2 - Structural.pdf
PDF 15 MB Posted
- Attached to
- Construct Corrosion Control Hangar Federal contract opportunity
- Solicitation number
- W50S8Z20B0001
About this file
This solicitation package outlines requirements for the construction of a corrosion control hangar at Kingsley Field in Klamath Falls, Oregon. The project scope includes building a pre-engineered metal hangar and adjacent support facilities totaling approximately 16,000 square feet. Additional work involves constructing a concrete aircraft tow lane. The solicitation will be issued on or around December 3, 2019 with a pre-bid conference scheduled for December 12. Questions are due by December 19 and bids are due by January 6, 2020. The contract duration is 365 calendar days from notice to proceed with a magnitude between $5-10 million. This project is set aside 100% for small businesses under NAICS code 236210 with a size standard of $36.5 million. Offerors must register in the System for Award Management and perform at least 15% of the work with their own employees. Interested parties should monitor the Federal Business Opportunities website for solicitation documents and any amendments.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch #4 - Revised - Door hardware.pdf | ||
| Attch #3 Revised Specs -Steel Sliding Doors -RFI 047.pdf | ||
| Attch # 2 - Sheet T-011 -RFI 040-41 Response.pdf | ||
| SF30 Amendment #4.pdf | ||
| Corrosion Control Pre-Bid Minutes 12 Dec.pdf | ||
| SF30 Amendment #3.pdf | ||
| SF30 Amendment #2.pdf | ||
| SF30.pdf | ||
| Sign-In Sheet.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 3.pdf | ||
| 1 - General and Civil.pdf | ||
| 4 - Fire Alarm and Fire Sprinkler.pdf | ||
| 5 - Plumbing.pdf | ||
| JA Brand Name - Automated Logic_Redacted.pdf | ||
| 8 - Technology Systems.pdf | ||
| 7 - Electrical.pdf | ||
| 6 - Mechanical.pdf | ||
| W50S8Z20B0001.pdf | ||
| JA Brand Name - Advantor (1)_Redacted.pdf | ||
| 3 - Architectural.pdf | ||
| JA Brand Name - Monaco Fire Alarm_Redacted.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 1.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 2.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ISSUED
10/04/19 REVISED BID
DOCUMENTS
SIGNHD
%c-OREGON srwil
EXP. 12/31/2020
90681 PE
M&H NO.: 3142200-121252.01
10/04/19DATE:
DESIGNED BY: GFR
MJE
JAL
DRAWN BY:
CHECKED BY:
DO NOT SCALE DRAWINGS
SHEET CONTENTS
STRUCTURAL NOTES
SHEET NO.:
S-001
Mead i luntI
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
TETRATECHIt www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
STRUCTURAL DESIGN CRITERIA FOUNDATION NOTES CONCRETE & REINFORCING STEEL NOTES EARTHWORK NOTES STRUCTURAL SYMBOLOGY FOUNDATION PLANGOVERNING CODE: 2015 IBC AS MODIFIED BY UFC 3-30-01 AND 2014 OSSC FOOTING SUBGRADES SHALL BE CLEAN AND FREE OF DEBRIS, STANDING
WATER, AND LOOSE SOIL.
MATERIAL PROPERTIES (U.N.O.)
COMPRESSIVE STRENGTH
CONCRETE REINFORCEMENT
REFERENCE SECTION 310000 - EARTHWORK FOR DEFINITION OF MATERIALS
AND COMPACTION REQUIREMENTS.
F-1. EW-1.1.
- F'c = 3 KSI
- Fy = 60 KSI (A615GR60)RISK CATEGORY:2.
TALL COLUMN FOOTINGS ARE TO BE CENTERED UNDER COLUMN
CENTERLINES, UNLESS INDICATED OTHERWISE.
REFERENCE THE GEOTECHNICAL INVESTIGATION REPORT AND SECTION
310000 - EARTHWORK FOR REQUIREMENTS FOR EXCAVATION AND
CONTROL OF SURFACE WATER AND GROUND WATER.
F-2. EW-2. H MASONRY (CMU) WALL
ON CONCRETE FOOTING
FLOOR LIVE LOAD (1603.1.1) PROVIDE HOT/COLD WEATHER PROCEDURES AND PROTECTION IN
ACCORDANCE WITH ACI RECOMMENDATIONS AND PROJECT
SPECIFICATIONS.
CR-1.3.
I
STORAGE, LIGHT:
OFFICE FLOORS:
125 PSF
50 PSF
F-3. THE FOUNDATION CONTRACTOR SHALL FULLY REVIEW UNDER-GROUND
PLUMBING DRAWINGS AND SHALL COORDINATE WITH THE UNDER-GROUND
PLUMBING CONTRACTOR TO DEPRESS FOOTINGS AND PROVIDE PIPE
SLEEVES THROUGH FOUNDATION WALLS AS NECESSARY TO ACCOMMODATE
PLUMBING LINES OR TRAPS WHICH PENETRATE CONCRETE FOOTINGS OR
FOUNDATIONS.
CONCRETE FOOTINGU.N.O., THE CONTRACTOR SHALL RETAIN AN INDEPENDENT, QUALIFIED
GEOTECHNICAL ENGINEERING FIRM/TESTING AGENCY TO IDENTIFY AREAS
OF POOR SOILS, TO MONITOR PROPER SUBGRADE PREPARATIONS AND TO
OVERSEE AND TEST THE PLACEMENT OF COMPACTED FILL MATERIAL.
EW-3.
CR-2. ALL CONCRETE DESIGN AND CONSTRUCTION SHALL CONFORM WITH THE
LOCAL BUILDING CODE REQUIREMENTS AND THOSE OF THE FOLLOWING
STANDARDS (LATEST EDITION):
4 CONCRETE FOUNDATION WALL
ON CONCRETE FOOTING
ROOF LIVE LOAD (1603.1.2)4.
I
*K TOFMINIMUM ROOF LIVE LOAD: 20 PSF
TOP OF FOOTING ELEVATION"ACI 318, BUILDING CODE REQUIREMENTS FOR REINFORCED CONC."
"ACI 315, DETAILS AND DETAILING OF CONCRETE REINFORCEMENT"
"ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BLDGS."
"ACI 305R, GUIDE TO HOT WEATHER CONCRETING"
"ACI 306R, GUIDE TO COLD WEATHER CONCRETING"
"ACI 307, RECOMMENDED PRACTICE FOR CONCRETE FORM WORK"
EW-4. ALL SUBTERRANEAN STRUCTURES, UTILITIES, PIPING, ETC. IIN THE AREA
OF EXCAVATIONS TO BE LOCATED AND MARKED BY CONTRACTOR PRIOR
TO EARTH REMOVAL WORK. CONTRACTOR TO MAINTAIN MARKERS UNTIL
EXCAVATION ACTIVITIES HAVE CEASED. IF UNDERGROUND UTILITY
CONFLICTS ARE DISCOVERED BEFORE OR ENCOUNTERED DURING
EXCAVATION, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY.
I 96'-0 ROOF SNOW LOAD (1603.1.3) F-4. PROVIDE PVC SLEEVES THROUGH FOUNDATION WALLS/FOOTINGS FOR PIPE, CONDUIT, AND CABLE PENETRATIONS, INCLUDING ELECTRICAL GROUNDING
SYSTEM CABLES. SEE APPROPRIATE DRAWINGS FOR LOCATIONS/SIZES.
PLACE SLEEVES IN LOCATIONS TO AVOID DISPLACING REINFORCING STEEL.
5.
TOWI TOP OF WALL ELEVATIONGROUND SNOW LOAD:
SLOPED AND FLAT-ROOF SNOW LOAD:
PG = 19 PSF
Pf = 20 PSF
(MIN. LOAD FROM COUNTY)
Ce = 0.9 Is = 1-0 Ct= 1.0
10O'-OI
I
REFER TO ELECTRICAL DRAWING SITE LIGHTING FOR POLE BASES.
SUPPLIED AND INSTALLED BY GENERAL CONTRACTOR.
SNOW EXPOSURE FACTOR:
SNOW LOAD IMPORTANCE FACTOR:
THERMAL FACTOR:
F-5. f FOOTING STEP
STRIP FOOTING DESIGNATIONCR-3. REINFORCING SHALL BE DETAILED IN ACCORDANCE WITH ACI 315. EW-5. BEFORE PLACING FOOTINGS, FOUNDATIONS OR SLAB-ON-GRADE, THE
SUB-GRADE SHALL BE PREPARED AND INSPECTED AS REQUIRED BY THE
SPECIFICATIONS.
|— SF1
--I- FW08 -COORDINATE WITH ARCHITECTURAL AND CIVIL DRAWINGS FOR
MISCELLANEOUS FOUNDATIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
ALL REINFORCEMENT BARS SHALL BE FABRICATED IN ACCORDANCE WITH
THE LATEST CRSI MANUAL OF STANDARD PRACTICE AND SHALL BE CLEAN
AND FREE OF GREASE AND SCALING RUST.
F-6. CR-4. FOUNDATION WALL DESIGNATIONiWIND DESIGN DATA (1603.1.4)6.
DENOTES DEPRESSION FOR
WALL/DOOR OPENING (-8" U.N.O.)
INDICATES PIER MARK
EW-6. DO NOT BACKFILL OR FILL SOIL MATERIAL ON SURFACES THAT ARE
MUDDY, FROZEN, OR CONTAIN FROST AND/OR ICE. IULTIMATE WIND SPEED (3-SECOND GUST):
WIND EXPOSURE:
INTERNAL PRESSURE COEFFICIENT:
F-7. CONTROL JOINTS IN THE CAST-IN-PLACE CONCRETE FOUNDATION WALLS
SHALL BE PLACED AT SPACING NOT TO EXCEED 20' O.C. OR AS LOCATED PER
DRAWINGS AND SHOULD ALIGN WITH MASONRY CONTROL JOINTS WHERE
APPLICABLE. SEE DETAIL SHEETS FOR CONTROL JOINT DETAILS. PROVIDE
VERTICAL "V" GROOVE AT ALL CONSTRUCTION AND CONTROL JOINTS.
CONTRACTOR SHALL SUBMIT PLANS OF JOINT LOCATIONS FOR APPROVAL.
Vult= 120 MPH
SEE SECTION 033000 OF SPECIFICATIONS FOR INFORMATION REGARDING
CONCRETE MIX DESIGN, TESTING, MATERIALS, AND ADMIXTURES.
C CR-5.
