ATTACHMENT 22-DRAWINGS-SAT-VOL 3 OF 4 Fire Protection Plumbing Mechanical 36 pages.pdf

PDF 9 MB Posted

Attached to
145 Airlift Wing Add/Alter Small Air Terminal Building 5
Solicitation number
W50S87-21-B-5005
Issued by

About this file

This solicitation is for the 145 Airlift Wing Addition/Alteration to the Small Air Terminal Building 5 project. Key details include the requirement to add and alter an existing small air terminal to support C-17 aircraft operations. The pre-bid conference will be held on June 2, 2021 and bids are due by June 18, 2021. The project involves the North Carolina Army National Guard and is funded by the Department of the Army. Construction is to be completed by January 2023.

View the file

Other files

File Type Posted
Questions and Answers 15 JULY 2021.pdf PDF
NC ANG SAT ADF Addendum No 4.pdf PDF
Questions and Answers 13 JULY 2021.pdf PDF
W50S87-21-B-5005-0003.pdf PDF
W50S87-21-B-5005 0002.pdf PDF
Amendment 0002 Revised Drawing and Specifications.pdf PDF
Questions and Answers 1 July 2021.docx DOCX document
ATTACHMENT 4 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 4 of 4 258 pages.pdf PDF
ATTACHMENT 21-DRAWINGS-SAT-VOL 2 OF 4 Architecture Interiors 32 pages.pdf PDF
Pre-Bid sign in sheet.pdf PDF
ATTACHMENT 3 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 3 of 4 476 pages.pdf PDF
ATTACHMENT 23-DRAWINGS-SAT-VOL 4 OF 4 Electrical 33 pages.pdf PDF
ATTACHMENT 20- DRAWINGS-SAT-VOL 1 OF 4 General Civil Landscape Structural 28 pages.pdf PDF
ATTACHMENT 18 Drawings ADF - Volume 1 of 2 General Civil Structural 24 pages.pdf PDF
ATTACHMENT 1 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 1 of 4 524 pages.pdf PDF
ATTACHMENT 19 Drawings ADF - Volume 2 of 2 Architecture FP Plumbing 58 pages.pdf PDF
Amendment 0001 Add Alter Small Air Terminal Building 5.pdf PDF
PreBidSlides_W50S87-21-B-5005 Date1 June 2021.pdf PDF
ATTACHMENT 2 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 2 of 4 578 pages.pdf PDF
ATTACHMENT 3 SPECS SAT FJRP052994 ADF FJRP199040 Volume 3 of 4.pdf PDF
ATTACHMENT 11 Brand name justification SAT Monaco Fire alarm trasceiver_Redacted.pdf PDF
ATTACHMENT 14 Pre Bid Conference and Site Visit Bid Drop-Off Map.pdf PDF
ATTACHMENT 1 SPECS SAT FJRP052994 ADF FJRP199040 Volume 1 of 4.pdf PDF
ATTACHMENT 10 Brand name justification SAT Interior and exterior finishes_Redacted.pdf PDF
ATTACHMENT 8 Brand name justification SAT Alerton - Direct Digital Controls_Redacted.pdf PDF
ATTACHMENT 12 Brand name justification SAT Sika Sarnafil PVC roof membrane_Redacted.pdf PDF
ATTACHMENT 7 STATEMENT OF WORK - Add-Alter Small Air Terminal.pdf PDF
W50S87-21-B-5005.pdf PDF
ATTACHMENT 2 SPECS SAT FJRP052994 ADF FJRP199040 Volume 2 of 4.pdf PDF
ATTACHMENT 16 145 AW Contractor Security Guide.pdf PDF
ATTACHMENT 15 145 AW Contractor Safety Guide.pdf PDF
ATTACHMENT 5 DRAWINGS 145 AW Air Drop Facility Vol 1 of 2.pdf PDF
ATTACHMENT 4 SPECS SAT FJRP052994 ADF FJRP199040 Volume 4 of 4.pdf PDF
ATTACHMENT 9 Brand name justification SAT Best Door hardware_Redacted.pdf PDF
ATTACHMENT 6 DRAWINGS 145 AW Air Drop Facility Vol 2 of 2.pdf PDF
ATTACHMENT 13 Visitor Request Worksheet.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C- 17A Globe m aster I II

C-17A Globemaster III

C-1 7A

Globe m as ter I

II

C-17A Globe m aster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III C- 17A Globe m aster I II

C-17A Globemaster III

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II rwall rwall walltank rwall

A I R P O R T D R I V E

HE

RC

UL

ES

Av e rwall rw al l rwall wall tank tank wall

PRIVATE ROAD

SABER DRIVE

BRICK SCR EEN WALL

C O N C.

RE

T AI N

I N G W A

L L

Payne Blvd

Hercules Ave

E n l i st e d

Dr i v e

H e r c ul es A v e

Stair s wall tank tank

Payne Avenue

MORRIS FIELD DRIVE

T

SOUTH ECP

S A

BE

R

DR

IV

E

PROJECT LOCATION

AIR DROP AND BUILDING 5

North Carolina Air National Guard

COMBINED PACKAGE

Charlotte, North Carolina

ISSUE FOR BIDS - MARCH 3, 2021

2000 East Lamar Boulevard, Suite 600 Arlington, Texas 76006

Telephone: 817.588.3010 www.fsb-ae.com

Frankfurt Short Bruza / Texas Architecture Engineering Planning Interior Design

C-17 Conversion: Air Drop Facility Project Number FJRP199040

C-17 Conversion: Small Terminal Project Number FJRP052994

C

-1

AD

AL

A ir

D ro p Fa c

SCALE: 1" = 30'-0"

PROJECT LOCATION1

N

0 30' 60'

THE TWO PROJECTS ISSUED FOR BID UNDER

THIS COVER SHALL BE PRICED INDEPENDENTLY

AS INDICATED ON THE BID SHEETS ISSUED BY

THE NORTH CAROLINA AIR NATIONAL GUARD.

THAT SHALL INCLUDE ANY CHANGES ISSUED

SUBSEQUENTLY DURING THE BIDDING OR

CONSTRUCTION PHASES.

THE LIMITS OF THE WORK FOR PRICING

PURPOSES IS INDICATED WITH EACH PROJECT

SET OF DRAWINGS. HOWEVER, THE WORK SHALL

BE SCHEDULED, PERFORMED AND

COORDINATED AS THOUGH IT WERE A SINGLE

SET OF CONSTRUCTION DOCUMENTS.

050024

C- 17A Globe m aster I II

C-17A Globemaster III

C-1 7A

Globe m as ter I

II

C-17A Globe m aster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III C- 17A Globe m aster I II

C-17A Globemaster III

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II rwall rwall walltank rwall

A I R P O R T D R I V E

HE

RC

UL

ES

Av e rwall rw al l rwall wall tank tank wall

PRIVATE ROAD

SABER DRIVE

BRICK SCR EEN WALL

C O N C.

