This solicitation seeks bids for the 145 Airlift Wing Add/Alter Small Air Terminal Building 5 project. The purpose is to issue the solicitation documents, drawings, specifications and attachments for renovating and expanding an existing air terminal building. A pre-bid conference will be held on June 2, 2021 where bidders must register to attend. Bids are due by June 16, 2021 and the contract is to be awarded by July 21, 2021. The renovation work includes interior renovations, new restrooms, upgrading mechanical and electrical systems, and constructing an addition. The solicitation is issued by the Department of the Army North Carolina Army National Guard.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM #4
h:\prj\20180720\08-submissions\21-addendum 4\nc ang sat-adf addendum #4.docx Page 1 of 2
FSB Federal Design Group 5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Date: 7/9/2021 Project: COMBINED:
FJRP052994 C-17 Conv: Add/Alter Small Air Terminal Bldg 5 FJRP199040 C-17 Conv: Air Drop Facility
Prepared By: Linda L. Phillips, AIA Sr. Project Manager
ADDENDUM #4
The drawings and specifications for this project are not yet bid or under contract. Therefore, the following clarifications and modifications should be issued to bidders and made a part of the Issued for Bid documents so that any related costs may be captured in the bids submitted to the government for review. The following documents have been revised accordingly, and the corresponding changes clouded and denoted as Addendum #4 on the drawing sheets. Please replace the revised documents with the like numbered or titled document provided herewith and insert the new specification section provided.
COMBINED SPECIFICATIONS:
1. TABLE OF CONTENTS - Reissued to reflect the following:
a. Revised to add Section 083323 – OVERHEAD COILING DOORS
b. Revised to delete Section 104416 – FIRE EXTINGUISHERS
2. SECTION 083323 – OVERHEAD COILING DOORS – To be added to Volume 2 of the Specifications and to the Table of Contents.
SMALL AIR TERMINAL DRAWINGS:
1. Sheet G-101 – LIFE SAFETY PLAN
2. Sheet SB101 – FOUNDATION PLAN – Revised reinforcing notes.
3. Sheet SB301 – FOUNDATION DETAILS – Revised reinforcing notes.
4. Sheet SF201 – FRAMING ELEVATIONS – Revised detail notes.
5. Sheet SF501 – FRAMING DETAILS – Revised detail note.
6. Sheet AE401 – ENLARGED PLANS AND INTERIOR ELEVATIONS – Revises toilet room elevations.
7. Sheet AE604 – ROOM FINISH SCHEDULE – Revises finishes, floor transitions, notes and designations.
AIR DROP FACILITY DRAWINGS:
8. Sheet G-101A – LIFE SAFETY PLAN
9. Sheet AE303A – WALL SECTIONS - Revised detail notes to indicate wall clips.
Addendum #4 July 9, 2021
FSB | DefineDesignDeliver
10. Sheet AE304A – WALL SECTIONS - Revised detail notes to indicate wall clips.
11. Sheet AE305A – WALL SECTIONS - Revised detail notes to indicate wall clips.
12. Sheet AE501A – DETAILS - Revised detail notes to indicate wall clips.
13. Sheet AE503A – DETAILS - Revised detail notes to indicate wall clips.
END OF ADDENDUM #4
NORTH CAROLINA AIR NATIONAL GUARD
SMALL AIR TERMINAL ADD/ALTER AIR DROP FACILITY
PROJECT FJRP052994 PROJECT FJRP199040
Addendum #4
Issue Date: July 9, 2021
COMBINED BID PACKAGE PROJECT MANUAL
050024
Frankfurt-Short-Bruza Architects Engineers Planners document1 Page 1 of 1 5801 Broadway Extension, Suite 500, Oklahoma City, Oklahoma 73118-7436
Telephone (405) 840-2931 Facsimile (405) 842-7750 Website www.fsb-ae.com
11949
SEAL
050568
ENGINEE
R
NORTH CAROLINA ANG FJRP052994 SMALL AIR TERMINAL
CHARLOTTE, NC FJRP199040 AIR DROP FACILITY
Addendum #3 Table of Contents
June 29, 2021 TOC - 2
TABLE OF CONTENTS
VOLUME 1 OF 4
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
AS PROVIDED BY THE NORTH CAROLINA AIR NATIONAL GUARD
DIVISION 01 - GENERAL REQUIREMENTS
SECTION 011000 – SUMMARY OF THE WORK
SECTION 011416 – COORDINATION WITH NORTH CAROLINA AIR NATIONAL GUARD
SECTION 013100 – PROJECT MANAGEMENT AND COORDINATION
SECTION 013200 – CONSTRUCTION PROGRESS DOCUMENTATION
SECTION 013300 – SUBMITTAL PROCEDURES
SECTION 013329 – SUSTAINABILITY REPORTING
SECTION 014000 – QUALITY CONTROL
SECTION 014200 – REFERENCES
SECTION 015000 – TEMPORARY FACILITIES AND CONTROLS
SECTION 015930 – SECURITY REGULATIONS
SECTION 015950 – SAFETY AND HEALTH
SECTION 015960 – HAZARDOUS MATERIAL STORAGE AND DISTRIBUTION
SECTION 016000 – PRODUCT REQUIREMENTS
SECTION 017000 – EXECUTION REQUIREMENTS
SECTION 017329 – CUTTING AND PATCHING
SECTION 017419 – CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
SECTION 017700 – CLOSEOUT PROCEDURES
SECTION 017820 – OPERATION AND MAINTENANCE DATA
SECTION 017839 – PROJECT RECORD DOCUMENTS
SECTION 018200 – DEMONSTRATION AND TRAINING
DIVISION 02 - EXISTING CONDITIONS
SECTION 024119 - SELECTIVE DEMOLITION AND REMEDIATION
DIVISION 03 - CONCRETE
SECTION 030130 - MAINTENANCE OF CAST-IN-PLACE CONCRETE
SECTION 033000 - CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
SECTION 042000 - UNIT MASONRY
SECTION 042113 - THIN BRICK MASONRY
SECTION 047315 - MANUFACTURED THIN STONE MASONRY
SECTION 047200 – CAST STONE MASONRY
DIVISION 05 - METALS
SECTION 051200 - STRUCTURAL STEEL FRAMING
Addendum #3 Table of Contents
June 29, 2021 TOC - 3
SECTION 052100 – STEEL JOIST FRAMING
SECTION 053100 - STEEL DECKING
SECTION 054000 – COLD FORMED METAL FRAMING
SECTION 055000 - METAL FABRICATIONS
SECTION 055113 - METAL PAN STAIRS
SECTION 055133 - ALTERNATING TREAD STEEL STAIRS
SECTION 055213 - PIPE AND TUBE RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 061000 - ROUGH CARPENTRY
SECTION 061600 - SHEATHING
SECTION 064116 - PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
SECTION 068300 - COMPOSITE PANELING
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 072100 - THERMAL INSULATION
SECTION 072119 - FOAMED-IN-PLACE INSULATION
SECTION 072726 - FLUID-APPLIED AIR AND WATER RESISTIVE BARRIER SYSTEM
SECTION 074113.16 – STANDING SEAM METAL ROOF PANLS
SECTION 074213.19 - INSULATED METAL WALL PANELS
SECTION 075419 - POLYVINYL-CHLORIDE (PVC) ROOFING
SECTION 076200 - SHEET METAL FLASHING AND TRIM
SECTION 077200 - ROOF ACCESSORIES
SECTION 077253 – SNOW GUARDS
SECTION 078413 - PENETRATION FIRESTOPPING
SECTION 078446 - FIRE-RESISTIVE JOINT SYSTEMS
SECTION 079200 - JOINT SEALANTS
SECTION 079500 – EXPANSION CONTROL
VOLUME 2 OF 4
DIVISION 08 - OPENINGS
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES
SECTION 081416 - FLUSH WOOD DOORS
SECTION 083113 - ACCESS DOORS AND FRAMES
SECTION 083313 - COILING COUNTER DOORS
SECTION 083323 – OVERHEAD COILING DOORS
SECTION 084113 - ALUMINUM-FRAMED ENTRANCES AND WINDOWS
SECTION 084523 – FIBERGLASS SANDWICH-PANEL ASSEMBLIES
SECTION 086200 – UNIT SKYLIGHTS
SECTION 087100 - DOOR HARDWARE
SECTION 088000 - GLAZING
DIVISION 09 - FINISHES
SECTION 090690 - COLOR SCHEDULE
SECTION 092216 - NON-STRUCTURAL METAL FRAMING
SECTION 092900 - GYPSUM BOARD
Addendum #3 Table of Contents
June 29, 2021 TOC - 4
SECTION 093013 - CERAMIC TILING
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
SECTION 096513 - RESILIENT BASE AND ACCESSORIES
SECTION 096519 - RESILIENT TILE FLOORING
SECTION 096723.15 – FUEL RESISTIVE RESINOUS FLOORING
SECTION 096813 - TILE CARPETING
SECTION 097200 - DRY ERASE WALLCOVERING
