6 - Mechanical.pdf
PDF 16 MB Posted
- Attached to
- Construct Corrosion Control Hangar Federal contract opportunity
- Solicitation number
- W50S8Z20B0001
About this file
This document summarizes a federal contract opportunity for construction services. The Oregon Air National Guard at Kingsley Field is soliciting bids to award a firm fixed-price contract to construct a corrosion control hangar and associated facilities totaling approximately 16,000 square feet. The project scope includes construction of a pre-engineered metal hangar, support shop spaces, and a concrete aircraft tow-lane. The solicitation will include a base bid and four options. The contract is set aside for small businesses and has a magnitude between $5-10 million. The NAICS code is 236210 with a $36.5 million size standard. The solicitation is anticipated to be issued on December 3rd with a pre-bid conference on December 12th and bids due on January 6th. The performance period is 365 days.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch #3 Revised Specs -Steel Sliding Doors -RFI 047.pdf | ||
| Attch # 2 - Sheet T-011 -RFI 040-41 Response.pdf | ||
| Attch #4 - Revised - Door hardware.pdf | ||
| SF30 Amendment #4.pdf | ||
| Corrosion Control Pre-Bid Minutes 12 Dec.pdf | ||
| SF30 Amendment #3.pdf | ||
| SF30 Amendment #2.pdf | ||
| SF30.pdf | ||
| Sign-In Sheet.pdf | ||
| JA Brand Name - Automated Logic_Redacted.pdf | ||
| 8 - Technology Systems.pdf | ||
| 7 - Electrical.pdf | ||
| 2 - Structural.pdf | ||
| W50S8Z20B0001.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 3.pdf | ||
| 1 - General and Civil.pdf | ||
| 4 - Fire Alarm and Fire Sprinkler.pdf | ||
| 5 - Plumbing.pdf | ||
| JA Brand Name - Advantor (1)_Redacted.pdf | ||
| 3 - Architectural.pdf | ||
| JA Brand Name - Monaco Fire Alarm_Redacted.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 1.pdf | ||
| KANGB Corr Control Hgr_Type B3 Revised Bid Spec Vol 2.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MeadHVAC SYMBOLS: PIPING SYMBOLS MECHANICAL PIPING: GENERAL NOTES:
I luntABBREVIATIONS AND SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT
APPLY TO THIS PROJECT. ADDITIONAL ABBREVIATIONS MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
1.O A COMPRESSED AIRAIRFLOW (SUPPLY/OUTSIDE AIR)
AIRFLOW (RETURN/EXHAUST)
PIPE TURNED TOWARD I
C- PIPE TURNED AWAY — BFW BOILER FEED WATER
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC, THEY MAY NOT SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR ELBOWS WHICH MAY BE REQUIRED FOR PROPER INSTALLATION OF VARIOUS MATERIALS, EQUIPMENT, PIPING AND DUCTWORK SYSTEMS IN ALLOTTED SPACES. EXAMINE THESE AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS AND INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF EQUIPMENT, PIPING, AND DUCTWORK FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB SITE
CONDITIONS SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA COST TO CONTRACT.
2.DG PIPE TURNED AWAY BOILER SURFACE BLOW DOWNBSDDOOR GRILLE
DCO O PIPE TURNED TOWARD — BBD BOILER BOTTOM BLOW DOWN3/4" DOOR UNDERCUT
CD- FLEXIBLE CONNECTOR
UNION
FLANGES
REDUCER (CONCENTRIC)
REDUCER (ECCENTRIC)
PIPE CAP/CLEAN OUT
CF CHEMICAL FEEDSUPPLY OR OUTDOOR AIR
H h
CHILLED WATER SUPPLYCHWSRETURN OR TRANSFER
CHWR CHILLED WATER RETURNEXHAUST {>+
ELEVATION OF PIPING AND DUCTWORK INDICATED ON THESE DRAWINGS ARE TO BE USED AS GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO
CHANGE.
3.
T CTS COOLING TOWER WATER SUPPLY It TETRATECHSUPPLY DUCT TURNED AWAYc
UL7 p COOLING TOWER WATER RETURNCTRSUPPLY DUCT TURNED TOWARD
RECTANGLE DUCT SIZE
(FIRST FIGURE IS SIDE SHOWN)
ROUND DUCT (RIGID)
www.tetratech.com
G PIPE PLUG cws CONDENSER WATER SUPPLY 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
12x12
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS, IS AS EXACT AS COULD BE SECURED. THE INFORMATION IS NOT
WARRANTED NOR GUARANTEED ACCURATE, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
PROCEEDING WITH WORK.
FLUID FLOW DIRECTION CWR CONDENSER WATER RETURN
(> 120 Cj PG
PIPE GUIDE
CONDENSATE DRAINCDPAOVAL DUCT12/120 — PIPE ANCHOR
GWS GLYCOL WATER SUPPLYPITCH
FLEXIBLE CONNECTION c ACCURATE AND LEGIBLE AS-BUILT DRAWING MARKUPS SHALL BE MAINTAINED AT THE JOB SITE, AND BE
SUBMITTED PRIOR TO FINAL PAYMENT FOR THE CREATION OF FINAL RECORD DRAWINGS.
5.PIPE PITCH DIRECTION GWR GLYCOL WATER RETURN
MDUCT (FLEXIBLE ROUND) NEW CONNECTION TO EXISTING HIGH PRESSURE CONDENSATE RETURNHPCR ALL NEW AND EXISTING ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION
ACTIVITIES.
TURNING VANES 6.EXISTING TO REMAIN
HIGH PRESSURE STEAMHPS
EXISTING TO BE REMOVED3 TRANSITION (SQUARE-TO-ROUND)
HWS HOT WATER SUPPLY
TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL CLOSURE CAN BE MADE.7.NEW TO BE INSTALLED © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
BACKDRAFT DAMPER
HWR HOT WATER RETURNBDD i PRESSURE GAUGE VERIFY ALL EQUIPMENT LOCATIONS AND PIPE AND DUCT ROUTING WITH OWNER PRIOR TO INSTALLATION.8.££ VOLUME DAMPER
IWS ICE WATER SUPPLY
TEMPERATURE GAUGEFIRE DAMPER WITH ACCESS
DOOR
r a £ SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL BE APPROVED PRIOR TO WORK BEING STARTED. SCHEDULED SHUTDOWNS SHALL BE CLOSELY COORDINATED WITH EXISTING OPERATIONS.
9.f IWR ICE WATER RETURNAD »FD
WATER HAMMER ARRESTOR
'4. LP LIQUID PETROLEUM[jJAVFIRE DAMPER IN VERTICAL
DUCT
10. MAINTAIN 3'-0" CLEAR HORIZONTALLY IN FRONT OF ALL ELECTRICAL EQUIPMENT.
AIR VENT (AUTO)
AIR VENT (MANUAL)
AUTOMATIC CONTROL VALVE (2-WAY)
AUTOMATIC CONTROL VALVE (3-WAY)
BALL VALVE
BALANCING VALVE
FD LPS LOW PRESSURE STEAMMV 11. COORDINATE POWER REQUIREMENTS FOR ALL POWER TO MECHANICAL EQUIPMENT INCLUDING CONTROL SYSTEM WITH ELECTRICAL CONTRACTOR AND INSURE ALL COSTS ASSOCIATED WITH SUCH ARE INCLUDED IN THE PROJECT BID COST. PROVIDE ELECTRICAL POWER, TRANFORMERS, RELAYS, ETC. AS NECESSARY
TO ALL HVAC AND MECHANICAL CONTROLS.