GCPI = +/- 0.55 EW-7. PLACE BACKFILL AND FILL SOIL MATERIALS EVENLY ON ALL SIDES OF
STRUCTURES TO REQUIRED ELEVATIONS AND UNIFORMLY ALONG
THE FULL LENGTH OF EACH STRUCTURE.
INDICATES PIER
EARTHQUAKE DESIGN DATA (1603.1.5) CONCRETE REINFORCEMENT PROTECTION/CLEAR COVER, U.N.O.:CR-6.7. /
INDICATES COLUMNIMPORTANCE FACTOR: Ie = 1.0 FOOTINGS:
BOTTOM & SIDES I1F-8. A LEAN CONCRETE MUD SLAB 2” TO 3” THICK SHALL BE USED IN THE FOOTING
EXCAVATION IF THE BOTTOM OF THE EXCAVATION TENDS TO BECOME
MUDDY AND SOFT DUE TO CONSTRUCTION ACTIVITY. LEAN CONCRETE
SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 PSI.
3" 2" INDICATES CONCRETE FOOTINGJMASONRY VENEER NOTESMAPPED, MCE, 5% DAMPED, SPECTRAL ACCELERATIONS:
Ss = 0.873 G Si = 0.347 G
TOP \<<AT SHORT PERIODS:
AT A PERIOD OF 1 SECOND: INDICATES SPREAD FOOTING MARKWALLS:
EXTERIOR EXPOSURE
INTERIOR EXPOSURE
MV-1. REFER TO ARCHITECTURAL PLANS AND DOOR/FRAME SCHEDULES FOR LINTEL
ROUGH OPENING LOCATIONS, SIZES, AND ELEVATIONS. SEE SEE DRAWINGS
FOR LINTEL SIZE AND SUPPORT DETAILS.
2"
1" INDICATES NEW GRID DESIGNATION
(HEXAGON SHAPE AT EXISTING GRID)
ACOORDINATE GROUNDING REQUIREMENTS FOR FOUNDATION/FOOTING
REINFORCING STEEL WITH ELECTRICAL DRAWINGS. COORDINATE
INSTALLATION OF GROUNDING WIRES/EQUIPMENT WITH ELECTRICAL
CONTRACTOR PRIOR TO CASTING CONCRETE. REFER TO NOTE CR-11
FOR ADDITIONAL INFORMATION.
SITE CLASS: D F-9.
DESIGN EARTHQUAKE SPECTRAL ACCELERATIONS
AT SHORT PERIODS:
AT A PERIOD OF 1 SECOND:
BEAMS/COLUMNS:
OVER TIES OR STIRRUPS MV-2. REFER TO STRUCTURAL AND/OR ARCHITECTURAL DRAWINGS FOR CONTROL
JOINT LOCATIONS. WHERE VENEER CONTROL JOINT LOCATIONS ARE NOT
INDICATED, PROVIDE THEM AT 20' MAXIMUM CENTERS AND IN THE SAME
LOCATIONS AS FOUNDATION WALL CONTROL JOINTS.
Sds = 0.670 G Sdi = 0.395 G
1 1/2"
FRAMING PLAN
ELEVATED SLABS: 1” INDICATES KNEE BRACING CONNECTED TO BEAM
(BELOW FRAMING MEMBER)
INDICATES BEAM FRAMING OVER HOLLOW
STRUCTURAL SECTION (HSS) COLUMN
SEISMIC DESIGN CATEGORY: F-10. SEE TYPICAL SLAB-ON-GRADE DETAILS FOR SLAB AND SUB-BASE
REQUIREMENTS. THESE WILL BE TYPICAL THROUGHOUT UNLESS NOTED
OTHERWISE.
SDC = D / 'v
ALL BAR LAPS SHALL CONFORM TO ACI 318 CLASS "B" SPLICE CRITERIA.
USE TOP BAR LAP LENGTHS FOR TOP BARS IN SLABS AND BEAMS OVER
14" DEEP. MINIMUM BAR LAPS AS FOLLOWS U.N.O.:
CR-7.
MV-3. TYPICAL MASONRY UNITS SHALL BE AS INDICATED ON ARCHITECTURAL
DRAWINGS.
[]SHOPS BUILDING:
BASIC SEISMIC-FORCE-RESISTING-SYSTEM: SFRS = SRMSW (ASCE 7-10
TABLE 12.2-1) F-11. FOUNDATIONS SHOULD NOT SPAN BOTH CUT AND FILL. IF THE FOUNDATIONS
SPAN BOTH CUT AND FILL, FOLLOW THE PROJECT GEOTECHNICAL
INVESTIGATION REPORT.
MV-4. WEEP HOLES SHALL BE AT LEAST 3/16” IN DIAMETER AND SPACED
LESS THAN 33" O.C. UNLESS NOTED OTHERWISE.
RESPONSE MODIFICATION FACTOR:
SEISMIC RESPONSE COEFFICIENTS:
R = 5 Cs = 0.13
#3= 1’-4" #8 = 5’-2"
#4 = 1 ’-4" #9 = 6'-4"
#5 = T-10" #10 = 7'-8"
#6 = 2'-7" #11 = 9'-0"
#7 = 4'-2" INDICATES BEAM FRAMING
OVER WIDE FLANGE (WF) COLUMN
INDICATES BRACING CONNECTED TO BEAM
(BELOW FRAMING MEMBER)
INDICATES BEAM FRAMING
INTO SIDE OF COLUMN
INDICATES MOMENT CONNECTION
INDICATES COLLECTOR CONNECTION
7^MV-5. ADJUSTABLE ANCHORS SHALL BE PROVIDED WITH A MAXIMUM HORIZONTAL
AND VERTICAL SPACING OF 16". PINTLE ANCHORS SHALL HAVE TWO PINTLE
LEGS OF WIRE SIZE W2.8 (3/16" DIAMETER) AND SHALL HAVE AN OFFSET
NOT EXCEEDING 1 1/4". PLACE ANCHORS WITHIN 12" OF ALL OPENINGS.
FOR EPOXY COATED BARS, PROVIDE 1.5 TIMES THE INDICATED LAP LENGTH.
FOR TOP BARS PROVIDE 1.3 TIMES THE INDICATED LAP LENGTH.
PRE-ENGINEERED METAL BUILDING:
BASIC SEISM IC-FORCE-RESISTING-SYSTEM: /SFRS = TBD BY PEMB MFR.
H H ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE LAP LENGTH SHALL BE SPECIFICALLY NOTED ON SHOP DRAWINGS WHERE
MORE THAN ONE BAR MAKES UP A CONTINUOUS STRING.
CR-8.MASONRY NOTES
MV-6. PROVIDE CONTINUOUS SINGLE WIRE JOINT REINFORCEMENT OF WIRE SIZE
W1.7 (9 GAUGE) AT A VERTICAL SPACING OF 16". MECHANICALLY ATTACH
THE ADJUSTABLE ANCHORS TO THE JOINT REINFORCEMENT WITH CLIPS
OR HOOKS.
GEOTECHNICAL DESIGN DATA (1603.1.6)8.
HORIZONTAL BARS SHALL BE DETAILED TO SHOW THE DISTANCE FROM AT
LEAST ONE END OF THE BAR TO THE NEAREST BUILDING GRID LINE OR
WALL.
CR-9.MATERIAL PROPERTIES (U.N.O.)
COMPRESSIVE STRENGTH
MASONRY REINFORCEMENT
MORTAR
GROUT AT 28-DAYS
NET ALLOWABLE SOIL BEARING PRESSURE: 2,000 PSF - F'm = 1500 PSI, U.N.O.
- Fy = 60 KSI (A615 GR 60)
- TYPE S (ASTM C270)
- 2500 PSI (ASTM C476)
INDICATES REQUIRED UPWARD CAMBER
IN BEAM (INCHES)un
REFERENCE CGI TECHNICAL SERVICES, INC. GEOTECHNICAL INVESTIGATION
REPORT. PROJECT: 11-1144.76, DATED AUGUST 16, 2017
r--
MV-7. EACH ADJUSTABLE ANCHOR SHALL BE ATTACHED WITH TWO (2) NO. 10
GALVANIZED SCREWS (NOMINAL SHANK DIAMETER OF 0.190 IN) UNLESS
NOTED OTHERWISE.
oCONTINUOUS TOP AND BOTTOM BARS, WHEN SHOWN IN TRANSVERSE
SECTION ONLY, SHALL BE LAPPED AS FOLLOWS:
CR-10. INDICATES BEAM SIZE
to COFLOOD DESIGN DATA (1603.1.7)9. TYPICAL MASONRY WALLS SHALL BE 8" CMU W/ #5 AT 16" O.C. VERTICAL
AND #5 AT 16" O.C. HORIZONTAL, CENTERED IN WALL, UNLESS NOTED
OTHERWISE. SEE PLAN FOR SPECIAL ELEMENTS.
XM-1. to oTOP BARS NEAR MID-SPANS; BOTTOM BARS DIRECTLY OVER SUPPORTS, U.N.O. INDICATES TOP OF STEEL ELEVATION§ oMV-8. FOR VENEER BACKING, COLD-FORMED STEEL FRAMING SHALL HAVE A
MINIMUM BASE METAL THICKNESS OF 0.043" (18 GAUGE).
BUILDING IS NOT LOCATED IN FLOOD HAZARD AREA; THEREFORE FLOOD
DESIGN DATA IS NOT REQUIRED
oo INDICATES NUMBER OF 3/4" x 5" SHEAR STUDS
FULLY WELDED TO TOP OF BEAM PER 1/2-SPAN
CR-11. PROVIDE ONE (1) HOOKED REINFORCING BAR IN CONCRETE FOOTING
TO SERVE AS A “CONCRETE ENCASED ELECTRODE” IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE. COORDINATE WITH ELECTRICAL
CONTRACTOR FOR EXACT LOCATION. HOOKED REINFORCING BAR SHALL
CONFORM TO THE FOLLOWING:
A. UNCOATED, LOW-ALLOY STEEL, CONFORMING TO ASTM A706.
B. BAR SIZE NUMBER 4 HOOKED AT ONE END ONLY.
C. MINIMUM HORIZONTAL LENGTH OF REINFORCING BAR ENCASED IN
CONCRETE FOOTING SHALL BE 20’-0” AS DEFINED IN NEC, ARTICLE 250.
D. MINIMUM VERTICAL PROJECTION OF REINFORCING BAR ABOVE
CONCRETE SLAB SHALL BE 0’-6”.