SECTION 097800 - FIBERGLASS REINFORCED PLASTIC PANELS
SECTION 099113 - EXTERIOR PAINTING
SECTION 099123 - INTERIOR PAINTING
DIVISION 10 - SPECIALTIES
SECTION 101423 - PANEL SIGNAGE
SECTION 102113.19 - PLASTIC TOILET COMPARTMENTS
SECTION 102213 - WIRE MESH PARTITIONS
SECTION 102239 - RETRACTABLE WALL SYSTEM
SECTION 102600 - WALL AND DOOR PROTECTION
SECTION 102800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
SECTION 104413 - FIRE EXTINGUISHER CABINETS
SECTION 104416 - FIRE EXTINGUISHERS
SECTION 105113 - METAL LOCKERS
SECTION 107316 - MANUFACTURED CANOPIES
DIVISION 11 - EQUIPMENT
SECTION 111323 - BAGGAGE SCALE EQUIPMENT
SECTION 115213 - PROJECTION SCREENS
DIVISION 12 - FURNISHINGS
SECTION 122413 - ROLLER WINDOW SHADES
SECTION 123661.16 - SOLID SURFACING COUNTERTOPS
SECTION 124813 - ENTRANCE FLOOR MATS AND FRAMES
DIVISION 13 - SPECIAL CONSTRUCTION
SECTION 133419 - METAL BUILDING SYSTEMS
DIVISION 14 - CONVEYING EQUIPMENT
SECTION 142123 - ELECTRIC TRACTION PASSENGER ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
SECTION 211100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING
SECTION 211313 - WET PIPE SPRINKLER SYSTEMS
SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS
SECTION 213119 - CONTROLLERS FOR FIRE-PUMP DRIVERS
SECTION 213413 - PRESSURE-MAINTENANCE PUMPS
DIVISION 22 - PLUMBING
Addendum #3 Table of Contents
June 29, 2021 TOC - 5
SECTION 220513 - COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
SECTION 220518 - ESCUTCHEONS FOR PLUMBING PIPING
SECTION 220519 - METERS AND GAGES FOR PLUMBING PIPING
SECTION 220523.12 - BALL VALVES FOR PLUMBING PIPING
SECTION 220523.14 - CHECK VALVES FOR PLUMBING PIPING
SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING
SECTION 220548.13 - VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220716 - PLUMBING EQUIPMENT INSULATION
SECTION 220719 - PLUMBING PIPING INSULATION
SECTION 221116 - DOMESTIC WATER PIPING
SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES
SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS
SECTION 221123.21 - INLINE, DOMESTIC-WATER PUMPS
SECTION 221313 - FACILITY SANITARY SEWERS
SECTION 221316 - SANITARY WASTE AND VENT PIPING
SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES
SECTION 221319.13 - SANITARY DRAINS
SECTION 221413 - FACILITY STORM DRAINAGE PIPING
SECTION 221423 - STORM DRAINAGE PIPING SPECIALTIES
SECTION 221429 - SUMP PUMPS
SECTION 221513 - GENERAL-SERVICE COMPRESSED-AIR PIPING
SECTION 221519 - GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS
SECTION 223400 - FUEL-FIRED, DOMESTIC-WATER HEATERS
SECTION 224213.13 - COMMERCIAL WATER CLOSETS
SECTION 224213.16 - COMMERCIAL URINALS
SECTION 224216.13 - COMMERCIAL LAVATORIES
SECTION 224216.16 - COMMERCIAL SINKS
SECTION 224223 - COMMERCIAL SHOWERS
SECTION 224713 - DRINKING FOUNTAINS
VOLUME 3 OF 4
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
SECTION 230518 - ESCUTCHEONS FOR HVAC PIPING
SECTION 230523.12 - BALL VALVES FOR HVAC PIPING
SECTION 230523.14 - CHECK VALVES FOR HVAC PIPING
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230548.13 - VIBRATION CONTROLS FOR HVAC
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 230713 - DUCT INSULATION
SECTION 230719 - HVAC PIPING INSULATION
SECTION 230923 - DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC
***(6) SUBSECTIONS REMOVED FROM TABLE OF CONTENTS
SECTION 231123 – FACILITY NATURAL-GAS PIPING
SECTION 232113 - HYDRONIC PIPING
SECTION 232116 - HYDRONIC PIPING SPECIALTIES
Addendum #3 Table of Contents
June 29, 2021 TOC - 6
SECTION 232123 - HYDRONIC PUMPS
SECTION 232300 - REFRIGERANT PIPING
SECTION 232513 - WATER TREATMENT FOR CLOSED-LOOP HYDRONIC SYSTEMS
SECTION 233113 - METAL DUCTS
SECTION 233300 - AIR DUCT ACCESSORIES
SECTION 233346 - FLEXIBLE DUCTS
SECTION 233416 - CENTRIFUGAL HVAC FANS
SECTION 233423 - HVAC POWER VENTILATORS
SECTION 233436 – AIR CIRCULATION FANS
SECTION 233600 - AIR TERMINAL UNITS
SECTION 233713.13 – AIR DIFFUSERS
SECTION 233713.23 – AIR REGISTERS AND GRILLES
SECTION 235123 - GAS VENTS
SECTION 235216 - CONDENSING BOILERS
SECTION 235523.13 - LOW-INTENSITY, GAS-FIRED, RADIANT HEATERS
SECTION 237313.16 - INDOOR, SEMI CUSTOM AIR HANDLING UNITS
SECTION 237423.13 - PACKAGED, DIRECT-FIRED, OUTDOOR, HEATING-ONLY MAKEUP-AIR UNITS
SECTION 238126 - SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 238239.16 - PROPELLER UNIT HEATERS
SECTION 238416.13 – OUTDOOR, MECHANICAL DEHUMIDIFICATION UNITS
DIVISION 25 - INTEGRATED AUTOMATION
NOT APPLICABLE
DIVISION 26 - ELECTRICAL
SECTION 260513 – MEDIUM VOLTAGE CABLES
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SECTION 260543 – UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
SECTION 260544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
SECTION 260573.13 - SHORT-CIRCUIT STUDIES
SECTION 260573.16 - COORDINATION STUDIES
SECTION 260573.19 - ARC-FLASH HAZARD ANALYSIS
SECTION 260923 - LIGHTING CONTROL DEVICES
SECTION 260936 – MODULAR DIMMING CONTROLS
SECTION 260943.23 – RELAY BASED LIGHTING CONTROLS
SECTION 261213 – LIQUID-FILLED MEDIUM VOLTAGE TRANSFORMERS
SECTION 262416 – PANELBOARDS
SECTION 262713.10 30 - ELECTRIC METERS
SECTION 262726 - WIRING DEVICES
SECTION 262913.03 - MANUAL AND MAGNETIC MOTOR CONTROLLERS
SECTION 262923 - VARIABLE-FREQUENCY MOTOR CONTROLLERS
SECTION 264113 - LIGHTNING PROTECTION FOR STRUCTURES
SECTION 264313 - SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 265100 - INTERIOR LIGHTING
SECTION 265119 - LED INTERIOR LIGHTING
SECTION 265619 - EXTERIOR LIGHTING
Addendum #3 Table of Contents
June 29, 2021 TOC - 7
VOLUME 4 OF 4
DIVISION 27 - COMMUNICATIONS
SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS
SECTION 270528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270544 - SLEEVES AND SLEEVE SEALS FOR COMMUNICATIONS PATHWAYS AND CABLING
SECTION 271100 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS
SECTION 271513 - COMMUNICATIONS COPPER HORIZONTAL CABLING
SECTION 275116 - PUBLIC ADDRESS SYSTEMS
SECTION 275313 - CLOCK SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
SECTION 283176 - FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
SECTION 310100 – SUBSURFACE EXPLORATION
SECTION 311000 – SITE CLEARING
SECTION 312000 – EARTH MOVING
SECTION 312319 – DEWATERING
SECTION 316600 - HELICAL PIERS w/Boring Logs Exhibit
DIVISION 32 - EXTERIOR IMPROVEMENTS
SECTION 321200 – PAVING AND SURFACING
SECTION 321313 – CONCRETE PAVING
SECTION 323113 - FENCING
SECTION 329113 - SOIL PREPARATION
SECTION 329200 - TURF AND GRASSES
SECTION 329300 - PLANTS
DIVISION 33 - UTILITIES
SECTION 330505 – WATER SANITARY AND DRAINAGE SITE PIPING
SECTION 334400 – STORMWATER UTILITY EQUIPMENT
DIVISION 34 - TRANSPORTATION
DIVISION 35 - WATERWAY AND MARINE CONSTRUCTION
DIVISION 40 - PROCESS INTEGRATION
Addendum #3 Table of Contents
June 29, 2021 TOC - 8
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
SECTION 412213.15 - BRIDGE CRANES, OVERHEAD ELECTRIC, UNDER RUNNING
SECTION 4122223.13 – PARACHUTE LIFT SYSTEM
DIVISION 42 - PROCESS HEATING, COOLING, AND DRYING EQUIPMENT
DIVISION 43 – 99
SECTION 083323 - OVERHEAD COILING DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Insulated service doors.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for miscellaneous steel supports.
