INFORMATION AND NOTES.

3R 1. MARK AMPACITY0 SIZEPHASE NEUTRAL EQ GND ISO GND4XRECESSED TROFFER

9.111111 A 3-# 12 1 -# 1220 20 1 1/2'RECESSED LINEAR THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE

DETAILS OF WORK, VERIFY DIMENSIONS IN THE FIELD,

AND ADVISE THE ARCHITECT/ENGINEER OF ANY

DISCREPANCY BEFORE PERFORMING ANY WORK.

2.A/E Mead & Hunt, Inc.

9600 NE Cascades Parkway

Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com

20Y 1 3-# 12 1 -# 12 1 -# 12 1/2'20O SURFACE ROUND LUMINAIRE AAC

3-# 10 1 -# 10 1/2'25 25 1ACCUh 1 SURFACE INDUSTRIAL LINE TYPE KEY 25Y 1 3-# 10 1 -# 10 1 -# 10 1/2'25AFFh 1 PENDANT INDUSTRIAL THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE

WITH THE ABA (AMERICANS WITH BARRIERS ACT).

3.AFG 1 3-# 10 1 -# 10 3/4'30 302 NEW WORK BY THIS CONTRACTOR

(DARK SOLID LINE)

EXISTING TO BE REMOVED BY THIS

CONTRACTOR (DARK DASHED LINE)

WALL BRACKET AHU 3-# 10 1 -# 10 1 -# 1030Y 30 1 3/4'

ALT REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED

WALLS AND FLOORS. MAKE RATED PENETRATIONS AS

REQUIRED. SEAL ALL RATED PENETRATIONS AS

IDENTIFIED IN DIVISION 1 REQUIREMENTS.

4.CEILING MOUNTED EXIT SIGN 1 3 - # 8 1 -# 10 3/4'35 35APE

3 - # 8 1 - # 8 1 -# 1035Y 35 1 3/4'ATSWALL MOUNTED EXIT SIGN

BLDG

BRKR

TETRATECHIt40 40 1 3 - # 8 1 -# 10 3/4'ONE-LINE EQUIPMENT ENCLOSURE<- ARROW DENOTES EXIT SIGN CHEVRON

1 - # 8 1 -# 1040Y 40 1 3 - # 8 1FLUSH MOUNT ALL TOGGLE SWITCHES AND

RECEPTACLES AT HEIGHTS ABOVE FINISHED FLOOR AS

SHOWN IN THE DEVICE MOUNTING HEIGHT DETAIL,

EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE

SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED

EXPOSED.

5.

EMERGENCY BATTERY UNIT C www. tetratech. comPANEL DIVISION LINES

1 -# 1045 45 1 3 - # 6 3/4'CB 711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

EEMERGENCY SHADING MODIFIER

LUMINAIRE CIRCUITRY & CONTROL KEY:

LUMINAIRE TYPE

SITE UNDERGROUND ELECTRIC 45Y 45 1 3 - # 6 1 - # 6 1 -# 10 1CF

3 - # 6 1 -# 1050 50 1 1CH

CHWP 50Y 1 3 - # 6 1 - # 6 1 -# 10 1-1/4'50

CKTSERVICE & DISTRIBUTION SYMBOLS CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT

IDENTIFICATION. CIRCUITING SHALL AGREE WITH

NUMBERING ON THE PANEL SCHEDULES PROVIDED.

BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE

BETWEEN EACH PHASE. COMMON NEUTRALS MAY NOT BE

USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON

PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.

6. 1 -# 1060 60 1 3 - # 4 1

CP

60Y 1 3 - # 4 1 - # 4 1 -# 10 1-1/4'60LOWER CASE LETTER INDICATES SWITCHLEG CONTROL

"R" INDICATES LIGHTING CONTROL PANEL

REFER TO LIGHTING CONTROL PANEL SCHEDULE

CRAC

1 3 - # 4 1 - # 8 1-1/4'70 70CRPGROUND ACCESS WELL

CUH 1 - # 4 1 - # 870 Y 70 1 3 - # 4 1-1/4'GROUND ROD

DCNUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER 1 3 - # 3 1 - # 8 1-1/4'80 80STATIC GROUND RECEPTACLE DDC

1 - # 3 1 - # 880Y 80 1 3 - # 3 1-1/4'LUMINAIRE CONTROL SYMBOLS DH 7. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES

WILL BE RUN IN SEPARATE RACEWAY FROM ALL OTHER

CIRCUITS.

A LIGHTNING AIR TERMINAL © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

100 100 1 3 - # 1 1 - # 8 1-1/2'DISC

DO 1 -# 1 1 - # 8100Y 100 1 3-# 1 1-1/2'GROUNDING CONDUCTOROCCUPANCY SENSOR CEILING MOUNT (X REPRESENTS

OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)

ELECTRONIC TIME CLOCK

PHOTO ELECTRIC CONTROL (X REPRESENTS

OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)

LOW VOLTAGE SWITCH

* DENOTES SWITCH NAME, SEE LIGHTING

CONTROL PANEL & SWITCH SCHEDULE.

SINGLE POLE SWITCH

SWITCH NOTATIONS:

DENOTES 3-WAY SWITCH

DENOTES 4-WAY SWITCH

DENOTES WALL BOX DIMMER SWITCH

WSX DENOTES OCCUPANCY SENSOR

(X REPRESENTS SCHEDULE DESIGNATION)

DENOTES PILOT SWITCH

DENOTES TIMER SWITCH

DWG 1 - # 6110 110 1 3-# 1 1-1/2'8. A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE

INSTALLED WITH CIRCUIT CONDUCTORS TO ALL

RECEPTACLES.

PANELBOARD E/O

110Y 110 1 3 - # 1 1 -# 1 1 - # 6 2EC

3-# 1/0 1 - # 6I~pe1 125 125 1 1-1/2'ECB

9. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE

CEILING, ETC. UNLESS OTHERWISE INDICATED ON THE

PLANS OR IN THE SPECIFICATIONS. CONDUIT IN

MECHANICAL ROOMS, AND STORAGE ROOMS WITHOUT

CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

EF 125Y 125 1 3-# 1/0 1 - # 1/0 1 - # 6 2

EM 1 - # 6150 150 1 3-# 1/0 1-1/2'

EMT

3-# 1/0 1 - # 1/0 1 - # 6150Y 150 1 2

ESs 175 175 1 3 - # 2/0 1 - # 6 2ETR

10. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED

WALLS SHALL BE OFFSET A MINIMUM OF 6"

HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE

ALLOWED.

3 - # 2/0 1 - # 2/0 1 - # 6175Y 175 1 2EWC

EWH

1 3 - # 3/0 1 - # 6200 200 24

FD 3 - # 3/0 1 - # 3/0 1 - # 6200Y 200 1 2-1/2'

FA

1 3 - # 4/0 1 - # 4225 225 2FCU 11. COORDINATE AND CO-LOCATE WALL MOUNTED

RECEPTACLE LOCATIONS WITH TECHNOLOGY

(VOICE/DATA, ETC) OUTLETS SHOWN ON THE T-SERIES

DRAWINGS UNLESS OTHERWISE NOTED, EACH

TECHNOLOGY OUTLET SHALL BE LOCATED WITHIN 24"OF

ITS ASSOCIATED RECEPTACLE. ASSOCIATED RECEPTACLE

SHALL BE DEFINED AS THE RECEPTACLE NEAREST THE

LOCATION OF, AND AT THE SAME HEIGHT AS,THE

TECHNOLOGY OUTLET WHEN MULTIPLE RECEPTACLES

ARE SHOWN ON A WALL.

P 225Y 1 3 - # 4/0 1 - # 4/0 1 - # 4 2-1/2'225GC

T

GD 1 - #4250 250 1 3-250 2-1/2'

GFI 250Y 1 1 -250 1 - #4250 3-250 3'

GND

1 - # 4300 300 1 3-350 3'GWH

300Y 1 1 -350 1 - # 4 3-1/2'300 3-350HDRECEPTACLE SYMBOLS HP 1 - # 3350 350 1 3-500 3'

HVAC 1 - # 3350Y 350 1 3-500 1 -500 3-1/2’

HWBDUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT 12. DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS

(EWC) SHALL BE CONCEALED BEHIND WATER COOLER

ACCESS PLATE OR BE DIRECTLY BELOW AND CENTERED

ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO

BE INSTALLED.

1 1 - # 3380 380 3-500 3'HWP

IEWHDOUBLE DUPLEX RECEPTACLE 1 - # 3380Y 380 1 3-500 1 -500 3-1/2’ o400 1 1 - # 3IH 400 3-500 3'ABOVE COUNTER DUPLEX RECEPTACLE IMC 1 - # 3400Y 400 1 3-500 1 -500 3-1/2’-e COSIMPLEX RECEPTACLE IWH CO13. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR

FURNITURE AND EQUIPMENT LOCATIONS WITH

ARCHITECTURAL PLANS, ELEVATIONS AND REVIEWED

SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL

ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL

ADJUST RECEPTACLES, OUTLETS OR CONNECTION

LOCATIONS TO ACCOMMODATE FURNITURE AND/OR

EQUIPMENT.