RE

T AI N

I N G W A

L L

Payne Blvd

Hercules Ave

E n l i st e d

Dr i v e

H e r c ul es A v e

Stair s wall tank tank

Payne Avenue

MORRIS FIELD DRIVE

T

SOUTH ECP

S A

BE

R

DR

IV

E

PROJECT LOCATION

North Carolina Air National Guard C-17 Conversion Add/Alter Small Air Terminal - Building 5

Charlotte, North Carolina Project Number: FJRP 052994

ISSUE FOR BIDS - MARCH 03, 2021

2000 East Lamar Boulevard, Suite 600 Arlington, Texas 76006

Telephone: 817.588.3010 www.fsb-ae.com

Frankfurt Short Bruza / Texas Architecture Engineering Planning Interior Design

NORTH CAROLINA CERTIFICATE

OF AUTHORIZATION

ARCHITECTURE: # 53655

EXP: 12/31/2021

NORTH CAROLINA CERTIFICATE

OF AUTHORIZATION

PE: # C-4735

EXP: 06/30/2021

SCALE 1" = 30'-0"

PROJECT LOCATION1

SHEET INDEX

NUMBER TITLE

PLUMBING

P-001 LEGEND & ABBREVIATIONS

PD101 PLUMBING DEMOLITION - UNDERFLOOR & FIRST

FLOOR

PD102 PLUMBING DEMOLITION - SECOND FLOOR &

ROOF

P-101 UNDERFLOOR PLUMBING

P-102 GROUND FLOOR PLUMBING

P-103 SECOND FLOOR PLUMBING

P-104 ROOF PLUMBING

P-501 PLUMBING DETAILS

P-601 DOMESTIC WATER RISER

P-602 WASTE AND VENT RISER

P-701 PLUMBING SCHEDULES

MECHANICAL

M-001 LEGEND & ABBREVIATIONS

MD101 GROUND FLOOR MECHANICAL DEMOLITION

PLAN

MD102 SECOND FLOOR MECHANICAL DEMOLITION

PLAN

MD103 ROOF MECHANICAL DEMOLITION PLAN

MH101 GROUND FLOOR MECHANICAL HVAC PLAN

MH102 SECOND FLOOR MECHANICAL HVAC PLAN

MH103 ROOF MECHANICAL HVAC PLAN

MP101 GROUND FLOOR MECHANICAL PIPING PLAN

MP102 SECOND FLOOR MECHANICAL PIPING PLAN

M-301 SECTIONS

M-401 ENLARGED PLANS

M-501 DETAILS

M-601 FLOW DIAGRAMS

M-701 MECHANICAL SCHEDULES

M-702 MECHANICAL SCHEDULES

M-801 MECHANICAL CONTROLS

M-802 MECHANICAL CONTROLS

ELECTRICAL

E-001 LEGEND, ABBREVIATIONS & MOUNTING HEIGHT

DETAIL

ES101 ELECTRICAL SITE LIGHTING PLAN

ES102 ELECTRICAL SITE PLAN

ED101 GROUND FLOOR ELECTRICAL DEMOLITION

PLAN

ED102 SECOND FLOOR ELECTRICAL DEMOLITION

PLAN

EG101 GROUNDING PLAN & GROUNDING SYSTEM

DIAGRAM

EG102 LIGHTNING PROTECTION PLAN

EG500 GROUNDING & LIGHTNING PROTECTION

DETAILS

EG501 GROUNDING & LIGHTNING PROTECTION

DETAILS

EP101 GROUND FLOOR POWER PLAN

EP102 SECOND FLOOR POWER PLAN

EP103 ROOF POWER PLAN

EP104 GROUND FLOOR MECHANICAL POWER PLAN

EP105 SECOND FLOOR MECHANICAL POWER PLAN

EP600 ONE-LINE DIAGRAM, FEEDER SCHEDULE &

MECHANICAL EQUIPMENT SCHEDULE

EP700 PANEL SCHEDULES

EP701 PANEL SCHEDULES

EL101 GROUND FLOOR LIGHTING PLAN

EL102 SECOND FLOOR LIGHTING PLAN

EL501 LIGHTING DETAILS

EL700 LIGHTING SCHEDULES

EY101 ELECTRICAL INTERIOR AUXILIARY SYSTEMS

EY101-PA ELECTRICAL SPECIAL SYSTEMS PUBLIC

ADDRESS

EY102 SECOND FLOOR SPECIAL SYSTEMS PLAN

EY501 SPECIAL SYSTEMS DETAILS

EY601 SPECIAL SYSTEMS RISER DIAGRAMS

ET101 GROUND FLOOR TELECOMMUNICATION PLAN

ET102 SECOND FLOOR TELECOMMUNICATION PLAN

ET501 TELECOM DETAILS

ET601 DIGITAL CLOCK RISER DIAGRAM

ET602 TELECOM RISER DIAGRAM

SHEET INDEX

NUMBER TITLE

GENERAL

G-001 COVER SHEET, SHEET INDEX & VICINITY PLAN

G-101 CODE AND LIFE SAFETY PLAN

G-102 APPENDIX B CODE SHEETS

CIVIL

C100 EXISTING CONDITIONS PLAN

C101 DEMOLITION PLAN

C102 SITE PLAN

C110 UTILITY PLAN

C111 TEMPORARY UTILITY PLAN

C112 EXTERIOR STAIRWAY PLAN

C501 CONSTRUCTION DETAILS

C502 CONSTRUCTION DETAILS

LANDSCAPE

LS100 LANDSCAPE SITE PLAN

LS400 ENLARGED LAYOUT PLANS

LP100 LANDSCAPE PLANTING PLAN

LP500 PLANTING DETAILS / PLANTING SCHEDULE

STRUCTURAL

S-001 GENERAL NOTES

S-002 TYPICAL DETAILS

SB101 FOUNDATION PLAN

SB301 FOUNDATION DETAILS

SB501 FOUNDATION DETAILS

SF101 SECOND FLOOR FRAMING PLAN

SF102 HIGH ROOF FRAMING PLAN

SF201 FRAMING ELEVATIONS

SF202 FRAMING ELEVATIONS

SF501 FRAMING DETAILS

SF502 FRAMING DETAILS

ARCHITECTURE

A-001 ABBREVIATIONS, ACCESSIBILITY, PARTITIONS &

SYMBOLS

AD101 DEMOLITION PLANS

AD102 DEMOLITION ROOF PLAN

AE101 GROUND FLOOR PLAN

AE102 SECOND FLOOR PLAN

AE103 REFLECTED CEILING PLANS

AE104 REFLECTED CEILING DETAILS

AE105 ROOF PLAN

AE201 BUILDING ELEVATIONS

AE301 BUILDING SECTIONS

AE310 WALL SECTIONS

AE311 WALL SECTIONS

AE401 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE402 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE403 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE404 INTERIOR ELEVATIONS