1.2 ACTION SUBMITTALS
A. Product Data: For each type and size of overhead coiling door and accessory.
1. Include construction details, material descriptions, dimensions of individual components, profiles for slats, and finishes.
2. Include rated capacities, operating characteristics, electrical characteristics, and furnished accessories.
3. Include description of automatic closing device and testing and resetting instructions.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data.
1. Include plans, elevations, sections, and mounting details.
2. Include details of equipment assemblies, and indicate dimensions, required clearances, method of field assembly, components, and location and size of each field connection.
3. Include points of attachment and their corresponding static and dynamic loads imposed on structure.
4. For exterior components, include details of provisions for assembly expansion and contraction and for excluding and draining moisture to the exterior.
5. Show locations of controls, locking devices, and other accessories.
6. Include diagrams for power, signal, and control wiring.
C. Samples for Initial Selection: Manufacturer's finish charts showing full range of colors and textures available for units with factory-applied finishes.
1. Include similar Samples of accessories involving color selection.
1.3 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 1
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
FJRP052995 SMALL AIR TERMINAL
FJRP199040 AIR DROP FACILITY
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For overhead coiling doors to include in maintenance manuals.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer for both installation and maintenance of units required for this Project.
B. Regulatory Requirements: Comply with applicable provisions in the U.S. Architectural & Transportation Barriers Compliance Board's ADA-ABA Accessibility Guidelines .
PART 2 - PRODUCTS
2.1 MANUFACTURERS, GENERAL
A. Source Limitations: Obtain overhead coiling doors from single source from single manufacturer.
1. Obtain operators and controls from overhead coiling door manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Structural Performance, Exterior Doors: Capable of withstanding the design wind loads.
1. Design Wind Load: Uniform pressure (velocity pressure) of 30 lbf/sq. ft., acting inward and outward.
2. Testing: According to ASTM E 330.
3. Deflection Limits: Design overhead coiling doors to withstand design wind load without evidencing permanent deformation or disengagement of door components.
4. Operability under Wind Load: Design overhead coiling doors to remain operable under design wind load, acting inward and outward.
B. Windborne-Debris Impact Resistance: Provide impact-protective overhead coiling doors that pass missile-impact and cyclic-pressure tests according to ASTM E 1996 for Wind Zone 1.
1. Large-Missile Test: For overhead coiling doors located within 30 feet of grade.
2.3 DOOR ASSEMBLY
A. Insulated Service Door: Overhead coiling door formed with curtain of interlocking metal slats.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 2
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
B. Operation Cycles: Door components and operators capable of operating for not less than 20,000 . One operation cycle is complete when a door is opened from the closed position to the fully open position and returned to the closed position.
C. Air Infiltration: Maximum rate of 0.08 cfm/sq. ft. at 15 and 25 mph when tested according to
ASTM E 283.
D. Curtain R-Value: 8.0 deg F x h x sq. ft./Btu.
E. Door Curtain Material: Galvanized steel.
F. Door Curtain Slats: Flat profile slats of 1-7/8-inch to 3-1/4-inch center-to-center height.
1. Insulated-Slat Interior Facing: Metal.
2. Gasket Seal. Manufacturer's standard continuous gaskets between slats.
G. Bottom Bar: Two angles, each not less than 1-1/2 by 1-1/2 by 1/8 inch thick; fabricated from hot-dip galvanized steel and finished to match door.
H. Curtain Jamb Guides: Galvanized steel with exposed finish matching curtain slats.
I. Hood: Match curtain material and finish.
1. Shape: Square.
2. Mounting: Face of wall.
J. Locking Devices: Equip door with slide bolt for padlock .
K. Electric Door Operator:
1. Usage Classification: Light duty, up to 10 cycles per hour.
2. Operator Location: Top of hood.
3. Motor Exposure: Interior.
4. Emergency Manual Operation: Chain type.
5. Obstruction-Detection Device: Automatic electric sensor edge on bottom bar.
a. Sensor Edge Bulb Color: Black.
6. Control Station(s): Interior mounted .
L. Curtain Accessories: Equip door with weatherseals.
M. Door Finish:
1. Powder-Coated Finish: Color as selected by Architect from manufacturer's full range.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 3
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
2.4 MATERIALS, GENERAL
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.5 DOOR CURTAIN MATERIALS AND CONSTRUCTION
A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to withstand wind loading indicated, in a continuous length for width of door without splices.
Unless otherwise indicated, provide slats of thickness and mechanical properties recommended by door manufacturer for performance, size, and type of door indicated, and as follows:
1. Steel Door Curtain Slats: Zinc-coated (galvanized), cold-rolled structural steel sheet;
complying with ASTM A 653/A 653M, with G90 zinc coating; nominal sheet thickness (coated) of 0.028 inch; and as required.
2. Insulation: Fill slats for insulated doors with manufacturer's standard thermal insulation complying with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E 84 or UL 723. Enclose insulation completely within slat faces.
3. Metal Interior Curtain-Slat Facing: Match metal of exterior curtain-slat face, with minimum steel thickness of 0.010 inch.
B. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes for guide adjustment. Provide removable stops on guides to prevent overtravel of curtain, and a continuous bar for holding windlocks.
2.6 HOODS
A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to prevent sagging.
1. Galvanized Steel: Nominal 0.028-inch- thick, hot-dip galvanized steel sheet with G90 zinc coating, complying with ASTM A 653/A 653M.
2.7 LOCKING DEVICES
A. Slide Bolt: Fabricate with side-locking bolts to engage through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 4
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
B. Safety Interlock Switch: Equip power-operated doors with safety interlock switch to disengage power supply when door is locked.
2.8 CURTAIN ACCESSORIES
A. Weatherseals for Exterior Doors: Equip each exterior door with weather-stripping gaskets fitted to entire exterior perimeter of door for a weather-resistant installation unless otherwise indicated.
1. At door head, use 1/8-inch- thick, replaceable, continuous-sheet baffle secured to inside of hood or field- installed on the header.
2. At door jambs, use replaceable, adjustable, continuous, flexible, 1/8-inch- thick seals of flexible vinyl, rubber, or neoprene.
2.9 COUNTERBALANCING MECHANISM
A. General: Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed bearings or self-lubricating graphite bearings for rotating members.
B. Counterbalance Barrel: Fabricate spring barrel of manufacturer's standard hot-formed, structural-quality, seamless or welded carbon-steel pipe, of sufficient diameter and wall thickness to support rolled-up curtain without distortion of slats and to limit barrel deflection to not more than 0.03 in./ft. of span under full load.
C. Counterbalance Spring: One or more oil-tempered, heat-treated steel helical torsion springs.
Size springs to counterbalance weight of curtain, with uniform adjustment accessible from outside barrel. Secure ends of springs to barrel and shaft with cast-steel barrel plugs.
D. Torsion Rod for Counterbalance Shaft: Fabricate of manufacturer's standard cold-rolled steel, sized to hold fixed spring ends and carry torsional load.
E. Brackets: Manufacturer's standard mounting brackets of either cast iron or cold-rolled steel plate.
2.10 ELECTRIC DOOR OPERATORS
A. General: Electric door operator assembly of size and capacity recommended and provided by door manufacturer for door and operation-cycles requirement specified, with electric motor and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake, clutch, control stations, control devices, integral gearing for locking door, and accessories required for proper operation.