450 3 - # 4/0 1 - # 2450 2 2 oJ-BOX O450Y 3 - # 4/0 1 - # 4/0 1 - # 2 2-1/2'450 2 CDMAURECEPTACLE NOTATIONS:

DENOTES DEDICATED OUTLETS

DENOTES ELECTRIC WATER COOLER OUTLETS

DENOTES GROUND FAULT INTERRUPTER OUTLETS

1 - # 2500 500 2 3-250 2-1/2'MAX a:a: <j>

MC 500Y 1 -250 1 - # 2500 2 3-250 3’EWC

GFCI

O'a: <

MCC 1 -# 1600 600 2 3-350 3’ oMDF

600Y 1 -350 1 -# 1600 2 3-350 3’ O CDWP DENOTES WEATHER PROOF OUTLETS MDP

CO1 - # 1/0700 700 2 3-500 3’14. ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT

SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND

MECHANICAL EQUIPMENT. ALL MOUNTING OF

ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON

EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL

BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

MIN.X1 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 OUTLETS

DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 OUTLETS o Ct3MNS 1 - # 1/0700Y 700 2 3-500 1 -500 3-1/2'X2

MTD

1 - # 1/0800 800 2 3-500 3’

MTG

1 - # 1/0800Y 800 2 3-500 1 -500 3-1/2'MTS COo1000 1000 1 - # 2/03 3-400 3’NIC EMOTOR & EQUIPMENT CONNECTION

SYMBOLS

1 - # 2/0NL 1000Y 1000 3 3-400 1 -400 3-1/2' CO15. CONTRACTOR TO PROVIDE SUITABLE MECHANICAL

PROTECTION AROUND ALL CONDUITS STUBBED OUT

FROM FLOORS, WALLS OR CEILINGS DURING

CONSTRUCTION TO PREVENT BENDING OR DAMAGING OF

STUB OUTS DUE TO CARELESSNESS WITH

CONSTRUCTION EQUIPMENT.

NL/EL 1200 1200 4 1 - # 3/03-350 3’ oa:NTS 1200Y 1200 4 1 -350 1 - # 3/03-350 3’

OC "OCD orELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS, SIZED

PER NEC. COORDINATE REQUIREMENTS WITH CONTRACTOR

FURNISHING MOTOR OR EQUIPMENT. REFER TO

SPECIFICATIONS AND EQUIPMENT WIRING SCHEDULE FOR

ADDITIONAL WORK ASSOCIATED WITH MOTOR OR EQUIPMENT.

2500 2500 7 3-500 1 -350 3-1/2'OFCI

OFOI

CD

2500Y 1 - 500 1 -350 4’2500 7 3-500 COPH 16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE

REPAIRED TO MATCH EXISTING BY A QUALIFIED

CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR.

ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

FEEDER SCHEDULE NOTES:

THE SCHEDULE IS A SCHEDULE OF TYPICAL FEEDERS AND SOME OF THE SIZES

MAY NOT APPLY TO THIS PROJECT.

PNL CD

PVC 1. COVFD o oDdVARIABLE FREQUENCY MOTOR CONTROLLER RCP O)

RECPTNON-FUSIBLE DISCONNECT SWITCH o o oALL THE CONDUCTOR AMPACITIES ARE BASED ON TABLE 310.15(B)(16) OF THE

2017 NEC FOR COPPER CONDUCTOR TYPE THHN/THWN-2

2.REF

FUSIBLE DISCONNECT SWITCH REQ’D 17. DRAWINGS INDICATE THE EXTENT OF HAZARDOUS

LOCATIONS. INSTALLATION MEANS AND METHODS SHALL

BE SUITABLY RATED FOR THE ENVIRONMENT INDICATED

ON THE DRAWINGS.

s RF FEEDER SIZES SHOWN ON THE RISER DIAGRAM INDICATE FEEDER AMPACITIES

AND DO NOT NECESSARILY CORRESPOND TO THE CIRCUIT BREAKER AMPACITIES.

CERTAIN FEEDERS MAY BE SIZED FOR DERATION FACTORS AND/OR OVERSIZED

FOR VOLTAGE DROP PER NEC REQUIREMENTS.

3.MOTOR STARTING SWITCH WITH OVERLOADS ISSUEDMS RGSs 10/04/19 REVISED BID

DOCUMENTS

MOTOR STARTING SWITCH WITHOUT OVERLOADSMX RMC£ 18. ALL INTERLOCKING REQUIRED BY THE DRIVE

MANUFACTURER BETWEEN THE VARIABLE FREQUENCY

DRIVE AND THE DISCONNECT SWITCHES SHALL BE THE

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

RTUMTS MANUAL TRANSFER SWITCHEo S/No l?bl PR0fiENCLOSED CIRCUIT BREAKERc SE=3

SEC-PT3

CD 19. SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM

REQUIREMENTS FOR BUS BRACING AND DEVICE RATING.

ALL EQUIPMENT SHALL BE FULLY RATED UNLESS

SPECIFICALLY NOTED AS SERIES RATED.

SFE

SP

IC&ITssoo T3 sw=3 OREGON so/v/sf

EXPIRES:

x

TBR 20. EC SHALL REFER TO T-SERIES AND FA-SERIES SET OF

DOCUMENTS INCLUDED IN THIS BID PACKAGE FOR ALL

TELECOMMUNICATION AND FIRE ALARM WORK

ASSOCIATED WITH THIS PROJECT. EC SHALL INCLUDE IN

THIS BID ALL LABOR AND MATERIALS REQUIRED FOR THE

COMPLETE BOXES AND RACEWAY SYSTEMS FOR BOTH

TELECOMMUNICATION AND FIRE ALARM SYSTEMS (BOTH

NEW AND FUTURE). ALL CABLE TRAY, CONDUITS, BOXES

AND OUTLETS REQUIRED FOR TELECOMMUNICATION AND

FIRE ALARM SYSTEM INSTALLATION SHALL BE

COORDINATED WITH THE ASSOCIATED DRAWING SET AND

VERIFIED IN FIELD WITH TELECOMMUNICATION AND FIRE

ALARM CONTRACTORS PRIOR TO ROUGH-IN.

COORDINATE CONDUIT BETWEEN ALL SYSTEMS FORA

CLEAN INSTALLATION.

C

TCPo

I TFA

TFBo

CM

TYP

UCcr

UG

LU

UHo

I 3142200-121252.01 10/04/19

M&H NO.:

LU UNO DATE:

DESIGNED BY: JRH

KAS

o UV

CM

LO VCM DRAWN BY:

VFDCM IMRCHECKED BY:VSo o DO NOT SCALE DRAWINGSCM wCM wcc SHEET CONTENTS

CO NOTES, SYMBOLS &

ABBREVIATIONS

WH03

O WLo

WP>CD XFMR¥

XPo

SHEET NO.:

CL

CM

CO

E-001CO

o

CM

O

E o o c =5

"O E oo ■O =5 X c o

Ih» o

CM

LU

O i

LU

O

CM

LO

CM

CM

i O o

CM

CM

CO

O o

O

CL

CM

CD

CO

O

MeadPOWER GENERAL NOTES:

lunt1. ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL BE

SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND OUTSIDE OF

THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE ROUTED

BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT SHALL NOT BE

ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL BE ATTACHED TO

HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL SUPPORTS AS

REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN HANGAR 123

SHALL BE NEMA4X. COORDINATE ROUTING WITH OTHER TRADES. ALL

CONDUIT IN HANGAR 123 SHALL BE RMC.

PANEL 1/LB ^ PANEL 1/LC

UNLESS NOTED OTHERWISE

PANEL 1/LD ^x PANEL 1/LD

UNLESS NOTED OTHERWISE

x PANEL 1/LF

UNLESS NOTED OTHERWISE

<T Mead & Hunt, Inc.

9600 NE Cascades Parkway

Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com

IUNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE

OFFICEI

@ CU-1 @ CU-219 9.304) 19

ft r112GFCI/WP GFCI/WP

€fftr5s 2. SEE DRAWINGS E-151 AND E-152 FOR AREA CLASSIFICATION ZONES.VES □<H>oooooooo29 1 111 REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU

LEAD-LINED WALLS.

3.□ ^25

9.301) TYP OF 4SW CUH72" TETRATECHIt1 1 "l

1 REFER TO E-603 FOR ELECTRICAL EQUIPMENT WIRING SCHEDULE.1 ' 4.u u u 27 2/LB-16.18

HP-3

25 31SW www. tetratech. com

BREAK ROOM KEYED NOTES29 711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

(9.312)1‘113 3n n n ft l27 SW GFCI/WP

■ TT10 EC□ 9.301 ROUTE MECHANICAL EQUIPMENT BRANCH CIRCUITS UNDERGROUND

BETWEEN EQUIPMENT AND DISCONNECTS.

CU-1

CU-21 I UP OFFICE1HP-1

(9.337) 1/LF-23,251 3109|ft IGFCI/WP GFCI/WPftPANEL 1/LD 31 PROVIDE 200A, 3-POLE, 4-WIRE GENERATOR RECEPTACLE. COORDINATE

EXACT NEMA REQUIREMENTS WITH BASE PRIOR TO ORDERING.

9.302IIpar Viol i=<n>l'°r 11

<U>7(0) OHD

oT 1/LC-9 <u> til rrsf(0)

2/LE-9

OHD I GFCI46' 1 9 11i/lb-8 □i 391 /LB-1,3,5

BEAD

9.304 ELECTRICAL MAIN SERVICE CHASE. ELECTRICAL CHASE CONTINUES UP TO

BOTTOM OF ELECTRICAL ROOM ON THE EQUIPMENT FLOOR. CONDUITS TO

ENTER THE BOTTOM OF SERVICE SWITCHBOARD. COORDINATE

INSTALLATION WITH TELECOM SERVICE CONDUITS AND FOUNDATION WALL

OPENING.

