08 36 19 - BR.pdf
PDF 33 KB Posted
- Attached to
- Construct VM/AGE Complex Federal contract opportunity
- Solicitation number
- W50S8W25RA003
- Issued by
- Department of the Army National Guard
About this file
This document is a technical specification (Section 08 36 19) for Vertical Lift Doors for a Combined Vehicle Maintenance and AGE Facility. The specification provides detailed requirements for vertical lift doors, including materials, fabrication, electrical operators, and installation standards. Key technical specifications include doors constructed with multiple sections that stack vertically, insulated door sections with a minimum U-factor of 0.14, and electric operators with specific motor and control requirements.
The document outlines comprehensive technical requirements for door construction, including steel and aluminum material specifications, galvanized finishes, hardware details, and glazing provisions. Electrical components must comply with NFPA 70 and include entrapment protection devices, control transformers, and specific control switch configurations. Installation requirements mandate precise anchoring, weathertightness, and operational testing to ensure proper door functionality. The specification is part of a solicitation for constructing a vehicle maintenance facility, with detailed submittal requirements for shop drawings, product data, and operation and maintenance documentation.
View the file
Other files for this federal contract opportunity
Show all 50
Construct VM/AGE Complex has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
100% Revised B3 Submission Combined Vehicle Maintenance and AGE Facility
SECTION 08 36 19
VERTICAL LIFT DOORS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 360 (2016) Specification for Structural Steel Buildings
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2022) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM C136/C136M (2019) Standard Test Method for Sieve Analysis of Fine and Coarse Aggregates
ASTM E330/E330M (2014; R 2021) Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference
DOOR AND ACCESS SYSTEM MANUFACTURERS ASSOCIATION (DASMA)
ANSI/DASMA 102 (2011) Specifications for Sectional Overhead-Type Doors
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
SECTION 08 36 19 Page 1
BID QUESTION REVISIONS
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA MG 1 (2021) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 ( 2020; ERTA 20-1 2020; ERTA 20-2 2020;
ERTA 20-3 2020; TIA 20-1; TIA 20-2; TIA
20-3; TIA 20-4; TIA 20-5; TIA 20-6; TIA
20-7; TIA 20-8; TIA 20-9; TIA 20-10; TIA
20-11; TIA 20-12; TIA 20-13; TIA 20-14;
TIA 20-15; TIA 20-16; ERTA 20-4 2022 )
National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 325 (2017; Reprint Feb 2020) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Doors ; G
SD-03 Product Data
Doors ; G
Motors ; G
Controls ; G
SD-08 Manufacturer's Instructions
Doors
SD-10 Operation and Maintenance Data
Doors , Data Package 2; G
SECTION 08 36 19 Page 2
1.2.1 Shop Drawing Information
Show types, sizes, locations, metal gages, hardware provisions, installation details, and other details of construction.
1.2.2 Operation and Maintenance Data
For electrically operated doors, include wiring diagrams for motors and controls.
1.3 DELIVERY, STORAGE, AND HANDLING
Protect doors and accessories from damage during delivery, storage, and handling. Clearly mark manufacturer's brand name. Store doors in dry locations with adequate ventilation, free from dust and water. Storage must permit easy access for inspection and handling. Remove damaged items that cannot be restored to like-new condition and provide new items.
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Steel Sheet
ASTM A653/A653M .
2.1.2 Steel Shapes
ASTM A36/A36M.
2.1.3 Aluminum Extrusions
ASTM B221, Alloy 6063-T5.
2.1.4 Aluminum Sheets and Strips
ASTM B209, alloy and temper best suited for the purpose.
2.1.5 Glass
Fully tempered, clear float glass, 1/8 inch thick.
2.2 DOORS
Doors must consist of multiple sections set one behind the other. Arrange door operation and travel so that sections arrive simultaneously at the full open position. Sections must stack vertically in a compact group above the head of the opening. Provide doors with counterweights. Design doors, components, and methods of installation in accordance with AISC 360 and ANSI/DASMA 102 . Design wind loads as indicated on drawings . Door wind load performance must be determined in accordance with ASTM E330/E330M .
Maximum wind load deflection of the door must not exceed the door height in inches divided by 120 and the door width in inches divided by 120. Doors must be operable during design wind load.
Form curtains from manufacturer's standard shapes of interlocking slats.
Supply a slat system with a minimum R-value of 26 when calculated. Slats to consist of a urethane or polystyrene core not less than 3 inch thick, completely enclosed within metal facings. Slat steel thickness as
SECTION 08 36 19 Page 3 required by the size of the door to meet specified performance requirements. The insulated slat assembly requires a flame spread rating of not more than 25 and a smoke development factor of not more than 50 when tested.