E. MINIMUM COVER ALL AROUND REINFORCING BAR SHALL BE 2”.
M-2. REFER TO SHEET S-521 FOR LAP SPLICES AND DEVELOPMENT LENGTHS. MV-9. REFER TO MASONRY VENEER SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
10. SPECIAL LOADS (1603.1.8)
TYPICAL MASONRY UNITS SHALL BE OPEN-ENDED CMU WITH LINTEL, BOND
BEAM, CLOSED END, ETC. UNITS AS REQUIRED, TO FACILITATE MAXIMUM
GROUT FLOW.
M-3. INDICATES CONNECTION DESIGNED BY FABRICATOR
TO DELIVER 46k VERTICAL LOAD TO CENTERLINE
OF COLUMN OR CONNECTION MEMBER
BLAST LOADING FOR GLAZING:
STANDOFF DISTANCE
EXPLOSIVE WEIGHT
315 FEET
CDI
ALL CMU SHALL BE GROUTED SOLID, UNLESS NOTED OTHERWISE.M-4. []ABBREVIATIONSSTANDOFF DISTANCE
EXPLOSIVE WEIGHT
82 FEET
INDICATES TYPICAL BEAM SHEAR SPLICEM-5. PROVIDE CORNER SPLICE BARS FOR ALL HORIZONTAL REINFORCING
OCCURRING AT CORNERS OR WALL INTERSECTIONS. SPLICE BAR TO BE THE
SAME SIZE AS BARS IN THE WALL. SEE DETAILS. ARCH = ARCHITECTURAL
= BOTTOM OF_________
= BASE PLATE TYPE
= BEARING
= CENTER TO CENTER
= CONSTRUCTION CONTROL JOINT
= CONTROL JOINT
= CONTROLLED LOW STRENGTH MATERIAL ("FLOWABLE FILL")
= CONCRETE MASONRY UNIT
= CONTINUOUS
= DOUBLE-TEE
= DIAMETER
= DOUBLE-TEE BEARING
= EACH FACE
= ELEVATION
= EACH WAY
= EXTERIOR
= SPREAD FOOTING TYPE
= FLOOR DRAIN
= FOUNDATION
= FIELD VERIFY
= GALVANIZED
= HIGH PERFORMANCE COATING
= INTERIOR
= JOIST BEARING
= LONG LEG HORIZONTAL
= LONG LEG VERTICAL
= NOT IN CONTRACT
= NOT TO SCALE
= ON CENTER
= OREGON STRUCTURAL SPECIALTY CODE
= PIER TYPE
= PRECAST BEARING (ELEVATION)
= PRE-ENGINEERED METAL BUILDING
= PRECAST
= REACTION
= STRUCTURAL ENGINEER OF RECORD
= STRIP FOOTING TYPE
= SIMILAR
= STAINLESS STEEL
= STEEL
= TOP OF_________
= TO BE DETERMINED
= TRENCH DRAIN
= TOP OF COLUMN
= TOP OF FOOTING
= TOP OF LEDGE
= TOP OF PIER
= TOP OF STEEL
= TOP OF WALL
= TOP OF PRECAST
= TOP OF SLAB
= TYPICAL
= UNLESS NOTED OTHERWISE
= WITH
= WELDED WIRE FABRIC/REINFORCEMENT
11. SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE INDICATES BEAM FRAMING INTO SIDE OF BEAM B.O.
BUILDING IS DESIGNATED SEISMIC DESIGN CATEGORY D; THEREFORE
SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE ARE REQUIRED. SEE
"STATEMENT OF SPECIAL INSPECTIONS" ON SHEET S-003.
INDICATES BEAM FRAMING OVER BEAMM-6. WHERE MASONRY IS APPLIED ADJACENT TO STEEL MEMBERS (BEAMS
AND COLUMNS) PROVIDE ANCHORING DEVICES PER SPECIFICATIONS.
BP#
CR-12. ALL CONCRETE FOUNDATION WALLS SHALL HAVE A MINIMUM OF (2) #5 BARS
CONTINUOUS TOP AND BOTTOM, UNLESS INDICATED OTHERWISE. BRG
C TO CM-7. REFER TO ARCHITECTURAL PLANS AND DOOR/FRAME SCHEDULES FOR
LINTEL ROUGH OPENING LOCATIONS, SIZES, AND ELEVATIONS. CCJ12. STRUCTURAL OBSERVATIONS FOR SEISMIC AND/OR WIND RESISTANCE CR-13. ALL OPENINGS IN CONCRETE FOUNDATION WALLS ARE TO HAVE (4) #5
DIAGONAL BARS EACH FACE OF THE WALL AND SHALL EXTEND 2 FEET
BEYOND OPENING ON EACH SIDE, UNLESS INDICATED OTHERWISE.
CJ
STRUCTURAL OBSERVATIONS FOR SEISMIC RESTANCE ARE REQUIRED, SEE
"STRUCTURAL OBSERVATION" ON SHEET S-002. M-8. WHERE CMU CONTROL JOINT LOCATIONS ARE NOT INDICATED, PROVIDE
THEM AT 25' MAXIMUM CENTERS AND AT LINTEL BEARING (8” MINIMUM
PAST END OF OPENING) LOCATIONS FOR SPANS GREATER THAN 6'-0";
SUBMIT CMU CONTROL JOINT LAYOUT TO THE SER FOR APPROVAL.
REFER TO DETAIL 3/S-521 AND ARCHITECTURAL ELEVATIONS.
CLSM
CMUCR-14. PROVIDE FOOTING DOWELS TO MATCH VERTICAL WALL REINFORCING.
WHERE WALL REINFORCING IS NOT INDICATED, DOWEL FOOTING TO
FOUNDATION WALLS WITH #5 REBAR AT 16" O.C. BY 3'-0" LONG, WITH
STANDARD HOOKS EMBEDDED A MINIMUM OF 9" INTO FOOTING.
GENERAL SYMBOLSCONT
DBLT
DIA
| SW# |—
KEYED NOTEDTBMASONRY DESIGN IS BASED ON INSPECTED WORKMANSHIP.M-9.
ALL PIER FOOTINGS TO HAVE DOWELS WITH STANDARD HOOKS OF SAME
SIZE AND QUANTITY AS PIER STEEL. DOWELS TO LAP PIER STEEL AS
REQUIRED FOR A CLASS ”B" TENSION SPLICE. HOOK UNDER FOOTING
REINFORCEMENT, UNLESS INDICATED OTHERWISE.
CR-15. EF STRUCTURAL WALL TYPEM-10, PROVIDE HOT AND COLD WEATHER PROCEDURES AND TEMPORARY
MOISTURE PROTECTION IN ACCORDANCE WITH ACI RECOMMENDATIONS
AND PROJECT SPECIFICATIONS.
ELGENERAL NOTES EW ELEVATION
EXT
DECK SPANFIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO START
OF CONSTRUCTION - RESOLVE ANY DISCREPANCY WITH ARCHITECT/ENGINEER.
HOOK HORIZONTAL WALL AND BEAM REINFORCING BARS AT
DISCONTINUOUS ENDS, TYPICAL UNLESS INDICATED OTHERWISE. EXTEND
REINFORCEMENT TO FAR FACE OF PIERS/PEDESTALS AND/OR COLUMNS
UNLESS INDICATED OTHERWISE.
G-1. CR-16. F#M-11. PROVIDE HORIZONTAL BOND BEAMS (DIAPHRAGM CHORDS) WITH
(2) #5 BARS CONTINUOUS, BENEATH FLOOR/ROOF MEMBER BEARING
ELEVATIONS AND AT DECK EDGE. UNLESS NOTED OTHERWISE.
FD ( SLAB X) STRUCTURAL SLAB TYPE
FDTNDO NOT SCALE DRAWINGS!!!!
FV
M-12. MASONRY SHALL BE PLACED IN ONE-HALF RUNNING BOND
UNLESS NOTED OTHERWISE. STRUCTURAL ELEVATIONS-201 #GALVG-2. FOR CLARITY, ALL EXTERIOR SLABS AND SIDEWALKS MAY NOT BE SHOWN.
FOR EXACT DIMENSIONS, LOCATIONS, JOINTS AND SCORE LINES, SEE
ARCHITECTURAL AND/OR CIVIL DRAWINGS.
CR-17. WATER STOPS SHALL BE PROVIDED IN HORIZONTAL AND VERTICAL
CONSTRUCTION JOINTS WHERE FINISHED FLOOR IS BELOW EXTERIOR
GRADE UNLESS OMISSION IS APPROVED BY THE ENGINEER.
HPC
M-13. REFER TO DETAIL 7/S-521 FOR TYPICAL CAST-IN ANCHOR BOLT INSTALLATION. I NT
#JB DETAILOR SECTIONG-3. VERIFY ALL SIZES, WEIGHTS AND LOCATIONS OF MECHANICAL AND
ELECTRICAL EQUIPMENT, ROOF PENETRATIONS, DUCTS, ETC. WITH
MECHANICAL AND ELECTRICAL CONTRACTORS AND FIELD CONDITIONS.
PROVIDE ADDITIONAL #4 BARS AT 4'-0" LONG 1" BELOW TOP OF SLAB AT
45° TO ALL RE-ENTRANT CORNERS,OPENINGS IN CONCRETE SLABS AND
AS INDICATED ON DRAWINGS.
CR-18.M-14. PRIOR TO INSTALLATION OF ANCHOR BOLTS AND EMBEDS, CONTRACTOR
SHALL COORDINATE LOCATION OF ALL REINFORCING BARS AND EMBEDDED
ITEMS TO AVOID CONFLICTS.
.S-50LLH
LLV L#
LINTEL DESIGNATIONNIC
G-4. DETAILS MARKED "TYPICAL" MAY OR MAY NOT BE CUT ON PLANS, BUT
SHALL APPLY UNLESS NOTED OTHERWISE.
REFER TO FLATWORK DRAWINGS AND/OR SPECIFICATIONS FOR
SLAB-ON-GRADE FINISH TYPES AND DEPRESSIONS REQUIRED FOR MATS,
TILE, AND OTHER FINISH MATERIALS.
CR-19.M-15. PENETRATIONS, SLEEVES, BLOCKOUTS SHALL BE SPACED 3x DIAMETER, OR 3x LARGEST DIMENSION, CLEAR. WHERE PENETRATIONS ARE SPACED
MORE CLOSELY, TREAT GROUP AS A SINGLE OPENING FOR REINFORCEMENT.
NTS
OC
OSSCG-5. STRUCTURAL SYSTEM IS DESIGNED TO WORK AS A COMPLETED SYSTEM,
ANY SHORING OR BRACING NECESSARY DURING CONSTRUCTION SHALL
BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR.