1. Comply with NFPA 70.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 5
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
2. Control equipment complying with NEMA ICS 1, NEMA ICS 2, and NEMA ICS 6, with NFPA 70 Class 2 control circuit, maximum 24-V ac or dc.
B. Usage Classification: Electric operator and components capable of operating for not less than number of cycles per hour indicated for each door.
C. Door Operator Location(s): Operator location indicated for each door.
1. Top-of-Hood Mounted: Operator is mounted to the right or left door head plate with the operator on top of the door-hood assembly and connected to the door drive shaft with drive chain and sprockets. Headroom is required for this type of mounting.
D. Motors: Reversible-type motor with controller (disconnect switch) for motor exposure indicated.
1. Electrical Characteristics:
a. Phase: Polyphase.
b. Volts: 460 V.
c. Hertz: 60.
2. Motor Size: Minimum size as indicated. If not indicated, large enough to start, accelerate, and operate door in either direction from any position, at a speed not less than 8 in./sec. and not more than 12 in./sec., without exceeding nameplate ratings or service factor.
3. Operating Controls, Controllers, Disconnect Switches, Wiring Devices, and Wiring:
Manufacturer's standard unless otherwise indicated.
4. Coordinate wiring requirements and electrical characteristics of motors and other electrical devices with building electrical system and each location where installed.
E. Limit Switches: Equip each motorized door with adjustable switches interlocked with motor controls and set to automatically stop door at fully opened and fully closed positions.
F. Obstruction Detection Devices: External entrapment protection consisting of indicated automatic safety sensor capable of protecting full width of door opening. For non-fire-rated doors, activation of device immediately stops and reverses downward door travel.
1. Electric Sensor Edge: Automatic safety sensor edge, located within astragal or weather stripping mounted to bottom bar. Contact with sensor activates device. Connect to control circuit using manufacturer's standard take-up reel or self-coiling cable.
G. Control Station: Three-button control station in fixed location with momentary-contact push-button controls labeled "Open" and "Stop" and sustained- or constant-pressure push-button control labeled "Close."
1. Interior-Mounted Units: Full-guarded, surface-mounted, heavy-duty type, with general-purpose NEMA ICS 6, Type 1 enclosure.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 6
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
H. Emergency Manual Operation: Equip each electrically powered door with capability for emergency manual operation. Design manual mechanism so required force for door operation does not exceed 25 lbf.
I. Emergency Operation Disconnect Device: Equip operator with hand-operated disconnect mechanism for automatically engaging manual operator and releasing brake for emergency manual operation while disconnecting motor without affecting timing of limit switch. Mount mechanism so it is accessible from floor level. Include interlock device to automatically prevent motor from operating when emergency operator is engaged.
J. Motor Removal: Design operator so motor may be removed without disturbing limit-switch adjustment and without affecting emergency manual operation.
2.11 GENERAL FINISH REQUIREMENTS
A. Comply with NAAMM/NOMMA's "Metal Finishes Manual for Architectural and Metal Products (AMP 500-06)" for recommendations for applying and designating finishes.
B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
2.12 STEEL AND GALVANIZED-STEEL FINISHES
A. Powder-Coat Finish: Manufacturer's standard baked-on finish consisting of prime coat and thermosetting topcoat. Comply with coating manufacturer's written instructions for cleaning, pretreatment, application, and minimum dry film thickness.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates areas and conditions, with Installer present, for compliance with requirements for substrate construction and other conditions affecting performance of the Work.
B. Examine locations of electrical connections.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install overhead coiling doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manufacturer's written instructions and as specified.
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 7
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
B. Install overhead coiling doors, hoods, controls, and operators at the mounting locations indicated for each door.
C. Accessibility: Install overhead coiling doors, switches, and controls along accessible routes in compliance with regulatory requirements for accessibility.
D. Power-Operated Doors: Install according to UL 325.
3.3 STARTUP SERVICE
A. Engage a factory-authorized service representative to perform startup service.
1. Perform installation and startup checks according to manufacturer's written instructions.
2. Test and adjust controls and safety devices. Replace damaged and malfunctioning controls and equipment.
3.4 ADJUSTING
A. Adjust hardware and moving parts to function smoothly so that doors operate easily, free of warp, twist, or distortion.
1. Adjust exterior doors and components to be weather-resistant.
B. Lubricate bearings and sliding parts as recommended by manufacturer.
C. Adjust seals to provide tight fit around entire perimeter.
3.5 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain overhead coiling doors.
END OF SECTION 083323
Addendum #4 July 9, 2021
OVERHEAD COILING DOORS
083323 - 8
NORTH CAROLINA ANG
CHARLOTTE, NC VOLUME 2 OF 4
UP
FIRE
COMM
102CORRIDOR
ELEC
UNISEX
RAMP
CARGO
FLEET STOR
JOINT
INSPECTION
LOCKERS
PPE
TRAINING
BAG
FLEET
OFFICE
117 COFFEE
JAN
ELEV
BAGGAGE
SCAN
CORRIDOR
FLEET
WORK
MEN
WOMEN
STAIR #1
PALLET
BUILD-UP
LAV TRUCK
CIRCULATION
Hoistway Req.
Depth Min. 6'-11" Width Min. 8'-6"
BAGGAGE
CHECK-IN
PASSENGER
HOLDING
TRAVEL DISTANCE (41'-0")
TRAVEL DISTANCE(70'-0")
TRAVEL DISTANCE
(58'-0")
TRAVEL DISTANCE (73'-0")
TRAVEL DISTANCE (88'-0")
TRAVEL DISTANCE (105'-0")
PASSENGER
HOLDING
STERILE
H
R
H R
1 HR
H
R
H
R
1 HR
3 2
CORRIDOR
BAGGAGE
SCAN
PUMP ROOM
132 1
1 HR
1 HR
H
R
H R
1 HR1 HR
H
R
H R
H
R
H R
BAGGAGE /
PALLET
COMMON PATH
(50'-0")
LIFE SAFETY LEGEND
ONE HOUR FIRE BARRIER1 HR
38'-0"
TRAVEL
DISTANCE
DENOTES
EXIT ROUTE
DENOTES
BUILDING EXIT
BREAK POINT
OCCUPANT LOAD NUMBER
AT EXIT COMPONENT
EXIT COMPONENT MAXIMUM
OCCUPANT CAPACITY NUMBER
# OCCUPANT LOAD FACTOR PER
UFC 3-600-01, TABLE 10-1
CLEAN AGENT TYPE FIRE EXTINGUISHER -
WALL BRACKET
MOUNTED AT 54" AFF
MULTI-PURPOSE TYPE FIRE EXTINGUISHER -
SEMI-RECESSED
MOUNTED AT 54" AFF
MULTI-PURPOSE TYPE FIRE EXTINGUISHER -
WALL BRACKET
MOUNTED AT 54" AFF
PLUMBING FIXTURES
FIXTURE TYPE REQ. #
BUSINESS (B) - 38 OCCUPANTS
W.C. (MEN)
W.C. (WOMEN)
LAV. (MEN)
LAV. (WOMEN)
TOTALS (ROUND UP)
W.C. (MEN) 0.39+0.76+0.06 2
W.C. (WOMEN) UNISEX
LAV. (MEN)
LAV. (WOMEN) UNISEX
D.F. 1
SERVICE SINK
STORAGE AND MECHANICAL- [(S-1)] - 12 OCCUPANTS
W.C. (MEN) 1 PER 100 0.06
W.C. (WOMEN)
LAV. (MEN)
LAV. (WOMEN)
IBC 2018 TABLE 403.1
LOAD FACTOR (LF) (OCC/LF)
1 PER 100
1 PER 100
1 PER 100
(6/100)
1 PER 25 FOR FIRST(50) (19/25) 0.76
0.48
1.21
(19/40) 0.48
ACTUAL
CALC.