£ £ LOW PRESSURE CONDENSATE RETURNLPCRMOTOR OPERATED DAMPER□ MOD
MPS MEDIUM PRESSURE STEAMCEILING MOUNTED ACCESS PANEL
MEDIUM PRESSURE CONDENSATE RETURNMPCR—
12. PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES ON ALL EQUIPMENT.CARBON MONOXIDE (CO) SENSORCO
G NATURAL GAS
CARBON DIOXIDE (C02) SENSORC02 —PCR— PUMPED CONDENSATE RETURNBUTTERFLY VALVE
RL REFRIGERANT LIQUIDBACKFLOW PREVENTION VALVENITROGEN DIOXIDE (N02) SENSORN02
CHECK VALVE REFRIGERANT SUCTIONRS
ROOM SENSORRS EQUIPMENT DRAIN VALVE RHG REFRIGERANT HOT GAS
FILTER
SRV STEAM RELIEF VENTSP STATIC PRESSURE SENSOR
FLOW MEASUREMENT STATION
VAC VACUUM
HUMIDISTATH GATE VALVE
GAUGE CONNECTION
TEMPERATURE SENSORTS h GLOBE ANGLE VALVE oTHERMOSTATT GLOBE VALVE
{X} COISOLATION/SHUT-OFF/MANUAL VALVE
COABBREVIATIONSINSULATED BASE THERMOSTATT oPLUG VALVE o££ CDr^PRESSURE REDUCING VALVE
A AMPS
AIR COMPRESSOR
AIR COOLED CONDENSER
AIR COOLED CONDENSING UNIT
AIR CONDITIONING UNIT
AUTOMATIC CONTROL VALVE
ACCESS DOOR
COMPRESSED AIR DRYER
AIR FOIL
ABOVE FINISHED FLOOR
AIR FLOW MEASURING STATION
AIR-TO-AIR HEAT EXCHANGER
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
ALUMINUM
AIR NATIONAL GUARD
ACCESS PANEL
APPROXIMATELY
AIR SEPARATOR
AIR TERMINAL
BOILER
BOOSTER COIL
BACKDRAFT DAMPER
BRAKE HORSEPOWER
BACKWARD INCLINED
BACKFLOW PREVENTION DEVICE
BRASS
BRONZE
BLACK (MILD) STEEL
BRANCH SELECTOR BOX
BRITISH THERMAL UNIT
BUTTWELD
BRONZE
CONVECTOR
COMBUSTION AIR
COMPRESSED AIR FILTER
COOLING COIL
CEILING DIFFUSER
CUBIC FEET PER MINUTE
CHILLER
CAST IRON
COMPRESSOR
CONTRACTING OFFICER'S REPRESENTATIVE
COMPUTER ROOM AIR CONDITIONING UNIT
CONDENSATE RETURN PUMP
COOLING TOWER
CLOSE TO CEILING
CLOSE TO COLUMN
CLOSE TO WALL
COPPER
CABINET UNIT HEATER
DOOR AIR CURTAIN
DECIBELS, BAND A
DOUBLE CHECK VALVE ASSEMBLY BPD
DIRECT DIGITAL CONTROL
DESICCANT DEHUMIDIFIER
DEMOLISH
DFD DEPARTMENT OF DEFENSE
DIVISION OF FACILITIES DEVELOPMENT
DEHUMIDIFIER
DIAMETER
DIMENSION
DISCHARGE
DOWN
DRAWING
EXISTING
EXHAUST AIR
ENTERING AIR TEMPERATURE
ELECTRIC BASEBOARD HEATER
ELECTRIC DUCT HEATER
EXHAUST FAN
EFFICIENCY
ENTERING FLUID TEMPERATURE
ETHYLENE GLYCOL
EXHAUST GRILLE
ELECTRIC HEATING COIL
EXPANSION JOINT
ELEVATION
ELECTRIC
END OF MAIN
EXPANSION TANK
EXISTING TO REMAIN
ENTERING WATER TEMPERATURE
FAHRENHEIT
AIR FILTER
FORCED AIR FURNACE
FLUID COOLER
FAN COIL UNIT
FIRE DAMPER
FUME EXTRACTOR
FULL LOAD AMPS
FLOW METER
FEET PER MINUTE
FEET
FLASH TANK
FINNED TUBE CONVECTOR
FEET WATER COLUMN PRESSURE
GALLON
GALLONS PER MINUTE
GALVANIZED STEEL
HEIGHT
HEATING COIL
HYDROSTATIC DESIGN BASIS
FLUID HEAT EXCHANGER
HEAT PUMP
HORSEPOWER
HOSE REEL
HUMIDIFIER
HEAT EXCHANGER
HERTZ
INSIDE DIAMETER
INVERT ELEVATION
INTAKE HOOD
INCH
INHG
INWC
INCHES MERCURY PRESSURE
INCHES WATER COLUMN PRESSURE
INFRARED HEATER
KITCHEN HOOD
LENGTH
LOUVER
LEAVING AIR TEMPERATURE
POUNDS
LINEAR DIFFUSER
LEAVING FLUID TEMPERATURE
LIQUIFIED PETROLEUM GAS
LEAVING WATER TEMPERATURE
MAXIMUM ALLOWABLE DIFFERENTIAL PRESSURE
MAKE-UP AIR UNIT
MAXIMUM ALLOWABLE WORKING PRESSURE
THOUSAND BTU PER HOUR
MECHANICAL COUPLING
MINIMUM CIRCUIT AMPACITY
MOTOR CONTROL CENTER
MANUFACTURER
MINIMUM
MILLION BTU PER HOUR
MINIMUM OVER CURRENT PROTECTION
MOTOR OPERATED CONTROL DAMPER
MANUFACTURERS STANDARDIZATION SOCIETY
MATERIAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
NATURAL GAS
NO-HUB
NOT IN CONTRACT
NORMALLY OPEN
NOMINAL
NET POSITIVE SUCTION HEAD
NPSH AVAILABLE
NPSH REQUIRED
OUTSIDE AIR
OUTSIDE DIAMETER
OPEN ENDED DUCT
OWNER FURNISHED, OWNER INSTALLED
PRESSURE
HYDRONIC PUMP
PRESSURE DROP/DIFFERENTIAL
PROPYLENE GLYCOL
PHASE
POUND PER HOUR
PROPELLER
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PSI ABSOLUTE
PSI DIFFERENTIAL
PSI GAGE
PACKAGED TERMINAL AIR CONDITIONER
PACKAGED TERMINAL HEAT PUMP
POLYVINYL CHLORIDE
RETURN AIR
RCP RADIANT CEILING PANEL
RETURN GRILLE
RELIEF HOOD
REVOLUTIONS PER MINUTE
RESISTIVE THERMAL DEVICE
ROOF TOP UNIT
SUPPLY AIR
SOUND ATTENUATING DEVICE
STANDARD CFM
SCHEDULE
SLOT DIFFUSER
SOLDER
STEAM FILTER
SUPPLY GRILLE
SEAMLESS
STATIC PRESSURE
SPECIFICATIONS
SQUARE
SUPPLY REGISTER
SAFETY RELIEF VALVE
STAINLESS STEEL
STEAM TRAP
STANDARD
STEEL
SOLVENT WELD
SOCKET WELD
TRANSFER AIR
TEMPERATURE CONTROL PANEL
TOTAL DEVELOPED HEAD
TOTAL DISSOLVED SOLIDS
TEMPERATURE
TRANSFER GRILLE
THREADED
TONS COOLING
TYPICAL
UNIFIED FACILITIES CRITERIA
UNDERGROUND
UNIT HEATER
UNLESS NOTED OTHERWISE
ULTRAVIOLET
VOLTS
VENT AIR
VEHICLE EXHAUST REEL
VARIABLE FREQUENCY DRIVE
VALVE
VARIABLE REFRIGERANT FLOW
WATTS OR WIDTH
WATER FILTER
O'SMOKE DETECTOR O' o> PRESSURE REGULATING VALVE AC DFD RG tr.O'IR
ACC DH RH$ SWITCH RELIEF VALVE oACCU DIA KH RPMs o oDIMACU L RTDAIR OUTLET/INLET TYPE
(CFM)
SOLENOID VALVE ONE-WAY (ELECTRIC)
STRAINER
CODISCHACV L RTU100 OAD DN LAT SA+ 03
AD DWG LB SADSTRAINER WITH BLOW OFF VALVE
AND NIPPLE <
S/I SNOW/ICE SENSOR
AF E LD SCFM
AFF EA LFT SCH 03A OAFMS EAT LPG SDTHROTTLING VALVE Esc FAN SPEED CONTROLLER AHE EBH LWT SD
03AHJ EDH MADP SFVACUUM BREAKER
AHU EF MAU SG oO'FS AL EFF MAWP SMLS
"OOANG EFT MBH SP O'FLOW SENSOR
CDAP EG MC SPEC
LS COAPPROX EG MCA SQ
AS EHC SRLEVEL SENSOR MCC
AT EJ MFR SRV CDPS
MINB EL SS COO' O OPRESSURE SENSOR BC ELEC MMBH
MOCP
MOD
ST 03
CBDD EOM STD o o oTS
BHP ET STL
TEMPERATURE SENSOR Bl ETR SVMSS
BPD EWT MTL SW
ISSUEDBRS °F NA TA
10/04/19 REVISED BID
DOCUMENTS
BRZ F NC TCP
BS FAF NFPA TDH
BSB FC NG TDS
BTU FCU NH TEMP
NICBW FD TG
BZ FE NO TH
C FLA NOM
NPSH
NPSHA
NPSHR
TONR£ TCA FM TYP0)> 101CAF FPM UFCT3
C cd cc UGDFTa:
EXPIRES:
CD FT OA UH
C/3 CFM FTC OD UNOCO
CH FTWC OED UVi Cl GAL OFOI Vo
CM COMP P VAGPM
COR GS P VER
CRAC H PD VFD
LLI CRP HC PG VLVo M&H NO.: 3142200-121252.01 10/04/19
CT HDB PH VRF
DATE:CTCLG
CTCLM
CTW
HE PPH Wo
DESIGNED BY: ADKHP PROP WFCM
LO
HP PRV ARCM DRAWN BY:
CM cu HR PSI BGDCHECKED BY:
o CUH HUM PSIA
PSID
PSIG
PTAC
PTHP
o DO NOT SCALE DRAWINGSCM DAC HXCM
SHEET CONTENTSDBA HZCO
NOTES, SYMBOLS
AND ABBREVIATIONS
DCVA IDCD
O
DDC IEo
IHDDH PVC>
CD INDEMO RACE
O
SHEET NO.:
LO
o
M-001oo o
CM
CM
O
MeadGENERAL HVAC NOTES:
I lunt1. INLET DUCT SIZE TO AIR TERMINAL DEVICES SHALL BE SAME AS INLET
SIZE UNLESS OTHERWISE NOTED. IF RUNOUT TO AIR TERMINAL BOX IS
GREATER THAN 6 FEET IN LENGTH, SIZE RUNOUT ONE EVEN INCREMENT
SIZE LARGER (MINIMUM 2" LARGER) UNLESS OTHERWISE NOTED TO
WITHIN 3 FEET OF BOX BEFORE REDUCING TO BOX INLET SIZE.
CU-1 I
CU-2
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
CUH-2
(CD-3) (CD-1) 2. DUCTWORK DOWNSTREAM OF AIR TERMINAL BOXES TO BE INTERNALLY
LINED FOR A MINIMUM OF 6'-0” FOR SOUND ATTENUATION. OUTLET DUCT
SIZES TO MATCH AIR TERMINAL BOX OUTLET UNLESS NOTED OTHERWISE.
365 100CD-3 ..) CD-3 HP-3
n365 365 s
CO RG-1 3. PROVIDE MANUAL BALANCE DAMPER AT EACH DIFFUSER, GRILLE, AND
BRANCH TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK.
LOCATE BALANCE DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE.
T 80 HP-1 It TETRATECH(RG-1) (RG-1) 4 CDRC AT-5 x800 29516x14 RA DUCT UP
TO MECHANICAL
MEZZANINE
CD
Q Q Q zL www.tetratech.como o o n ioxi oh10x8; 42x18 RA DUCT
TO EQUIPMENT
ROOM 201
\ 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
12x18 EA (Tj j 4. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME AS
NECK SIZE UNLESS NOTED OR DETAILED OTHERWISE.