P#THICKEN THE SLAB-ON-GRADE BENEATH INTERIOR MASONRY PARTITIONS
8 INCHES BELOW BOTTOM OF SLAB ON GRADE. THICKENED PORTION TO
EXTEND 8 INCHES BEYOND THE FACE OF THE WALL ON EACH SIDE.
REINFORCE THE THICKENED PORTION WITH (3) #3 CONTINUOUS,
LONGITUDINAL REINFORCING BARS AND #5 TRANSVERSE BARS AT 16" O.C.,
UNLESS INDICATED OTHERWISE.
CR-20.M-16. REINFORCE ALL NEW CMU AROUND OPENINGS PER DETAIL 5/S-521.
PCB
PEMB
PRCST
Rxn
M-17. PROVIDE REINFORCEMENT PLATES AT ALL PENETRATIONS GREATER THAN
8” WIDE THROUGH EXISTING CMU WALLS: PL3/8”x(PENETRATION DIMENSION
+ 16”) EACH FACE OF WALL. PROVIDE 3/4” THROUGH BOLTS 8" O.C. THROUGH
GROUTED HOLES. DO NOT DAMAGE REINFORCEMENT. IF REINFORCEMENT
IS CUT, ADDITIONAL REINFORCEMENT MAY BE NECESSARY, CONTACT
ENGINEER.
G-6. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING PLANS
FOR SLEEVES, INSERTS, ETC. NOT SHOWN ON STRUCTURAL PLANS.
SERG-7. NO PIPES OR SLEEVES FOR MECHANICAL AND ELECTRICAL TRADES SHALL
PASS THROUGH STRUCTURAL MEMBERS WITHOUT APPROVAL OF THE
STRUCTURAL ENGINEER.
PITCH CONCRETE TO FLOOR DRAINS. COORDINATE WITH PLUMBING AND
ARCHITECTURAL DRAWINGS.
SF#CR-21.
SIM
M-18. PROVIDE (2) #5 CHORD BARS AT EACH FLOOR AND ROOF LEVEL UNLESS
OTHERWISE NOTED.
SST
G-8. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL SITE SAFETY AND ALL
ACCIDENTS WHICH RESULT IN DEATH, PERSONAL INJURY, OR DAMAGE TO
PROPERTY ARISING OUT OF OR IN CONNECTION WITH THE PERFORMANCE
OF THE WORK.
PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS-ON-GRADE
AT 15 FOOT MAXIMUM CENTERS EACH DIRECTION, UNLESS INDICATED
OTHERWISE. CONTRACTOR SHALL SUBMIT PLANS OF JOINT LOCATIONS TO
THE ARCHITECT/ENGINEER FOR APPROVAL PRIOR TO CASTING SLABS-ON
GRADE. COORDINATE WITH ARCHITECTURAL DRAWINGS AND FLOOR
FINISHES SUCH AS TILE AND TERRAZZO.
CR-22. STL
T.O.
TBD
TD
CONTRACTOR SHALL POST LIVE LOADS PER SECTION 106.1 OF THE
GOVERNING CODE.
G-9. TOC
TOFALL DOWELS INTO EXISTING CONCRETE OR SOLID MASONRY TO BE EPOXY
ADHESIVE ANCHORS.
CR-23.
TOLG-10. SECTIONS, DETAILS, AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED
TO BE TYPICAL AND SHALL APPLY TO SIMILAR CONDITIONS ELSEWHERE,
UNLESS OTHERWISE SHOWN.
TOP
CR-24. ALUMINUM CONDUIT IS NOT PERMITTED TO BE EMBEDDED IN CONCRETE. TOS
TOW
TPC
TSL
TYP
UNO
W/
WWF
K in gs le y F ie ld , K la m at h
Fa lls
, O R
O R
AN
G
C O
N
ST
R U
C T
C O
R R
O
SI
O N
C O
N
TR
O L H
AN
G
AR
C :\R ev it
Lo ca l\3
-1
2.
-S
-C
EN
TR
AL
-2 lv r.r vt
/1
/2
5:
:1
PM
DOCUMENTS
SIGNHD
%c-OREGON srwil
EXP. 12/31/2020
90681 PE
M&H NO.: 3142200-121252.01
10/04/19DATE:
DESIGNED BY: GFR
MJE
JAL
DRAWN BY:
CHECKED BY:
DO NOT SCALE DRAWINGS
SHEET CONTENTS
STRUCTURAL NOTES
SHEET NO.:
S-002
Mead I luntI
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
TETRATECHIt www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
PRE-ENGINEERED
METAL BUILDING NOTESSTRUCTURAL STEEL NOTES STEEL BAR GRATING NOTES POST-INSTALLED ANCHORS
MATERIAL PROPERTIES OJ.N.OJ
W-SHAPES
C-SHAPES & ANGLES
PLATES & BARS
RECTANGULAR HSS
ROUND HSS
GRATING SHALL BE AS SPECIFIED IN SECTION 055013 OF THE PROJECT
MANUAL.
GT-1. PA-1. POST-INSTALLED ANCHORS BASIS OF DESIGNS UNLESS INDICATED
OTHERWISE;- Fy = 50 KSI (A992 OR A572 Gr 50)
- Fy = 36 KSI (A36)
- Fy = 36 KSI (A36)
- Fy = 46 KSI (A500 Gr B)
- Fy = 42 KSI (A500 Gr B)
- Fy = 35 KSI (A53 Gr B)
- Fy = 36 KSI (A36)
MB-1. THE ENTIRE PRE-ENGINEERED METAL BUILDING SYSTEM SHALL BE
DESIGNED BY THE METAL BUILDING MANUFACTURER IN CONFORMANCE TO
THE INTERNATIONAL BUILDING CODE AND/OR STATE/LOCAL
REQUIREMENTS, AND THE "LOW-RISE BUILDING SYSTEMS MANUAL" AS
PUBLISHED BY THE METAL BUILDING MANUFACTURER'S ASSOCIATION.
WHERE THESE CRITERIA CONFLICT, THE MORE STRINGENT CRITERIA SHALL
APPLY.
GT-2. GRATING AND ASSOCIATED HARDWARE SHALL BE OF SAME MATERIAL. A. EXPANSION ANCHORS
CONCRETE BASE MATERIAL
MASONRY BASE MATERIAL
- HILTI KWIK BOLT-TZ
- HILTI KWIK BOLT-3GT-3. GRATING SHALL BE BANDED.
PIPE
BUTT GRATING OF ADJACENT SPANS AT BEAM CENTERLINES.RODS GT-4. B. CONCRETE SCREW ANCHORS
CONCRETE BASE MATERIAL
MASONRY BASE MATERIAL
- SIMPSON TITEN-HD
- SIMPSON TITEN-HDS-1. STEEL BEAMS WITH RESIDUAL CAMBER RESULTING FROM MILL FABRICATION
OR ROLLING SHALL BE SHOP FABRICATED AND ERECTED SUCH THAT THIS
RESIDUAL CAMBER COUNTERACTS GRAVITY LOAD DEFLECTION.
GT-5. UNLESS NOTED OTHERWISE, ATTACH GRATING TO EACH SUPPORT WITH
SADDLE CLIP AND 1/4” DIA. FASTENER. MINIMUM 4 CONNECTIONS PER
PANEL, ONE AT EACH SUPPORT.
MB-2. IT IS THE PRE-ENGINEERED METAL BUILDING MANUFACTURER'S
RESPONSIBILITY TO DESIGN THE COMPLETE BUILDING SYSTEM (STEEL
FRAMING, ANCHOR BOLTS, PURLINS, GIRTS, BRACING, CONNECTIONS,
ROOFING, WALL PANELS, ETC. SUBMIT A CERTIFICATION LETTER BEARING
THE SEAL OF A PROFESSIONAL ENGINEER STATING THE BUILDING SYSTEM
DESIGN MEETS THE INDICATED CODE, PERFORMANCE, AND LOADING
REQUIREMENTS.
C. EPOXY ANCHORS
CONCRETE BASE MATERIAL
MASONRY BASE MATERIAL
REBAR
- HILTI HIT-HY 200-R
- HILTI HIT-HY 70
- HILTI HIT-RE 500 V3
S-2. ALL BOLTED CONNECTIONS SHALL UTILIZE 3/4 INCH DIAMETER A325
BOLTS TIGHTENED TO THE SNUG-TIGHT CONDITION. THE SNUG-TIGHT
CONDITION IS DEFINED BY THE RCSC'S "SPECIFICATION FOR STRUCTURAL
JOINTS USING ASTM A325 OR A490 BOLTS”, UNLESS INDICATED OTHERWISE.
GT-6. REMOVABLE OR HINGED SECTIONS OF GRATING SHALL BE LOCKABLE.
COORDINATE WITH OWNER.
THE PRE-ENGINEERED METAL BUILDING MANUFACTURER SHALL BE
CERTIFIED BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION
CATEGORY MB.
MB-3.
STEEL CONNECTIONS NOT DETAILED ON THE PLANS ARE TO BE THE
FABRICATOR'S STANDARD AND ARE TO BE SELECTED AND DESIGNED IN
ACCORDANCE WITH AISC ASD SPECIFICATIONS, TYPE 2 FRAMING
CONNECTIONS, FOR THE REACTIONS INDICATED.
S-3.
THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF THE ENTIRE METAL
BUILDING SYSTEM FOR REVIEW. THE CONTRACTOR SHALL ALSO SUBMIT A
COMPLETE STRUCTURAL DESIGN ANALYSIS OF THE BUILDING SYSTEM. THE
SHOP DRAWING SUBMITTAL SHALL INCLUDE ALL ANCHOR BOLT
REQUIREMENTS AND FOUNDATION REACTIONS. ALL SHOP DRAWING AND
CALCULATION SUBMITTALS SHALL BEAR THE SEAL OF A PROFESSIONAL
ENGINEER.
MB-4.
DELEGATED DESIGN SUBMITTALS
MINIMUM NO. BOLTS PER CONNECTION
n = 2 FOR MEMBERS 10 INCHES DEEP OR LESS n = 3 FOR MEMBERS 12, 14, OR 15 INCHES DEEP n = 4 FOR MEMBERS 16 OR 18 INCHES DEEP n = 5 FOR MEMBERS 21 OR 24 INCHES DEEP n = 6 FOR MEMBERS 27 OR 30 INCHES DEEP n = 8 FOR MEMBERS 33 OR 36 INCHES DEEP
METAL DECK
DOCUMENTS FOR DELEGATED DESIGN SUBMITTAL ITEMS SHALL BE REVIEWED
BY THE ENGINEER OF RECORD IN RESPONSIBLE CHARGE WHO SHALL FORWARD
THEM TO THE BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THEY HAVE
BEEN REVIEWED AND ARE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE
BUILDING.