3+2 UR
0.25+0.48+0.06 1
0.8
1 PER 25 FOR FIRST(50)
1 PER 40 FOR FIRST(80)
1 PER 40 FOR FIRST(80)
0.75+0.76+0.06 1.57
0.25+0.48+0.06 0.8
0.06
0.06
0.06
(19/40)
(19/25) 0.76
(6/100)
(6/100)
(6/100)
ASSEMBLY (A) - 98 OCCUPANTS
W.C. (MEN)
W.C. (WOMEN)
LAV. (MEN)
LAV. (WOMEN)
1 PER 125 (49/125) 0.39
0.25
(49/200) 0.25
1 PER 65
1 PER 200
1 PER 200
(49/200)
(49/65) 0.75
CORR
DCC
ADMIN
IDO
SIPR
ATOC
UNISEX
UNISEX
CONF
CORR
216SUPERVISOR
/ MANAGER
CORR
TO LIBRARY
/ HOTEL / QC
BREAKRM
LOAD
PLANNING
CORR
CORRIDOR
ADMIN
MECH.
STAIR #1
ELEV
OPEN TO BELOW
ROOF BELOW
TRAVEL DISTANCE (89'-8")
TRAVEL DISTANCE (90'-8")
TRAVEL DISTANCE
(32'-0")
(49'-0")
H
R
H R
1 HR
H
R
H
R
1 HR
1 1
2 2
STAIR IS NOT AN ACCESSIBLE MEANS OF
EGRESS. ACTUAL STAIR LOAD IS 25
OCCUPANTS. STAIR WIDTH IS 38". THIS
INCLUDES HANDRAIL PROTRUSION IN
CLEARANCE DIMENSION. STAIR IS IN
COMPLIANCE WITH IBC 2018, SECTION
1011.2, EXCEPTION 1.
COMMON
PATH
(40'-0")
COMMON
PATH
(29'-0")
ROOMS SHALL BE CLASSIFIED AS
BUSINESS PER 2018 IBC, CHAPTER 3,
SECTION 303, PARAGRAPH 303.1.2,
OCCUPANCY LEGEND
ASSEMBLY
BUSINESS
STORAGE
UNOCCUPIED
4930 MINUTEMAN WAY
CHARLOTTE, NC 28208
2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com
Architecture Engineering Planning Frankfurt Short Bruza / Texas
817.588.3010
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
MAY 29, 2020
20180720
LLP
P ro je c t
N o
F
J R
P
C h a rl o tt e A
N G
B a s e C
D
IA
N
C
N o rt h
C a ro li n a A ir N a ti o n a l G u a rd
C -1
C o n v e rs io n
A d d
/A lt e r
S m a ll T e rm in a l B ld g
C :\U s e rs \o a e
\D o c u m e n ts
\M y R e v it\8
A rc h
O
E s tra d a
S
Z
.rv t
/9 /2
:5
:2
P
M
CODE AND LIFE SAFETY PLAN
G-101
JMI
OAE
MBP
SCALE 1/8" = 1'-0"
CODE AND LIFE SAFETY GROUND FLOOR PLAN
CODE SUMMARY
USE AND OCCUPANCY: (IBC 2018)
INDIVIDUAL CLASSIFICATION OF OCCUPANCY
ASSEMBLY: GROUP A-3 (SECTION 303.4)
BUSINESS: GROUP B (SECTION 304.1)
STORAGE: GROUP S-1 (SECTION 311.1)
PRELIMINARY CODE ANALYSIS BASED ON NON
SEPARATED MIXED USE OCCUPANCY USING THE MOST
RESTRICTIVE OCCUPANCY CLASSIFICATION S-1
(508.3.2)
OCCUPANCY GROUP(S) (NFPA 101-2018):
INDIVIDUAL CLASSIFICATION OF OCCUPANCIES:
ASSEMBLY (SECTION 6.1.2)
BUSINESS (SECTION 6.1.11)
STORAGE- ORDINARY HAZARD (SECTION 6.1.13)
TYPE OF CONTRUCTION (IBC 2018 TABLE 601):
TYPE II-B WITH SPRINKLER SYSTEM
ALLOWABLE HEIGHT (IBC 2018):
75 FT PER TABLE 504.3
ACTUAL HEIGHT: 28'-4" FT
ALLOWABLE AREA (IBC 2018):
PER SECTION 507.5, 507.6 UNLIMITED AREA FOR TWO
STORY
SPRINKLERED GROUP A, B AND S.
ACTUAL AREA: 15,243 GSF
SCALE 1/8" = 1'-0"
CODE AND LIFE SAFETY SECOND FLOOR PLAN
0 4' 8' 16'
1/8" = 1'-0"
N
1 ADDENDUM #1 03/03/2021
2 ADDENDUM #4 07/09/2021
Frankfurt-Short-Bruza Architects Engineers Planners document1 Page 1 of 1 5801 Broadway Extension, Suite 500, Oklahoma City, Oklahoma 73118-7436
Telephone (405) 840-2931 Facsimile (405) 842-7750 Website www.fsb-ae.com
11949
SF202
SF202
SF202
SF202
A A
BB
CC
DD
EE
FF
15'-11" 15'-11" 15'-11" 15'-11" 14'-7" 2'-8" 17'-3" 10" 20'-3" 25'-1"
/8
/2
8"
11 1/2"
7 1/2"
/2
/2
8"
SB301
SB301
3 3
EXISTING SPOT
FOOTING TYP
EXISTING
CONTINUOUS
FOOTING TYP
SB501
SB501
SB501
SB501
H S S 4X
4X 1/
B P 1 H
S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P
F
H S S 4X
4X 1/
B P
F
F2
F2
H S S 4X
4X 1/
B P 2 H
S S 4X
4X 1/
B P
H S S 6X
6X 1/
B P13
F3
F2 F2
H S S 6X6X1/4
BP7 F3
H S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P 6 H
S S 4X
4X 1/
B P 6 H
S S 4X
4X 1/
B P
H S S 4X
4X 5/
B P
F
H S S 4X
4X 1/
B P
F
H S S 4X
4X 1/
B P
F
H S S 4X
4X 5/
B P
H S S 4X
4X 1/
B P
F
H S S 4X
4X 1/
B P12
F4
H S S 4X
4X 1/
B P 12H
S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P
H S S 4X
4X 1/
B P
/2
2 1/2" 2
/2
/2
7 3/8" 13'-0 5/8" 2'-3"
/2
/8
/2
/2
/2
/8
/2
8'-0 5/8"7 3/8" 15'-3 5/8"
10"
/2
F5 F5
F6F6
7 5/16"
9'-0 11/16" 5'-11"
F7 F7
FOUNDATION PLAN NOTES
1. ALL CMU WALLLS TO SIT ON EXISTING SLAB.
2. EXISTING EXTERIOR STAIR UNDER NEW CANOPY
TO REMAIN AND BE REPAIRED. REFER
ARCHITECTURE.
8" REINFORCED CMU ELEVATOR SHAFT WALL.
FULLY GROUTED WITH #5 VERTICAL BARS AT
16" ON CENTER AND #5 HORIZONTAL IN BOND
BEAM AS INDICATED IN ELEVATOR SHAFT
SECTIONS.
8" REINFORCED CMU WALL. WITH #5 VERTICAL
BARS AT 24" ON CENTER AND #5 HORIZONTAL
IN BOND BEAM AT 4'-0" ON CENTER.
COORDINATE FINAL LOCATIONS WITH
ARCHITECTURE.
EXISTING CMU WALL
REMOVE EXISTING COLUMN. EXISITNG
FOOTING TO REMAIN.
18"x18"x24" DEEP SUMP. LOCATE PER
ELEVATOR MFGR REQUIREMENTS.
REFER DETAIL 1/SF201
REFER DETAIL 2/SF201
REFER DETAIL 3/SF201
REFER DETAIL 1/SF202
6" REINFORCED CMU STAIR SHAFT WALL
FULLY GROUTED WITH #5 VERTICAL BARS
AT 24" OC AND #5 HORIZONTAL BARS IN
BOND BEAMS AT 4'-0" OC.
HELICAL PIER UNDERPINNING WITH BRACKETS
TO EXISTING SPREAD FOOTINGS FOR
ELEVATOR PIT EXCAVATION. PROVIDE 50 KIP
SERVICE LOAD CAPACITY AT EACH SPREAD
FOOTING.
ANTICIPATED EXTENTS OF SLAB DEMOLITION
AND REPLACEMENT FOR ELEVATOR PIT
CONSTRUCTION. CONTRACTOR TO SIZE FOR
SOIL LAY-BACK DURING CONSTRUCTION.