(cdT)UP 110p (CD?) CD-2V
14x10___| OOPEN ENDED -
FAN INLET WITH
WIRE MESH
SCREEN
CD-1; 4012x8 Q) 18x12 i ID) EQUIPI ICE/Tti r 200 200/F 150 12x124 /60 AT-6 COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
- 5.14 J / 80^1 jjz80llll)
(CD-4) ME RG-1) RG-1,
W 7.119 7.1047.120 Q
(CD-4) CD-2;400 90 1^80,11111350(TG-2) TG-2 (TG-2)100 (I o ) III III Ip 8x6 CD AT-1
(7.132) PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS. FLEXIBLE
DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER AND SHALL NOT
EXCEED 5 FEET IN LENGTH.
6.CM425 2001O0^T
CDX 4iC=6x6=0 EG-2 oCOi CM
(eg?) ]())] 8x8t 14x10 T i:Xo CD 200 CDOXX X B EF-3 O100x CO CDCMCM CMO 6x6: 18x2418x24 ix X
(RG-1)3
7.125 8x81 TT7.119 © Copyright 2017
This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
©) 8x8: THERMOSTATS SHALL BE MOUNTED AT A HEIGHT OF 46" AFF TO ENSURE
TOP AND BOTTOM OF THERMOSTAT FALLS ONTO CMU COURSE.
7.CNT 170CNAT-2(CD?) □ X425 io0^r CM3 X COEG-1400 1O0~[T :^(rg)T)120---- (j 58x6; 120TG^' JlT ) 8x850( RG-6) (RG-6) EG-2 120CM
(CD?) ■CD-4800 400 TX 150 CO500 500[ T T r n12x12 16x12 4i ) 30x18 iT 4-
J L L J
7.131 ) 60:x< N-8x8 EA =
UP
w CM O14x12 CD-1X CM6x6: o XCM i EG-1 COX7.119 75CM
(RG-7)CD CMCO TG-2TG-2(CD-1)
X- 1008x613 , X 24x18CM- 1300CM KEYED NOTES18x8/EG-2DCO 75
AT-3-•-1-
20018x16 SA DUCT
TO MECHANICAL
MEZZANINE
7.100s 120x36 SA DUCT UP
TO FLOOR ABOVE
10x10;
xCD
4 M-40160 7.100 4" DIA. DRYER VENT FROM BELOW THROUGH ROOF. TERMINATE WITH VENT
I80: 1003 CAP.
(CD-1)— 44a <AT-7co a 75o:(45-2) CD-2, co JR 7.102 OFOI BLAST BOOTH WITH DEDICATED VENTILATION SYSTEM.ROi 120__ J 431204 )CO
RG-1,X200 200 T CO
(CD?)CD-4a 40 7.103 OFOI PAINT BOOTH WITH DEDICATED VENTILATION SYSTEM.CO <'CD-1; a: Jl -6x6: i500 500AC-2 o (CD-1)00 355 x 44 6060/ I L ] I I I18x14 EA UP THRU
FLOOR TO EF-4
IT) CM ZU X 7.104 4" DIA. EXHAUST DUCTS FROM OIL SAMPLING MACHINE UP THROUGH ROOF.
TERMINATE WITH VENT CAP.(RG-1) 4
XV 50T 3 CDs CM
250 (RG-77.102 7.103
(RG-5)T 1300 J=6x6^J 7.106 EF-1 MOUNTED OUTSIDE BUILDING ON CONCRETE PAD. PAD LENGTH AND
WIDTH SHALL EXCEED EQUIPMENT SIZE BY 4" ALL AROUND. REFER TO
STRUCTURAL DRAWINGS.
10018x14 OED
WITH WIRE
MESH SCREEN
AT-4IFIRE
PROTECT (CD?) 7.116TS
100 ID I I100;V"290
7.127 o7.107 RUN 20x20 SA DUCT AT 20 FT. AFF. RUN 16x16 SA BRANCH DUCTS DOWN
WITH SUPPLY GRILLES AT 8FT. AFF DISCHARGING DOWNWARD.I CD-1 (CD-4) (CD-4)
100 500 500
120 \l ■1I!___ 1204 \] I I I I I Q COi 7.108 RUN 20x20 EA DUCT AT 20 FT. AFF. RUN 16x16 EA BRANCH DUCTS DOWN
WITH EXHAUST GRILLES AT 8 FT. AFF.
00co o(SG?)
e125 oCUH-1IR-1 & IR-2 CDHJ D-11
6x6; iehSG-2SG-2 44SG-2 SG-2 7.116 PROVIDE LEAD SHIELDING AS SHOWN ON DETAIL 9, SHEET M-502.20x20 SA DUCT TO MECHANICAL MEZZANINE O'AT-8 O' CJ>7.126 7.11636x24 OED
WITH WIRE
MESH SCREEN
750 750 750 750 (kE)_ z z cr.T 7.119 PROVIDE CABLE-OPERATED BALANCING DAMPER. MOUNT ALL CABLE
OPERATORS AT CEILING ACCESS PANEL. <
7.107 7.12220x20 SA oo o co7.120 REMOTE VENTILATION KILL SWITCH LOCATION. o 03
7.122 SUPPORT DUCTWORK IN HANGAR FROM CEILING, COLUMNS, OR GIRTS. DO
NOT ATTACH DUCTWORK SUPPORTS TO LEAD-LINED WALL.
(7.128 7.130 03O7.124 4" DIAMETER RADIANT HEATER VENT UP THROUGH ROOF. TERMINATE WITH ROOF CAP. Eor -m 03HP-2IR-1 IR-2
7.124 7.124 7.125 10x10 HAZMAT ROOM EXHAUST UP THROUGH ROOF TO GOOSENECK. oO' TDDF-1 DF-2 DF-3 7.126 MOUNT TEMPERATURE SENSOR, CONDUIT, AND CONTROL WIRING ON
COLUMN. DO NOT PENETRATE LEAD-LINED WALL WITH ANY SUPPORTS OR
FASTENERS.
o O' CD
CO
7.127 INSTALL TEMPERATURE SENSOR FOR AT-8 IN RETURN DUCT AS SHOWN. CD
COO' O O7.128 REFER TO PLUMBING DRAWINGS FOR NATURAL GAS CONNECTION. 03
Co o o7.130 4" INDIVIDUAL COMBUSTION AIR INTAKE VENT AT EACH INFRARED HEATER
CONNECTING TO 6" COMMON UP THROUGH ROOF TERMINATING WITH RAIN
CAP. REFER TO DETAIL 8, M-502.
ISSUED
7.131 EXHAUST DUCTWORK FROM EACH INLET GRILLE TO ERU-1 SHALL BE OF
ALUMINUM CONSTRUCTION.
10/04/19 REVISED BID
DOCUMENTS
7.132 EXHAUST DUCTWORK FROM EACH INLET GRILLE TO 12x12 CONNECTION
SHALL BE OF ALUMINUM CONSTRUCTION.DF-4 DF-5 DF-6
1 IR-4IR-3 T0)> 101T3
(7.124) (7.I24)c
7.128 <7.130)03
CT
Xyirfy
EXPIRES:
(J)
IIs-- O
7.106CM
D-12 4TT 4 — 4 ,—7.108 20x20 EA 7.122
LLI
TO (EG?)EG-3 M&H NO.: 3142200-121252.01
10/04/19 (7.126) \: EFr-1
750 750 750 750 DATE:
O
ADKDESIGNED BY:CN IR-3 & IR-4LO CONTROLS FOR DF FANS ARCM DRAWN BY:
CM BGDCHECKED BY:
O o DO NOT SCALE DRAWINGS
CM
CM
Tt
SHEET CONTENTS2co FIRST FLOOR HVAC
PLAN
M-40103 o o
CD
CT
O
SHEET NO.:
O
FIRST FLOOR HVAC PLAN3 M-101Nrt 100 1/8M = r-o’03
O
CM
I Mead(EE) | GENERAL HVAC NOTES:
SIZE UNLESS OTHERWISE NOTED. IF RUNOUT TO AIR TERMINAL BOX IS
GREATER THAN 6 FEET IN LENGTH, SIZE RUNOUT ONE EVEN INCREMENT
SIZE LARGER (MINIMUM 2" LARGER) UNLESS OTHERWISE NOTED TO
WITHIN 3 FEET OF BOX BEFORE REDUCING TO BOX INLET SIZE.
I (7.129) Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
(7.111 )D~ :he . L D-1
2. DUCTWORK DOWNSTREAM OF AIR TERMINAL BOXES TO BE INTERNALLY
LINED FOR A MINIMUM OF 6’-0" FOR SOUND ATTENUATION. OUTLET DUCT
SIZES TO MATCH AIR TERMINAL BOX OUTLET UNLESS NOTED OTHERWISE.D-5 (TOP) -------
D-6 (MIDDLE)
D-7 (BOTTOM)
D-4 r ■ \ /
■ 3. PROVIDE MANUAL BALANCE DAMPER AT EACH DIFFUSER, GRILLE, AND
BRANCH TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK.
LOCATE BALANCE DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE.
Y- -4 It TETRATECHAC-1AC-37.115 h------\ T UH-12000 CFM www.tetratech.comEF-2 j=E=l
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
// 4. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME AS
NECK SIZE UNLESS NOTED OR DETAILED OTHERWISE.\
HVAC CONTROL PANEL
< <O% 5. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
< O\ <b+ 00 O CDXN CMo o X ERU-1CM CM OX o AFMS-3 Ml CM
6. PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS. FLEXIBLE
DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER AND SHALL NOT
EXCEED 5 FEET IN LENGTH.
FD
42x36 EA DUCT UP
TO ROOFD-3 AD
Eur 12x18 EADUCT DOWN
TO FIRST FLOOR
© Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
v II >
7. THERMOSTATS SHALL BE MOUNTED AT A HEIGHT OF 46" AFF TO ENSURE
TOP AND BOTTOM OF THERMOSTAT FALLS ONTO CMU COURSE.
i Ju. AFMS-1
AD
i
7.10918x18 MIN OA yLA 26x26 RA\i
16x12 RA DUCT TO FIRST FLOOR 42x18 RADUCT DOWN
TO FIRST FLOOR
D-200
^ ADX
FD
AFMS-2<
LU
oo
KEYED NOTESX
CO
40x26
7.100 4" DIA. DRYER VENT FROM BELOW THROUGH ROOF. TERMINATE WITH VENT
CAP.AFMS-4
AHU-2
7.109 42x18 RA UP FROM FIRST FLOOR. 32x18 ECONOMIZER RELIEF UP THROUGH
ROOF TO GOOSENECK.