Provide complete manufacturer's standard vision panels assembly consisting of clear acrylic glazing panels or fire-rated glass as required for the type door.
2.3 ELECTRIC OPERATORS
Provide operators of the type recommended by the door manufacturer.
Operators must be labeled and listed to the requirements of UL 325 .
Operators must include electric motor, machine-cut reduction gears, steel chain and sprockets, magnetic brake, brackets, pushbutton controls, limit switches, magnetic reversing contactor, a manual operator as specified above for emergency use, and other accessories necessary for operation.
The electric operator must be designed so that the motor may be removed without disturbing the limit switch timing and without affecting the manual operator. The manual operator must be clutch controlled so that it may be engaged and disengaged from the floor; operation must not affect limit switch timing. Provide an electrical or mechanical device that disconnects the motor from the operating mechanism when the manual operator is engaged.
2.3.1 Motors
NEMA MG 1, high-starting torque, reversible type with sufficient horsepower and torque output to move the door in either direction from any position. Motor must produce a door travel speed of not less than two-thirds foot or more than one foot per second without exceeding the rated capacity. Motors must operate on current of the characteristics indicated at not more than 3600 rpm . Single-phase motors must not have commutation or more than one starting contact. Install motors in approved locations.
2.3.2 Controls
Each door motor must have an enclosed, across-the-line type, magnetic reversing contactor, thermal overload and undervoltage protection, solenoid-operated brake, limit switches, and control switches. Locate control switches at least 5 feet above the floor so the operator will have complete visibility of the door at all times. Control equipment must conform to NEMA ICS 1 and NEMA ICS 2 . Control enclosures must be NEMA ICS 6 , Type 12 or Type 4, except that contactor enclosures may be Type 1. Each control switch station must be of the three-button type;
buttons must be marked "OPEN," "CLOSE," and "STOP." The "OPEN" and "STOP" buttons must require only momentary pressure to operate. The "CLOSE" button must require constant pressure to maintain the closing motion of the door. If the door is in motion and the "STOP" button is pressed or the "CLOSE" button released, the door must stop instantly and remain in the stop position; from the stop position, the door may be operated in either direction by the "OPEN" or "CLOSE" buttons. Pushbuttons must be full-guarded to prevent accidental operation. Provide limit switches to automatically stop doors at the fully open and closed positions. Limit switch positions must be readily adjustable.
SECTION 08 36 19 Page 4
2.3.3 Entrapment Protection Devices
Entrapment protection devices must be provided for electrically operated doors in accordance with UL 325 . These devices must immediately stop and reverse the door in its closing travel upon sensing an obstruction in the door opening or upon failure of the device or any component of the control system. Any momentary door-closing circuit must be automatically locked out and the door must be operable manually or with constant pressure controls until the failure or damage has been corrected. No entrapment protection device can be used as a limit switch unless its function is specifically intended to do so.
2.3.4 Control Transformers
UL 325 . Provide transformers in power circuits as necessary to reduce the voltage on the control circuits to 120 volts or less.
2.3.5 Electrical Components
NFPA 70 . Provide manual or automatic control and safety devices, including extra flexible Type SO cable and spring-loaded automatic takeup reel or equivalent device, as required for operation of the doors.
Conduit, wiring, and mounting of controls are specified in Section 26 20 00
INTERIOR DISTRIBUTION SYSTEM.
2.3.6 Hazardous Locations
Electrical materials, equipment, and devices for installation in hazardous locations, as defined by NFPA 70 , must be specifically approved by Underwriters Laboratories or by another independent testing agency using equivalent standards, for the particular chemical group and the class and division of hazardous location involved.
2.4 WEATHER SEALS AND SENSING EDGES
Provide exterior doors with weatherproof joints between sections, a rubber or vinyl adjustable weatherstrip at the top, and a compressible neoprene or rubber weather seal attached to the bottom of the door. On exterior doors that are electrically operated, where a sensing edge is employed, the bottom seal must be a combination compressible weather seal and sensing edge for stopping and reversing door movement.
2.5 FINISHES
Concealed ferrous metal surfaces must be hot-dip galvanized. Exposed ferrous metal surfaces must be hot-dip galvanized and shop primed.