FF
15'-11" 15'-11" 15'-11" 15'-11" 14'-7" 2'-8" 17'-3"
EXISTING
STAIRS TO
REMAIN
11"
3'-0" 6'-0" 11"
EDGE OF BUILDING
2'-6" 2'-6"
12" MAX TOTAL
DEPTH X 8" MAX
WIDTH COL, TYP
ALL FRAME AND
PORTAL COL
SB501
PORTAL FRAME
F7F7F7
F7 F7 F7
EXISTING EXTERIOR CONC
PAVEMENT TO REMAIN
4930 MINUTEMAN WAY
CHARLOTTE, NC 28208
2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com
Architecture Engineering Planning Frankfurt Short Bruza / Texas
817.588.3010
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
MAY 29, 2020
20180720
LLP
P ro je c t
N o
F
J R
P
C h a rl o tt e A
N G
B a s e C
D
IA
N
C
N o rt h
C a ro li n a A ir N a ti o n a l G u a rd
C -1
C o n v e rs io n
A d d
/A lt e r
S m a ll T e rm in a l B ld g
C :\U s e rs
\b a w
\D o cu m e n ts \M y R e v it\8
S tru b w illh o ite .rv t
/8 /2
:2
:3
P
M
FOUNDATION PLAN
SB101
BJW
KAC
BJW
0 4' 8' 16'
1/8" = 1'-0"
N
SCALE 1/8" = 1'-0"
FOUNDATION / SLAB PLAN
SCALE 1/8" = 1'-0"
FOUNDATION / SLAB PLAN
ISOLATED FOOTING SCHEDULE
FOOTING MARK WIDTH LENGTH THICKNESS
F1 5'-6" 5'-6" 2'-0"
F2 4'-0" 4'-0" 2'-0"
F3 5'-0" 10'-6" 1'-2"
F4 2'-0" 3'-0" 1'-2"
F5 1'-6" 8'-0"
F6 4'-0" 10'-6"
F7 5'-0" 5'-0"
1'-6"
1'-2"
NOTES:
1. FOOTING F5 WITH 2 HELICAL PIERS AT 17k EACH
2. EXISTING FOOTING F7 WITH NEW HELICAL PIERS
TO SUPPORT EXISTING FOOTING DURING
ELEVATOR PIT CONSTRUCTION. PROVIDE 50k
TOTAL SUPPORT CAPACITY TO BE LEFT IN PLACE.
HELICAL PIERS TO BE SYMETRIC ABOUT FOUNDATION .
3. PROVIDE (6) #5 REINFORCING BARS EACH WAY IN
BOTTOM OF FOOTING F1.
4. PROVIDE (4) #5 REINFORCING BARS EACH WAY IN
BOTTOM OF FOOTING F2.
5. TOP OF ALL NEW FOOTINGS ARE AT FINISHED FLOOR
ELEVATION IN THIS BUILDING.
2'-6"
1 ADDENDUM #4 07/09/2021
TOP OF SLAB
100'-0"
SECOND FLOOR
FRAMING
111'-4"
ROOF FRAMING
124'-8"
F
3" 1'-7" 7'-8 3/8" 10" 3"
WATERSTOP
TYP
10" CONC WALL
W/ #4 AT 8" OC
HORIZ AND VERT
DEMO EXISTING SLAB
EXIST CONT
FOOTING
24" CONC SLAB W/
#5 BARS AT 12" OC EW
(TOP AND BOT)
8"
118'-8"
122'-0"
EL
EL
EL
1/4"x7 1/2" PLATE W/ 1/2"x16" DBA AT 16" OC
TO MATCH CMU VERTICAL REINF.
PLUG WELD TO EXISTING BEAM WITH
3/4" PLUG WELDS AT 16" OC
110'-8"
108'-0"
EL
EL
128'-0"
C L R
C L R
CLR
3"
MIN
WATERPROOFING
MEMBRANE
#5x2'-0" DOWELS
AT 16" OC EPOXY
6" INTO EXIST
GRADE BEAM
1'-7" CONC WALL
TO MATCH EXIST
GRADE BEAM WIDTH
#4 BARS AT 8" OC
HORIZ AND VERT
#4 DOWELS
AT 16" OC
20"
SAW CUT OPENING
IN EXIST SLAB FOR
PIT EXCAVATION
REPLACE INTERIOR SLAB
WITH 6" CONC W/ #4 @ 16" OC
EW ON VAPOR RETARDER
OVER 6" SAND FILL
GROUT FILL NOTCH TO
MAKE SLOPING LEDGE
L5x3-1/2x5/16" W/
1/2" Ø EPOXY ANCHORS
AT 16" OC (5" EMBED)
TO SUPPORT DECK
# 4 DWLS x 1'-6" @ 16" OC
EPOXY 6" INTO EXISTING SLAB
(TYP AT SLAB REPLACEMENT)
15.00°
L3x3x3/16" W/
1/2" Ø EPOXY ANCHORS
AT 16" OC AT ALL 4 WALLS
(5" EMBED)
CREAT NEW JOIST SEAT
PER 6/SF502
GROUT CMU WALL
SOLID AROUND JOIST
CUT JOIST FLUSH WITH CMU WALL
AFTER JOIST WEB MEMBERS ARE
ADDED AND WALL IS CONSTRUCTED
REMOVE OLD
JOIST END
AFTER JOIST IS
SUPPORTED ON
NEW CMU WALL
TOP OF SLAB
100'-0"
SECOND FLOOR
FRAMING
111'-4"
ROOF FRAMING
124'-8"
4 5
3" 10"
EXISTING CONC
SLAB TYP
CMU ELEVATOR
SHAFT WALL
REFER PLAN TYP
WATERSTOP TYP
10" CONC WALL W/
#6 BARS AT 12" OC
VERT EACH FACE
W/ (2) #4 BARS AT
10" OC HORIZ TYP
DEMO EXISTING SLAB
30" CONC SLAB W/
#6 BARS AT 12" OC
EACH WAY TOP
AND BOTTOM
2'-3" 8'-8 3/4" 4'-11 1/4"
3"10"
128'-0"
126'-0"
122'-0"
119'-4"
115'-4"
110'-8"
108'-0"
104'-0"
124'-0"
EL
EL
EL
EL
EL
EL
EL
EL
EL
L3x3x3/16" W/
1/2" Ø EPOXY ANCHORS
AT 16" OC AT ALL 4 WALLS
(5" EMBED)
PL 6x6x3/8" W/
(2) 3/8" x4" HSA AT EACH
ROOF BEAM BEARING
WELD TO BEAM
3/16 3
L3x3x3/16" W/
1/2" Ø EPOXY ANCHORS
AT 16" OC (5" EMBED)
#4 DOWELS
AT 16" OC
20"
SAW CUT OPENING
IN EXIST SLAB FOR
PIT EXCAVATION
REPLACE INTERIOR SLAB
WITH 6" CONC W/ #4 REINF @ 16" O.C.E.W.
ON VAPOR RETARDER OVER 6" SAND FILL
# 4 DWLS x 1'-6" @ 16" O.C.
EPOXY 6" INTO EXISTING SLAB
(TYP AT SLAB REPLACEMENT)
WATERPROOFING
MEMBRANE
1'-6"
NOTE: PIT LADDER SUPPLIED
AND INSTALLED BY
ELEVATOR SUPPLIER.
1" BAR GRATING OVER SUMP.
SUMP EDGE FRAMING
L1-1/4"x1-1/4"x1/4" W/ 3/8" Ø x 4" HSA AT 12" OC
#5 X 3'-4" DOWELS @ 16" O.C. AT
ELEVATOR SHAFT WALLS. EMBED 1'-4"
BELOW FF ELEVATION.1
4930 MINUTEMAN WAY
CHARLOTTE, NC 28208
2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com
Architecture Engineering Planning Frankfurt Short Bruza / Texas
817.588.3010
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
MAY 29, 2020
20180720
LLP
P ro je c t
N o
F
J R
P
C h a rl o tt e A
N G
B a s e C
D
IA
N
C
N o rt h
C a ro li n a A ir N a ti o n a l G u a rd
C -1
C o n v e rs io n
A d d
/A lt e r
S m a ll T e rm in a l B ld g
C :\U s e rs
\b a w
\D o cu m e n ts \M y R e v it\8
S tru b w illh o ite .rv t
/8 /2
:2
:4
P
M
FOUNDATION DETAILS
SB301
BJW
KAC
BJW
SCALE 3/4" = 1'-0"
SECTION THROUGH ELEVATOR PIT
1 SCALE 3/4" = 1'-0"
SECTION THROUGH ELEVATOR PIT
1' 3'2'0
3/4" = 1'-0"
1 ADDENDUM #4 07/09/2021
24" LONG DOWELS, SIZE AND SPACING
TO MATCH VERTICAL REINFORCING OF
NEW CMU WALLS. EPOXY INTO SLAB
(4" EMBED). TYP EXCEPT AT ELEVATOR
SHAFT WALLS.