(7.112) 7.111 16x18 VENTILATION AIR INTAKE WITH MOTORIZED DAMPER FOR MECH
ROOM (BOTTOM OF 3 STACKED DUCTS).
18x18
AHU-1
D-8 7.112 18x18 ERU-1 EXHAUST UP THROUGH ROOF TO GOOSENECK.
(7.113)(7.117) 7.113 20x18 MECH ROOM EXHAUST UP THROUGH ROOF TO GOOSENECK.
— ■ D-10> — d-91 7.114 4" DIAMETER COMBUSTION AIR AND VENT UP THROUGH ROOF TO GOOSENECK. oM-402
W CD 7.115 OPEN-ENDED DUCT WITH WIRE-MESH SCREEN. CO COcoX CO oX X o00 o CD7.117 18x14 FIRE PROTECTION ROOM EXHAUST UP THROUGH ROOF TO
GOOSNECK.
CM
r^
FD^ --- ;
O'-AD O' G3
18x16 SA DUCT
TO FIRST FLOOR
8x8 EA tr.7.129 24" DEEP INTAKE PLENUM, SAME DIMENSION AS LOUVER. PARTITION
INTERIOR OF PLENUM AS SHOWN ON DETAIL 7, SHEET M-501. O' <
o?DN o*EF-4 EF-2 O o oCP 7.133 ROUTE DUCT IN FIRE-RATED, LEAD-LINED SHAFT. REFER TO
ARCHITECTURAL DRAWINGS.
COy o 03
03OAD..- E
FD^0 40 EA _ 20x36 SA DUCT DOWN
TO FIRST FLOOR 03
7.100 oO' "Do O' 0n< co< DLULU 7.114co
XX 0no00
CM B-1 if)O' O o 03cO O OB-2 n
X ]2> (7.114)Is-
ISSUEDCO
10/04/19 REVISED BID
DOCUMENTS
n\ = 18x14 EA DOWN
F TO FIRST FLOOR
FD
AS-1
AD □W
7.115 7.11516x12 16x12 P-1t «r T0) 1000 CFM 1000 CFM> MAU-1 101■a c cc a:
sty, wtfgx
EXPIRES:
□ocrl'</>
CO P-2<
I o
CM
o.+
LU O
o CP M&H NO.: 3142200-121252.01
10/04/19 UH-2 y
DATE:
To
DESIGNED BY: ADKCM FD
LO
ARCM UH-2 DRAWN BY:
CM BGDCHECKED BY:GF-1 ET-1ADo \ / (7.133) o DO NOT SCALE DRAWINGSx
CM
CM
(5W~4______
SHEET CONTENTS
CO EQUIPMENT ROOM
HVAC PLAN
CHEMICAL POT FEEDER0
O o
20x20 SA DUCT
TO HANGER>
0 2cr M-402
O
SHEET NO.:
CM
O
M-10200 EQUIPMENT ROOM HVAC PLAN03
M 1O CM 1/4" = r-oM
MeadGENERAL HVAC NOTES:
SIZE UNLESS OTHERWISE NOTED. IF RUNOUT TO AIR TERMINAL BOX IS
GREATER THAN 6 FEET IN LENGTH, SIZE RUNOUT ONE EVEN INCREMENT
SIZE LARGER (MINIMUM 2" LARGER) UNLESS OTHERWISE NOTED TO
WITHIN 3 FEET OF BOX BEFORE REDUCING TO BOX INLET SIZE.
I Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
DUCTWORK DOWNSTREAM OF AIR TERMINAL BOXES TO BE INTERNALLY
LINED FOR A MINIMUM OF 6'-0" FOR SOUND ATTENUATION. OUTLET DUCT
SIZES TO MATCH AIR TERMINAL BOX OUTLET UNLESS NOTED OTHERWISE.
2.
PROVIDE MANUAL BALANCE DAMPER AT EACH DIFFUSER, GRILLE, AND
BRANCH TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK.
LOCATE BALANCE DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE.
3.
It TETRATECH www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-92544. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME AS
NECK SIZE UNLESS NOTED OR DETAILED OTHERWISE.
<7.123
COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
5.
<7.104)42x36 EA GOOSENECK
PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS. FLEXIBLE
DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER AND SHALL NOT
EXCEED 5 FEET IN LENGTH.
6.
F 7r 18x18 EA GOOSENECK10x10 EA GQQSENECKI EXl © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
7.123 THERMOSTATS SHALL BE MOUNTED AT A HEIGHT OF 46" AFF TO ENSURE
TOP AND BOTTOM OF THERMOSTAT FALLS ONTO CMU COURSE.
7.(7.123)7.123
14x18 EA GOOSENECK 18x20 EA GOOSENECKvVL-
4" LAUNDRY
EXHAUST KEYED NOTES
7.104 4" DIA. EXHAUST DUCTS FROM OIL SAMPLING MACHINE UP THROUGH ROOF.
TERMINATE WITH VENT CAP.
-^£ED
4” COMBUSTION AIR AND EXHAUST
7.123 PAINT ALL GOOSENECK DUCT TERMINATIONS TO MATCH ROOF.
-^EED
7.124 4" DIAMETER RADIANT HEATER VENT UP THROUGH ROOF. TERMINATE WITH
ROOF CAP.
7.130 4" INDIVIDUAL COMBUSTION AIR INTAKE VENT AT EACH INFRARED HEATER
CONNECTING TO 6" COMMON UP THROUGH ROOF TERMINATING WITH RAIN
CAP. REFER TO DETAIL 8, M-502.
o CO COoo CD o' O' CD tr.O' < oo o co
O 03
03O E+ 03(7.124) 7.130 7.124 oO' "Oo O' CD
CO
CD
COO' O O O)cO O O
ISSUED
10/04/19 REVISED BID
DOCUMENTS
1 £-f0> 101■o 7.124 7.130 7.124c 03cr
EXPIRES:
CO
IIs- O
CM
LD
O M&H NO.: 3142200-121252.01
10/04/19DATE:
O
DESIGNED BY: ADKCM
LO
ARCM DRAWN BY:
CM BGDCHECKED BY:
O o DO NOT SCALE DRAWINGSCM
CM
SHEET CONTENTS
CO ROOF HVAC PLANCD
Oo
CT
O
SHEET NO.:
CO
o
ROOF HVAC PLAN M-103100 1/8- = r-o"CD
O
CM
I MeadGENERAL PIPING NOTES:CU-1 I luntPIPING RUNOUTS TO ALL EQUIPMENT TO BE 3/4" UNLESS NOTED
OTHERWISE.
1.CU-2
IJ7
2. WELD-O-LETS AND THREAD-O-LETS MAY BE USED FOR BRANCH
TAKE-OFFS UP TO ONE-HALF THE DIAMETER OF THE MAIN.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
'EST.
111fZJ
CUH-2 =Yi □ 8.104
\_____________/ i0 3. INSTALL DIELECTRIC FITTINGS WHERE PIPING OF DIFFERENT MATERIALS
IS JOINED.(TYP OF 4 PIPING SETS)OFFICE
112 HP-3
INSTALL PIPING FREE OF SAGS AND BENDS.4.0 8.101
T 7 1 “I rrrniThi.□ E□_ LOCATE ALL VALVES FOR EASY ACCESS. INSTALL VALVES WITH STEM
UP OR HORIZONTAL.
5.TRAINING
/BREAK
ROOM
UP0 m hp-1 it TETRATECHLll JLAT-5 VV \113 INSTALL DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM AND
ELSEWHERE AS REQUIRED FOR SYSTEM DRAINAGE. INSTALL MANUAL
AIR VENTS AT ALL HIGH POINTS IN PIPING, AT HEAT-TRANSFER COILS,
AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
6.□ www.tetratech.com
AT-6□
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
m, .I, V REFRIGERANT PIPING
UP TO MECHANICAL
MEZZANINE
□3a M-402PAINT
MIXING
ROOM/
HAZ-MAT
STOR
OFFICE£ OIL
109EQUIPMENT
ROOM
ANALYSIS
ROOM■tb MEN'S 126 110114 108AT-1 /ra
r. KEYED NOTESB D E
AT-2 T ] .n___i
MEN'S
LOCKER
ROOM
8.100 UNDERSLAB SNOW MELT SYSTEM WITH 1 LOOP, 3.3 GPM. AREA: 282 SF,
TUBE TYPE: 1" PEX, TUBE SPACING: 9" OC.
Ml JAN © Copyright 2017
This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
116115 > / pmme 8.101 RACK REFRIGERANT PIPING VERTICALLY ALONG EXTERIOR WALL ABOVE
DOORWAY AND DOWN ALONG WALL TO UNITS. PIPING TO BE SIZED BY
RESPECTIVE EQUIPMENT MANUFACTURERS. PAINT JACKETING TO MATCH
ADJACENT SURFACE.
FILM
1 EWING
ROOM
fP .: k 1
■WOMEN'S
LOCKER
ROOM
n Q ’OMEN'S AT-3V118 8.104 RL AND RS PIPING SIZES AS REQUIRED BY EACH CONDENSING UNIT / HEAT
PUMP MANUFACTURER. PAINT JACKETING TO MATCH ADJACENT SURFACE.
LAUNDRY
ROOM 117
BEAD
BOOTH
ROOM
□119PAINT
BOOTH-1
8.106 MOUNT UNIT ON CONCRETE PAD. PAD DIMENSIONS SHALL BE EQUAL TO
THE UNIT DIMENSIONS PLUS 4" ON ALL SIDES. REFER TO STRUCTURAL
DRAWINGS FOR CONSTRUCTION OF PAD.
125-11
£ IVG FILM
PROC
ROOM
( > n
"PPE □ cr 106CLEAN
ROOM/
CIRCULAT
: g HALLWAY 8.107 INSTALL ZONE VALVE AND PUMP ON STRUT ASSEMBLY MOUNTED TO
FLOOR. DO NOT FASTEN TO LEAD-LINED WALL.