AE405 ENLARGED STAIR PLANS & SECTION

AE406 ENLARGED STAIR PLANS & ELEVATIONS

AE407 ENLARGED ELEVATOR PLANS & DETAILS

AE408 ENLARGED EXTERIOR STAIRS

AE501 PLAN DETAILS

AE601 DOOR SCHEDULE AND DETAILS

AE602 DOOR DETAILS

AE603 GLAZING DETAILS

AE604 ROOM FINISH SCHEDULE

AG101 GROUND FLOOR SIGNAGE PLAN

AG102 SECOND FLOOR SIGNAGE PLAN

AG103 SIGNAGE DETAILS

AG104 SIGNAGE DETAILS & SCHEDULE

INTERIORS

IF101 GROUND FLOOR FURNITURE PLAN

IF102 SECOND FLOOR FURNITURE PLAN

FIRE PROTECTION

FP001 FIRE PROTECTION, LEGEND, ABBREVIATIONS,

AND PIPING SCHEMATIC

FP101 GROUND FLOOR FIRE PROTECTION PLAN

FP102 SECOND FLOOR FIRE PROTECTION PLAN

FP401 FIRE PROTECTION ENLARGED PLANS AND

SECTIONS

FP501 FIRE ALARM & MASS NOTIFICATION RISER

DIAGRAM

FP601 FIRE ALARM & MASS NOTIFICATION

INPUT/OUTPUT MATRIX

SEAL

050568

ENGINEE

R

Frankfurt-Short-Bruza Architects Engineers Planners

11949

VOLUME 3 OF 4

ABBREVIATIONS

............................................................ ABOVE

....................................... ADMINISTRATIVE

.............................. ABOVE FINISHED FLOOR

...................................................... BUILDING

............................... BACKFLOW PREVENTER

....................... CONTINUE, CONTINUATION

............................................... DEPARTMENT

........................................ DETECTOR, DETAIL

.................................................... DUCTILE IRON

................................................. DISCHARGE

................................................. EXTRA HAZARD

................................................. EQUIPMENT

....................................................... FIRE ALARM

FACU

.............. FIRE DEPARTMENT CONNECTION

...................... FIRE PROTECTION, FIRE PUMP

....................................................... FOOT, FEET

................ INSPECTOR'S TEST CONNECTION

..................................................... JOCKEY PUMP

.................................................... LIGHT HAZARD

................................................. MECHANICAL

........................................ NORMALLY CLOSED

........................... OUTSIDE STEM AND YOKE

................................. POST INDICATING VALVE

........................................... ORDINARY HAZARD

................................................... PRESSURE

........................... POUNDS PER SQUARE INCH

....................................... REFERENCE, REFER

..................... RELEASING SYSTEM FSCP

.................................................... SQUARE FOOT

.................................................. SOUNDER BASE

................................. GALLONS PER MINUTE

............................................................. TYPICAL

.............................................. TEMPERATURE

.................................... UNDERGROUND

............................ WET PIPE, WEATHERPROOF

..................................................................... WITH

........................................................... WITHOUT

........................................................... HAZARD

.................................................. HYDRAULIC

............................................... NOT APPLICABLE

................................................................ EQUAL

......................... FIRE ALARM ANNUNCIATOR

...................... MASS NOTIFICATION SYSTEM

................................................. NOT TO SCALE

................................................................ SHEET

........................ UNLESS NOTED OTHERWISE

.......................................................... CANDELA

................................................................ FLOOR

........................ HIGH VOLUME LOW SPEED

................ AQUEOUS FILM-FORMING FOAM

.......................................... FIRE DEPARTMENT

.............. FOAM SYSTEM CONTROL PANEL

..................................................... TRANSMIT

............................................................. SYSTEM

................................................................. PUMP

................................................ SUPERVISORY

............................................................ STATION

.............................................. AUTOMATION

............ ENHANCED DISCREET I/O MODULE

.............................................. INPUT / OUTPUT

................................................... SUPERVISION

........................................................ SCHEDULE

................. SEISMIC SEPARATION ASSEMBLY

ABV

ADMIN

AFF

BLDG

BFP

.......................... CONNECT, CONNECTION

CONT

DEPT

DET

DI

DISCH

EH

EQUIP

FA

...................... FIRE ALARM CONTROL UNIT

FDC

FP

FT

ITC

JP

LH

MECH

N.C.

OS&Y

PIV

OH

PRESS

PSI

REF

RSFACU

SF

SB

GPM

TYP

TEMP

UGND, UG

WP

W/ W/O

HAZ

HYDR

NA

EQ

FAA

MNS

NTS

SHT

UNO

CD

FL

HVLS

AFFF

FD

FSCP

TRANS

SYS

PMP

SUPV

STA

AUTO

EDIO

I / O

........................................ CARBON MONOXIDE

SUP

SCH

SSA

CONN

CO

LOC...........................LOCAL OPERATING CONSOLE

WET PIPE SPRINKLER SUPPLY

SYMBOL

FIRE ALARM MANUAL PULL STATION

WALL MOUNTED FIRE ALARM/MNS

SPEAKER/STROBE, XX INDICATES CD

RATING

CEILING MOUNTED FIRE ALARM SPEAKER

CEILING MOUNTED FIRE ALARM/MNS

SPEAKER/STROBE, XX INDICATES CD

RATING

FIRE DEPARTMENT CONNECTION

WALL MOUNTED FIRE ALARM/MNS

SPEAKER

ANGLE VALVE

CHECK VALVE

CONTROL VALVE

FPW

FP

XX

CEILING MOUNTED FIRE ALARM/MNS

STROBE, XX INDICATES CD RATING

WATERFLOW ALARM SPEAKER / STROBE.

XX INDICATES CANDELA RATING

F

C

XX

P

S C

XX

S

C

WP

XX

DESCRIPTION SYMBOL DESCRIPTION

FIRE PROTECTION LEGEND

FIRE PROTECTION PIPING

SMOKE DETECTOR - PHOTOELECTRIC

DUCT SMOKE DETECTOR; XX INDICATES

ASSOCIATED UNIT

TRANSCEIVER ANTENNA

FAPX POWER EXTENDER PANEL

FAA FIRE ALARM ANNUNCIATOR

FACU

FIRE ALARM & MASS NOTIFICATION

CONTROL UNIT

LOC LOCAL OPERATING CONSOLE

SPD SURGE PROTECTION DEVICE

K

DUCT SMOKE DETECTOR KEYED REMOTE

TEST STATION

AIM ADDRESSABLE INPUT MODULE

AOM ADDRESSABLE OUTPUT MODULE

OPEN FUNNEL DRAIN

POST INDICATING VALVE

RISER CHECK VALVE

INSPECTORS TEST CONNECTION (WITH

PRESSURE RELIEF)

PRESSURE GAUGEPI

PIPE OR CONDUIT BREAK / CONTINUATION

WATERFLOW SWITCH (VANE TYPE)WF

VALVE SUPERVISORY SWITCHVS

SYMBOL DESCRIPTION

DIGITAL ALARM COMMUNICATOR

TRANSMITTERDACT

DOOR HOLDER-WALL MOUNTED W-TAGDH

END OF LINE RESISTOREOL

FLOW METERM

FREE STANDING SIAMESE FDC

AIRFLOW ARROW

PIPE FLOW ARROW

HEAT DETECTOR-CEILING MOUNTED WITH

TEMPERATUREXX°

INSULATING FLANGE & GASKET KIT

PIPE CONTINUATION

REDUCER TRANSITION

WALL MOUNTED FIRE ALARM/MNS STROBE,

XX INDICATED CD RATING

PIPE BALL DRIP

PIPE CAP

OS&Y GATE VALVE

VS

XX

HYDRONIC FLOW ARROW

P

ELEVATOR LOBBY SMOKE DETECTOR -

PHOTOELECTRICL

ET TEXTUAL VISUAL APPLIANCE

PULL DOWN

FIRE ALARM

I R E

F

" M

IN

" M

IN

NOTES:

A. VERIFY EXACT MOUNTING

HEIGHTS WITH PROJECT

REQUIREMENTS. DEVICES MAY

OR MAY NOT APPLY TO THIS

PROJECT. REFER TO PLANS.

B. ALL NEW DEVICES SHALL BE

INSTALLED ACCORDING TO THE

MOUNTING HEIGHTS INDICATED

U.N.O.

AUDIBLE/VISUAL

UNIT

VISUAL

ONLY UNIT

MANUAL PULL

STATION

TOP OF

PULL

STATION

HANDLE

FINISHED FLOOR

I R E

F

I R E

F

AUDIBLE

ONLY UNIT

TEXT SIGN

0"

M A

X.

FDC

PUMP TEST

HEADER ONE (1) 2.5"

HOSE

FROM FDC

PUMP TEST

HEADER

FLOW

METER

VS

FIRE

PUMP

VS VS

JOCKEY

PUMP

6" FP SUPPLY

REFER TO SHEET

C110 FOR CONT.

FP

WP-1

VS

V S

V S

DOUBLE DETECTOR

CHECK VALVE

BACKFLOW PREVENTER

WF

PIPE MAIN DRAIN TO EXTERIOR

OF BUILDING TO A CONCRETE

SPLASH BLOCK OR PAVEMENT

OS&Y VALVE W/TAMPER

SWITCH (TYP)

N.C

PI

PI

PI PI

PI

ISOLATION FLANGE,

GASKET KIT, AND

REDUCER

PI PI

BYPASS LINE

TO 1ST FLOOR WET PIPE

SPRINKLER SYSTEM

VS VS

V S

VS

WF

TO SECOND FLOOR WET PIPE

SPRINKLER SYSTEM

V S

VS2 x DIA 5 x DIA.