TOP OF SLAB
100'-0"
SF201
ROOF FRAMING
111'-6 1/2"
FIELD VERIFY
M
IN
V E
R
IF
Y
F
IE
L D
R O
COORD W/ ARCH
3'-4" RO
HSS4X4X3/16
H S
S X
X
/1
H S
S X
X
/1
EXISTING ROOF
FRAMING
3/16
TYP
TOP OF SLAB
100'-0"
SECOND FLOOR
FRAMING
111'-4"
SF201
M A
X
V E
R
IF
Y
F
IE
L D
R O
COORD W/ ARCH
6'-4" RO
EXISTING ROOF
FRAMING
HSS8X8X3/16
H S
S X
X
/1
H S
S X
X
/1
3/16
TYP
TOP OF SLAB
100'-0"
F
ROOF FRAMING
111'-6 1/2"
FIELD VERIFY
VERIFY
11"
FIELD
M A
X
V E
R
IF
Y
F
IE
L D
VERIFY
6 1/2"
FIELD
1/2"
M
IN
EXISTING PRECAST
WALL PANEL
EXISTING ROOF
AND FRAMING
1/4"x4" PLATE
(NS ONLY)
1/8" BENT PLATE
CLOSURE
3/16
TYP
TYP
2 @12
TYP
TYP
1/2 12
TYP
L3x3x1/4x4" W/
3/4" DIA HILTI
HAS HAD ROD
AND HILTI
HY-200 EPOXY
(OR EQUAL)
EMBED 4"
TOP OF SLAB
100'-0"
SF201
ROOF FRAMING
111'-6 1/2"
FIELD VERIFY
R O
V E
R
IF
Y
F
IE
L D
M A
X
COORD W/ ARCH
3'-4" RO
HSS4X4X3/16
H S
S X
X
/1
H S
S X
X
/1
EXISTING ROOF
FRAMING
3/16
TYP
TOP OF SLAB
100'-0"
B
ROOF FRAMING
111'-6 1/2"
FIELD VERIFY
VERIFY
11"
FIELD
M A
X
V E
R
IF
Y
F
IE
L D
2" 8" 1"
M
IN
EXISTING PRECAST
WALL PANEL
EXISTING ROOF
AND FRAMING
1/4"x4" PLATE
(NS ONLY)
NEW BRICK AS
REQ'D
3/16
TYP
TYP
TYP
3/16 2 @12
TYP
2 @12
TYP
1/4" PLATE LINTEL
L3x3x1/4x4" W/ 3/4"
DIA HILTI HAS
ROD AND HILTI
HY-200 EPOXY
(OR EQUAL)
EMBED 4"
TOP OF SLAB
100'-0"
SECOND FLOOR
FRAMING
111'-4"
F
VERIFY
11"
FIELD
M A
X
V E
R
IF
Y
F
IE
L D
4" 6"
M
IN
EXISTING PRECAST
WALL PANEL
EXISTING FLOOR
AND FRAMING
1/4"x4" PLATE
(NS ONLY)
NEW BRICK AS
REQ'D
3/16
TYP
2@12
TYP
TYP
3/16 2 @12
TYP
1/4" PLATE LINTEL
L3x3x1/4x4" W/ 3/4"
DIA HILTI HAS
ROD AND HILTI
HY-200 EPOXY
(OR EQUAL)
EMBED 4"
4930 MINUTEMAN WAY
CHARLOTTE, NC 28208
2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com
Architecture Engineering Planning Frankfurt Short Bruza / Texas
817.588.3010
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
MAY 29, 2020
20180720
LLP
P ro je c t
N o
F
J R
P
C h a rl o tt e A
N G
B a s e C
D
IA
N
C
N o rt h
C a ro li n a A ir N a ti o n a l G u a rd
C -1
C o n v e rs io n
A d d
/A lt e r
S m a ll T e rm in a l B ld g
C :\U s e rs
\b a w
\D o cu m e n ts \M y R e v it\8
S tru b w illh o ite .rv t
/8 /2
:2
:4
P
M
FRAMING ELEVATIONS
SF201
BJW
KAC
BJW
SCALE 3/4" = 1'-0"
FRAMING ELEVATION
1' 3'2'0
3/4" = 1'-0"
SCALE 3/4" = 1'-0"
FRAMING ELEVATION
SCALE 1" = 1'-0"
SECTION DETAIL
SCALE 3/4" = 1'-0"
FRAMING ELEVATION
SCALE 1" = 1'-0"
SECTION DETAIL
SCALE 1" = 1'-0"
SECTION DETAIL
0 6" 1' 2'
1" = 1'-0"
1 ADDENDUM #4 07/09/2021
SECOND FLOOR
FRAMING
111'-4"
F
10"
8"
/2
/2
B E
A M
B O
N D
B E
A M
B O
N D x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PLATE
EDGE ANGLE
9"5
/2
EXISTING 8" CMU
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXIST
GROUTED CELLS
EMBED 4"
(2) ADD'L #5 VERT
AT BEAM BEARING
#4 BENT DOWEL
AT 24" OC
ALT HOOK DIR
20"
3/16
TYP
3/4"x6"x8" BEARING PL W/ (2) 1/2" Ø x12" DBA
3/16 2 AT 12
TYP
GROUT
SOLID
STEEL BEAMS
REFER PLAN
1/4" WEB STIFF PL
(NS AND FS)
CONC SLAB REFER PLAN
ANCHOR TO CMU W/ (1)
1/4" TAPCON AT 12" OC
AS REQ"D
x
SF501
SECOND FLOOR
FRAMING
111'-4"
F
2 1/2"
7 1/2" x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PLATE
EDGE ANGLE
/2
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXIST
GROUTED CELLS
EMBED 4"
3/16 2 AT 12
TYP
EXISTING 8" CMU
AND COLUMN
HSS COLUMN
REFER PLAN
REFER TYPICAL
CONNX DETAILS
STEEL BEAMS
REFER PLAN
CONC SLAB
REFER SLAB
9"5
/2
SECOND FLOOR
FRAMING
111'-4"
7 1/2" x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PLATE
EDGE ANGLE
6 1/2"5
/2
EXISTING 8" CMU
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXIST
GROUTED CELLS
EMBED 4"
#4 BENT DOWEL
AT 24" OC
ALT HOOK DIR
20"
3/16 2 AT 12
TYP
CONC SLAB REFER PLAN
ANCHOR TO CMU W/ (1)
1/4" TAPCON AT 12" OC
AS REQ'D
x
/2
/2
B E
A M
B O
N D
B E
A M
B O
N D
HSS COLUMN
REFER PLAN
STEEL BM
REFER PLAN
BLOCKOIUT WALL (BEYOND)
AS REQ'D FOR BEAM (BEYOND)
AND GROUT SOLID
REFER TO TYPICAL
CONNX DETAILS
NEW 8" CMU
BEYOND
SECOND FLOOR
FRAMING
111'-4"
4"
/2 x x x
3/16 2 AT 12
TYP
1/4" CONT BENT PL
EDGE ANGLE
4"
/2
CONC SLAB
REFER PLAN
STEEL BEAM
REFER PLAN
REFER TO TYPICAL
CONNX DETAILS
1/2" Ø x 1'-6" DBA
LOCATED EACH
SLEEVE MOUNT
1 1/2" Ø STD PIPE
REMOVABLE GUARDRAIL
SYSTEM REFER ARCH
2" Ø STD PIPE SLEEVE
MOUNT W/ 1/2" Ø THRU BOLT
CAP BOT OF SLEEVE
TYP
HSS COLUMN
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
7 5/8" 2 1/2" 7 1/2"
/2
/8
B E
A M
B O
N D
B E
A M
B O
N D x x x
CONC SLAB
REFER PLAN
x
1/4" CONT BENT PL
EDGE ANGLE W/
1/2" Ø x1'-6" DBA
AT 24" OC
7"
/2
STEEL BEAM
REFER PLAN
REFER TO TYPICAL
CONNX DETAILS
HSS COLUMN
REFER PLAN
EXTEND VERT REINF
TO TOP OF WALL
8" CMU WALL
5/8" X 1'-6" THREADED ROD @ 24"
O.C. THRU STD HOLES IN BENT
PLATE. POST-INSTALL INTO CMU
WITH EPOXY (16" EMBED).