MATERIAL PROPERTIES (U.N.O)
ROOF DECK: GALVANIZED, Fy = 33 KSI FORM DECK: GALVANIZED, Fy = 33 KSI MB-5. DESIGN LOADS TO BE USED IN CONNECTION WITH THE METAL BUILDING
DESIGN ARE PER THE "DESIGN CRITERIA NOTES". IN ADDITION TO THE
ACTUAL DEAD LOAD, AN ADDITIONAL COLLATERAL ROOF FRAMING DEAD
LOAD OF 5 PSF SHALL BE INCLUDED. COORDINATE ANY EQUIPMENT LOADS
WITH THE MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND
ARCHITECTURAL DRAWINGS.
MD-1. SEE PLAN FOR DEPTH AND GAUGE. DS-1. PRE-ENGINEERED METAL BUILDING - SPECIFICATIONS SECTION 133419
AND PRE-ENGINEERED METAL BUILDING NOTES.
THE MINIMUM CONNECTION PLATE/ANGLE THICKNESS SHALL BE 5/16", THE
MINIMUM WELD 1/4", AND THE MINIMUM DESIGN LOAD ON ANY CONNECTION
10 KIPS, UNLESS INDICATED OTHERWISE.
S-4.
MD-2. METAL DECKING SHALL BE CONTINUOUS OVER 3 SPANS AND HAVE JOINTS
OVER SUPPORTING MEMBERS, UNLESS INDICATED OTHERWISE. DS-2. ANCHORAGE AND BRACING REQUIREMENTS FOR MECHANICAL, HVAC, PLUMBING, PROCESS AND ELECTRICAL EQUIPMENT INCLUDING FLOOR
AND ROOF SUPPORTED EQUIPMENT.
ALL CONNECTIONS TO PIPE AND TUBE COLUMNS SHALL BE THROUGH PLATE
CONNECTIONS UNLESS OTHERWISE INDICATED.
S-5. MD-3. BUTTON PUNCHING ROOF DECK IS NOT PERMITTED. REFERENCE
DRAWINGS FOR ROOF DECK ATTACHMENT REQUIREMENTS. STRUCTURAL
DIAPHRAGM ACTION IS PROVIDED BY THE ROOF DECK AND ITS
ATTACHMENT.
MB-6. CALCULATIONS FOR FRAME DEFLECTIONS SHALL BE DONE USING ONLY
THE BARE FRAME METHOD. REDUCTIONS BASED ON ENGINEERING
JUDGEMENT USING THE ASSUMED COMPOSITE STIFFNESS OF THE
BUILDING ENVELOPE SHALL NOT BE PERMITTED. DRIFT SHALL FOLLOW
AISC'S "SERVICEABILITY DESIGN CONSIDERATIONS FOR LOW-RISE
BUILDINGS". CALCULATIONS SHALL BE SUBMITTED VERIFYING THAT THE
ACTUAL DRIFT UNDER CODE REQUIRED LOADINGS DOES NOT EXCEED THE
ALLOWABLE.
DS-3. PIPE AND TUBE RAILINGS - SPECIFICATION SECTION 055200.ALL ANCHOR BOLTS ARE TO BE 3/4" INCH DIAMETER F1554 Gr. 36 THREADED
RODS UNLESS INDICATED OTHERWISE. (2)-1/2 INCH DIAMETER ANCHOR BOLTS
SHALL BE PROVIDED AT ALL BEAM AND LINTEL BEARINGS ON CONCRETE
OR MASONRY, UNLESS INDICATED OTHERWISE.
S-6.
DS-4. FALL PROTECTION SYSTEM IN HANGER - SPECIFICATIONS SECTION 112429.
ALL MISCELLANEOUS OPENINGS IN METAL ROOF DECK ARE TO BE FRAMED
BY L5x3x3/8 ANGLES. LONG LEG OF ANGLES SHALL BE VERTICAL. ANGLES
SHALL BE WELDED TO THE TOP CHORD/FLANGE OF ROOF FRAMING AND
EACH OTHER, UNLESS INDICATED OTHERWISE.
MD-4.
DS-5. ROOF ACCESS LADDERS - SPECIFICATIONS SECTION 055133.
POST INSTALLED ANCHORS ARE TO BE ADHESIVE ANCHORS. INSTALL
ANCHORS WITH EMBEDMENT DEPTHS INDICATED, UNLESS INDICATED
OTHERWISE.
S-7.
DS-6. CORROSION CONTROL HANGAR DOORS - SPECIFICATIONS SECTION 083416
THE PRE-ENGINEERED MANUFACTURER SHALL PROVIDE ALL GIRTS,
PURLINS, AND OTHER COMPONENTS REQUIRED FOR A COMPLETE SYSTEM.
ALL WALL SYSTEMS, SUCH AS METAL STUDS, STOREFRONTS, ETC. SHALL
BE PROPERLY SUPPORTED BY THE METAL BUILDING SYSTEM. ALLOWABLE
DEFLECTIONS OF COMPONENTS SHALL BE IN ACCORDANCE WITH THE
INTERNATIONAL BUILDING CODE.
MB-7.MD-4. CONTRACTOR IS RESPONSIBLE FOR PROVIDING POUR STOPS AT EDGES OF
METAL DECK PER SDI POUR STOP SELECTION TABLE/RECOMMENDATIONS
OR BENT PLATE POUR STOPS AS REQUIRED TO FORM THE SLAB EDGE.S-8. STUD ANCHORS ARE TO BE NELSON STUDS OR EQUAL (ASTM A108).
SHOP DRAWINGSBEAM AND LINTEL PLATES SHALL BE FULLY GROUTED WITH A MINIMUM
1/2" NON-SHRINK GROUT.
S-9. MD-5. PROVIDE LEDGERS AT ALL NEW METAL DECK EDGES AT SUPPORTING
WALLS, UNLESS NOTED OTHERWISE AND EVEN IF NOT SPECIFICALLY
DETAILED. SEE TYPICAL FLOOR AND ROOF DECK SUPPORT DETAILS ON
STRUCTURAL DETAIL SHEETS.
SD-1. SHOP DRAWINGS SHALL BE SUBMITTED FOR STRUCTURAL ITEMS AS
REQUIRED BY THE SPECIFICATIONS. CONSTRUCTION DOCUMENTS SHALL
NOT BE REPRODUCED FOR USE AS SHOP DRAWINGS.
S-10. ALL WELDING OF NEW STEEL IS TO BE WITH E70XX ELECTRODES, U.N.O.
WELDING SHALL BE IN ACCORDANCE WITH THE LATEST AWS SPECIFICATIONS
BY CERTIFIED WELDERS.
THE FOUNDATION DESIGN IS BASED UPON INDUSTRY STANDARDS. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ANY
REVISIONS REQUIRED AS A RESULT OF A CHANGE IN THE BUILDING DESIGN
ASSUMPTIONS, INCLUDING REDESIGN OF THE FOUNDATIONS.
MB-8.
PROVIDE ADDITIONAL BUTTON PUNCH EACH SIDE OF PENETRATIONS AND
OPENINGS AT FLOOR DECK. PROVIDE ADDITIONAL SIDELAP FASTENING
FOR ROOF DECK.
MD-6.
SD-2. THE GENERAL CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS AND
PRODUCT DATA FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS
PRIOR TO SUBMITTAL. REVIEWED SUBMITTALS SHALL BE STAMPED BY THE
CONTRACTOR. ANY SHOP DRAWING OR PRODUCT DATA NOT REVIEWED AND
STAMPED BY THE GENERAL CONTRACTOR WILL BE REJECTED. GENERAL
CONTRACTOR SHALL CLOUD OR FLAG ALL ITEMS NOT IN ACCORDANCE WITH
THE CONTRACT DOCUMENTS AND SHALL VERIFY ALL DIMENSIONS.
S-11. WHEN FIELD WELDING TO EXISTING STEEL, ADJUST WELDING PROCEDURES
AS REQUIRED TO BE COMPATIBLE WITH THE NEW AND EXISTING STEEL. THE SIZE, NUMBER AND PLACEMENT PATTERN OF ALL ANCHOR BOLTS
SHALL BE DETERMINED BY THE PRE-ENGINEERED BUILDING
MANUFACTURER. MINIMUM ANCHOR BOLT EMBEDMENTS ARE INDICATED
ON THE CONTRACT DRAWINGS.
MB-9.
SEE SHEET S-541 FOR TYPICAL FLOOR DECK OPENING DETAILS. FOLLOW
THE MORE STRINGENT OPENING DETAILS OF:
- INDICATED ON DRAWINGS
- MANUFACTURER'S STANDARDS.
MD-7.S-12. THE CONTRACTOR SHALL FURNISH AND INSTALL MISCELLANEOUS STEEL
(CURBS, HANGERS, BRACING, ETC.) AS INDICATED AND AS NECESSARY
PER ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS.
MB-10. THE PRE-ENGINEERED METAL BUILDING SHALL BE DESIGNED BY THE
MANUFACTURER TO RESIST LATERAL LOADS AS FOLLOWS:S-13. ALL EXTERIOR MASONRY SHELF ANGLES, LINTEL BEAMS, AND LINTEL
PLATES SHALL BE HOT DIPPED GALVANIZED ACCORDING TO ASTM A123.
SD-3. ANY CHANGES, SUBSTITUTIONS OR DEVIATIONS FROM THE ORIGINAL
CONTRACT DRAWINGS SHALL BE CLOUDED BY THE MANUFACTURER OR
FABRICATOR. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS WHICH ARE
CLOUDED OR FLAGGED BY SUBMITTING PARTIES SHALL NOT BE CONSIDERED
APPROVED AFTER THE ENGINEER'S REVIEW, UNLESS SPECIFICALLY NOTED
ACCORDINGLY BY THE ENGINEER.
MD-8. SEE SHEET S-552 FOR TYPICAL ROOF DECK OPENING DETAILS. FOLLOW
THE MORE STRINGENT OPENING DETAILS OF:
- INDICATED ON DRAWINGS
- MANUFACTURER'S STANDARDS.
INTERIOR FRAME LINES - RIGID FRAMES (PINNED BASED COLUMNS)
PERIMETER WALL LINES - BRACED BAYS OR PORTAL FRAMESS-14. ALL EXPOSED ENDS OF PIPES AND TUBES SHALL HAVE CAP PLATES
PER 4/S-601.
MB-11. THE METAL BUILDING ERECTOR SHALL PROVIDE ALL TEMPORARY GUYING
AND BRACING (SEE "GENERAL STRUCTURAL NOTES”).