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ghg\D o cum ents\M y R evit\80720_FP_gh g.rvt

5/28/2020 8:25: 14 AM

FIRE PROTECTION, LEGEND,

ABBREVIATIONS, AND PIPING

SCHEMATIC

FP001

LFO

NRS

NRS

GENERAL NOTES

A. THE DESIGN AND INSTALLATION OF THE FIRE

PROTECTION SYSTEM SHALL BE IN STRICT

ACCORDANCE WITH UFC 4-021-01 (CHANGE 1

JANUARY 2010); ECB, 2018-17 (25 OCT 2018); UFC

3-600-01 (CHANGE 3, 10 MAY 2019); NFPA 13, 2019

EDITION; NFPA 20, 2019 EDITION; NFPA 70, 2017

EDITION; NFPA 72, 2019 EDITION; NFPA 90A, 2018

EDITION; ADOPTED STATE AND LOCAL CODES,

AND THE CONTRACT DOCUMENTS.

B. HISTORIC HYDRANT FLOW TEST CONDUCTED

11/27/2018 INDICATED A WATER SUPPLY WITH A

STATIC PRESSURE OF 49 PSI AND RESIDUAL

PRESSURE OF 44 PSI FLOWING 754 GPM.

CONTRACTOR SHALL PERFORM THEIR OWN

HYDRANT FLOW TEST ON WHICH THE HYDRAULIC

CALCULATIONS ARE BASED.

C. PROVIDE AUTOMATIC WET PIPE SPRINKLER

SYSTEM IN ACCORDANCE WITH UFC 3-600-01

REQUIREMENTS WITH DESIGN DENSITY AND

DESIGN AREA FOR THE HAZARD CLASSIFICATION

LISTED IN THE FIRE PROTECTION DESIGN

SCHEDULE.

D. ALL SYSTEM COMPONENTS SHALL BE U.L. LISTED

OR F.M. APPROVED.

E. THE INSPECTOR'S TEST VALVES SHALL BE

LOCATED NO MORE THAN 7 FEET AFF.

F. ALL HANGERS SHALL BE PROVIDED AND

INSTALLED IN ACCORDANCE WITH NFPA 13.

G. ALL VALVES (DRAINS, INSPECTOR'S TEST,

CONTROL) SHALL BE IDENTIFIED BY SIGNAGE AS

REQUIRED BY NFPA 13.

H. BRANCH LINES SHALL BE ARRANGED FOR

FLUSHING. READILY REMOVABLE FITTINGS SHALL

BE PROVIDED AT THE END OF ALL CROSS MAINS.

I. ALL SPRINKLERS SHALL BE INSTALLED IN THE

CENTER OF THE CEILING TILES +/- 6 INCHES.

J. ALL DRAINS AND TEST CONNECTIONS SHALL

DISCHARGE TO THE EXTERIOR OF THE BUILDING

ONTO CONCRETE SPLASH BLOCK OR PAVEMENT.

K. ALL CONTROL VALVES SHALL BE SUPERVISED BY

THE FIRE ALARM SYSTEM.

L. PROVIDE AUTOMATIC FIRE ALARM/MASS

NOTIFICATION SYSTEM WITH VISUAL/AUDIO

NOTIFICATION APPLIANCES IN ACCORDANCE WITH

UFC 3-600-01, UFC 4-021-01, ECB 2018-17, AND

NFPA 72 REQUIREMENTS.

M. SPEAKERS AND VISUAL NOTIFICATION SHALL BE

PROVIDED THROUGHOUT THE BUILDING FOR

VOICE INTELLIGIBILITY AND OCCUPANT

NOTIFICATION. EXTERIOR SPEAKER SHALL BE

PROVIDED IN PUBLIC AREAS AND ANY AREAS

COMMONLY USED BY OCCUPANTS.

N. VISUAL NOTIFICATION SHALL BE PROVIDED IN ALL

EMPLOYEE WORK, COMMON, AND PUBLIC AREAS.

O. MANUAL PULL STATIONS SHALL BE PROVIDED AT

THE BUILDING EXITS, EXITS ADJOINING ASSEMBLY

OCCUPANCIES, AND BOILER ROOM EXITS AND

SHALL BE EASILY ACCESSIBLE, UNOBSTRUCTED,

AND VISIBLE.

P. DUCT SMOKE DETECTORS SHALL BE PROVIDED IN

ALL HVAC MAIN SUPPLY DUCTS WHERE REQUIRED

BY NFPA 90A, IN RETURN DUCTS WHEN SYSTEMS

ARE GREATER THAN 15,000 CFM, AND SHALL HAVE

AUXILIARY CONTACTS TO PROVIDE CONTROL,

INTERLOCK, AND SHUTDOWN FUNCTIONS OF THE

HVAC SYSTEMS. DETECTORS SHALL BE POWERED

BY THE FIRE ALARM/MASS NOTIFICATION

CONTROL PANEL.

Q. ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED IN

CONDUIT AND SHALL BE SECURELY FASTENED TO

THE STRUCTURE.

R. INSTALL SURGE PROTECTION DEVICES

EVERYWHERE FIRE ALARM WIRING ENTERS AND

EXITS THE BUILDING.

S. PROVIDE SMOKE DETECTION AT EACH POWER

EXTENDER PANEL.

T. PROVIDE SPRINKLERS BELOW ALL

OBSTRUCTIONS TO DISCHARGE, INCLUDING,

PLATFORMS, DOORS, AND DUCTS, PER NFPA 13.

U. PROVIDE AUTOMATIC AIR VENTS AT HIGH POINTS

OF PIPING TO VENT MINIMUM 98% OF THE

SYSTEM'S VOLUMETRIC CAPACITY. SLOPE PIPING

TO RISER, DRAIN TRAPPED PIPING

V. PROVIDE DRAIN VALVES FOR TRAPPED

SPRINKLER PIPING IN SPRINKLER PIPING.

DISCHARGE TO BUILDING EXTERIOR AT 18" ABOVE

GRADE ONTO CONCRETE SPLASH BLOCK.

W. COORDINATE SPEAKER LOCATIONS WITH LOC'S IN

ORDER TO PREVENT FEEDBACK.

SCALE NTS

FIRE ALARM MOUNTING HEIGHT DETAIL2SCALE NTS

FIRE PROTECTION PIPING SCHEMATIC1

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

035238

ENG INEER

F

F F

F

F

F F

F

F

S

S S

S

S

P

LOC

C C

C

C

C

C

C

C

S C

C

S

S

FACU

P

ET

ET

ET

ET

ET

ET

FAA

C

C

ET

F

112 111

120119118

104105

AA

B B

C C

D D

E E

F F

FP401

PLATFORM TO MEZZ. PROVIDE

SPRINKLERS BELOW.

UP TO 2ND FLOOR.

REFER TO SHEET

FP102.

75cd

75cd

15cd

15cd

75cd

15cd

75cd

30cd

75cd

110cd

110cd

15cd

15cd

110cd

30cd

30cd

75cd

LOCATE LOC AWAY FROM

SPEAKER TO MINIMIZE

FEEDBACK

FROM SPRINKLER RISER.