I GFCIi SWPFT

EQUIPMENT

ROOM

1/LD-3939 1 1

^7 i 7^46 1 1

HD@MEN’S 91/LC-5

EEWS-1

/ 11 OIL ANALYSIS

ROOM

SW1107 PANEL 1/LB 1/LD-33 © Copyright 2018

This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

(9.312) 1 9X1I ft•fLi ft/ 108SW7!46' \ XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL

THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL

INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO

WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH

THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX

IN CMU WALL.

9.307 3 O tt>3. A

GFCI/WP^ EEWS-1

1/LF-28

GFCI 46’■ P/^INT MIXING

HibOM/STOR

6 22JAN Il 46"MEN'S

LOCKER

ROOM

37 ft9\/\ 1/LD-39

____ I I I GFCI 116 y PANEL 1/LF(ON ROOF) 126 G@PFT <H>\. A 13STORAGE115 3146”

4 , 9.312 RECEPTACLES DESIGNATED WITH 'SW' ARE CONTROLLED VIA OCCUPANCY

SENSOR. PROVIDE PLUG LOAD POWER PACK(S) ASSOCIATED WITH CEILING

MOUNTED OCCUPANCY SENSOR(S). REFER TO ASSOCIATED LIGHTING

PLANS FOR OCCUPANCY SENSOR TYPE AND LOCATION.

^6 n 115A W

II A Igfci , 2 —Ll-l'Q/ r * L 46" 13 1324 ^GFCI m WOMEN'SWOMEN'S

LOCKER

ROOM

1/LB-2 _

EEWS-1 (Ql

_ 1/LC-7

IQ) EEWS-1

22° d1 INSPECTION 1/LF-14.16 (3#10, 3/4"C.)

-0 L6-30R

^ PL-1

3 PL-2

9.313 PROVIDE 4” SQUARE BOX WITH 1" CONDUIT INSTALLED BETWEEN JUNCTION

BOX AND PANEL 1/LD FOR FUTURE. PROVIDE PULL STRING. JUNCTION BOX

INSTALLED AT 18”AFF. COORDINATE WITH MILLWORK CONTRACTOR.

1/LD-41 BAY

HALLWAYHDGFCI GFCI□ 10311813(§) BLAST @

1024 4PAINT 1 GFCI/WPGFCI FILM VIEWING

ROOM 5 9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER

FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS

REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR

WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE

ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.

46' 4 tBEAD BOOTH

ROOM

I □\GFCIPAINT BOOTH

GFCI^tr™r <H><

17 107 17 46"<H>e125 LAUNDRY

ROOM

PANEL PPE CLEAN

ROOM/

CIRCULAT.

127 6 20 1 /

15 15@CR119 tI gjGFCI^ ^ GFCI REFER TO DETAIL 2/E-501 FOR SCHEMATIC DIAGRAM OF X-RAY INTERLOCK

SYSTEM.

9.320PL-1 1/LF-10120

1/LF-2,4,6 <U> 1/LF-18

XRAY

I

19PANEL 1/LB

UNLESS NOTED OTHERWISE

X-RAY CR 6I____ I <u> 9.321 PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED

WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).

PROVIDE WALL MOUNT BRACKET LWMB2.

10524 i i® 1/LF-8■24 oBEACON LIGHT

@ 7-6"STENCIL

ROOM @CR31 V21FIRE

PROTECTION

ROOM

ALL DISCONNECT SWITCHES IN HANGAR 123 SHALL BE NEMA4X.9.332

H 1/LF-12 320) •AIR LOCKI 9.320 CO9.I GFCI/WP 18 COb 121 ■H h rI 6 9.321 o9.337 PROVIDE A TOTAL OF TEN (10) - 1" SPARE CONDUITS WITH PULL STRING

FROM PANEL 1/LD (SECOND TUB) TO ABOVE ACCESSIBLE CEILING AND CAP

FOR FUTURE USE.

I 24 oI V^ST. CD122 I m a: a: UiI 21MPM■CUH O'PANEL 1/LA

UNLESS NOTED OTHERWISE a:1©24

□ ofl X-RAY VAULT ROOM(9.332) lI O CDGFCI/WP COL1

5 104TTP-3 REM-1 oSMS 26 [26\ COGFCI/WP

1/LD-26

1/LA-33 1/LA-27 □ft ft1/LA-37 46" 46' 2vBAP-1

1/LA-25

tL I rl /z z zII BEACON LIGHTn A \<U)I @ 7'-6"GFCI/WP COo5I E9.320

CO9.321I rTO ELEC ROOM GROUND BUS oI a:1/LD-38,40 "OI ^ PANEL 1/LF

UNLESS NOTED OTHERWISE CD q:HP-2 CDI CO13

46' GFCI/WP

GFCI/WP CD1

COO ODdPANEL 1/HA O) FIRST FLOOR POWER PLANF o o oLCP i 1 1/8" = r-o"(9.316

OHD@

1/LA-17

ISSUED

(0) DOOR-1

1/LE-1,3,5

(0) DOOR-2

1/LE-2,4,6

10/04/19 REVISED BID

DOCUMENTSa£

E o o c =5

"O

CO

CD

E □ I

\$\T,o 13o ■o

46=5 OREGON

so/v/sf

EXPIRES:

GFCI/WP^

PANEL 1/LA^

x c L 1 1 . vZ o 4 45 DC/1LEl I GFCI GFCI

10 10o JICM cnPANEL H MTS/1 LE < Icr

L GENERATOR

PLUG

GFCI/WP

-o (9.302)ILU LAUNDRY

ROOM

GFCIo I 3142200-121252.01

10/04/19

M&H NO.:

II42 MOUNT UNDER SINK FOR

FUTURE GARBAGE DISPOSAL

ILU

12 DATE:1 119o I JRHDESIGNED BY:CM

— DOOR-1

DOOR-2

10 11 fUIL3

64" 64' KAS7ICM DRAWN BY:.31346" EF-1 1GFCI3K(f)>42 (J)21 ^ GFCI <n>42" 11 13CM 1/LA-39 IMRGFCI/WPGFCI/WPGFCI/WP 1/HA-1,3,5 DRY(C

1/LD-14.16

\ 46 CHECKED BY:

SMS 1o ■^>■9 ftGFCI 17a 15O DO NOT SCALE DRAWINGSJCN ECN

<U> <u> SHEET CONTENTSi r 1 i^-nGFCI/WPCO GFCI/WP FIRST FLOOR

POWER PLAN

rCD 3 3o GFCI/WPo

CD

ENLARGED LAUNDRY - ROOM 111 ENLARGED KITCHEN AREA - ROOM 113o 3 2______ PANEL 1/LA y

(9.332) UNLESS NOTED OTHERWISE “

1/4" = 1-0" 1/4" = 1-0"H h

SHEET NO.:

CL

c» NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS OTHERWISE NOTED. NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS

OTHERWISE NOTED.

-H-

CO

E-101CO

a) o

CN

Mead l luntKEYED NOTES I

9.202 MOUNT FIXTURE AT 9'-0" AFF MEASURED FROM BOTTOM OF FIXTURE. Mead & Hunt, Inc.

9600 NE Cascades Parkway

Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com

9.203 MOUNT FIXTURE AT 8'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.

4.

9.204 MOUNT FIXTURE AT 8'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.

MOUNT FIXTURE AT 7'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.9.205

MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM

OF FIXTURE.

9.212 TETRATECHIt

9.314 FIRE PUMP CONTROLLER www. tetratech. com

711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

9.315 JOCKEY PUMP CONTROLLER

Il=l@ <H)46"AP 9.317 INSTALL L5-20 SIMPLEX RECEPTACLE TO SIDE OF CABLE TRAY (TYPICAL OF 4). REFER TO DETAIL 8/E-501.2/LB-11 1 (9.330)XFMR T-1MSB/HA PANEL MDP/LA PANEL 2/LE a PROVIDE SURGE PROTECTIVE DEVICES (SPD) ON ALL 120VAC CIRCUITS

ASSOCIATED WITH EQUIPMENT FED FROM PANEL 2/LE. PROVIDE HINGED

TERMINAL BOX ADJACENT TO PANEL 2/LE FOR ALL SPD(S). SPD MUST HAVE

BOTH UL 1449 AND UL 1283 LISTING.

9.330

PANEL 2/LA

(9.331 )(9.317}1

ELEC.

IT 9.331 HOUSEKEEPING PAD BY OTHERS. COORDINATE SIZE AND LOCATION WITH

GENERAL CONTRACTOR PRIOR TO INSTALLATION.