2.5.1 Galvanized and Shop Primed
Surfaces specified must have a zinc coating, a phosphate treatment, and a shop prime coat of rust-inhibitive paint. The galvanized coating must conform to ASTM A653/A653M , coating designation G90 , for steel sheets, and ASTM A123/A123M for assembled steel products. The weight of coatings for assembled products must be as designated in Table I of ASTM A123/A123M for the class of material to be coated. The prime coat must be a type especially developed for materials treated by phosphates and adapted to application by dipping or spraying. Repair damaged zinc-coated surfaces by the application of galvanizing repair paint and spot prime. At the Contractor's option, a two-part system including bonderizing, baked-on
SECTION 08 36 19 Page 5 epoxy primer, and baked-on enamel topcoat may be applied to slats before forming in lieu of prime coat specified.
2.5.2 Aluminum
Surfaces must receive a clear anodized finish, AA-M10-C22-A41, in accordance with NAAMM AMP 500.Exposed surfaces must receive a pretreatment and a baked-on enamel finish as standard with the manufacturer.
PART 3 EXECUTION
3.1 FABRICATION
3.1.1 Door Sections
Provide vertical and horizontal door section members constructed of structural steel angle or channel shapes. Cover door section exteriors with sheet steel not lighter than 14 gage , bolted, plug welded, or edge welded to frame at not more than 9 inches on centers. Provide intermediate horizontal or vertical stiffeners so the maximum unsupported area of sheet is 20 square feet . Corners and intersections of frame members must be welded and ground smooth on exposed surfaces. Welds must develop the full strength of frame.
3.1.1.1 Insulated Sections
Insulated door sections must be insulated with material providing a "U" factor of 0.14 or less when tested in accordance with ASTM C136/C136M.
Interior of door sections must be covered with steel sheets not lighter than 24 gage to completely enclose the insulating material.
3.1.1.2 Aluminum Sections
At the Contractor's option, door sections may be constructed of aluminum in lieu of steel. Aluminum sections must, as a minimum, provide the same structural and thermal properties as steel sections.
3.1.2 Guides and Jamb Plates
Door sections must run in structural steel guides, securely fastened to the counterweight tower and to the idler tower, which must be attached to the building construction. The counterweight enclosure must extend approximately to the same height as the guides. Set back guides and tower faces on walls to provide clear door opening unobstructed by door guides, except when indicated otherwise.
3.1.3 Hardware
Door sections must be supported by chain or steel cable with a safety factor of five. The sheaves over which the chain or cable passes to the door must have permanently sealed precision bearings. Cast-iron counterweights must be stacked on a steel weight rod or in a special container. The counterweight tower must be enclosed with a removable steel cover not lighter than 14 gage to a height of 7 feet above the floor. Provide doors with a positive locking device and cylinder lock with two keys.
SECTION 08 36 19 Page 6
3.1.4 Glazing
Provide glass panels where indicated. Install panels using rubber gaskets as standard with the door manufacturer.
3.2 INSTALLATION
NFPA 70 . Install doors in accordance with approved detail drawings and manufacturer's instructions. Accurately locate anchors and inserts for guides, brackets, motors, switches, hardware, and other accessories. Upon completion, doors must be weathertight and free from warp, twist, or distortion. Doors must be lubricated and adjusted to operate freely.
3.3 ELECTRICAL WORK
NFPA 70 . Conduit, wiring, and mounting of controls are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEMS.
3.4 TESTING
After installation is complete, operate doors to demonstrate installation and function of operators, safety features, and controls. Correct deficiencies.
-- End of Section --
SECTION 08 36 19 Page 7
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 08 36 19 Page 8
| 08 36 19 - VERTICAL LIFT DOORS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.2.1 Shop Drawing Information |
| 1.2.2 Operation and Maintenance Data |
1.3 DELIVERY, STORAGE, AND HANDLING
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.1.1 Steel Sheet |
| 2.1.2 Steel Shapes |
| 2.1.3 Aluminum Extrusions |
| 2.1.4 Aluminum Sheets and Strips |
| 2.1.5 Glass |
| 2.2 DOORS |
| 2.3 ELECTRIC OPERATORS |
| 2.3.1 Motors |
| 2.3.2 Controls |
| 2.3.3 Entrapment Protection Devices |
| 2.3.4 Control Transformers |
| 2.3.5 Electrical Components |
| 2.3.6 Hazardous Locations |
| 2.4 WEATHER SEALS AND SENSING EDGES |
| 2.5 FINISHES |
| 2.5.1 Galvanized and Shop Primed |
| 2.5.2 Aluminum |
| PART 3 EXECUTION |
| 3.1 FABRICATION |
| 3.1.1 Door Sections |
| 3.1.1.1 Insulated Sections |
| 3.1.1.2 Aluminum Sections |
| 3.1.2 Guides and Jamb Plates |
| 3.1.3 Hardware |
| 3.1.4 Glazing |
| 3.2 INSTALLATION |
| 3.3 ELECTRICAL WORK |
| 3.4 TESTING |