REFER TO SHEET FP401

30cd

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ctj\D oc um ents\M y R evit\80720_FP_C Jo nesN

955U .rvt

3/10/2021 10:35 :28 AM

GROUND FLOOR FIRE

PROTECTION PLAN

FP101

LFO

NRS

NRS

SCALE 1/8" = 1'-0"

GROUND FLOOR FIRE PROTECTION PLAN1

FIRE PROTECITON DESIGN SCHEDULE - GROUND FLOOR

NUMBER NAME HAZARD NOTES

101 FIRE OH

102 COMM OH 1, 2, 3

103 CORRIDOR LH

104 ELEC OH 2, 3

105 TOILET LH

106 JOINT INSPECTION OH

107 FLEET STOR OH

108 CORRIDOR LH

109 STAIRS LH

111 CARGO OH

112 RAMP OH

113 PALLET BUILD-UP OH

114 LAV TRUCK OH

115 CIRCULATION OH

116 PPE TRAINING BAG OH

117 FLEET OFFICE LH

118 COFFEE LH

119 JAN OH

120 ELEV ELEVATOR

121 LOCKERS OH

122 BAGGAGE / PALLET OH

123 FLEET WORK OH

124 MEN LH

125 WOMEN LH

126 BAGGAGE SCAN OH

127 BAGGAGE CHECK-IN OH

128 PASSENGER HOLDING LH

129 PASSENGER HOLDING STERILE LH

130 BAGGAGE SCAN OH

131 CORRIDOR LH

NOTES:

1. PROVIDE CONCEALED SIDEWALL SPRINKLERS. DO NOT ROUTE

PIPING INTO THIS ROOM.

2. DO NOT RUN PIPING ABOVE ELECTRICAL EQUIPMENT.

3. ONLY PIPING SERVING THIS ROOM SHALL ENTER THIS ROOM.

0 4' 8' 16'

1/8" = 1'-0"

N

L

1 ADDENDUM #1 3/3/2021

SEAL

050568

ENGINEE

R

P

S

S C

S C

C

C

CC

C C

CC

C

C

C

S C

S C

C

C

C

P 135º°

203204

212 213

OPEN

TO

BELOW

A

B B

C C

D D

E

E

F F

ROOF

BELOW

PROVIDE SPRINKLERS

BELOW PLATFORM

PROVIDE DRY SIDEWALL SPRINKLERS

FOR OUTSIDE STAIR CANOPY

L 15cd

30cd

15cd

15cd

30cd30cd

15cd

15cd

15cd

15cd

30cd

30cd

15cd 15cd

UP FROM 1ST FLOOR. REFER TO

SHEET FP101. PROVIDE SPRINKLER

FLOOR CONTROL VALVE

ASSEMBLY

AHU-01

SUPPLY

MAU-01

SUPPLY

NEAR SPRINKLERS AT TOP

OF ELEV. HOISTWAY

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ghg\D o cum ents\M y R evit\80720_FP_gh g.rvt

5/28/2020 8:25: 20 AM

SECOND FLOOR FIRE

PROTECTION PLAN

FP102

LFO

NRS

NRS

SCALE 1/8" = 1'-0"

SECOND FLOOR FIRE PROTECTION PLAN1

FIRE PROTECITON DESIGN SCHEDULE - SECOND FLOOR

NUMBER NAME HAZARD NOTES

201 STAIRS LH 2

202 CORR LH

203 TOILET LH

204 TOILET LH

205 CORRIDOR LH

206 ATOC LH

207 DCC LH

208 ADMIN LH

209 IDO LH

210 SIPR LH

211 CORR LH

212 LOAD PLANNING LH

213 COFFEE / BREAKRM LH

214 TO LIBRARY / HOTEL / QC LH

215 CONF LH

216 CORR LH

217 CORR LH

218 SUPERVISOR / MANAGER LH

219 ELEV ELEVATOR 1

220 ADMIN LH

221 MECH. OH

NOTES:

1. ELEVATOR EQUIPMENT ROOM IS AT TOP OF SHAFT. PROVIDE

AN ORDINARY OR INTERMEDIATE TEMPERATURE RATED

SPRINKLER WITH A GUARD AT THE TOP OF THE SHAFT,

CONTROL VALVE WITH TAMPER SWITCH, SMOKE AND HEAT

DETECTOR AND ELEVATOR SHUNT STRIP PER NFPA 13 AND

NFPA 72.

2. PROVIDE SPRINKLER AT TOP OF STAIR.

0 4' 8' 16'

1/8" = 1'-0"

N

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

FA

P

X

FAPX

F

S

P

B B

C C

FP401

FP401

FIRE PUMP CONTROLLER

JOCKEY PUMP CONTROLLER

MONACO CONTROL PANEL

DOUBLE DETECTOR CHECK

BFP W/TAMPER SWITCH

6" DI POLY WRAPPED FP SUPPLY

PIPE. REFER TO SHEET C110 FOR

CONT.

OS&Y VALVE

W/TAMPER SWITCH

ELECTRIC VERTICAL IN-LINE

FIRE PUMP ON 6" CONCRETE

HOUSEKEEPING PAD

CHECK VALVE

OS&Y VALVE

W/TAMPER SWITCH

RISER CHECK VALVE

MAIN DRAIN

FDC CHECK VALVE

TO WP-1

SPRINKLERS

JOCKEY PUMP ON 6" CONCRETE

HOUSEKEEPING PAD

SPLASH BLOCK

(1) 2-1/2" PUMP AND

BFP TEST HEADER

CONN.

BUTTERFLY VALVE

W/TAMPER SWITCH

(NORMALLY CLOSED)

OS&Y VALVE

W/TAMPER SWITCH

FIRE

WATERFLOW

HORN/STROBE

W/SIGNAGE110cd

FDC

BC

TO SPRINKLER RISER

JOCKEY PUMP ON 6" CONCRETE

HOUSEKEEPING PAD

OS&Y VALVE

W/TAMPER SWITCH

OS&Y VALVE

W/TAMPER SWITCH

DOUBLE DETECTOR

CHECK BFP W/TAMPER

SWITCH

FLOW METER

OS&Y VALVE

W/TAMPER SWITCHVG

ELECTRIC VERTICAL IN-LINE

FIRE PUMP ON 6" CONCRETE

HOUSEKEEPING PAD 6" DI POLY WRAPPED FP SUPPLY

PIPE. REFER TO SHEET C110 FOR

CONT.

TO BFP TEST HEADER

MAIN DRAIN FROM

SPRINKLER RISER

MAIN DRAIN

SPLASH BLOCK

CHECK VALVE

FIRE

BYPASS LINE

5 x DIA. 2 x DIA.

FROM FIRE PUMP

OS&Y VALVE W/TAMPER

SWITCH

RISER CHECK VALVE

MAIN DRAIN

FROM FDC

NAC EXTENDER

PANEL

TO WP-1 SPRINLKERS

FA/MNS SPEAKER

WATERFLOW SWITCH

FIRE

PROVIDE GROOVED

TEE FOR FUTURE

EXPANSION

B B

C C

AIM

AIM

BFP

AIM

AIM

AIM

AIM

BYPASS

FIRE

PUMP

AIM

AIM

FLOW

METER AIM

BFP TEST

HEADERVS

VS

VS

VS

VS

VS

VS

VS

VS

AIM

AIM

SPRINKLER

RISER

VS

WF

AIM FIRE PUMP

RUNNING

AIM

FIRE PUMP

CONTROLLER

MAIN SWITCH

NOT IN AUTO

AIM

FIRE PUMP

ALTERNATE

POWER

SOURCE

AIM

FIRE PUMP

AC POWER

LOSS

AIM FIRE PUMP

PHASE

REVERSAL

FIRE

AIM

AIM

JOCKEY

PUMP

VS

VS

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ghg\D o cum ents\M y R evit\80720_FP_gh g.rvt

5/28/2020 8:25: 23 AM

FIRE PROTECTION ENLARGED

PLANS AND SECTIONS

FP401

LFO

NRS

NRS

SCALE 1/2" = 1'-0"

FIRE ROOM 101 ENLARGED PLAN1

SCALE 1/2" = 1'-0"

FIRE PUMP SECTION4

SCALE 1/2" = 1'-0"

SPRINKLER RISER SECTION3

0 1' 2' 4'

1/2" = 1'-0"

N

SCALE NTS

FIRE ROOM 101 DEVICE PLAN2

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

101 102

FIRE ALARM

CONTROL UNIT

RM 127

LOC

120V

(2) TELEPHONE LINE

A118

30cd

ROOM

CANDELA RATING

DEVICE LEGEND

WATERFLOW

HORN/STROBE.