1 202PANEL 2/LB PANEL MP/HA

203 2/LA-1

$46'' iGNDlGNDl

2/LA-11 © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

(JP 46" 46'

& I M.La t n ni—1

ENLARGED FIRE PROTECTION ROOM 122 ENLARGED PLAN - ELEC 2034 31/4" = r-o’ i/4n = r-o"

NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LB, UNLESS NOTED OTHERWISE.

o CO COtr o_ ................... ...................__ o CDIT N

♦ [ ] 2/LA-2[-(9.203) N1ET I203 J a:ELEC.N1 N1 IT ELEC. a: a> (TYP.)( 9.204} 202 I 203 202 O'a: <

2/LA-2 2/LA-2 92/LA-2t In oGFCI/WP46'NE l__3 3g 2/LA-2 s s O CD17t'1 4 CO2/LA-2 PANEL 2/LA- 7 o Ct31/LD-36

OCEN .N {^2} DM

[ 1 I 1 1/HA-12Ra

* VIA LCP FOR PE ON /

“TIMECLOCK OFF

2/LA-2 2/LA-2

COo E=□ ERU-1

CO/

oa:NEN N / [ 1 I I 1 h ■O46" CD or2/LA-2 2/LA-22/LA-2 2/LA-2 17 CD/

CO/

< CD

COO ODd/ O)N

I 1 O o o/2/LA-2 2/LA-2N N @AHU-2t 1 I I

2/LA-2 2/LA-2 /

EQUIPMENT

ROOM

ISSUED

10/04/19 REVISED BID

DOCUMENTS201 EF-2 (0)

2/LA-35

E o NE NEo N N

[ 1 ] 1 PRO/,c =3 2/LA-2 2/LA-2 2/LA-2/LA-2 2/LA-2 46'T3 17to

CD

E

IC&IT,oo ■O

=5 OREGON

so/v/sf tyfj. HUO^

EXPIRES:

x C o I

N N N N1 I 1 \ ] 1O

2/LA-2 2/LA-2 2/LA-2 2/LA-2CM □ □

LU

O

I 3142200-121252.01 10/04/19

(§) MAU-1 M&H NO.:

LU

DATE:

o

JRHDESIGNED BY:CM

LO

KASCM NE NEN N DRAWN BY:

I- ] [ ]CM IMR2/LA-2 2/LA-2 CHECKED BY:2/LA-2 2/LA-2oo DO NOT SCALE DRAWINGSHPW-2 HPW-1CM

CM @ O SHEET CONTENTS

CO EQUIPMENT FLOOR

ELECTRICAL PLANS

COoo ilrr? mn r>

CD

EQUIPMENT FLOOR LIGHTING REFLECTED CEILING PLAN EQUIPMENT FLOOR POWER PLANo

12 1/8" = 1 '-O' 1/8" = 1'-0' SHEET NO.:

CL

O

LO

CD NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LA, UNLESS NOTED OTHERWISE.

E-102CO

a) o

MeadLIGHTNING PROTECTION AND

GROUNDING GENERAL NOTES: lunt

1. THE LIGHTNING PROTECTION SHALL REQUIRE AN INSPECTION PRIOR TO

ACCEPTANCE PER UFC 3-575-01. THE SYSTEM SHALL BE INSPECTED BY A

COMMERCIAL, 3RD PARTY INSPECTOR WHOSE SOLE WORK IS LIGHTNING

PROTECTION AND SHALL BE CERTIFIED BY THIS 3RD PARTY INSPECTOR AS

COMPLIANT WITH AFI 32-1065 AND NFPA 780.

Mead & Hunt, Inc.

9600 NE Cascades Parkway

Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com

THE USE OF BUILDING STEEL AS DOWN CONDUCTORS IS NOT PERMITTED.2.G G

INSTALLATION OF THE LIGHTNING PROTECTION SYSTEM SHALL NOT VOID

THE WARRANTY OF THE ROOF.

3.

4. ANY EXHAUST AND VENTS SHALL BE PROTECTED BY ADDITIONAL AIR

TERMINALS. REFER TO MECHANICAL AND PLUMBING PLANS. TETRATECHIt www. tetratech. com

711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254KEYED NOTES

322}9.

A PROVIDE BIMETALLIC CONNECTOR BETWEEN #1/0 AL AND #2 AWG CU DOWN

CONDUCTOR. PROVIDE #2 AWG CU "DOWN CONDUCTOR" FROM ROOF TO

GROUND TERMINAL AS INDICATED. "DOWN CONDUCTOR" SHALL BE

ROUTED IN CONDUIT INTERIOR TO THE BUILDING AND WITHIN CMU/STUD

CAVITY WHEREVER POSSIBLE.

9.322VA A

G

G

LIGHTNING PROTECTION SYSTEM GROUND TERMINALS SHALL BE MINIMUM

3/4" X 10'-0" COPPER-CLAD STEEL GROUND ROD BURIED INTO EARTH 1'-6"

TO TOP OF GROUND ROD. CONDUCTORS SHALL BE PERMANENTLY

CONNECTED TO GROUND TERMINAL WITH EXOTHERMIC WELD. PROVIDE

MINIMUM ONE (1) GROUND TERMINAL IN A GROUND ACCESS WELL FOR

TESTING REQUIREMENTS. REFER TO PLANS FOR EXACT QUANTITY OF

ACCESS WELLS.

9.323

G © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

A A G

A A PROVIDE #1/0 AL "MAIN-SIZE LIGHTNING CONDUCTOR" FOR INTERCONNECT

OF ALL AIR TERMINALS ON ROOF.

9.324

G

CONNECT LIGHTNING PROTECTION SYSTEM / GROUND RING TO BUILDING

GROUND VIA MAIN GROUND BAR IN ELECTRICAL ROOM. REFER TO DETAIL

1/E-503 FOR ADDITIONAL REQUIREMENTS.

9.325

G

PROVIDE #1/0 BARE COPPER COUNTERPOISE GROUND RING SYSTEM

INSTALLED A MINIMUM OF 3'-8" AWAY FROM STRUCTURE. GROUND RING

SHALL BE BURIED AT LEAST 30" BELOW GRADE.

9.326

GA A

20'-0" MAXIMUM SEPARATION BETWEEN AIR TERMINALS ALONG ROOF

PERIMETER AND AS INDICATED (TYPICAL).

9.327

A A

BOND STRIKE TERMINATION DEVICE DIRECTLY TO TOP OF MECHANICAL

UNIT.

9.328

G

BOND TO BOTTOM OF MECHANICAL UNIT METALLIC ENCLOSURE.9.329

G

A A G oGA A CO CO ooG CD cccc<j>A o'G cc< =a= o

O CD co O Ct3

<LIGHTNING PROTECTION

AND GROUNDING SYMBOLS coo E

CO

<§> GROUND ROD ooc ~oCD orGROUND ACCESS WELL CD

COA LIGHTNING AIR TERMINAL

< CDSTATIC GROUND RECEPTACLE

COO ODC O)

o O OG GROUNDING CONDUCTOR

ISSUED

10/04/19 REVISED BID

DOCUMENTS(9.323

E o o c =5

"O

CO

E

IC&IToo ■O

=5 OREGON

so/v/sf

EXPIRES:

x C o I i*-o

CM

LU

O

I 3142200-121252.01 10/04/19

M&H NO.:

LU

DATE:

O

JRHDESIGNED BY:CM

LO

KASCM DRAWN BY:

CM IMRCHECKED BY:

O o DO NOT SCALE DRAWINGSCM

CM

SHEET CONTENTS

CO

LIGHTNING

PROTECTION AND

GROUNDING PLAN

CO

O o

QC

O

LIGHTNING PROTECTION AND GROUNDING PLAN SHEET NO.:1CL

i/8n = r-o1

LO

CO

E-103CO

CD

o

MeadLIGHTING GENERAL NOTES:

PANEL 1/LB ^ PANEL 1/LC

UNLESS NOTED OTHERWISE

PANEL 1/LD y

UNLESS NOTED OTHERWISE “

x PANEL 1/LD

UNLESS NOTED OTHERWISE

x PANEL 1/LF

UNLESS NOTED OTHERWISE<TI luntUNLESS NOTED OTHERWISE

1. REFER TO SHEET E-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.

OB OAEVIA LCP FOR PE ON /

TIMECLOCK OFF

1/HA-14Rb

VIA LCP FOR

PE ON/OFF

(MTD ON ROOF)

2. REFER TO SHEET E-601 FOR LUMINAIRE SCHEDULE.1/HA-12Ra

VIA LCP FOR PEON/®

TIMECLOCK OFF

Mead & Hunt, Inc.

9600 NE Cascades Parkway Suite 100

Portland, OR 97220 phone: 503-548-1494 meadhunt.com

OCE

REFER TO SHEET E-602 FOR OCCUPANCY SENSOR, LIGHTING CONTROL

PANELAND SWITCH STATION SCHEDULES.

3.1/HA-12Ra

X

IB1E

34 •-

VEST. 4. EC SHALL ALLOW TIME AND EFFORT FOR ALL OCCUPANCY SENSOR AND

PHOTO SENSOR CALIBRATION.

D1 D1E D1E0 0 0 11130a 30a 30a a DiA3OCE—

1/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

OFFICEI LOCATION OF CEILING OCCUPANCY SENSORS ON THIS PLAN ARE SHOWN

DIAGRAMMATICALLY AND DOESN'T SUGGEST ACUTAL LOCATIONS. EC SHALL

COORDINATE EXACT PLACEMENT IN FIELD BASED ON THIE INSTALLED

DUCTWORK, PIPING AND DIFFUSERS TO PREVENT OCCUPANCY SENSOR

NUISANCE TRIPPING. DO NOT INSTALL SENSORS WITHIN 3'-0" OF DIFFUSERS.

5.TRAINI MG /

BREAK ROOM

30 mD3 D3 '□ (

- OC11230b 30b uJ 30c OSI l-01/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

-(9.216)

112 ®3SDc ( 9.211)—| u X1 TETRATECHIts-D |©303 bO D3o ® Dba,b,c,d

■a,b,c,d 30b 0BEOC1 OC1 OCE OAESS 05- (9.212PANEL 1/LD(9.211 6. ALL EMERGENCY BATTERY OPERATED EXIT LIGHTS AND EBU'S SHALL BE

WIRED FROM SAME LIGHTING BRANCH CIRCUIT AS ROOM BEING SERVED.