AT-7 x 102
INSPECTION 0CM BAY120 L+J
103-1 8.110 PROTECT HOT WATER AND REFRIGERANT PIPE PENETRATIONS OF
LEAD-LINED WALL IN ACCORDANCE WITH DETAIL 14, DRAWING M-511.
C/3
§1AC-2 /I
X-RAY CRCM
105LHOT WATER PIPING
UP TO MECHANICAL
MEZZANINE
17 4, > \FIRE
PROTECTION
ROOMCTAIR LOCK( H t STENCIL
ROOM I ]CO cm124 drier AT-4121
X-RAY
VAULT
ROOM
0 oCUH-1RZ-1 CONTROL PANEL AND P-3 104
VEST.8.107 J CO101 COHOT WATER PIPING
UP TO MECHANICAL
MEZZANINE
□! G ) II o_.□FI:m OAT-8 CD□8.110-L 21Vo □ o' o' CD—r hwr-F ■1" HWS cr.r ------------1 o' < -\ Oo o8.104) CO
O 03
■ ( S/I
(I
8.106
TS 03OHP-2
E 03( E Mi oO' "Do O'n <D
CO
CD
COO' O OHANGAR 03
123 cO O O8.100 >|
ISSUED
10/04/19 REVISED BID
DOCUMENTS
D
1 0:
0> 101
■O c
CT
sty, wngx
EXPIRES:
t/)
IIs-
O LCM
1 C F mmLll Bo M&H NO.: 3142200-121252.01 10/04/19
IT□
DATE:
O
DESIGNED BY: ADKCM
LO
ARCM DRAWN BY:
CM BGDCHECKED BY:
O o DO NOT SCALE DRAWINGSCM
CM A
SHEET CONTENTS
CO
FIRST FLOOR PIPING
PLAN
CD
Oo
CDcr o 6 7 8 91 ) ( 4 i' 5
SHEET NO.:
FIRST FLOOR PIPING PLAN<
Is- 1O
1/8" = r-o"
M-131oo
CD
o
CM
I MeadGENERAL PIPING NOTES:
I lunt1. PIPING RUNOUTS TO ALL EQUIPMENT TO BE 3/4" UNLESS NOTED
OTHERWISE. In:
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100
Portland, OR 97220 phone: 503-548-1494 meadhunt.com
2. WELD-O-LETS AND THREAD-O-LETS MAY BE USED FOR BRANCH
TAKE-OFFS UP TO ONE-HALF THE DIAMETER OF THE MAIN.
3. INSTALL DIELECTRIC FITTINGS WHERE PIPING OF DIFFERENT MATERIALS
IS JOINED.
4. INSTALL PIPING FREE OF SAGS AND BENDS.
5. LOCATE ALL VALVES FOR EASY ACCESS. INSTALL VALVES WITH STEM
UP OR HORIZONTAL. It TETRATECH
AC-1AC-3
6. INSTALL DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM AND
ELSEWHERE AS REQUIRED FOR SYSTEM DRAINAGE. INSTALL MANUAL
AIR VENTS AT ALL HIGH POINTS IN PIPING, AT HEAT-TRANSFER COILS,
AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
www.tetratech.comft3/4" CD0>
J=S=L 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
8.104 rPITCH0-01UH-1 '
00 REFRIGERATION PIPING
DOWN TO OUTDOOR UNITS
U
DN
O X oo st* Q.
CO
KEYED NOTES4
_□ 8.103 © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
8.102 LOCATION OF DIFFERENTIAL PRESSURE SENSOR.
8.103 BOILER EMERGENCY POWER-OFF SWITCH.
Y I
X 8.104 RL AND RS PIPING SIZES AS REQUIRED BY EACH CONDENSING UNIT / HEAT
PUMP MANUFACTURER. PAINT JACKETING TO MATCH ADJACENT SURFACE.8.1045-8.104 CO
X i$
8.108 REFER TO PLUMBING DRAWINGS FOR NATURAL GAS PIPING CONNECTION.x
S"
CO
8.109 RUN CONDENSATE DRAIN PIPE TO FLOOR DRAIN. REFER TO PLUMBING
DRAWINGS FOR LOCATION.
0 U
8.109 8.109 8.111 HOT WATER SYSTEM BYPASS VALVE FOR MINIMUM FLOW.
8.113 REFER TO DETAIL 5, M-511 FOR PIPING TO CHEMICAL POT FEEDER.------- 0
0--------0 r c c
Q X O 0 1 1/4'o -
1 1/4' c4X CO
0 0AHU-2 0
AHU-1
PITCHn c)
18.109 3/4” CD
1 oM-402
EQUIPMENT
ROOM CO CO201 oK o CDr^8.102DP O' O' CD tr.: o' < oo o co O 03
03O E0— oO' "Do O' CD COn
03" O
(?)—3"- CDnc/3
COO' O OC/3 B-1
§ 03x
CCM o o oX 8.108iX co
XX
B-2COCM
n
O ISSUED3"-
3" 10/04/19 REVISED BID
DOCUMENTS□ (
n
3'I AS-1
3" HW DECOUPLER
D=>=^-3"
1 P-1x Hr T§0)> >01x ■a MAU-1c COco
P-2X sty, wngx
EXPIRES:
3" '□Mj'0----- 0------ 00>► 2" HWR
2" HWS----- -C
1 1/2"0>to CO c-1 1/2"-< 0
I 001 1/2" 0------1 1/2"----
- HOT WATER PIPING
0 DOWN TO FIRST FLOOR
N-
000o
CN <N 00 3" HWS
CM
LU
O M&H NO.: 3142200-121252.01
10/04/19DATE:
O
DESIGNED BY: ADKCM
LO
ARc\i UH-2 DRAWN BY:
CM BGDCHECKED BY:
O GF-1 -ET-1o DO NOT SCALE DRAWINGSCM
CM
1”
8-113 (6^~ SHEET CONTENTS
CO EQUIPMENT ROOM
PIPING PLAN
; g }CD O CHEMICAL POT FEEDERo
HOT WATER PIPING TO HANGER
DOOR SNOWMELT SYSTEM °>
CD
X 2 O M-402
SHEET NO.:
co EQUIPMENT ROOM PIPING PLANO
1 M-1321/4- = r-o1oo
CD
( 9o
CM
MeadGENERAL HVAC NOTES: I luntI1. INLET DUCT SIZE TO AIR TERMINAL DEVICES SHALL BE SAME AS INLET
SIZE UNLESS OTHERWISE NOTED. IF RUNOUT TO AIR TERMINAL BOX IS
GREATER THAN 6 FEET IN LENGTH, SIZE RUNOUT ONE EVEN INCREMENT
SIZE LARGER (MINIMUM 2" LARGER) UNLESS OTHERWISE NOTED TO
WITHIN 3 FEET OF BOX BEFORE REDUCING TO BOX INLET SIZE.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
DUCTWORK DOWNSTREAM OF AIR TERMINAL BOXES TO BE INTERNALLY
LINED FOR A MINIMUM OF 6'-0" FOR SOUND ATTENUATION. OUTLET DUCT
SIZES TO MATCH AIR TERMINAL BOX OUTLET UNLESS NOTED OTHERWISE.
2.
12x10 r hws PROVIDE MANUAL BALANCE DAMPER AT EACH DIFFUSER, GRILLE, AND
BRANCH TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK.
LOCATE BALANCE DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE.
3.AT-3
It TETRATECHAr 22x22 18x24 -I! 24x18 120/ www.tetratech.comr HWRl\ 7T jZ -AT-2 ME80 8x8 SA 60 711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
.Lijj T“ I---- /t 4. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME AS
NECK SIZE UNLESS NOTED OR DETAILED OTHERWISE.
3/4" HWR< s s3/4" HWS 24x18 RA 18x20 8x8co CM CM
IZO
CO
X-CO-
COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
RG-7 5.jJ 24x18 1300CD-4,- (CM)
(RG-Y)500 500 CD-I 1
PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS. FLEXIBLE
DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER AND SHALL NOT
EXCEED 5 FEET IN LENGTH.
6.120 75
© Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
THERMOSTATS SHALL BE MOUNTED AT A HEIGHT OF 46" AFF TO ENSURE
TOP AND BOTTOM OF THERMOSTAT FALLS ONTO CMU COURSE.
7.INSPECTION FILM
BAY PRC
ROOM103-1
GENERAL PIPING NOTES:
1. PIPING RUNOUTS TO ALL EQUIPMENT TO BE 3/4" UNLESS NOTED
OTHERWISE.INSPECTION BAY SECTION - LOOKING NORTH
1/4" = r-o"
WELD-O-LETS AND THREAD-O-LETS MAY BE USED FOR BRANCH
TAKE-OFFS UP TO ONE-HALF THE DIAMETER OF THE MAIN.
2.
INSTALL DIELECTRIC FITTINGS WHERE PIPING OF DIFFERENT MATERIALS
IS JOINED.
3.
INSTALL PIPING FREE OF SAGS AND BENDS.4.
G E D B
5. LOCATE ALL VALVES FOR EASY ACCESS. INSTALL VALVES WITH STEM
UP OR HORIZONTAL.
INSTALL DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM AND
ELSEWHERE AS REQUIRED FOR SYSTEM DRAINAGE. INSTALL MANUAL
AIR VENTS AT ALL HIGH POINTS IN PIPING, AT HEAT-TRANSFER COILS,
AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
6.
o7.124 7.124 co77.130 7.130 COn
OL O CD
"7T
O' O' CD
tr.O' <KEYED NOTES O< <DF-5LU LUDF-2 o oJs s
- xf CO
7.107 RUN 20x20 SA DUCT AT 20 FT. AFF. RUN 16x16 SA BRANCH DUCTS DOWN
WITH SUPPLY GRILLES AT 8FT. AFF DISCHARGING DOWNWARD. o 03
<7.108 RUN 20x20 EA DUCT AT 20 FT. AFF. RUN 16x16 EA BRANCH DUCTS DOWN WITH EXHAUST GRILLES AT 8 FT. AFF.0 03IR-2 IR-4 o E7.122 SUPPORT DUCTWORK IN HANGAR FROM CEILING, COLUMNS, OR GIRTS. DO
NOT ATTACH DUCTWORK SUPPORTS TO LEAD-LINED WALL. 03I |
i oO'7.124 4" DIAMETER RADIANT HEATER VENT UP THROUGH ROOF. TERMINATE WITH ROOF CAP. "Oo O' CD■
CO7.130 4" INDIVIDUAL COMBUSTION AIR INTAKE VENT AT EACH INFRARED HEATER
CONNECTING TO 6" COMMON UP THROUGH ROOF TERMINATING WITH RAIN
CAP. REFER TO DETAIL 8, M-502.