W/"WATERFLOW"

SIGNAGE

110cd

SPD

DACT

15cd

C c c c

S c c c c

15cd 15cd c c

205 204

15cd 15cd c c

203 202

75cd 110cd c c

130 129 c c cccc c

S c ccc S c

S c

S c ccc

EXTERIOR

S c

EXTERIOR

EOL

F

15cd

15cd

75cd

15cd

75cd

75cd

75cd

75cd

15cd

116 117

75cd

15cd

110cd

30cd

30cd

15cd

15cd

15cd

30cd30cd15cd

30cd15cd 30cd 30cd 15cd 15cd

211 212 213 214 215 216 220 c

WP

SPD

VS

AIM

VS

AIM

FIRE

PUMP

VS

AIM

VS

AIM

JOCKEY

PUMP

VS

AIM

FIRE PUMP

TEST HEADER

(N.C.)

AIM

FIRE PUMP

CONTROLLER

MAIN SWITCH

NOT IN AUTO

AIM

FIRE PUMP

RUNNING

AIM

FIRE PUMP

AC POWER

LOSS

AIM

FIRE PUMP

PHASE

REVERSAL

AIM

FIRE PUMP

ALTERNATE

POWER

SOURCE

S S

SSSS

S

WP WP WP WP

WP

F

101101101101101101101101101101

F

F

F

F

F

114 122 P

ELEVATOR

F

F

127 127 P

FACU

F

F

VS

WF

BFP

AIMAIM

VS

AIM

WP-1

c

TRANSCEIVER

ANTENNA

F

F

216217 P

ELEVATOR

AIM

AHU-01

SUPPLY

F c

30cd

ET EOL

x 7

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ctj\D oc um ents\M y R evit\80720_FP_C Jo nesN

955U .rvt

3/10/2021 10:35 :29 AM

FIRE ALARM & MASS

NOTIFICATION RISER DIAGRAM

FP501

LFO

NRS

NRS

SCALE NTS

FIRE ALARM RISER DIAGRAM1

1 ADDENDUM #1 3/3/2021

SEAL

050568

SYSTEM INPUTS

MANUAL FIRE ALARM PULL STATIONS1

AC

TU

AT

E

CO

M

M

ON

A

LA

RM

S

IG

NA

L

IN

DI

CA

TO

R

A

AC

TU

AT

E

AU

DI

BL

E

AL

AR

M S

IG

NA

L

B

AC

TU

AT

E

CO

M

M

ON

S

UP

ER

VI

SO

RY

S

IG

NA

L

IN

DI

CA

TO

R

C

AC

TU

AT

E

AU

DI

BL

E

SU

PE

RV

IS

OR

Y

SI

GN

AL

D

AC

TU

AT

E

CO

M

M

ON

T

RO

UB

LE

S

IG

NA

L

IN

DI

CA

TO

R

E

AC

TU

AT

E

AU

DI

BL

E

TR

OU

BL

E

SI

GN

AL

F

AC

TU

AT

E

AU

DI

BL

E

NO

TI

FI

CA

TI

ON

A

PP

LI

AN

CE

S

G

AC

TU

AT

E

VI

SI

BL

E

NO

TI

FI

CA

TI

ON

A

PP

LI

AN

CE

S

H

DI

SP

LA

Y/

PR

IN

T

CH

AN

GE

O F

ST

AT

US

I

TR

AN

SM

IT

F

IR

E

AL

AR

M

S

IG

NA

L

TO

S

UP

ER

VI

SI

NG

S

TA

TI

ON

J

TR

AN

SM

IT

F

IR

E

SU

PE

RV

IS

OR

Y

SI

G

NA

L

TO

S

UP

ER

VI

SI

NG

S

TA

TI

ON

K

TR

AN

SM

IT

F

IR

E

TR

O

UB

LE

S

IG

NA

L

TO

S

UP

ER

VI

SI

NG

S

TA

TI

O

N

L M N O P Q

SH

UT

DO

W

N

AS

SO

CI

AT

ED

A

IR

H

AN

DL

IN

G

UN

IT

R

AC

TU

AT

E

PR

IM

AR

Y

FL

OO

R

EL

EV

AT

OR

R

EC

AL

L

U

AC

TU

AT

E

AL

TE

RN

AT

E

FL

OO

R

EL

EV

AT

OR

R

EC

AL

L

V

AC

TU

AT

E

EL

EV

AT

O

R

SH

UN

T

TR

IP

C

IR

CU

IT

B

RE

AK

ER

W X Y Z

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AA BB CC

DE

-A

CT

IV

AT

E

FI

RE

A

LA

RM

N

OT

IF

IC

AT

IO

N

AP

PL

IA

NC

ES

IF

A

CT

IV

E(

VI

SU

AL

AC

TI

VA

TE

M

AS

S

NO

TI

FI

CA

TI

ON

S

TR

O

BE

S

TR

AN

SM

IT

M

AS

S

NO

TI

FI

CA

TI

O N

SI

GN

AL

T

O

SU

PE

RV

IS

IN

G

ST

AT

IO

N

DE

-A

CT

IV

AT

E

M

AS

S

NO

TI

FI

CA

TI

O N

SI

GN

AL

A

FT

ER

M

IN

UT

ES

SMOKE DETECTOR - PANEL

HEAT DETECTOR

WATERFLOW SWITCH

DUCT SMOKE DETECTOR

SMOKE DETECTOR - 1ST FLOOR ELEVATOR LOBBY

SMOKE DETECTOR - ALL OTHER ELEVATOR LOBBIES

SMOKE DETECTOR - ELEVATOR EQUIPMENT ROOM

HEAT DETECTOR - ELEVATOR EQUIPMENT ROOM

SHUNT TRIP BREAKER - CONTROL POWER SUPERVISION

VALVE TAMPER SWITCH

FIRE ALARM CONTROL PANEL AC POWER FAILURE

FIRE ALARM CONTROL PANEL LOW BATTERY

OPEN CIRCUIT

GROUND FAULT

NOTIFICATION APPLIANCE CIRCUIT SHORTED

ALL OTHER TROUBLES

ACU MICROPHONE KEYED-ALL CALL

LOC MICROPHONE KEYED-ALL CALL

MASS NOTIFICATION SYSTEM SWITCH INPUT 1

MASS NOTIFICATION SYSTEM SWITCH INPUT 2

MASS NOTIFICATION SYSTEM SWITCH INPUT 3

MASS NOTIFICATION SYSTEM SWITCH INPUT 4

MASS NOTIFICATION SYSTEM SWITCH INPUT 5

MASS NOTIFICATION SYSTEM SWITCH INPUT 6

MASS NOTIFICATION SYSTEM SWITCH INPUT 7

MASS NOTIFICATION SYSTEM SWITCH INPUT 8

MASS NOTIFICATION SYSTEM ACTIVATED DURING FIRE EVENT

TS

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

ON

M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

AC

TU

AT

E

AS

SO

CI

AT

ED

M

AS

S

NO

TI

FI

CA

TI

O

N M

ES

SA

GE

ALARM CONDITIONS

SUPERVISORY CONDITIONS

TROUBLE CONDITIONS

MASS NOTIFICATION CONDITIONS

A B C D E F G H I J K L M N O P Q R U V W X Y Z AA BB CCTS

AC

TU

AT

E

W

AT

ER

FL

O W

H

OR

N/

ST

RO

BE

SYSTEM OUTPUTS

CONTROL UNIT

ANNUNCIATION NOTIFICATION AUXILIARY FUNCTIONS MASS NOTIFICATION SYSTEM

DD

DD

EE

EE FF GG HH II JJ KK LL MM

FF GG HH II JJ KK LL MM NN

NN

FIRE PUMP RUNNING

FIRE PUMP CONTROLLER MAIN SWITCH NOT IN AUTO

FIRE PUMP ALTERNATE POWER SOURCE

FIRE PUMP ROOM LOW TEMPERATURE

FIRE PUMP REVERSAL

HVAC EMERGENCY SHUT DOWN SWITCH

SH

UT

DO

W

N

AL

L

HE

AT

IN

G, V

EN

TI

LA

TI

NG

, A

ND

A

IR

C

ON

DI

TI

ON

IN

G

PE

R

UF

C

4-

1-

S

EC

TI

ON

-4

.2

EMERGENCY SHOWER/EYEWASH STATION

PP QQ RR SS TT UU VV

PP QQ RR SS TT UU VV

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\ghg\D o cum ents\M y R evit\80720_FP_gh g.rvt