Da www. tetratech. com341/LA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF '

1/LA-12Ra VIA LCP FOR PE ON / f

TIMECLOCK OFFQ

1/HA-12Ra

^«VIA LCP FOR PE ON/

1/HA-12Ra 'OSl)0DD1 D1E D1 D1E 711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

D1® VIA LCP FOR PE ON /

TIMECLOCK OFF

0 0 0 0 03430a 30a 30a 30a TIMECLOCK OFF30a ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL

BE SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND

OUTSIDE OF THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE

ROUTED BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT

SHALL NOT BE ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL

BE ATTACHED TO HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL

SUPPORTS AS REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN

HANGAR 123 SHALL BE NEMA4X. COORDINATE ROUTING WITH OTHER

TRADES. ALL CONDUIT IN HANGAR 123 SHALL BE RMC.

7.■3 - z z z

=FD1\J MEN'S

$ S3 \(9.209 Sa30a OFFICE[—(9.21o) X1 X1r^. EQUIPMENT

ROOM

(0S10-" a/4T4-4 ]N3 U 30d U 30d AE A0 [X1 D1Es 19C 30aC 30bOCE 0 19B

I® ”QE 2 110A AEQ Q QE 3bCO 30a1/HA-12Ra'~'

VIA LCP FOR PE ON /

TIMECLOCK OFF

L 34

SJ3 d

.osi OIL ANALYSIS

ROOM

(TYP.

30b 30a® ®a

T k _D2

19 19D1E -D1 D1E D1 D1<RB€JT MIXING

ROOM/STOR

OSUb •0 0 030b 30b 30b 30a (OS3) r D 108PANEL 1/LB- TYP. /T REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU

LEAD-LINED WALLS.

8.126 , A AI7 7 2 D2 .OSI3DC 30a 0BE 19 1930 w30 IN3

|-( 9.206) /n? C 30C^^l

30a 340D1 3b 30b

C CI

© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

KEYED NOTES2 (osi)b N2E N2JAND2- [ ] hs /.----- N1N1-P.0S2 30 21b30b MEN'S 30b

LOCKER CE

ROOM

21a116s 30Q Q Q PANEL 1/LF4 C

L30

0 ws a C03bws- 9.206 OCCUPANCY SENSORS SHALL BE PENDANT MOUNTED BELOW ALL

STRUCTURAL BEAMS, PLUMBING AND MECHANICAL PIPING AND DUCTWORK

TO ALLOW FOR CLEAN VIEWING ANGLE.

INSPECTIONI CO D0 BE YCOL WSN1 30 \

/ \ C 32a

PD2'- D2

32 32

-SI® ©a

BAY♦(9.210)

(TYP.)

//. D30b30b 3a AI \ Aco34 ] 103□ ,N2 N2Bs ■ \ \ \ \□ C 32a 34T- 9.207 REFER TO DETAIL 1/E-501. TYPICAL FOR ALL WALL MOUNTED EXIT SIGNS

SHOWN ON THIS PLAN.

3CO C03 21a 21br 197 7 2 2 19WOMEN'S.

0D1 32b

3bCO C 32b

D1D1E0 (0Sl)b 0LAUNDRY

ROOM .

11732a .0S232b FILM VIEWING

ROOM

WS /a,b 9.208 MOUNT FIXTURE AT 32'-0” AFF MEASURED FROM BOTTOM OF FIXTURE.A .OSI.0: CO aBEAD BOOTH

ROOM

32119 BPAINT BOOTH 107N2 N2E /u BE 9.209 MOUNT FIXTURE AT 10'-O" AFF MEASURED FROM BOTTOM OF FIXTURE.I-125 D1 D1 3434 21a127 0 0 32a 21b3b 32bPANEL 1/LC-

HALLWAY A A 9.210 MOUNT FIXTURE AT 13'-0" AFF MEASURED FROM BOTTOM OF FIXTURE OR

ON NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL TYPE F FIXTURES

SHALL BE MOUNTED AT SAME HEIGHT.

II SQE 102

PE-CLEAN ROOM/

CIRCULAT.

WOMEN'S

LOCKER!

B

F xi® 19I 19X1 0S3 N2 N2BE BEB BBE L120 .0S3 9.211 MOUNT FIXTURE AT 13'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.t hCO34 34 34 34 340 34 21a 21bT18 03 B4CO, X-RAY CRI

342 MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM

OF FIXTURE.

9.212•-s 105PANEL 1/LB

UNLESS NOTED OTHERWISE

3 AE

cf=b 19AIR LOCK cEBUT 9.214 MOUNT FIXTURE AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.N1 N1 N2E N2I

21b9.209.0S2 21a32 32 9.215 PROVIDE WITH NEMA 4X ENCLOSURE./

Q FIRE I

PROTECTION

,ROOM |

(TYP.)( 9.206)-—(0S2)OB STENCIL

ROOM .

I 9.216 MOUNT FIXTURE BELOW MEZZANINE STAIR LANDING AT 9'-6" AFG

MEASURED FROM BOTTOM OF FIXTURE.

a,b /1/HA-14Rb

VIA LCP FOR

PE ON/OFF

(MTD ON PARAPET)

I o/9.307 W121122 N2 N2 / X-RAY VAULT

ROOM

[ h 19 C 19 9.217 FIXTURE SHALL BE TRAPEZE MOUNTED BELOW MECHANICAL DUCTWORK AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE. CO/21a 21bN1 N1 CO9.223 0-I2PANEL 1/HA

UNLESS NOTED OTHERWISE

o: 104VEST.MOUNT ON ROOF

AIM NORTH. I o<>>♦(9 32 32I CD.224 101l 9.220 MOUNT FIXTURE AT ROUGHLY 8'-6” AFF TO BOTTOM OF FIXTURE OR ON

NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL EBUS SHALL BE

MOUNTED AROUND HANGAR AT SAME HEIGHT.

sa a: a: o>. - N2 N2E C 19 C 19“ tLT PE O'WP 21aOC 21b 0£f510Re I__B c/*b 5f a

EBU1 I 1/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

F [-(9.209) J ® 3aSS o3b 3SX1EBU1 EBU1 EBU1 10Re (9.209

VIA LCP FOR PE ON /

TIMECLOCK OFF

1/HA-12Ra

X30)‘ l-O OCE

10Re 9.221 PROVIDE ADDITIONAL NEMA 4X STRUT SUPPORTS OFF OF STRUCTURAL

GIRDER TO ALLOW FOR EXIT SIGN MOUNTING. TYPICAL OF EXIT SIGNS IN

HANGAR 123. O CDm -+-EBU1WP OL COOAE SOCE f 1/HA-12Ra f VIA LCP FOR PE ON /

TIMECLOCK OFF

OC2Ra 1/HA-12Ra o1/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

CO

(9.209 (9.209VIA LCP FOR PE ON /

TIMECLOCK OFF 9.222 MOUNT TO COLUMN.

(9.208°2l <A1

PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED

WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).

PROVIDE WALL MOUNT BRACKET LWMB2. MOUNT BEACON LIGHT AT 7'-6".

BEACON LIGHTS (TYPICAL OF 3 WITH THIS NOTE) CONTROLLED BY SWITCH

IN AIR LOCK 124. BEACON LIGHTS SHALL BE CIRCUITED TO PANEL 1/LA-41.

WP 9.223o

HD-< 9.223)

O COJ o1/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

(9.316) Ex PANEL 1/LF UNLESS NOTED OTHERWISEfcm! CO10Rf oa: u9.224 PROVIDE SWITCH WITH ENGRAVED NAMEPLATE "XRAY BEACON LIGHTS". CDH or

— PANEL 1/HA

LCP 9.215)

EBU?g|

CD

C/)O^Rb O^Rb O^Rb oL 9.307 XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL

THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL

INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO

WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH

THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX

IN CMU WALL.

4Rb

< CD

COO ODdHANGAR O)

(9.208 9.211)123 o o o9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER

FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS

REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR

WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE

ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.

obOOC2 OC111/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

1/LA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

1/HA-14Rb

VIA LCP FOR

PE ON/OFF

(MTD ON ROOF)

ISSUED

10/04/19 REVISED BID

DOCUMENTS

E

O EBuii o Lo

6Rcc =5

"O

03 B1□9.222CD

E WP

IC&IToo (9.208

■o F=5 OREGON so/v/sf

EXPIRES: blio/fl lORf0^*x C

OC2o 1/HA-12Ra

VIA LCP FOR PE ON /

TIMECLOCK OFF

l i*-o

CM

9.221< OsRd (9.222) o 8Rd O EBU?fl

LL WP9.207 9.316)

F

QlORg

8Rd 8RdB2ir 10Rg2[^C^pEBU1

LU

O

I 3142200-121252.01 10/04/19

M&H NO.:EBU1 FX3 EBUIC^p ^lORgLU C^pEBUIA2 DATE:

UWPo

JRHDESIGNED BY:CM

LO

OCE O

1/HA-12Ra -

VIA LCP FOR PE ON /

TIMECLOCK OFF

□ □ KASCM DRAWN BY:1

CM IMRCHECKED BY:

9.223)

{9.209)

O

O DO NOT SCALE DRAWINGSCM

CM

SHEET CONTENTS

CO

FIRST FLOOR

LIGHTING PLAN

CD

O O PANEL 1/HA y

UNLESS NOTED OTHERWISE To i-

OB>

CD 1/HA-14Rb

VIA LCP FOR

PE ON/OFF

(MTD ON PARAPET)

x o

FIRST FLOOR LIGHTING PLAN SHEET NO.:1CL 1/8" = r-o"

LO

CO

E-121CO

o

Eoo c =5 "O

CD

E oo ■O=5 X c o

Ih» o

CM

LU

O iLU O

CM

LO

CM

CM

iOo

CM

CM

CO

03Oo

>cd¥ O

CL

O Is-

CO

o c =5 "O

CD

E oo ■O=5 X c o

Ih» o

CM

LU

O iLU O

CM

LO

CM

CM

iOo

CM

CM

CO

03Oo cd¥ O

CL

CM

O Is-

CO

o c =5 "O E oo ■O=5 X c o

Ih» o

CM

LU

O iLU O

CM

LO

CM

CM

iOo

CM

CM

CO

03Oo

>0¥ O

CL

CM

O Is-

CO

o c =5 "O E oo ■O=5 X c o

Ih» o

CM

LU

O iLU O

CM

LO

CM

CM

iOo

CM

CM

CO

03Oo

>0¥ O

CL

coo Is-

CO

o

Mead lunt

#2 GRD CABLE TRAY Mead & Hunt, Inc.