COLD FORMED STEEL FRAMING NOTES SD-4. THE APPROVED SHOP DRAWINGS DO NOT REPLACE THE ORIGINAL
CONTRACT DRAWINGS. ITEMS OMITTED OR SHOWN INCORRECTLY ARE NOT
TO BE CONSIDERED CHANGES TO THE ORIGINAL CONTRACT DRAWINGS. IT IS
THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ITEMS OMITTED OR
SHOWN INCORRECTLY ARE CONSTRUCTED IN ACCORDANCE WITH THE
CONTRACT DRAWINGS.
UNLESS OTHERWISE NOTED OR SPECIFIED, ALL STEEL MEMBERS SHALL
BE CLEANED AND PAINTED IN ACCORDANCE WITH MANUFACTURER'S
STANDARD PROCEDURES OR THE CONTRACT DOCUMENTS, WHICHEVER
IS MORE STRINGENT.
MB-12.
CF-1. COLD FORMED STEEL WORK SHALL CONFORM TO THE 2012 EDITION
(INCLUDING ALL APPLICABLE SUPPLEMENTS AND STANDARDS) OF AISI'S
"NORTH AMERICAN SPECIFICATION OF FOR THE DESIGN OF COLD-FORMED
STEEL STRUCTURAL MEMBERS" MB-13. THE FOUNDATIONS HAVE BEEN DESIGNED BASED ON PINNED COLUMN
BASES. "FIXED BASE" COLUMNS ARE NOT PERMITTED WITHOUT THE
ENGINEER'S WRITTEN APPROVAL.
SD-5. SHOP DRAWING REVIEW IS INTENDED ONLY FOR GENERAL CONFORMANCE
TO THE DESIGN CONCEPT AND CONSTRUCTION DOCUMENTS.CF-2. REFER TO SPECIFICATIONS FOR COLD FORMED METAL FRAMING MATERIAL
PROPERTIES AND OTHER GENERAL REQUIREMENTS. COLD FORMED STEEL
SHALL BE GALVANIZED G-60 U.N.O. SD-6. SHOP DRAWINGS WILL BE RETURNED FOR RESUBMITTAL IF MAJOR ERRORS
ARE FOUND DURING REVIEW.CF-3. STUD, TRACK, AND OTHER APPLICABLE ROLLED SHAPES SHALL CONFORM
TO THE NOMENCLATURE AND DIMENSIONS SET FORTH BY THE STEEL STUD
MANUFACTURER'S ASSOCIATION (SSMA). REFER TO SSMA'S "PRODUCT
TECHNICAL INFORMATION” CATALOG AND ICC ER 4943P FOR MINIMUM
SECTION PROPERTIES AND DIMENSIONS.
SD-7. ALLOW A MINIMUM OF (10) WORKING DAYS FOR REVIEW OF SHOP DRAWINGS
BY THE STRUCTURAL ENGINEER.
BUILDING SYSTEMS SUPPORT
AND RESTRAINT ANCHORAGE NOTES
CF-4. SCREWS FOR ATTACHING COLD FORMED STEEL TO COLD FORMED STEEL
SHALL BE CORROSION RESISTANT, SELF DRILLING, SELF TAPPING, #8 OR
#10 AS INDICATED, PAN OR HEX HEAD, WITH LENGTH, POINT STYLE AND
INSTALLATION METHOD IN ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS. PROVIDE 3/4” MINIMUM SPACING BETWEEN SCREWS AND
3/4” MINIMUM EDGE DISTANCE U.N.O. SR-1. TAKE CARE TO PROPERLY SUPPORT ALL COLLATERAL ELEMENTS, EQUIPMENT, DISTRIBUTION AND COMPONENTS (SUCH AS MECH, ELEC, PLUMBING, FIRE PROTECTION). SUPPORT SHALL NOT RESULT IN DAMAGE, WARPING, BUCKLING, TORSION, AND ECCENTRICITIES ON THE STRUCTURE. STRUCTURAL OBSERVATIONCF-5. ALL CONNECTIONS SHALL HAVE AT LEAST (2) #8 SCREWS U.N.O.
CF-6. FASTENERS FROM COLD FORMED STEEL TO STRUCTURAL STEEL OR
CONCRETE SHALL BE 0.157" DIAMETER POWDER DRIVEN FASTENERS "SHOT
PINS" UNLESS OTHERWISE NOTED. USE HILTI "X-U" FASTENERS WITH 1"
EMBEDMENT INTO CONCRETE WITH WASHERS PER MANUFACTURER, U.N.O.
SIZE LENGTH OF SHOT PINS AS REQUIRED BY MANUFACTURER'S ICC ES
REPORT FOR ATTACHMENT TO STRUCTURAL STEEL. MANUFACTURER'S
EDGE DISTANCE AND SPACING REQUIREMENTS SHALL BE MET AND VERIFIED
BY THE CONTRACTOR IN THE FIELD.
OB-1. STRUCTURAL OBSERVATION BY THE ENGINEER IS REQUIRED. PROVIDE
ACCESS AND SCHEDULE ALLOWANCES FOR STRUCTURAL OBSERVATION.
STRUCTURAL OBSERVATION DOES NOT ACCOUNT FOR ANY OF THE
REQUIRED SPECIAL INSPECTIONS.
SR-2. FOR SUPPORT FROM WIDE FLANGE BEAMS PROVIDE CONCENTRIC
CONNECTIONS AND LIMIT HANGER LOADS TO 500 LB / BEAM TOTAL.
LIMIT ECCENTRIC CONNECTIONS TO 200 LB.
SR-3. DO NOT BRACE TO THE BOTTOM FLANGE OF BEAMS UNLESS ADEQUATELY
BRACED OR UNLESS THE BRACE LINE OF FORCE IS PARALLEL TO THE BEAM
AND ALIGNED AT THE CENTERLINE.
OB-2. COORDINATE WITH ENGINEER THE NECESSARY HOLD POINTS FOR
STRUCTURAL OBSERVATION AT A PRECONSTRUCTION MEETING.
MINIMUM HOLD POINTS ARE LISTED BELOW:
- FOUNDATION PRE-PLACEMENT
- CMU IN PROGRESS
- STRUCTURAL STEEL IN PROGRESS
- EQUIPMENT ROOM SLAB ON METAL DECK PRE-PLACEMENT
- FINAL STRUCTURE PRIOR TO CONCEALMENT.
SR-4. DESIGN AND PROVIDE CONNECTIONS TO THE STRUCTURE THAT MINIMIZE
CONCENTRATED LOCAL EFFECTS TO THE STRUCTURE, IN COORDINATION
WITH OTHER TRADES.
CF-7. WALL TRACKS AND ACCESSORIES SHALL BE THE SAME GAUGE AND WIDTH
AS THE STUDS, U.N.O.
CF-8. PROVIDE SUFFICIENT STUDS AND BLOCKING/BACKING AT ALL GRAB BARS
AND WALL HUNG EQUIPMENT, MONITORS, CABINETS, TOILET ACCESSORIES,
ETC.
OB-3. CORRECTIONS OF DEFICIENCIES NOTED BY THE ENGINEER AND SIMILAR
DEFICIENCIES SHALL BE CORRECTED AND OBSERVED BEFORE
CONCEALMENT.
K in gs le y F ie ld , K la m at h
Fa lls
, O R
O R
AN
G
C O
N
ST
R U
C T
C O
R R
O
SI
O N
C O
N
TR
O L H
AN
G
AR
C :\R ev it
Lo ca l\3
-1
2.
-S
-C
EN
TR
AL
-2 lv r.r vt
/1
/2
5:
:1
DOCUMENTS
SIGNHD
%c-OREGON srwil
EXP. 12/31/2020
90681 PE
M&H NO.: 3142200-121252.01
10/04/19DATE:
DESIGNED BY: GFR
MJE
JAL
DRAWN BY:
CHECKED BY:
DO NOT SCALE DRAWINGS
SHEET CONTENTS
STATEMENT OF
SPECIAL
INSPECTIONS AND
NOTES
SHEET NO.:
S-003
Mead I luntI
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
TETRATECHIt www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
STATEMENT OF
SPECIAL INSPECTION AND TESTING
TABLE 1: SPECIAL INSPECTION AND TESTING TABLE 1: SPECIAL INSPECTION AND TESTING
SPECIAL INSPECTION TESTING CODE / STANDARD REF. SPECIAL INSPECTION TESTING CODE/STANDARD REF.
SOILS COMMENTS MASONRY COMMENTSCONTIN
UOUS
PERI
ODIC
CONTIN
UOUS
PERI
ODIC
(SEE (SEE(IBC 2015 UNO) (IBC 2015 UNO)SPECS) SPECS) TI-1. THE CONTRACTOR SHALL RETAIN THE SERVICES OF ONE OR MORE
APPROVED AGENCIES TO PROVIDE SPECIAL INSPECTIONS AND TESTS DURING
CONSTRUCTION ON THE TYPES OF WORK SPECIFIED IN SECTION 1705 AND
IDENTIFY THE APPROVED AGENCIES TO THE AHJ. THESE SPECIAL
INSPECTIONS AND TESTS ARE IN ADDITION TO THE INSPECTIONS BY THE
CONTRACTOR THAT ARE IDENTIFIED IN SECTION 110.
CMU MATERIAL VERIFICATION, INSPECTION OF CMU
PLACEMENT, MORTAR PRODUCT VERIFICATION,
MORTAR MIXING AND CURING, MORTAR JOINTS
TMS 602 / AC I 530.1 / ASCE 6 /
ART. 2.1,2.6A, 2.6B, 2.6C, 2.4
G.1.b, 3.3B
VERIFICATION THAT OVER-EXCAVATION EXTENDS TO
PROPER DEPTH, HAS REACHED PROPER MATERIAL,
AND HAS EXTENDED TO PROPER HORIZONTAL
EXTENTS
X X INCLUDE MORTAR SAMPLES
BY PROJECT GEOTECHNICAL ENGINEERX TABLE 1705.6 (2)
MORTAR COMPRESSIVE STRENGTH TESTING X TMS 602 / AC I 530.1 / ASCE 6
PRIOR TO PLACEMENT OF COMPACTED FILL,
OBSERVATION OF SUBGRADE AT BOTTOM OF
OVER-EXCAVATION, AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY
TI-2. THE SIA SHALL BE INDEPENDENT FROM THE CONTRACTOR RESPONSIBLE
FOR THE WORK BEING INSPECTED. SPECIAL INSPECTION AND TESTING
SHALL BE DONE BY APPROVED, QUALIFIED PERSONNEL SATISFACTORY
TO THE AUTHORITY HAVING JURISDICTION.