I
CD
COO' O O7.1087.133 037.133 ROUTE DUCT IN FIRE-RATED, LEAD-LINED SHAFT. REFER TO
ARCHITECTURAL DRAWINGS. c20x20 EA o o oHANGARI20x20 SA DUCT
TO MECHANICAL
MEZZANINE
20x20 SA
20x20 123 J
V r hws r HWR
ISSUED
10/04/19 REVISED BID
DOCUMENTS
CM
CNIX 7.122CN X
CNt £IJ
0> 101■o c
CT
EXPIRES:
O CN7.122 xt/) o03 CN<
I N- O
CN
7.107
(E^3)SG-2)
750750 co
LU a.
o M&H NO.: 3142200-121252.01
10/04/19DATE:
DUO
DESIGNED BY: ADKCM
LO
ARCM DRAWN BY:
CM BGDCHECKED BY:
20x20 EA TO EF-1r
O
O DO NOT SCALE DRAWINGSCN
CN
SHEET CONTENTS
CO ENLARGED PLANS
AND SECTIONS
uO
CD
Oo
CT
o
SHEET NO.:
O
M-401HANGER SECTION - LOOKING EASToo 03 2o 1/4" = r-on
CN
CN
Mead GENERAL HVAC NOTES: I luntI9 INLET DUCT SIZE TO AIR TERMINAL DEVICES SHALL BE SAME AS INLET
SIZE UNLESS OTHERWISE NOTED. IF RUNOUT TO AIR TERMINAL BOX IS
GREATER THAN 6 FEET IN LENGTH, SIZE RUNOUT ONE EVEN INCREMENT
SIZE LARGER (MINIMUM 2" LARGER) UNLESS OTHERWISE NOTED TO
WITHIN 3 FEET OF BOX BEFORE REDUCING TO BOX INLET SIZE.
1.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
2. DUCTWORK DOWNSTREAM OF AIR TERMINAL BOXES TO BE INTERNALLY
LINED FOR A MINIMUM OF 6'-0” FOR SOUND ATTENUATION. OUTLET DUCT
SIZES TO MATCH AIR TERMINAL BOX OUTLET UNLESS NOTED OTHERWISE.
It TETRATECH3. PROVIDE MANUAL BALANCE DAMPER AT EACH DIFFUSER, GRILLE, AND
BRANCH TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK.
LOCATE BALANCE DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE. www.tetratech.com
2 co
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
M-402 x X CO o
CM
4. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME AS
NECK SIZE UNLESS NOTED OR DETAILED OTHERWISE.
d-io 20x18 EA FOR
MECH ROOM
20x20 OA
TO MAU-1 D-9 J
LU 5. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
ITT L8x8EA j CM
V o) -=ftf> - 0
=1”: 1 1/4' vf XZL CDiv 7i COrREFRIGERANT PIPING
UP TO EQUIPMENT ROOM 20x8 OA I n18x18 26x40 OAI -4\ 6. PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS. FLEXIBLE
DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER AND SHALL NOT
EXCEED 5 FEET IN LENGTH.
/ft- C. ,\i y< i TJ VI
(T)RS AFMS-2ft Lft K/ “7
<8.101 i l________ -u18x18 EA O— < — © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
q RSCD ftJCDQoo xo
7. THERMOSTATS SHALL BE MOUNTED AT A HEIGHT OF 46" AFF TO ENSURE
TOP AND BOTTOM OF THERMOSTAT FALLS ONTO CMU COURSE.
X 00CO st-
COX
AHU-1 i AHU-2 4r v
ADERU-1 -TJ— XAD J--
14x16 RA DUCT DOWN
TO FIRST FLOOR
--J12x16 RA u-^r_ _^7______ _ FD 18x42 RA DUCT DOWN
3 TO FIRST FLOOR
FD
3/4" CD TO
FLOOR DRAIN
3/4" CD TO
FLOOR DRAIN GENERAL PIPING NOTES:18x12 EA DUCT DOWN
TO FIRST FLOORCU-1HP-1 HP-3 CU-2
PIPING RUNOUTS TO ALL EQUIPMENT TO BE 3/4" UNLESS NOTED
OTHERWISE.
1.
WELD-O-LETS AND THREAD-O-LETS MAY BE USED FOR BRANCH
TAKE-OFFS UP TO ONE-HALF THE DIAMETER OF THE MAIN.
2.
REFRIGERATION PIPING RACK - LOOKING WEST EQUIPMENT ROOM SECTION - LOOKING NORTH3 INSTALL DIELECTRIC FITTINGS WHERE PIPING OF DIFFERENT MATERIALS
IS JOINED.
3.
1/8" = r-0' 1/4" = 1’-0'
INSTALL PIPING FREE OF SAGS AND BENDS.4.
LOCATE ALL VALVES FOR EASY ACCESS. INSTALL VALVES WITH STEM
UP OR HORIZONTAL.
5.
INSTALL DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM AND
ELSEWHERE AS REQUIRED FOR SYSTEM DRAINAGE. INSTALL MANUAL
AIR VENTS AT ALL HIGH POINTS IN PIPING, AT HEAT-TRANSFER COILS,
AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
6.
o CO COoo CD o' O' CD tr.O'KEYED NOTES
< O O o co7.129 24" DEEP INTAKE PLENUM, SAME DIMENSION AS LOUVER. PARTITION
INTERIOR OF PLENUM AS SHOWN ON DETAIL 7, SHEET M-501. o 03
8.101 RACK REFRIGERANT PIPING VERTICALLY ALONG EXTERIOR WALL ABOVE
DOORWAY AND DOWN ALONG WALL TO UNITS. PIPING TO BE SIZED BY
RESPECTIVE EQUIPMENT MANUFACTURERS. PAINT JACKETING TO MATCH
ADJACENT SURFACE.
03O E 031G K M-402 oO' "Oo O' 0
CO
COO' O O O)cO O O
2" HWS o oV -No 02" 8x20 OAfee 1 1/2" HWRi.i
ISSUED4n r ___ LL±20x20 OA 26x40 OAJ------ 10/04/19 REVISED BID
DOCUMENTS
/ \"T D-5\
AFMS-4 \ D-118x18 MIN OAUH-2 CM JX _ \5 18x18 EA ^i -N-
CO
X cn \CM cn 00-
§x XXt 00 (kD(X 7.129 T0)> 1017 r-v"r —■a qc FD — ii— in 20x20 SA I r i
Nil IV I I 16x12 RA ; ERU-1 .
--------- 1—--------- -7i Af + 4U /
VLJ 1
03 (SG-3)16x18 SAMAU-1 AHU-2X 18x16 SA • L sty.
EXPIRES:
2000</>
CO
D-7<
I 3/4" CD TO
FLOOR DRAIN
3/4" CD TO
FLOOR DRAINo
C\l
LU
o M&H NO.: 3142200-121252.01
10/04/19i DATE:
O
DESIGNED BY: ADKCM EQUIPMENT ROOM SECTION - LOOKING WESTLO
ARCM 2 DRAWN BY:
CM 1/4" = r-o" BGDCHECKED BY:
O o DO NOT SCALE DRAWINGSCM
CM
SHEET CONTENTS
00 ENLARGED PLANS
AND SECTIONS
Oo
CT
o
SHEET NO.:
M-402oo o
CM
MeadROOF INTAKE CAP
I luntSTORM COLLAR
I36" MINIMUM ADJUSTABLE ROOF FLASHING
ACCESS SECTION HOT WATER COIL AIR COOLED CONDENSING
UNIT6" PIPE Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
1 DX COIL TYPE FF-1 FINAL FILTERS /'ROOF
ACCESS SECTION
SUPPLY FAN
TYPE PF-1 PRE-FILTERS
MIXING SECTION
V
W.P. DISCONNECT BY
SWITCH GEAR SUPPLIER
CONCRETE PAD
(REFER TO STRUCTURAL AND CIVIL
DRAWINGS)
LOW VOLT
.04" INTAKE PIPE 4” INTAKE PIPE
It TETRATECH D D www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
BURNER
CONTROL
BURNER
CONTROL
HIGH VOLT
REFRIGERATION LINE
CONNECTIONBOX BOX
NOTE:AIR INLET CONNECTION
(FLEXIBLE BOOT AND
BAND CLAMPS ARE
RECOMMENDED)
AIR INLET CONNECTION
(FLEXIBLE BOOT AND
BAND CLAMPS ARE
RECOMMENDED)
1. CONCRETE PAD SHALL BE 4" LARGER
THAN CONDENSING UNIT FOOTPRINT IN
EACH DIRECTION AND A MINIMUM 4" THICK.
4" THICK HOUSEKEEPING PAD
(SEE STRUCTURAL DRAWINGS
FOR TYPE AND SIZE)
NOTE:
1. DX COIL SECTION AND ACCESS SECTION IMMEDIATELY
DOWNSTREAM FOR AHU-1 AND AHU-2 ONLY.