9600 NE Cascades Parkway

Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com

TYPICAL: DRY-TYPE TRANSFORMER IN ELECTRICAL ROOMS.

SEE PLANS FOR EXACT LOCATIONS AND ROOM NUMBERS.

#3/0 GRD #6 GRD TELECOM EQUIPMENT RACK(S)

W

EQUIPMENT GROUNDING

CONDUCTOR

PER NEC 250.122. SEE

FEEDER SCHEDULE

MAIN TELECOM ROOM

MAIN GROUNDING BUSBAR (TMGB) TETRATECHIt

STREET SIDE OF BUILDING

WATER METER. CONNECT TO

METALLIC WATER MAIN

WITHIN 5'-0" OF WATER

SERVICE ENTRANCE. PROVIDE

JUMPER ACROSS WATER METER.

A www. tetratech. com ww #3/0 GRD 711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

t

AAAALEAD-LINED SIDE OF HANGAR

123 OR XRAY ROOM 104.LEAD WRAP CONDUIT

ELBOW. PROVIDE ELBOW

ADJACENT TO WALL ---------

Y PANELBOARD(S) GROUND BUS

REBAR STUBBED THROUGH FLOOR BY FOUNDATION

CONTRACTOR.

15KVA-#8 AWG

30KVA-#6 AWG

45KVA-#4 AWG

75KVA-#3 AWG

112.5KVA-#2 AWG

150KVA - #1/0 AWG

225KVA - #3/0 AWG

300KVA-#4/0 AWG

J

CONDUIT PENETRATING LEAD WALL UL LISTED FITTINGS FOR THE

PURPOSE (TYP)#3/0 GRD

L © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

FOUNDATION REBAR

LEAD LINING. SEE ARCHITECTURAL PLANS. CONCRETE FOOTING

GROUND RING♦SWITCHBOARD

NEUTRAL BUS

GROUND BUS LOCATED IN

ELECTRICAL ROOM.

GROUND BUS

SWITCHBOARD

REMOVABLE LINK MAIN BONDING JUMPER -

SIZED PER NEC 250.28(D). @----- ©------®v GR GR GR

\NOTES:

GROUNDING ELECTRODE CONDUCTOR

SIZED PER NEC 250.66.

1. ALL GROUND CONDUCTORS TO BE ROUTED IN PVC CONDUIT.

2. ALL GROUND CONDUCTORS ON THIS DIAGRAM SHALL BE COPPER.

3. REFER TO SHEET E-103 FOR CONNECTIONS OF LIGHTNING PROTECTION SYSTEM TO GROUND RING.

® © GROUNDING SYSTEM DETAIL (TYP)CONDUIT THRU LEAD-LINED WALL DETAIL

NO SCALE NO SCALE

o

CO CO

oo CD a: a: <j> o'a: < o O CD co O Ct3

RED PLASTIC WARNING TAPE;

12" BELOW GRADE

CAST-IN PLACE CONCRETE

ENCASEMENT. COo E

CO

SECURE TOP SPACER TO PREVENT

CONDUITS FROM FLOATING DURING

CONCRETE POUR. oa:1" ABOVE SIDES OF DUCT.

CROWN DUCT TO A PEAK ■OCD orcdDUCTBANKS CONDUITS. SEE DIV.

26 SECTIONS FOR SIZES AND

QUANTITIES. CO

CD

(?) POWER

2) POWER SPARE

EPOXY COATED #4 REBAR;

CONTINUOUS ALONG

DUCTBANK (TYP)

COO ODd O) o O OPLASTIC CONDUIT

SPACERS/SUPPORTS

CONCRETE PAVERS FOR

LEVELING

ISSUED

10/04/19 REVISED BID

DOCUMENTS

E ' II- :| I l=l I :| I l=l I 111=11 11=1 I 1=1oo c ----- 3’ 3’ 3’ 3" UNDISTURBED EARTH=3

T3 DETAIL NOTES:to

CD

E

CONCRETE COVER DIMENSIONS SHOWN ARE MINIMUM.

IC&IToo

DUCT BANK SHALL BE A MINIMUM OF 36” BELOW GRADE.■o

=5 OREGON

so/v/sf

EXPIRES:

x C o I © ELECTRICAL DUCTBANK TYPICAL SECTION - 2 X 4i*-o

CM NO SCALE

<cr

LU

O

I 3142200-121252.01 10/04/19

M&H NO.:

LU

DATE:

DESIGNED BY: JRH

KAS

o

CM

LO

CM DRAWN BY:

CM IMRCHECKED BY:

Oo DO NOT SCALE DRAWINGSCM

CM

SHEET CONTENTS

CO

DETAILS©

Oo

><d

QC

O

SHEET NO.:

CL

o Is-

E-503CO

a) o

MeadOPTIONS/ACCESSORIES CODE LISTING: LUMINAIRE SCHEDULE 01 AIR HANDLING CAPABILITY - RETURN AIR luntSEE SPECIFICATION FOR ADDITIONAL INFORMATION REGARDING LUMINAIRE AND INSTALLATION REQUIREMENTS. PROVIDE OPTIONS AND ACCESSORIES REFERENCED BY THE COLUMN TITLED " OPTIONS/ACCESSORIES". MANUFACTURERS LISTED ACCEPTABLE SHALL MEET ALL

REQUIREMENTS AND FEATURES INDICATED. ACCEPTABLE MANUFACTURERS MUST MEET THE PHOTOMETRIC PERFORMANCE OF THE LISTED UNIT.NOTE:

3" DEEP PARABOLIC LOUVERS02

ABBREVIATIONS: GWB = GYPSUM WALL BOARD

ES = EXPOSED STRUCTURE

LG = LAY-IN GRID

R = RECESSED V = VARIES

S = SURFACE W = WALL MOUNTED

UNV = UNIVERSAL VOLTAGE

P = PENDANT

PLAS = PLASTER

PL = POLE MOUNTED

4" DEEP PARABOLIC LOUVERS03

Mead & Hunt, Inc.

9600 NE Cascades Parkway Suite 100

Portland, OR 97220 phone: 503-548-1494 meadhunt.com

04 SEMI-SPECULAR PARABOLIC LOUVER

LOW IRIDESCENT PARABOLIC LOUVER05 LED SYSTEM

INPUT

WATTAGE

LEDBALLAST/

DRIVER

CEILING

TYPE

FIXTURE

DEPTH

OPTIONS /

ACCESSORIES

KEYED

NOTEDELIVERED

LUMENS

DES. MANUFACTURER CATALOG SERIES DESCRIPTION LAMP DATA VOLTAGE MOUNT ACCEPTABLE MANUFACTURERSFLAT ALUMINUM DOOR FRAME06

REGRESSED ALUMINUM DOOR FRAME07

HE WILLIAMS 50 SERIES

3-1/4'A METALUX 24GR-LD5-34-A125-UNV-L840-CD1-U 2’ X 4' RECESSED LENSED TROFFER LED, 4000K UNV D R LG 26.7 3,51408 FLAT STEEL DOOR FRAME DAYBRITE LT LED SERIES SINGLE GASKETED DOOR FRAME09 TETRATECHItHE WILLIAMS 50 SERIES24GR-LD5-34-A125-UNV-EL14W-L840-

CD1-UAE METALUX SAME AS ’A' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV LG 3-1/4'D R 26.7 3,514 DAYBRITE LT LED SERIES10 DOUBLE GASKETED DOOR FRAME www. tetratech. com

CREE ZR SERIES

A2 METALUX 24CZ-LD5-35-S-UNV-L840-CD1-U 2' X 4' RECESSED VOLUMETRIC TROFFER LED, 4000K UNV LG 3-1/4'D R 25.3 3,63511 TRIPLE GASKETED DOOR FRAM, LENS & BODY 711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

HE WILLIAMS AT SERIES

ANTIMIRCOBIAL PROTECTION PAINTED FINISH12 CREE ZR SERIES24CZ-LD5-35-S-UNV-EL14W-L840-CD1 SAME AS 'A2' EXCEPT WITH EMERGENCY BATTERY OPTION 3-1/4'A2E METALUX LED, 4000K UNV D R LG 25.3 3,635-U HE WILLIAMS AT SERIES13 DAMP LOCATION LISTED CREE ZR SERIES14 STAINLESS STEEL TRIM & DOOR FRAME A3 METALUX 24CZ-LD5-50-S-UNV-L840-CD1-U 2' X 4' RECESSED VOLUMETRIC TROFFER LED, 4000K UNV LG 3-1/4' 40.7D R 5,190

HE WILLIAMS AT SERIES

MATTE DIFFUSE CLEAR REFLECTOR15 PHILIPS GUTH SERIESCLMF-24-4-ALH-INA-A19156-LD4-2LO- 40-UNV-EDD1-EL14WA4E FAIL-SAFE 2' X 4' RECESSED LENSED TROFFER WITH EMERGENCY BATTERY OPTION LED, 4000K UNV GWB 3-1/2' 52.4 5,461D R