PRIOR TO GROUTING, INSPECTION OF REINFORCING
STEEL PLACEMENT, ANCHORAGE AND EMBEDDED
ELEMENTS
TMS 402 / ACI 530 / ASCE 5
SEC. 1.16/ TMS 602 / ACI 530.1
/ ASCE 6 ART. 2.4, 3.4, 3.2, 3.6A
XBY PROJECT GEOTECHNICAL ENGINEERX X TABLE 1705.6 (5)
GROUT PLACEMENT -
VERIFICATION OF REQUIRED DESIGN MIX
TI-3. REFER TO PROJECT SPECIFICATIONS FOR COST RESPONSIBILITY OF
SPECIAL INSPECTION AND TESTING.
CLASSIFICATION AND TESTING OF COMPACTED FILL
MATERIALS
VERIFY PRIOR TO DEPOSITING TMS 602 / ACI 530.1 / ASCE 6XBY PROJECT GEOTECHNICAL ENGINEERX X TABLE 1705.6 (3)
TMS 602/ACI 530.1 /
ASCE 6 ART. 3.3 F
GROUT PLACEMENT -
SIZE AND LOCATION OF STRUCTURAL ELEMENTS
DURING PLACEMENT AND COMPACTION OF
COMPACTED FILL, VERIFICATION OF USE OF PROPER
MATERIALS, DENSITIES AND LIFT THICKNESSES
TI-4. SPECIAL INSPECTION AND TESTING DOES NOT REPLACE CODE-REQUIRED
INSPECTIONS OR STRUCTURAL OBSERVATIONS.
X
BY PROJECT GEOTECHNICAL ENGINEERX X TABLE 1705.6 (4)
GROUT PLACEMENT -
TYPE SIZE, AND LOCATION OF ANCHORS INCLUDING
OTHER DETAILS OF ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES OR OTHER
CONSTRUCTION
TI-5. CONTRACTOR’S RESPONSIBILITY:
A. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT ALL STRUCTURAL
WORK FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS.
ANY INSPECTION PROVIDED BY OTHERS DOES NOT RELIEVE THE
CONTRACTOR OF THIS RESPONSIBILITY. ANY DEVIATIONS FROM THE
CONTRACT DOCUMENTS THAT ARE FOUND AT A LATER DATE AND ARE
DECLARED TO BE SIGNIFICANT BY THE STRUCTURAL ENGINEER SHALL
BE CORRECTED BY THE CONTRACTOR WITHOUT COST OR ANY DELAY
TO THE PROJECT SCHEDULE.
VERIFICATION THAT FOOTING EXCAVATION EXTENDS
TO PROPER DEPTH AND HAVE REACHED PROPER
MATERIAL
TMS 402 / ACI 530 / ASCE 5
SEC. 1.16.4.3, 1.17.1XBY PROJECT GEOTECHNICAL ENGINEERX X TABLE 1705.6 (2)
VERIFICATION OF MATERIALS BELOW FOOTINGS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY
X X BY PROJECT GEOTECHNICAL ENGINEER TABLE 1705.6 (1) GROUT PLACEMENT -
TESTING FOR SLUMP, AIR CONTENT, TEMPERATURE AT
TIME WHEN STRENGTH SAMPLES ARE MADE
TMS 602 /ACI 530.1 /
ASCE 6 ART. 1.5 B.1.b.3X X
VERIFICATION THAT UNDERSLAB BASE MATERIALS
HAVE BEEN PROPERLY PLACED AND COMPACTED BY PROJECT GEOTECHNICAL ENGINEERX X TABLE 1705.6 (4)
B. THE CONTRACTOR SHALL PROVIDE THE SIA ACCESS TO ALL PLACES
WHERE THE WORK IS BEING PERFORMED. A MINIMUM OF 24 HOURS
NOTIFICATION SHALL BE GIVEN TO THE SIA AND DESIGN PROFESSIONAL
PRIOR TO THE COMMENCEMENT OF WORK REQUIRING TESTING OR
INSPECTION. THE WORK FOR WHICH SPECIAL INSPECTION IS REQUIRED
SHALL REMAIN ACCESSIBLE AND EXPOSED FOR SPECIAL INSPECTION
PURPOSES UNTIL COMPLETION OF THE REQUIRED SPECIAL INSPECTIONS.
GROUT PLACEMENT -
INSPECTION OF GROUT PLACEMENT FOR PROPER
APPLICATION / CONSOLIDATION
TMS 602/ACI 530.1 /
ASCE 6 ART. 3.5, 3.6CXSPECIAL INSPECTION TESTING CODE / STANDARD REF.
CONCRETE REINFORCEMENT COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE (IBC 2015 UNO)SPECS) GROUT COMPRESSIVE STRENGTH TESTING TMS 602 / ACI 530.1 / ASCE 6X
TABLE 1705.3(1)/
ACI 318:3.5, 7.1-7.7
VERIFICATION OF PROTECTION FROM THE ADVERSE
EFFECTS OF WEATHER, HEATING EQUIPMENT,
WELDING AND OTHER POTENTIALLY HARMFUL
CONDITIONS.
INSPECTION OF REINFORCING STEEL AND PLACEMENT X
X TMS 602 / ACI 530.1 / ASCE 6
C. TEMPORARY CONSTRUCTION AND SITE SAFETY ARE THE RESPONSIBILITY
OF THE CONTRACTOR. THE SIA IS NOT INSPECTING FOR O.S.H.A.
COMPLIANCE OR REQUIRED TO INSPECT TEMPORARY CONSTRUCTION,
SUCH AS TEMPORARY BRACING OR SHORING.
VERIFICATION OF A706 STEEL FOR WELDED
REINFORCEMENT
TABLE 1705.2.2/AWS D1.4 /
ACI 318 3.5.2CONFIRM WITH MILL CERTIFICATEX
SPECIAL INSPECTION TESTING CODE/STANDARD REF.
SHEAR REINFORCEMENT (STIRRUPS, TIES, SPIRALS) X TABLE 1705.2.2/1705.2.1 STEEL DECK COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE (IBC 2015 UNO) D. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A
MAIN WIND OR SEISMIC FORCE RESISTING SYSTEM OR COMPONENT
LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A
WRITTEN STATEMENT OF RESPONSIBILITY TO THE AUTHORITY HAVING
JURISDICTION (BUILDING OFFICIAL) AND THE OWNER PRIOR TO THE
COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE
CONTRACTOR’S STATEMENT OF RESPONSIBILITY SHALL CONTAIN
ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS
CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION.
SPECS)SPECIAL INSPECTION TESTING CODE / STANDARD REF.
CONCRETE COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE INCLUDES FORM DECK, ROOF DECK, COMPOSITE
DECK. FOR COMPOSITE CONSTRUCTION SEE
ALSO STRUCTURAL STEEL SPECIAL INSPECTION
AND TESTING NOTES
(IBC 2015 UNO)SPECS) MATERIAL VERIFICATION -
MARKINGS AND CONFORMANCE TO ASTM STANDARDS X TABLE 1705.2.2 (1a)
PRE-PLACEMENT INSPECTION OF CAST-IN-PLACE
ANCHORS AND EMBEDS
COORDINATE WITH STEEL INSPECTION
REQUIREMENTS
TABLE 1705.3 (3)/ACI 318:
8.1.3, 21.2.8/ACI 318 D9.2X
PRE-PLACEMENT INSPECTION OF FORMWORK FOR
SHAPE, LOCATION, DIMENSIONS
MATERIAL VERIFICATION -
MANUFACTURER’S CERTIFIED TEST REPORTS
TABLE 1705.3 (12)/
ACI 318: 6.1.1X X TABLE 1705.2.2 (1b)
E. STRUCTURAL STEEL: THE CONTRACTOR AND SUBCONTRACTOR(S)
RESPONSIBLE FOR ERECTION AND FABRICATION SHALL BE RESPONSIBLE
FOR QUALITY CONTROL INSPECTORS (QCI) IN ACCORDANCE WITH AISC
360 AND AISC 341. REFER TO STRUCTURAL STEEL TESTING AND
INSPECTION NOTES.
INSPECTION OF DECK FASTENING
(WELDING AND OTHER FASTENERS)
TABLE 1705.2.2 (2a)/
AWS D1.3
VERIFY PRIOR TO DEPOSITING. NOTE ADDITIVES
(ADMIXTURES, WATER, ETC) ADDED PRIOR TO
PLACEMENT
XTABLE 1705.3 (5)/
ACI 318: CH. 4, 5.2-5.4PLACEMENT-VERIFICATION OF REQUIRED DESIGN MIX X
SPECIAL INSPECTION TESTING CODE/STANDARD REF.
COLD FORMED STEEL COMMENTSCONTIN
UOUS
PERI
ODIC
(SEEPLACEMENT -TESTING FOR SLUMP, AIR CONTENT,
TEMPERATURE AT TIME WHEN STRENGTH SAMPLES
ARE MADE
TABLE 1705.3 (6)/
ASTM C 172, ASTM C 31 /
ACI 318:5.6, 5.8
(IBC 2015 UNO)SPECS)X X
TI-6. THE SIA IS NOT AUTHORIZED TO DIRECT OR APPROVE ANY CHANGES FROM
THE CONTRACT DOCUMENTS. IF THE CONTRACTOR WISHES TO QUESTION
THE SIA'S INTERPRETATION OF THE CONTRACT DOCUMENTS, HE MAY DO
SO WITH THE OWNER ASSISTED BY THE DESIGN PROFESSIONAL.
VERIFY WITH AWS
D1.3 REQUIREMENTS
INSPECTION
FREQUENCY SHALL
BE NO LESS THAN
PERIODIC.
INSPECTION OF CONCRETE PLACEMENT FOR PROPER
APPLICATION / CONSOLIDATION
TABLE 1705.3 (7)/
ACI 318: 5.9, 5.10X
(LIGHT FRAME CONSTRUCTION)
WELDING INSPECTION
WELDING AND WELDING INSPECTOR
QUALIFICATION PER AWS D1.3
1705.2.2.1.1 / AWS D1.3COMPRESSIVE STRENGTH TESTING X ACI 318: 5.6 TI-7. THE SIA IS NOT AUTHORIZED TO STOP OR DELAY THE WORK. IF THE
CONTRACTOR ELECTS TO CONTINUE WITH A CERTAIN PORTION OF WORK
AFTER BEING NOTIFIED BY THE SIA THAT SUCH WORK IS NOT IN ACCORDANCE
WITH THE CONSTRUCTION DOCUMENTS, THE CONTRACTOR DOES SO AT
THEIR OWN RISK AND MAY BE REQUIRED TO CORRECT THE WORK AT A
LATER DATE.