SECOND FLOOR
FRAMING
111'-4"
1'-6" 1'-6"
/2 x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PL
EDGE ANGLE
17"
/2
3/16 2 AT 12
TYP CONC SLAB
REFER PLAN
x
1/2" Ø x 3'-0" DBA
AT 24" OC
STEEL BEAM
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
6 1/4" x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PL
EDGE ANGLE
5 1/2"
/2
3/16 2 AT 12
TYP CONC SLAB
REFER PLAN
x
/2
STEEL BEAM
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
7 1/2"5 5/8"7'-9 7/16"3 13/16"
/2
/2
1/2"
1 1/2"
2"
/2
/2
/2
(2) 3/4" Ø HAS ROD W/
HY-200 EPOXY (OR EQUAL)
IN GROUTED CELLS
BOTH WALLS
EMBED 4"
(2) 3/4" Ø
A325 BOLTS
L4x4x1/4
STRIP BEAM FLNG'S
AS REQ'D
CONT 1/4" BENT PL
EDGE ANGLE
STEEM BEAM
REFER PLAN
/2
/2
/2
/2 x x x
3/4"x4" HEADED STUD
REFER PLAN
3/16 2 AT 12
TYP
CONC SLAB
REFER PLAN
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXISTING
GROUTED CELLS
EMBED 4"
1/4" CONT BENT PL
EDGE ANGLE
7"
/2
STEEL BEAM
REFER PLAN
EXISTING 8" CMU
NEW 6" CMU
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
10" x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PL
EDGE ANGLE
9"
/2
3/16 2 AT 12
TYP CONC SLAB
REFER PLAN
x
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXIST
GROUTED CELLS
EMBED 4"
/2
STEEL BEAM
REFER PLAN
REFER TO TYPICAL
CONNX DETAILS
EXIST ROOF
FRAMING BEYOND
EXISTING CMU
HSS COLUMN
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
C
10" x x x
3/4"x4" HEADED STUD
REFER PLAN
1/4" CONT BENT PL
EDGE ANGLE
9"
/2
3/16 2 AT 12
TYP CONC SLAB
REFER PLAN
x
3/4" HAS ROD W/ HY-200
EPOXY (OR EQUAL)
AT 24" OC IN EXIST
GROUTED CELLS
EMBED 4"
STEEL BEAM
REFER PLAN
EXISTING WALL AND
FLOOR FRAMING
SECOND FLOOR
FRAMING
111'-4"
7 1/2"VERIFY
4"
/2 x x x
3/4"x4" HEADED STUD
REFER PLAN
3/16 2 AT 12
TYP
1/4" CONT BENT PL
EDGE ANGLE
6 1/2"
/2
CONC SLAB
REFER PLAN
EXISTING FLOOR
FRAMING
NOTE
CONTRACTOR TO
VERIFY SLAB EDGE
LOCATION
STEEL BEAM
REFER PLAN
REFER TO TYPICAL
CONNX DETAILS
SECOND FLOOR
FRAMING
111'-4"
B
/2 x x x x
STEEL BEAM
REFER PLAN
STEEL BEAM
REFER PLAN
HSS COLUMN
REFER PLAN
REFER TO TYPICAL
CONNX DETAILS
3/4"x4" HEADED STUD
REFER PLAN
CONC SLAB
REFER PLAN
SECOND FLOOR
FRAMING
111'-4"
7 5/8" 7 1/2"
/2 x x x x
1/4" CONT BENT PL
EDGE ANGLE W/
1/2" Ø x1'-6" DBA
AT 24" OC
14"
/2
ELEVATOR DOOR
SUPPORT AS REQ'D
BY MANUF
CMU JAMB AT
ELEVATOR DOOR
8" SOLID GROUTED CMU
REFER TO DETAILS FOR
VERT REINF AND BOND
BEAM LOCATIONS
3/16 2 AT 12
TYP CONC SLAB
REFER SLAB
3/4"x4" HEADED STUD
REFER PLAN
3/4" Ø HAS ROD W/ HY-200
EPOXY (OR EQUAL) AT 24" OC
IN GROUTED CELLS BEYOND
EMBED 4"
1/4" BENT PL EDGE
ANGLE (BEYOND)
6 1/2"
/2
SECOND FLOOR
FRAMING
111'-4"
/2
/2 "3
1/2"
1 1/2"
2" x x x
5 1/2"
/2
3/16
TYP CONC SLAB
REFER SLAB
3/4"x4" HEADED STUD
REFER PLAN
3/4" Ø HAS ROD W/ HY-200
EPOXY (OR EQUAL) AT 24" OC
IN GROUTED CELLS
EMBED 4"
1/4" CONT BENT PL
EDGE ANGLE
8" SOLID GROUTED CMU
REFER TO DETAILS FOR
VERT REINF AND BOND
BEAM LOCATIONS
/2
/2
/2
(2) 3/4" Ø HAS ROD W/
HY-200 EPOXY (OR EQUAL)
IN GROUTED CELLS
EMBED 4"
STEEL BEAM
REFER PLAN
(2) 3/4" Ø
A325 BOLTS
L4x4x1/4
STRIP BEAM FLNG'S
AS REQ'D
SECOND FLOOR
FRAMING
111'-4"
VERIFY
4"
7 1/2"1'-3 1/2"
6 1/2"
/2
3/16 2 AT 12
TYPCONC SLAB
REFER SLAB
1/4" CONT BENT PL
EDGE ANGLE
xxxx
/2
3/4"x4" HEADED STUD
REFER PLAN
EXISTING FLOOR
FRAMING
REFER TO TYPICAL
CONNX DETAILS
STEEL BEAMS
REFER PLANTYP
1 1/2"
TYP
1 1/2"
1/4" FULL HEIGHT
WEB STIFF
(NS AND FS)
HSS COLUMN
REFER PLAN
3/4" CAP PLATE
NOTE
CONTRACTOR TO VERIFY
SLAB EDGE LOCATION
SECOND FLOOR
FRAMING
111'-4"
6"
/2
6"
STEEL BEAM
REFER PLAN
8" BOND BEAM
8" CMU WALL
(2) ADD'L #5 VERT
AT BEAM BEARING
3/16 2 AT 12
TYP
CONC SLAB REFER PLAN
ANCHOR TO CMU W/ (1)
1/4" TAPCON AT 12" OC
AS REQ"DREFER TYPICAL
CONNX DETAILS
GROUT
SOLID
4930 MINUTEMAN WAY
CHARLOTTE, NC 28208
2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com
Architecture Engineering Planning Frankfurt Short Bruza / Texas
817.588.3010
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
MAY 29, 2020
20180720
LLP
P ro je c t
N o
F
J R
P
C h a rl o tt e A
N G
B a s e C
D
IA
N
C
N o rt h
C a ro li n a A ir N a ti o n a l G u a rd
C -1
C o n v e rs io n
A d d
/A lt e r
S m a ll T e rm in a l B ld g
C :\U s e rs
\b a w
\D o cu m e n ts \M y R e v it\8
S tru b w illh o ite .rv t
/8 /2
:2
:4
P
M
FRAMING DETAILS
SF501
BJW
KAC
BJW
SCALE 1" = 1'-0"
FRAMING SECTION
0 6" 1' 2'
1" = 1'-0"
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
SCALE 1" = 1'-0"
FRAMING SECTION
1 ADDENDUM #4 07/09/2021
LOC
5 7 8
C C
D D
MEN
WOMEN
AE401
AE401
A3A3
A3
2'-5 5/8" 4'-2 3/4" 10'-1 1/8" 2'-11 1/4" 2'-11 3/8" 3'-7 1/4" 3'-6" 7'-2 3/8" 2 1/2"
D4
A1
A3
D2
A1
D4D4
A2A2
A3
/4
3'-0" 1" 5'-0"
D4
A2A1
A3
A5
A5
A3 F1
A2
A2A2
A2
D4
D4
A6
A1
A1
1'-11 3/8"4'-11 3/4"D4
/8
/4
/8
A1
1'-6" 1'-6"
1"
1'-6" 1'-6"
/8
6 6
/8
/8
/8
125A124A
9 7/8"
/8
/8
5'-0" 1" 3'-0" 1" 3'-0"
5 5
D4
/4
2'-5 5/8" 1'-4 1/2" 1'-8 1/8" 4'-0 5/8"…