16 REFLECTOR COLOR OTHER THAN CLEAR KURTZON

HE WILLIAMS AT SERIES17 WHITE MILLIGROOVE BAFFLE 2’ X 2' RECESSED VOLUMETRIC TROFFER 2-3/4'B METALUX 22CZ-LD5-24-S-UNV-L840-CD1-U LED, 4000K UNV D R LG 19.6 2,570

CREE ZR SERIES

BLACK MILLIGROOVE BAFFLE18 HE WILLIAMS AT SERIES22CZ-LD5-24-S-UNV-E14W-L840-CD1- © Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

BE METALUX SAME AS 'B' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV LG 2-3/4' 19.6D R 2,570UADA COMPLIANT19 CREE ZR SERIES

HE WILLIAMS AT SERIES22CZ-LD5-24-S-U N V-E14 W-L840-CD1 -

U-DF-22-W

FURNISH WITH SYMMETRIC REFLECTOR20 B1E METALUX SAME AS 'BE' EXCEPT CEILING TYPE LED, 4000K UNV DW 2-3/4' 19.6D R 2,570

CREE ZR SERIES

FURNISH WITH ASYMMETRIC REFLECTOR21

HE WILLIAMS AT SERIES

2’ X 2' RECESSED VOLUMETRIC TROFFER 2-3/4'B2 METALUX 22CZ-LD5-34-S-UNV-L840-CD1-U LED, 4000K UNV D R LG 29.4 3,638FURNISH WITH SLOPE ADAPTER - VERIFY SLOPE22 CREE ZR SERIES

DAYBRITE LT LED SERIESFURNISH WITH AUXILIARY EMERGENCY BATTERY PACK23 14GR-LD5-20-A125-UNV-L840-CD1-U- DF-14-WUC METALUX 1' X 4' RECESSED LENSED TROFFER LED, 4000K UNV GWB 5-5/8' 17.2D R 2,062

HE WILLIAMS 50 SERIES24 FURNISH WITH WIRE GUARD

DAYBRITE LT LED SERIES14GR-LD5-20-A125-UNV-EL14 W-L840-

CD1-U-DF-14-WU SAME AS ’C EXCEPT WITH EMERGENCY BATTERY OPTION 5-5/8'CE METALUX LED, 4000K UNV D R GWB 17.2 2,062FURNISH WITH CHAIN MOUNTING ACCESSORIES25 HE WILLIAMS 50 SERIES

FURNISH WITH RIGID PENDANT STEMS26 DAYBRITE LT LED SERIES

5-5/8'C1 METALUX 14GR-LD5-32-A125-UNV-L840-CD1 -U 1’ X 4' RECESSED LENSED TROFFER LED, 4000K UNV D R LG 29.8 3,310

HE WILLIAMS 50 SERIESFURNISH WITH SWIVEL CANOPY27

PORTFOLIO LD6A SERIES

D GOTHAM EVO-40/15-6AR-MD-LSS-MVOLT-EZ10 6" DIAMETER DOWNLIGHT LED, 4000K UNV V 7-9/16' 19 1,572PATTERN 12 ACRYLIC LENS - 0.125" MIN. THICKNESS D R28

PHILIPS CALCULITE SERIES

PATTERN 12 ACRYLIC LENS - 0.156" MIN. THICKNESS29 PORTFOLIO LD4A SERIES

EVO-40/10-4AR-MD-LSS-MVOLT-EZ10 4" DIAMETER DOWNLIGHT 7-9/16'D1 GOTHAM LED, 4000K UNV D R V 13 1,189

PHILIPS CALCULITE SERIESPATTERN 12 ACRYLIC LENS - 0.187" MIN. THICKNESS30

PORTFOLIO LD4A SERIESEVO-40/10-4AR-MD-LSS-MVOLT-EZ10FURNISH WITH SOLID FRONT31 SAME AS ’D1’ EXCEPT WITH EMERGENCY BATTERY OPTION 7-9/16'D1E GOTHAM LED, 4000K UNV D R V 13 1,189-EL PHILIPS CALCULITE SERIES

FURNISH WITH PHOTO CELL32 PHILIPS CAPRI SERIESH457-ICAT-1E-EL406-940-TL402HS-TR

M400SND2 HALO 4" DIAMETER DOWNLIGHT (SHOWER LUMINAIRE) LED, 4000K UNV D GWB 5-3/8' 13R 900

1/2" X 1/2" X 1/2" SILVER PARACUBE LOUVER33 ACUITY JUNO SERIES

PINNACLE FINA SERIESFSDEP-2-FL-3000DN-0UP-940K-1C-UN

V-L11-SM-WH

34 WHITE STRAIGHT BLADE LOUVERS FOCAL POINT 24" DIAMETER SURFACE MOUNTED DOWNLIGHTD3 LED, 4000K UNV D S LG 3' 27 3,000

FURNISH TRIM SUITABLE FOR USE WITH NARROW TEE CLG SYSTEM35 PINNACLE FINA SERIESFSDEP-2-FL-7000DN-0UP-940K-1C-UN V-L11-SM-WH oFOCAL POINT 48" DIAMETER SURFACE MOUNTED DOWNLIGHTD4 LED, 4000K UNV D S LG 3.7' 63 7,000CUSTOM PAINTED FINISH - COLOR AS SELECTED BY ARCHITECT36

KIM LIGHTING CFL SERIESDSXF2LED-P2-40K-WFL-277-THK-DM

G-DNAXD

FROSTED LENS REFLECTOR, SATIN LENS DIFFUSER37 COF LITHONIA 8" X 12" LED FLOOD LUMINAIRE LED, 4000K W 12'277 D 78 10,678 COINVUE VFS SERIES oWET LOCATION LISTED38 oMETALUX VISIUM SERIES CDPHZL-70L-4K-80CRI-27-P-W-W-D-UPH -35-277V-WH-PF-122-A 28-1/2" DIAMETER INDUSTRIAL ROUND PENDANTL HOLOPHANE LED, 4000K 277 D P ES 24.34' 589 63,851 1BALLAST/DRIVER CODE LISTING: (SEE SPECIFICATIONS)

LED DIMMABLE POWER SUPPLY (0-10V).

DIALIGHT VIGILANT SERIES cccc<j>

COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8

0CRI-WH-EC36

D O'N LITHONIA 4’ X 10" INDUSTRIAL LOW BAY LUMINAIRE LED, 4000K UNV V 3-1/4'D P 29 3,636 cc< oGENERAL NOTES: COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8

0CRI-E7W-WH-EC36 O CDNE LITHONIA SAME AS 'N' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV V 3-1/4'D P 29 3,636 CO1. EC SHALL VERIFY AND COORDINATE ALL LUMINAIRE TRIMS/FLANGES WITH RESPECTIVE CEILING TYPES SCHEDULED AND/OR SUBMITTED BY THE GC PRIOR TO ORDERING OF THE LUMINAIRES. SCHEDULE INDICATES TRIM TYPES BASED ON THE GENERIC CEILING INFORMATION AVAILABLE AT THE TIME BIDDING DOCUMENTS WERE ISSUED AND DOES NOT REFLECT ACTUAL THICKNESS OF GYPSUM WALL BOARD OR PLASTER CEILING OR EXACT GRID TYPE SPECIFIED BY

THE ARCHITECT.

oCOLUMBIA LCR SERIES Ct3MSL-4000LM-SBL-MVOLT-GZ10-40K-8 0CRI-WHLITHONIA 3-1/4'N1 SAME AS 'N' EXCEPT SURFACE MOUNTED LED, 4000K UNV D S V 29 3,636

<COLUMBIA LCR SERIESMSL-4000LM-SBL-MVOLT-GZ10-40K-8

0CRI-E7W-WHN1E LITHONIA SAME AS 'N1' EXCEPT WITH EMERGENCY BATTERY OPTION LED, 4000K UNV S V 3-1/4'D 29 3,636 COo EKEYED NOTES: COLUMBIA LCR SERIES8ILED-LD5-W-CL-UNV-L840-CD1-U-AY C-CHAIN/SET/U CON2 METALUX 8' X 11" INDUSTRIAL LOW BAY LUMINAIRE LED, 4000K UNV ES 4-15/16'D P 65 10,052

EC TO VERIFY AND COORINDATE ALL MOUNTING ACCESSORIES REQUIRED FOR ALTERNATE MANUFACTURER.1. oocCOLUMBIA LCR SERIES8ILED-LD5-W-CL-UNV-L840-EL14W-C D1-U-AYC-CHAIN/SET/U SAME AS ’N2’ EXCEPT WITH EMERGENCY BATTERY OPTION 4-15/16'N2E METALUX LED, 4000K UNV D P ES 65 10,052CONFIRM FILTERS REQUIRED WITH COR PRIOR TO ORDERING.2. "OCD ocCDHOLOPHANE HXPL SERIESFIELD VERIFY EXACT LENGTH OF FIXTURE REQUIRED TO ACCOMMODATE THE DESIGNATED LOCATION AND LENGTH

SHOWN ON LIGHTING PLANS. PROVIDE ALL ACCESSORIES REQUIRED TO CREATE A COMPLETE AND OPERATIONAL

SYSTEM.