INSPECTION OF FOR MAINTENANCE OF SPECIFIED
CURING TEMPERATURE AND TECHNIQUES
TABLE 1705.3 (8)/
ACI 318: 5.11-5.13X
SPECIAL INSPECTION TESTING CODE /STANDARD REF.VERIFICATION OF PROTECTION FROM THE ADVERSE
EFFECTS OF WEATHER, HEATING EQUIPMENT,
WELDING AND OTHER POTENTIALLY HARMFUL
CONDITIONS.
ARCHITECTURAL ELEMENTS (SEISMIC) COMMENTSCONTIN
UOUS
PERI
ODIC
(SEEACI 318, ACI 305, ACI 306X (IBC 2015 UNO)SPECS)
TI-8. THESE NOTES AND THE PROJECT SPECIFICATIONS TYPICALLY INDICATE
THE FREQUENCY OF TESTING AND SPECIAL INSPECTIONS. WHERE THE
FREQUENCY IS NOT INDICATED, THE SIA SHALL SUBMIT A PROPOSAL OF
SPECIAL INSPECTION AND TESTING INTERVALS TO THE OWNER.
NOT REQUIRED FOR WALLS AND VENEER 30 FEET
OR LESS IN HEIGHT ABOVE GRADE OR WALKING
SURFACE; NOTE REQUIRED FOR CLADDING AND
VENEER SYSTEMS 5 PSF OR LESS; NOT
REQUIRED FOR INTERIOR NON-BEARING WALL
SYSTEM 15 PSF OR LESS
VERIFICATION OF IN-SITU CONCRETE STRENGTH PRIOR
TO REMOVAL OF SHORES OR FORMS FROM BEAMS
AND STRUCTURAL SLABS.
NOT REQUIRED AT FOOTINGS, SLABS ON GRADE
OR OTHER GROUND SUPPORTED CONCRETE
TABLE 1705.3 (11)/
ACI 318 6.2
VERIFICATION OF PROPER ERECTION AND FASTENING
FOR EXTERIOR CLADDING, INTERIOR NON-BEARING
WALLS AND EXTERIOR VENEER
X X 1705.11.5
TI-9. THE SIA SHALL ISSUE ONGOING REPORTS OF INSPECTIONS AND TESTS TO
THE CONTRACTOR AND DESIGN PROFESSIONAL.FOLLOW ALL REQUIREMENTS LISTED FOR CAST-IN-PLACE CONCRETE.
FOR COMPOSITE DECK COORDINATE WITH STEEL SPECIAL INSPECTION
AND TESTING REQUIREMENTS
INSPECTION AND TESTING OF CONCRETE ON
COMPOSITE METAL DECK OR FORM DECK
TABLE 1705.3/
AISC 360, AISC 341 TI-10. THE SIA SHALL KEEP REPORTS OF EACH INSPECTION AND TESTING ACTIVITY.
REPORTS SHALL INDICATE WHETHER THE WORK WAS IN COMPLIANCE WITH
THE APPROVED CONSTRUCTION DOCUMENTS. DEFICIENCIES SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR
CORRECTION.
BE BROUGHT TO THE ATTENTION OF THE AUTHORITY HAVING JURISDICTION
(BUILDING OFFICIAL) AND DESIGN PROFESSIONAL PRIOR TO THE COMPLETION
OF THAT PHASE OF THE WORK.
SPECIAL INSPECTION TESTING CODE/STANDARD REF.
SPECIAL INSPECTION TESTING CODE / STANDARD REF. MECHANICAL/ ELECTRICAL COMPONENTS COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE (IBC 2015 UNO)SPECS)CONCRETE POST-INSTALLED ANCHORS COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE IF THEY ARE NOT CORRECTED, THE DISCREPANCIES SHALL(IBC 2015 UNO)SPECS) INSPECTION OF SEISMIC ANCHORAGE FOR
EMERGENCY AND STANDBY POWER SYSTEMS X 1705.11.6 (1)
INSPECTION OF POST-INSTALLED MECHANICAL
ANCHORS; VERIFICATION OF APPROVED RESEARCH
REPORT ACI 355.2 PREQUALIFIED
INSPECT IN ACCORDANCE WITH APPROVED
RESEARCH REPORT
TABLE 1705.3 (3)/
ACI 318X
NOT REQUIRED FOR ITEMS UNDER 20 LBS. OR
LESS IN ANY LOCATION; NOT REQUIRED FOR
FLOOR-SUPPORTED ITEMS 400 LBS OR LESS AND
HAVING CENTER OF GRAVITY 4 FT. OR LESS
ABOVE FLOOR.
INSPECTION AND VERIFICATION OF SUPPORTS,
ATTACHMENTS AND SEISMIC BRACING. VERIFICATION
OF RESTRAINT ELEMENTS MEET PROJECT
REQUIREMENTS.
TI-11. THE SIA SHALL PREPARE AND SUBMIT A FINAL REPORT DOCUMENTING
REQUIRED SPECIAL INSPECTIONS AND CORRECTION OF ANY DISCREPANCIES
NOTED IN THE INSPECTIONS SHALL BE SUBMITTED AT A POINT IN TIME
AGREED UPON PRIOR TO THE START OF WORK BY THE APPLICANT AND THE
BUILDING OFFICIAL.
1705.12.3/
ASCE 7-10 13.2.1 /
ASCE 7-10 TABLE 13.2-1
X
INSPECTION OF POST-INSTALLED ADHESIVE ANCHORS
(INCLUDING ANCHORS W/ SUSTAINED TENSION AND
UPWARDLY INCLINED ANCHORS); VERIFICATION OF
INSTALLER CERTIFICATION; VERIFICATION OF
APPROVED RESEARCH REPORT ACI 355.2
PREQUALIFIED
INSPECT IN ACCORDANCE WITH APPROVED
RESEARCH REPORT (CONTINUOUS - DO NOT
LOWER INSPECTION FREQUENCY)
TABLE 1705.3 (4)/
ACI 318: 3.8.6, 8.1.3, 21.2.8, /
ACI 318 D9.2, D9.2.4
X
INSPECTION OF VIBRATION ISOLATION SYSTEMS X 1705.11.6 (5)
TI-12. FABRICATOR SPECIAL INSPECTIONS: UNLESS OTHERWISE APPROVED,
SPECIAL INSPECTIONS SHALL BE PERFORMED FOR WORK AT FABRICATION
SHOPS. SPECIAL INSPECTIONS AT THE FABRICATION SHOP BY THE SIA
COULD BE WAIVED BY THE OWNER IF THE FABRICATION SHOP IS
REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT SPECIAL
INSPECTION IN ACCORDANCE WITH CODE (1704.2.5.2). APPROVAL SHALL BE
EVALUATED BY THE SIA AND ESTABLISHED WITH THE OWNER PRIOR TO
FABRICATION. THE FABRICATOR SHALL SUBMIT A CERTIFICATE OF
COMPLIANCE TO THE OWNER AND BUILDING OFFICIAL IN ACCORDANCE
WITH CODE (1704.5.2) STATING THAT THE WORK WAS PERFORMED IN
ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. THE
OWNER AND SIA RESERVE THE RIGHT TO INSPECT THE WORK AT THE
FABRICATION SHOP REGARDLESS OF FABRICATOR QUALIFICATIONS /
CERTIFICATIONS.
SPECIAL INSPECTION TESTING CODE/STANDARD REF.
FIRE PROTECTION COMMENTSCONTIN
UOUS
PERI
ODIC
(SEE (IBC 2015 UNO)SPECS)
SPRAYED, MASTIC, INTUMESCENT, PENETRATIONS AND
JOINTS
NOT COVERED IN THIS TABLE.
REFER TO FIRE PROTECTION DRAWINGS AND CODE REQUIREMENTS
1705.13, 1705.14, 1705.16, 1705.17
TABLE NOTES:
A. REFER TO SPECIFICATIONS FOR TESTING REQUIREMENTS AND ADDITIONAL QUALITY ASSURANCE REQUIREMENTS.
TI-13. STRUCTURAL SPECIAL INSPECTION AND TESTING BY THE SIA SHALL
INCLUDE SCOPE LISTED IN TABLE 1. WHERE PROJECT GEOTECHNICAL
ENGINEER IS INDICATED, THE ENGINEER RESPONSIBLE FOR THE SOILS
REPORT RELIED ON FOR DESIGN, OR HIS DESIGNEE, SHALL PERFORM
THE INSPECTIONS AND TESTING.
TI-14. REFER TO STRUCTURAL STEEL SPECIAL INSPECTION NOTES FOR
STRUCTURAL STEEL AND STEEL ELEMENTS SIMILAR TO STRUCTURAL
STEEL. FOR PEMB STRUCTURAL SYSTEM AND OTHER NON-PEMB STEEL
Ki ng sl ey
F ie ld , K la m at h F al ls
, O R
O R
AN
G
C O
N
ST
R U
C T
C O
R R
O
SI
O N
C O
N
TR
O L H
AN
G
AR
C :\R ev it
Lo ca l\3
-1
2.
-S
-C
EN
TR
AL
-2 lv r.r vt
/1
/2
5:
:1
DOCUMENTS
SIGNHD
%c-OREGON srwil
EXP. 12/31/2020
90681 PE
M&H NO.: 3142200-121252.01
10/04/19DATE:
DESIGNED BY: GFR
MJE
JAL
DRAWN BY:
CHECKED BY:
DO NOT SCALE DRAWINGS
SHEET CONTENTS
STRUCTURAL STEEL
SPECIAL
INSPECTIONS AND
NOTES
SHEET NO.:
S-004
Mead I luntI
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
TETRATECHIt www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
© Copyright 2018 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
STRUCTURAL STEEL
SPECIAL INSPECTION AND TESTING
TABLE 2: STRUCTURAL STEEL SPECIAL INSPECTION AND TESTING TABLE 2: STRUCTURAL STEEL SPECIAL INSPECTION AND TESTING
INSPECTION INSPECTION
CODE / STANDARD REF.
(AISC 360-10 UNO)
CODE / STANDARD REF.
(AISC 360-10 UNO)STRUCTURAL STEEL/STEEL ELEMENT ITEM TESTING COMMENTS STRUCTURAL STEEL/STEEL ELEMENT ITEM TESTING COMMENTSQAI QAIQCI QCI(SIA) (SI A) SSTI-1.