INFRARED RADIANT HEATER COMBUSTION AIR INTAKE PENETRATION INSIDE AIR HANDLING UNIT (AHU & MAU) SCHEMATIC ELEVATION SLAB MOUNTED CONDENSING UNIT5NO SCALE NO SCALE NO SCALE © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
VENT CAP
STORM COLLAR
3-0" MIN.ADJUSTABLE ROOF FLASHING
ROOF
1" MINIMUM
CLEARANCE
1” MINIMUM CLEARANCE -
USE ATTIC INSULATION
SHIELD (FIELD SUPPLIED)
GASKET ALL AROUND
PERIMETER
1" MIN. HIGH-DENSITY
FIBERGLASS INSUL.MAX. LENGTH NOT TO EXCEED 5-0'-
FIRE STOP SPACER METAL CLAMP CAULK ALL AROUND
DUCT WORK
INSULATION
DOVETAILSMAX. SAG = 1/2" PER
FOOT OF LENGTHF~ TV' — — METAL DUCT ELBOW,
LONG RADIUS, DIE STAMPED
SAME SIZE AS DIFFUSER
INLET CONNECTION
CEILING
DURAVENTTYPE PVP VENTING OR EQUAL
v* -
/v Qv
VENT ADAPTER DIFFUSER
3"3"vHEATER
SINGLE-WALL VENT PIPE MAX MAX BANDING7- -- — 7-/'V
SASH CAM AND LATCH
JACKETx— FLEXIBLE DUCT
— COLLAR
---METAL CLAMP
---- VOLUME DAMPER
---- 45° BRANCH DUCT TAKE-OFF
- SUPPLY DUCTWORK
- DUCT INSULATION
DOOR - SAME MATERIAL
AS DUCTBANDING
FULL LENGTH
PIANO HINGE
FRAME - SAME
MATERIAL AS DUCT
oSINGLE-WALL ELBOW OR
ALTERNATE TEE FITTING
CO 00o#8 SHEET METAL SCREWS o CDHINGED ACCESS DOOR FOR
INSULATED RECTANGULAR DUCT CXcxCT>INFRARED RADIANT HEATER VENT ROOF PENETRATION FLEXIBLE DUCT TO CEILING DIFFUSER orCX10 6 2
< ONO SCALE NO SCALE NO SCALE
o oDUCT CONNECTION
(TYP)
CO
O 03ACCESS DOOR 18"x18"
OR 2" SMALLER THAN
DUCT SIZE ALL AROUND
(SEE DETAIL)
FIRE DAMPER
3-2" 2'-0" 4'-2"
/ WALL 037 o24" DEEP PLENUM.
FULL DIMENSIONS OF
LOUVER
EPROVIDE ANGLES AT
TOP AND SIDES
DAMPER WHERE SPECIFIED
9 20x8 >
032" MAX.
FINISHED FLOOR
(RATED) ocxSEE DRAWINGS FOR DUCT
SIZE, SEE SPECIFICATION
FOR INSUL. REQUIREMENTS
~oO ex0CD
ICONNECTION
TYP FOR TOP
AND SIDES
CNI CO140x26 Q_ o
18x18 CD 0ACCESS DOOR
(MIN 10"x10")jV cocx o oSLEEVE
MOUNTING ANGLE (TYP)
DUCTWORK
-SEE PLANS AND SPECIFICATIONS
FOR SIZE AND MATERIAL
03LOUVER AS
SCHEDULED
INSECT SCREEN TO
BE REMOVABLE OR HINGED
AT TOP
CO O o20x20CD
WATERPROOF
CAULKING
ALL AROUND
CM SHEET METAL PARTITION
IN LOUVER PLENUM (TYP) SLOPE BOTTOM OF PLENUM
TO DRAIN THROUGH LOUVER ISSUED
16x18
NOTE: 10/04/19 REVISED BID
DOCUMENTS
-7\
CAULK EDGE
FOR AIRTIGHTNESS.
9'-4" INSTALL FIRE DAMPER ACCORDING TO MANUFACTURERS WRITEN INSTRUCTIONS.
LOUVER L-1 PARTITION HORIZONTAL FIRE DAMPER DETAIL KEYED NOTES:
NO SCALE NO SCALE
> USE PVC COATED METALLIC DUCT FOR BOTTOM OF OUTSIDE
AIR INTAKE DUCT FROM LOUVER TO THIS POINT.
t 0:
0> 101■o SUPPLY AIRc cx
EXPIRES:
DUCT CONNECTION TO LOUVERC/3 3CO LINTEL< NO SCALEI
FIRE DAMPER
ACCESS DOOR 18"x18"
OR 2" LESS THAN DUCT
SIZE ALL AROUND
(SEE DETAIL)
o
CM
PROVIDE A MINIMUM OF 3-0" OF
STRAIGHT DUCT UPSTREAM OF
INLET FLOW SENSOR FOR INLET
SIZES 12" DIAMETER AND BELOW.
PROVIDE A MINIMUM OF 3X THE
INLET DIAMETER OF STRAIGHT
DUCT UPSTREAM OF THE INLET
FLOW SENSOR FOR INLET SIZES
ABOVE 12" DIAMETER. -
REHEAT COIL 2" MAX
LLI
O M&H NO.: 3142200-121252.01
10/04/19
AIR TERMINAL UNIT
DATE:
O
DESIGNED BY: ADKCM
LO
ARCM DRAWN BY:WRAP THE REHEAT COIL WITH EXTERNAL
INSULATION AS INDICATED IN SPECIFICATION
SECTION 23 07 00 - THERMAL INSULATION
FOR MECHANICAL SYSTEMS.
CM BGDCHECKED BY:
o
FIRE ALARM PANEL AND WIRING
(BY FIRE PROTECTION CONTRACTOR)
o DO NOT SCALE DRAWINGSCM
CM
-71- SHEET CONTENTSDUCTWORK
-SEE PLANS AND SPECIFICATIONS
FOR SIZE AND MATERIAL
- MOUNTING ANGLE (TYP)
— SLEEVE
CO
HVAC DETAILSDUCT MOUNTED SMOKE DETECTOR
(PROVIDED AND INSTALLED BY
CONTROLS CONTRACTOR)
CD DUCT ACCESS DOORS. REFER TO
SPECIFICATION SECTION 23 00 00 -
AIR SUPPLY, DISTRIBUTION, VENTILATION,
AND EXHAUST SYSTEMS FOR
REQUIREMENTS.
Soo
DUCTCDa:
o RATED WALL
PROVIDE AT LEAST 24" OF CLEARANCE ON
CONTROLLER SIDE OF AIR TERMINAL UNIT.
THE CLEARANCE AREA SHALL EXTEND THE
FULL LENGTH OF THE AIR TERMINAL UNIT.
NOTE:
INSTALL FIRE DAMPER ACCORDING TO MANUFACTURERS WRITTEN INSTRUCTIONS.
SHEET NO.:
< FACTORY INSTALLED REHEAT COIL
CM DUCT MOUNTED SMOKE
DETECTOR CONTROL DIAGRAM (TYPICAL) M-501SUPPLY AIR TERMINAL UNIT WITH REHEAT COIL VERTICAL FIRE DAMPER DETAIL00
03 12 8 4O NO SCALE NO SCALE NO SCALECM
MeadHANGER ROD - SAME
SIZE AS SUPPORT
BRACKET HOLE, ATTACH
TO BUILDING STRUCTURE I luntDEPRESSED TO AVOID IVIBRATION ISOLATORS
-TYPICAL FOR 4AN OBSTRUCTION FLEXIBLE DUCT -
CONNECTOR (TYP) Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
MOTOR AND GUARD FOR
BELT DRIVE UNITS IN
ACCESSIBLE POSITION
DUCTWORK - SAME SIZE AS
INDICATED ON DRAWINGSm
24 GAUGE SHEET METAL SLEEVE
EXTEND 1 1/2" BEYOND EACH SIDE FAN HOUSING
SMOOTH RADIUS ELLS
TO AVOID AN OBSTRUCTION
FIRE RATED WALL
SUPPORT BRACKETS
DUCT TRANSITION
AS REQUIRED (TYP OF 2)
SEAL SLEEVE TO WALL OPENING
WITH FIRE RESISTANT SEALANT It TETRATECH
TAPE (2" MIN. WIDTH)
FIRE RESISTANT SEALANT ON
ENDS OF DUCT INSULATION
www.tetratech.comDUCT INSULATION
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
x
FAN DUCTED INLET/OUTLETTYPICAL DUCT OFFSET 17 DUCTWORK
NO SCALE NO SCALE
7?
SCREEN
ANGLE IRON
REINFORCING
- BOLTSTYPE T INSULATION
(U.S. GYPSUM THERMAFIBER BATS) © Copyright 2017
This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
FIRE RATED WALL
METAL SCREEN
FRAMENOTES: OUTLET AREA
SHALL BE 25%
LARGER THAN
DUCT SIZE
THIS DETAIL APPLIES ONLY FOR INSULATED DUCTS REQUIRING
CONTINUOUS INSULATION THROUGH WALL, AND DUCTS NOT REQUIRING
FIRE DAMPERS.
1VENT CAP
WATERPROOF
SEAMS AND
JOINTS (TYP)
24" MAXIMUM
18" MINIMUM
12'
36' 24 GAUGE SHEET METAL SLEEVE
EXTEND 1 1/2" BEYOND EACH SIDE 30.00°
REFER TO ARCHITECTURAL
DRAWINGS FOR ROOF
PENETRATION
SEAL SLEEVE TO WALL OPENING
WITH SEALANT
TAPE (2" MIN. WIDTH)
DRIP FLASHING
AROUND ENTIRE
DUCT AND CURB
NON-RATED WALL 36" MIN.
ABOVE
ROOF
FINISHED ROOF
DUCT INSULATION v
A-
R(W/2)
ONE-PIECE SHEET METAL
CURB/FLASHING (REFER
TO ARCH. DRAWINGS)
COMBUSTION AIR INTAKE
DUCTWORK ARCHITECTURAL
METAL ROOF
EXHAUST AIR VENT
MOTORIZED DAMPER
NON-RATED WALL DAMPER ACTUATOR oDUCT PENETRATION THRU INTERIOR WALL5 COAIRTIGHT ---------
ACCESS DOOR
COBOILER NO SCALE EXHAUST DUCT oo CD o' O' CD3/4" BALL VALVE WITH
THREADED CONNECTION
AND CAP
EQUIPMENT PAD
(REFER TO STRUCTURAL DRAWINGS)
FINISHED ROOF
0£O' < oo oJL co
O COBOILER COMBUSTION AIR AND VENTING GOOSENECK ROOF TERMINATION
8 2NO SCALE NO SCALE
03O E1/2"x1/2" BIRDSCREEN
ON OUTLET
CORROSION
RESISTANT
FLEXIBLE
CONNECTION -------------
CORROSION
RESISTANT
EXHAUST DUCT -
SEE DWGS AND
SPEC. FOR SIZE
AND MATERIAL------------
CD
oO'ro NOTE:o
(?) MINIMUM FIVE (5) DUCT DIAMETERS OF
STRAIGHT DUCT - SAME SIZE AS FAN
CONNECTION.