5/28/2020 8:25: 18 AM

FIRE ALARM & MASS

NOTIFICATION INPUT/OUTPUT

MATRIX

FP601

LFO

NRS

NRS

SCALE NTS

FIRE ALARM & EMERGENCY COMMUNICATIONS INPUT/OUTPUT MATRIX1

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

CO

HB

C

CO

Ø.................................ROUND

ϕ..................................PHASE

Ø............................DIAMETER

°...............................DEGREE

∠..................................ANGLE

%.............................PERCENT

TEXT SYMBOLS

CHECK VALVE (SWING GATE)

(GPM)

WH

A

ABBREVIATIONSDESCRIPTIONSYMBOL

NPW NON-POTABLE WATER (MAKE-UP)

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

SOIL OR WASTE VENTV

SOIL OR WASTE - ABOVE FLOORSS

COMPRESSED AIR - ABOVE FLOORA

SOIL OR WASTE - BELOW FLOOR

OR GRADESS

COMPRESSED AIR - BELOW FLOOR

OR GRADEA

DRAIND

NATURAL GAS, LOW

PRESSURE (0.5 PSI)G

NATURAL GAS, MEDIUM

PRESSURE (50 PSIG)MG

FIRE PROTECTION MAINFP

CONDENSATE DRAINCD

RISER DOWN (ELBOW)

RISER UP (ELBOW)

RISE OR DROP

TEE DOWN

TEE UP

TOP CONNECTION

BOTTOM CONNECTION

SIDE CONNECTION

BALL VALVE

GATE VALVE OR ISOLATION VALVE

CIRCUIT BALANCING VALVE -

SET FOR GPM SHOWN IN ().

ANGLE VALVE

CHECK VALVE (STRAIGHT)

GLOBE VALVE

PRESSURE REDUCING VALVE

ASME RELIEF VALVE

PRESSURE AND

TEMPERATURE RELIEF

REDUCER, ECCENTRIC

REDUCER, CONCENTRIC

CLEANOUT, FLOOR

CLEANOUT, WALL

WATER HAMMER ARRESTOR

STRAINER, "Y" TYPE

DOUBLE CHECK VALVE BACKFLOW

PREVENTION DEVICE

REDUCED PRESSURE BACKFLOW

PREVENTER W/STRAINER

HOSE BIBB

WALL HYDRANT

PIPE ANCHOR

PIPE SLEEVE THRU

WALL, FOOTING ETC

FLOW IN DIRECTION OF ARROW

PIPE SLOPE IN

DIRECTION OF ARROW

T1

THERMOMETER

THERMOMETER WELL

TW

PI

PRESSURE GAUGE WITH GAUGE

COCK (C=COMPOUND GAUGE)

LUBRICATED PLUG VALVE

UNION

BLIND FLANGE

CAP

COMPRESSED AIR RELIEF VALVE

RELIEF VALVE

PIPE ROUTED TO FLOOR DRAIN

LAVATORY

WATER CLOSET

URINAL

SERVICE SINK/BASIN

SINK

SHOWER HEAD

DRINKING FOUNTAIN

FLOOR DRAIN

COMPRESSED AIR OUTLET STATION

ABV* ABOVE

AFF ABOVE FINISHED FLOOR

AGA AMERICAN GAS ASSOCIATION

ALT ALTERNATE

APPROX APPROXIMATE

ARCH ARCHITECT,ARCHITECTURAL

AUTO AUTOMATIC

AUX AUXILIARY

AVG AVERAGE

B/B BACK TO BACK

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTER

BLDG BUILDING

BTU BRITISH THERMAL UNIT

BTUH BTU/HOUR

CA* COMPRESSED AIR

CAP CAPACITY

CBV* CIRCUIT BALANCING VALVE

CFH* CUBIC FEET PER HOUR

CI CAST IRON

CL CENTER LINE

CLG CEILING

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

CONN CONNECT

CONT CONTINUE, CONTINUOUS

COORD COORDINATE

CORR CORRIDOR

CP* CHROME PLATED

CTR CENTER

CW COLD WATER

D DRAIN

DEG DEGREE

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGRAM, DIAGRAMMATIC

DN DOWN

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWV DRAIN, WASTE, VENT

E EAST

EA EACH

EL ELEVATION

ELEC ELECTRIC

ELL* ELBOW

EMER EMERGENCY

EQUIP EQUIPMENT

EQUIV EQUIVALENT

EST ESTIMATE

ETC ET CETERA (AND SO FORTH)

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXT EXTERIOR

F FAHRENHEIT

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FF* FINISHED FLOOR

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

FH FIRE HYDRANT

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLR FLOOR

FM FACTORY MUTUAL

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FOOT, FEET

FTG FOOTING

FURN FURNISHED

FV FLUSH VALVE

FIG FIGURE

FIXT FIXTURE

G NATURAL GAS

GA GAGE, GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GPH GALLON PER HOUR

GPM GALLON PER MINUTE

HB HOSE BIBB

HORIZ HORIZONTAL

HOSP HOSPITAL

HP HORSEPOWER

HR* HOUR

HSKPG HOUSEKEEPING

HT HEIGHT

HW HOT WATER

HWR HOT WATER RETURN

HYD HYDRAULIC

HYD HYDRANT

Hz HERTZ

ID INSIDE DIAMETER

IE INVERT ELEVATION

IN WC INCHES WATER COLUMN

IN* INCHES

INFO INFORMATION

INSUL INSULATION

INV EL INVERT ELEVATION

IPC* INTERNATIONAL PLUMBING CODE

IPS IRON PIPE SIZE

ISO ISOMETRIC

JAN CLO JANITOR'S CLOSET

K THOUSAND

KW KILOWATT

KWH KILOWATT HOUR

L LITER

LAV LAVATORY

LBS POUNDS

LF LINEAR FEET (FOOT)

LKR LOCKER

MA* MEDICAL AIR

MAINT MAINTENANCE

MATL MATERIAL

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MC MECHANICAL CONTRACTOR

MECH MECHANICAL

MED MEDIUM

MEZZ MEZZANINE

MFG MANUFACTURING

MFR MANUFACTURER

MG* MEDIUM PRESSURE NATURAL GAS

MIN MINIMUM

MISC MISCELLANEOUS

MOD MODIFY

MTD MOUNTED

MULT MULTIPLE

N NORTH

NA NOT APPLICABLE

NCS* NATIONAL CAD STANDARDS

NEG NEGATIVE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NPW NONPOTABLE WATER

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OPT OPTIONAL

DESCRIPTIONSYMBOL

OPP OPPOSITE

ORIG ORIGINAL

OUT OUTLET

OZ OUNCE

PCT PERCENT

PH PHASE

PKG PACKAGE

PLBG PLUMBING

PPM PARTS PER MILLION

PRELIM PRELIMINARY

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQ. IN. ABSOLUTE

PSIG POUNDS PER SQ. IN. GAGE

PVC POLYVINYL CHLORIDE

PWR POWER

QA QUALITY ASSURANCE

QTY QUANTITY

RD ROOF DRAIN

REF REFERENCE

REQD REQUIRED

REV REVISE, REVISION

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RM ROOM

RPBP* REDUCED PRESSURE

BACKFLOW PREVENTER

RPM REVOLUTIONS PER MINUTE

RPS REVOLUTIONS PER SECOND

S SOUTH

s* SECOND

SCHED SCHEDULE

SCHEM SCHEMATIC

SECT SECTION

SF SQUARE FEET (FOOT)

SPEC SPECIFICATION

SQ SQUARE

STOR STORAGE

STRUCT STRUCTURAL

SYS SYSTEM

T&P TEMPERATURE AND PRESSURE

TECH TECHNICAL

TEMP TEMPERATURE

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

THRU THROUGH

TSTAT THERMOSTAT

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

V* VOLT

VOL VOLUME

VTR VENT THRU ROOF

W WATT

W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSE

WC WATER COLUMN

WG WATER GAGE

WH WATER HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

WT WEIGHT

XFMR TRANSFORMER

YH YARD HYDRANT

YR YEAR

NOTES:

1. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT.