3. 2’ LED HAZARDOUS LOCATION LINEAR FIXTURE WITH CLEAR

POLYCARBONATE LENS AND IP66 & CLASS I DIV II RATED.N3 EATON DLL-2-UNV1-S903-TF-WH LED, 4000K UNV S GWB 34.3D 2.7' 3,958 CO

HE WILLIAMS

8VT2-LD4-9-DR-UNV-L840-CD1-WL-U-

VT2-CHAIN/SET-U CD8' X 7" INDUSTRIAL VAPORTITE LUMINAIRE 5-7/8'Q METALUX LED, 4000K UNV D P ES 105 9,000

(/)o oDC O)HE WILLIAMS8VT2-LD4-9-DR-UNV-L840-EL10W-CD 1 -W L-U-VT2-CHAIN/SET-U SAME AS ’Q’ EXCEPT WITH EMERGENCY BATTERY OPTION 5-7/8'QE METALUX LED, 4000K UNV D P ES 105 9,000 o o oCOOPER LIGHTING

U PHILIPS CONTINUOUS UNDERCABINET LIGHT LED, 4000K 120 S 1.7' 25 / 4FT 1,079/4FT523-000027.77 D 3

LITHONIA LIGHTING

ISSUEDPORTFOLIO LD6A SERIESEVO-40/10-6AR-MD-LSS-MVOLT-EZ10 6" DIAMETER DOWNLIGHT 7-9/16'OAE GOTHAM LED, 4000K UNV D R V 12 1,059 10/04/19 REVISED BID

DOCUMENTS

-EL PHILIPS CALCULITE SERIES

£ FEDERAL SIGNALE RED OBSTRUCTION LIGHTOB ADB SAFEGATE OBSL-L-1-1-1-0-0-0-1-0-0 LED UNV S 10.8' 12o EATON ERL SERIESo

PR Qfic CREE EDGE SERIES=3 oc LITHONIA DSXW1 LED-10C-350-40K-T3M-MVOLT 14" X 6-1/2" WALL PACK LED, 4000K UNV W 10' 14 1,488DT3 PHILIPS 122 SCONCE SERIEScd

CD

E CREE EDGE SERIESSAME AS ’OC’ EXCEPT WITH EMERGENCY BATTERY AND BACK BOX

OPTIONS

DSXW1 LED-10C-350-40K-T3M-MVOLT

-BBW-ELCWLITHONIAOCE LED, 4000K UNV D W 14' 14 1,488

PHILIPS 122 SCONCE SERIES IC&IToo

■O CREE EDGE SERIES=5

OREGON

so/v/sf

EXPIRES:

LITHONIA 14" X 6-1/2" WALL PACKOC1 DSXW1 LED-10C-530-40K-T3M-MVOLT LED, 4000K UNV D W 10’ 20 2,159x

PHILIPS 122 SCONCE SERIESC

o CREE EDGE SERIES OC2 LITHONIA DSXW1LED-20C-530-40K-T3M-MVOLT 14" X 6-1/2" WALL PACK LED, 4000K UNV W 10'D 36 4,288i

PHILIPS 122 SCONCE SERIES

o

CM LITHONIA, DUAL-LITE, PHILIPS

ISOLITE EMERGENCY BATTERY UNIT LED W/UNIT 2-3/16'EBU RL2-LED-WH-SD UNV W 4 125<oc LITHONIA, DUAL-LITE, PHILIPSLU EBU1 ISOLITE RL2LEDWP-2-WH-SD EMERGENCY BATTERY UNIT LED W/UNIT UNV W 3.4' 4 125o i 3142200-121252.01 10/04/19

M&H NO.:

LU

DATE:

DESIGNED BY: JRH

KAS

SURE-LITE CAX SERIESo X1 LITHONIA LE-S-1-R-ELN-SD SINGLE FACE LED EXIT SIGN LED W/UNIT UNV V V 7-7/8' 2.5CM PHILIPS 46 SERIESLO CM DRAWN BY:SURE-LITE CAX SERIESCM IMRLITHONIA DOUBLE FACE LED EXIT SIGN LED W/UNIT 7-7/8'X2 LE-S-2-R-ELN-SD UNV V V 2.5 CHECKED BY:PHILIPS 46 SERIESoo DO NOT SCALE DRAWINGSCM SURE-LITE UX SERIESCM -H- X3 LITHONIA WLTE-W-1-R-EL-SD SINGLE FACE LED EXIT SIGN (WET LOCATION) LED W/UNIT UNV W 2-1/2' 2.7 SHEET CONTENTS

DUAL-LITE EVE4X SERIESCO

SCHEDULESCD

O o

CD

o

SHEET NO.:

CL

■sl-o h-

E-601CO

CD

o

MeadLIGHTING CONTROL PANEL SCHEDULE (LCP) OCCUPANCY/VACANCY/PHOTO SENSOR SCHEDULE luntOVERRIDE

DEVICE

RELAY

NUMBER

RELAY TYPE AREA

CONTROLLED

KEYED

NOTE

TECHNOLOGYSENSOR COVERAGE

AREA

CIRCUIT DESCRIPTIONVOLTAGE PATTERN MOUNTING KEYED NOTEIDPOLES VOLTAGE SIZE PIR MICRO Mead & Hunt, Inc.

9600 NE Cascades Parkway Suite 100

Portland, OR 97220 phone: 503-548-1494 meadhunt.com

1/HA-2Ra1 1 277V 20A LV A, A1, A2 HANGAR 123

SINGLE-POLE, WALL MOUNT SWITCH TYPE OCCUPANCY SENSOR. CAT# WSX PDT AUTO-ON OR

VACANCY120/277WS X X 180 UP TO 800 SF WALL 1,31 277V 20A 1/HA-4Rb LV A, A1, A2 HANGAR 1232

1/HA-6RC3 1 277V 20A LV A, A1, A2 HANGAR 123

SINGLE-POLE, WALL MOUNT SWITCH TYPE DIMMING OCCUPANCY SENSOR. CAT# WSX D; 0-10

VOLT,1% ELDO DRIVER COMPATIBLE

4 1 277V 20A 1/HA-8Rd LV A, A1, A2 HANGAR 123 120/277WS1 X X 180 UP TO 800 SF WALL 1,2 1 277V 20A 1/HA-10 Re LVA, B, B1, B2 HANGAR 1235

CEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY; CAT# CM PDT, SMALL

MOTION

1/HA-10Rf6 1 277V 20A LVA, B, B1, B2 HANGAR 123 OS1 12-24V X X UP TO 500 SF CEILING 4, 5,6360 1 277V 20A 1/HA-10Rg LVA, B, B1, B2 HANGAR 1237

1/HA-12Ra PE ON / TS OFF BUILDING EXTERIOR8 1 277V 20A TETRATECHItCEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY; CAT# CM PDT, LARGE MOTIONOS2 12-24V X X 360 UP TO 2000 SF CEILING 4, 5,61 277V 20A 1/HA-14Rb PE ON / OFF OBSTRUCTION9 www. tetratech. com

10 1 277V 20A SPARE UP TO 28' @9' MH ;

UP TO 36'@ 15'

711 TANK FARM ROAD, SUITE 110

SAN LUIS OBISPO, CA 93401

PHONE: (805) 542-9052 FAX: (805) 542-9254

OS3 12-24V X X CEILING MOUNTED PROGRAMMABLE WITH ADJUSTABLE TIME DELAY, CAT#CM PDT, HALLWAYS CEILING360 2,611 1 277V 20A SPARE

MH

12 1 277V 20A SPARE

SINGLE ZONE DAYLIGHT SENSOR WITH SELECTABLE ON/OFF OR DIMMING APPLICATION; CAT # CM

PC ADCGENERAL NOTES: DS 12-24V N/A N/A N/A CEILING 7

SITE LIGHTING TO TURN ON AT 5:00 PM AND OFF AT MIDNIGHT.

BUILDING PHOTO EYE WILL OVERRIDE THE SITE LIGHTING DURING DAYTIME HOURS.

INTERIOR BUILDING LIGHTING TO TURN OFF AT 1:00 AM. LIGHTS SHALL BLINK 5 MINUTES PRIOR TO SHUTOFF. AUTO

OFF 1:00 AM; 1:00 AM TO 7:00 AM - LV SWITCH OVERRIDE ON FOR 2 HRS.

1.

0 FC (MIN) TO 50-750 FC (MAX) OUTDOOR PHOTOCELL INSTALLED IN APPROPRIATELY RATED

ENCLOSURE

2. N/A N/A N/APE 12-24V ROOF 8

3.

GENERAL NOTES:

1. COLOR OF DEVICES SHALL BE COORDINATED/MATCHING COLOR OF RECEPTACLES AND SWITCHES AS IDENTIFIED IN SPECIFICATION SECTION 26 27 26

PROVIDE ADEQUATE SUPPORT FOR CONTROL WIRING, REFER TO WIRING DIAGRAMS SUPPLIED WITH SELECTED DEVICES. FOLLOW MANUFACTURER INSTRUCTIONS

FOR ADDITIONAL INFORMATION REFER TO SPECIFICATION SECTION 26 51 00.

ALL LOW VOLTAGE SENSORS SHALL BE PROVIDED WITH 20A RATED POWER PACKS WITH ZERO CROSS SWITCHING TECHNOLOGY AND MANUAL ON MODE

PROVIDE 8’ OF ADDITIONAL WIRING ABOVE ACCESSIBLE CEILING.

ALL POWER PACKS AND SLAVE PACKS SHALL BE INSTALLED IN APPROVED ENCLOSURES RATED FOR THE ENVIROMENTAL SPACES WHERE THEY ARE INSTALLED

WHERE OCCUPANCY SENSORS CONTROLLING LIGHTS OF A DIFFERENT VOLTAGES A SEPARATE POWER/SLAVE PACK…