"OO O' CD
AIR FLOW CO("W" + "H") x 2
AIR FLOW
LEAD WRAP DUCT (REFER TO
ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS)
LOCATE DAMPER AS
FAR FROM GRILLE AS
POSSIBLE
ABOVE GRADE CD(Xoo
COO' O O CD24" FAN DISCHARGE
EXTENSION, SAME DIMENSIONS
AS FAN OUTLET
CSHEET METAL
DUCTWORK o o o■w
WEATHER PROOF
MOTOR COVER
PERMISSIBLE TRANSITIONSMIN. 2" LEAD-LINING
OVERLAP AROUND
ENTIRE DUCT
PENETRATION
W ISSUEDDUCT HEIGHT
ABOVE CEILING "H 10/04/19 REVISED BID
DOCUMENTSR=1 1/2 W4 VIBRATION ISOLATORS
- TYP. OF 4FAN INLET
FAN SUPPORT FRAME
LEAD-LINED CEILINGLEAD WRAP
DUCT OR WRAP
TO CEILING AS
SHOWN -
R
DUCT WIDTH "W
CONCRETE PAD
ON GRADE. REFER
TO STRUCTURAL
DRAWINGS
W
-t DIFFUSER OR GRILLE «r:0) <- A> XT' ■ 101R=1 1/2 W■o c LEAD-LINED CEILING DUCT PENETRATION UTILITY FAN03 a:
EXPIRES:
9 3RNO SCALE NO SCALEcoro \< /I LOCATE DAMPER AS FAR
FROM GRILLE AS POSSIBLER
o
CM
SEAL DUCT CONNECTION
AIR TIGHT (CONNECTION MAY
BE ON TOP OF PLENUM)
R=1 1/2 W
LLI
O w M&H NO.: 3142200-121252.01
10/04/19PERMISSIBLE ELBOWS SHEET METAL PLENUM.
PAINT INTERIOR OF METAL
PLENUM FLAT BLACK
DATE:
O
DESIGNED BY: ADKCM
LO
ARCM DRAWN BY:
CM BGD<xxxxxxxxxxxxx: CHECKED BY:RETURN/EXHAUST
GRILLE
oo DO NOT SCALE DRAWINGSAIR FLOW AIR FLOWCM
CM
SHEET CONTENTS
CO CEILING HVAC DETAILS03
Oo
> iCD
CE
O
SHEET NO.:
RETURN/EXHAUST
GRILLE DUCT CONNECTION
CM
M-502TYPICAL DUCT TRANSITIONSOO
6 4CT>
NO SCALE NO SCALEo
CM
MeadKEYED NOTES:
<T> NOT REQUIRED WHEN SUCTION DIFFUSER
IS SCHEDULED OR SPECIFIED.
(2 NOT REQUIRED WHEN TRIPLE-DUTY VALVE
IS SCHEDULED OR SPECIFIED.
I luntI3/4" CONNECTED TO SUCTION
SIDE OF SECONDARY PUMPS
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com
?SIZE GLOBE VALVE
SEE DWGS FOR SIZE
HANGER RODS TO
STRUCTURE
-AS INDICATED ON PLANS ACV4? REDUCING TEE SIGHT GLASS OR
FLOW INDICATOR
BALANCING VALVE
{X} HWR—[X]------V INTERIOR WALL
CONNECT
TO MAINSPRESSURE GAGE 1/2" TO r
CLEARANCE
ALL SIDES
WALL SLEEVE, OF
SPECIFIED MATERIAL
ESCUTCHEON
WHERE SPECIFIED
PIPE INSULATION
AND JACKETING
WHERE CALLED FOR
TIGHTLY CAULK WITH
SILICONE SEALANT
FOR MIN. 2" EACH END
PRESSURE GAUGE
WITH COCKX- FUNNEL
3/4" FILL AND
VENT VALVE
PRESSURE RATED POT FEEDER
MIN CAPACITY 1/1000 OF TOTAL
SYSTEM VOLUME
hws ; ;
SHUTOFF VALVE (TYP) <2>
BALANCING VALVE (2)
CHECK VALVE <2>
It TETRATECHREDUCER (TYP) -AS REQUIRED SHUTOFF VALVEri www.tetratech.comSTRAINERFLEXIBLE PIPE ------------
CONNECTOR (TYP)
<T> STRAINER --------------
WITH BLOW OFF
VALVE AND NIPPLE
GLOBE VALVE
OR FIXED
ORIFICE PLATE
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254PUMP AIR FLOWUNIT
HEATER UNION TYPICAL
MOTOR
SHUTOFF
VALVE (TYP)
BYPASS ON-HALF OF
MAIN PIPE SIZE
MINIMUM 3/4"
HOLD DOWN BOLTS
— PUMP BED PLATE
{XhREDUCING TEELEVEL GROUT PIPE-MUST BE
FREE OF STRAIN
TIGHTLY PACKED
WITH FOAM - IN
PLACE INSULATION
A h3" THICK CONCRETE
EQUIPMENT PAD TO
EXTEND 6" BEYOND PUMP
BED PLATE ON ALL SIDES
UNION (TYP) 1" DRAIN VALVE
CAPPED
DRAIN VALVEAr
3/4" CONNECTED TO DISCHARGE
SIDE OF SECONDARY PUMPSHOT WATER UNIT HEATER
PIPING w/ TEMPERATURE CONTROL AND ACV © Copyright 2017 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
END SUCTION PUMP PIPING CHEMICAL POT FEEDER INTERIOR WALL PIPE SLEEVE12 9 15NO SCALE NO SCALE NO SCALE NO SCALE
1/4" SOFT COPPER
TUBING
VENT VALVE, LOCATE
VALVE AT MOST
ACCESSIBLE LOCATION
GAS SUPPLY
FIRE RATED WALL
SIZE AS INDICATED
ON DRAWINGS 24 GAUGE SHEET METAL SLEEVE
EXTENDED 1 1/2” BEYOND EACH SIDE■v 6" MIN.—
/SHUT-OFF VALVE SEAL SLEEVE TO WALL OPENING
WITH FIRE RESISTANT SEALANTBRANCH OR
MAIN PIPINGIN-LINE PUMP PRESSURE GAGE
WITH COCK (TYP)
REDUCER (TYP)
-AS REQUIRED
SHUTOFF VALVE (TYP)
TAPE (2" MIN. WIDTH)SCREWED UNION CONNECTIONS SO PUMP -
CAN BE REMOVED WITHOUT
DISTURBING CONNECTED PIPING
FLEXIBLE -
CONNECTOR (TYP)
COILS AND SUBCIRCUITS3
SAME SIZE AS
EQUIPMENT
CONNECTION
1/2" PIPE INSULATION
3-xEQUIPMENT 6" MIN.
/DIRT POCKET l HOT WATER PIPE
CD
FIRE RESISTANT SEALANT ON
ENDS OF PIPE INSULATIONCHECK VALVE
BALANCING
VALVE
STRAINER WITH BLOW OFF
VALVE AND NIPPLE oPLUG OR CAP3'-0' TYPE "T" INSULATION
(U.S. GYPSUM THERMAFIBER BATS)— MAIN PIPESMAX INSULATED PIPE
THRU FIRE RATED WALL CO COoEQUIPMENT GAS CONNECTION (TYP) IN-LINE PUMP PIPING AIR VENT PIPING O CD13 6 2 r^NO SCALE NO SCALE NO SCALE NO SCALE
O' O' CD
tr.O' < oo o co
O 03TO AIR SEPARATOR
<COLD WATER FILL
2" AIR GAP
INTERIOR
MASONRY/CONCRETE WALL
03O1/2" TO 1"
CLEARANCE
ALL SIDES
EPRESSURE RELIEF
VALVE
SET AT 50 PSIG
COVER WALL SLEEVE MATERIAL
AS SPECIFIED
03HIGH CAPACITY AIR VENT
EQUAL TO BELL & GOSSET
MODEL #107a -
T
GLYCOL/WATER
STORAGE TANK oO'ESCUTCHEON MATERIAL AS
SPECIFIED
PIPE INSULATION AND
JACKETING WHERE CALLED
LEVEL SWITCH 4 ' "OI A' > o O'REDUCER
WHERE REQ'D
LSTRAINER
FLEX CONNECTOR
PRESSURE GAUGE CDO'MIN. 2" OVERLAP AROUND
ENTIRE PENETRATION COFORAVFROM PRIMARY
HEATING
EQUIPMENT —
COLD WATER FILL
FROM GLYCOL TANK
Z PRESSURE SWITCH
PUMP
P CD
ANCHORSWRAP LEAD AROUND ENTIRE
PIPE AND INSULATION
CIRCUMFERENCE
AIR SEPARATOR
REDUCER
(WHERE REQ’D)
COO' O ORADIATION ROOM X-RAY
SOURCE SIDE 2 O)O’ CHECK VALVE c
4 o o oPIPE-MUST BE FREE
OF STRAIN
TIGHTLY PACKED WITH
FOAM-IN-PLACE
INSULATION
SEE PLANS
FOR PIPE SIZE TO0X1 NOTE:
UNLESS OTHERWISE INDICATED, SEE PLANS AND
SPECIFICATIONS FOR PIPE SIZE AND MATERIAL.
SYSTEM
PUMPS(S)
SEE PLANS
FOR PIPE SIZE
AUTOMATIC
AIR VENT
ISSUED
H
INTERIOR
WALL SLEEVE INSULATED PIPE
10/04/19 REVISED BID
DOCUMENTSPRESSURE
GAUGE -
SHUT-OFF
VALVE (TYP) -
VERTICAL BLADDER
T…