2. ABBREVIATIONS WITH * PREFIX ARE NOT INCLUDED IN THE CURRENT NATIONAL CAD STANDARDS.

STORM DRAINSD

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec tN o.

:F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

,N C

N or th C ar ol in a

A ir

N at io na lG ua rd C

-1

C on ve rs io n:

A dd

/A lte rS m al lT er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

5/27/2020 8:59: 52

AM

LEGEND & ABBREVIATIONS

P-001

LLP

WBB

WBB

GENERAL NOTES

(APPLIES TO ALL SHEETS)

A. SLOPE SOIL AND WASTE PIPE 4" AND LARGER

AT 1/8" PER FT. MINIMUM, SIZE LESS THAN 4"

SLOPE 1/4" PER FT. MINIMUM, UNLESS NOTED

OTHERWISE.

B. ALL PIPING SHALL BE COORDINATED WITH

CIVIL UTILITY PIPING, FIRE PROTECTION,

DUCTWORK, MECHANICAL PIPING, LIGHTING,

STRUCTURAL AND ARCHITECTURAL SYSTEMS.

C. PIPE CLEANOUTS SHALL BE LINE SIZE (6"

MAX.). LOCATE 100' APART MAXIMUM FOR

SIZES UP THROUGH 6".

D. PLUMBING VENTS THROUGH ROOF (VTR)

SHALL BE 3" MINIMUM. SMALLER VTR'S

INDICATED SHALL INCREASE TO 3" PIPE, 12"

BELOW ROOF. INSTALL VENT THRU ROOF (VTR)

PENETRATIONS PER ROOFING

MANUFACTURER'S RECOMMENDATIONS.

E. ACCESS PANELS SHALL BE PROVIDED FOR ALL

WATER HAMMER ARRESTORS LOCATED IN

WALLS TO ACCESS EQUIPMENT. PANEL SHALL

BE AS LARGE AS PRACTICAL FOR THE

FUNCTION THEY ARE INTENDED.

F. ALL FLOOR DRAINS AND FLOOR SINKS SHALL

HAVE TRAP PRIMERS.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 F

SEAL

ALL BELOW-GRADE

PLUMBING PIPING TO BE

CAPPED & ABANDONED

EXCEPT FOR STORM DRAIN

PIPING & UNLESS

OTHERWISE NOTED

8 8

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

EXISTING 8" SD

TO REMAIN

DEMO EXISTING 4"

SD TO THIS POINT

DEMO EXISTING 4" SD

TO ABOVE FLOOR

DEMO EXISTING

DOMESTIC WATER

ENTRANCE TO

BELOW FLOOR

AND CAP

ABANDON EXISTING

WATER LINE

ALL PLUMBING EQUIPMENT,

PIPING, & ACCESSORIES TO

BE DEMOLISHED UNLESS

NOTED OTHERWISE.

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

9 10 9 9

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec tN o.

:F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

,N C

N or th C ar ol in a

A ir

N at io na lG ua rd C

-1

C on ve rs io n:

A dd

/A lte rS m al lT er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

5/27/2020 8:59: 36

AM

PLUMBING DEMOLITION -

UNDERFLOOR & FIRST FLOOR

PD101

LLP

WBB

WBB

SCALE 1/8" = 1'-0"

UNDERFLOOR PLUMBING - DEMOLITION1

SCALE 1/8" = 1'-0"

GROUND FLOOR PLUMBING - DEMOLITION2

SHEET KEYNOTES

GENERAL NOTES

N

0 4' 8' 16'

1/8" = 1'-0"

1. EXISTING FIXTURE TO BE DEMOLISHED.

SANITARY SEWER, VENT, & DOMESTIC WATER

PIPING TO BE CAPPED BELOW FLOOR OR

REMOVED AS REQUIRED FOR NEW WORK.

2. APPROXIMATE LOCATION OF EXISTING

DOMESTIC WATER ENTRANCE, PIPING TO BE

DEMOLISHED TO BELOW FLOOR AND CAPPED.

3. DEMO FITTINGS AND CAP LATERALS.

4. DEMO TO ABOVE FINISHED FLOOR.

5. EXISTING SANITARY SEWER PIPING BELOW

FLOOR TO BE DEMOLISHED OR ABANDONED AS

REQUIRED FOR NEW WORK (NOT ALL EXISTING

PIPING IS SHOWN).

6. NOT USED

7. NOT USED

8. APPROXIMATE EXTENTS (SHOWN CROSS-

HATCHED) OF FLOOR SLAB DEMOLITION

REQUIRED FOR NEW WORK. CONTRACTOR TO

SUBMIT FULL SHOP DRAWINGS FOR APPROVAL

FROM ENGINEER PRIOR TO COMMENCEMENT

OF FLOOR DEMOLITION.

9. DEMO EXISTING 4" VERTICAL SD TO 6" ABOVE

FLOOR AND CAP.

10. DEMO EXISTING 4" VERTICAL SD TO BELOW

FLOOR AND CAP.

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

B. EXISTING SANITARY SEWER PIPING BELOW

GRADE TO BE ABANDONED UNLESS NOTED

OTHERWISE.

C. EXISTING SANITARY & VENT PIPING ABOVE

GRADE TO BE DEMOLISHED.

D. EXISTING STORM DRAIN PIPING TO REMAIN

UNLESS NOTED OTHERWISE.

E. EXISTING DOMESTIC WATER PIPING TO BE

DEMOLISHED.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 F

SEAL

LOW ROOF, RE: ROOF PLAN

OPEN TO BELOW

OPEN TO BELOW

ALL PLUMBING EQUIPMENT,

PIPING, & ACCESSORIES TO

BE DEMOLISHED.

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

4 4 4 4

1 1 1 1

FOR MECH. EQUIP., RE: MECH. PLANS

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec tN o.

:F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

,N C

N or th C ar ol in a

A ir

N at io na lG ua rd C

-1

C on ve rs io n:

A dd

/A lte rS m al lT er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

5/27/2020 8:59: 55

AM

PLUMBING DEMOLITION -

SECOND FLOOR & ROOF

PD102

LLP

WBB

WBB

SHEET KEYNOTES

GENERAL NOTES

1. DEMO EXISTING ROOF DRAIN INLETS TO ALLOW

NEW ROOF DRAINS (WITH DOME STRAINERS)

TO BE INSTALLED IN SAME LOCATION &

ATTACHED TO EXISTING PIPING BELOW DECK.

COORDINATE THIS DEMO & REPLACEMENT

WORK TO MINIMIZE RAIN WATER INTRUSION

INTO THE BUILDING BELOW OR PONDING ON

THE ROOF (IF DRAINS ARE BLOCKED DURING A

STORM).

2. EXISTING ROOF HATCH, TO BE RELOCATED, RE:

ARCH.

3. EXISTING ROOF HATCH ABOVE, TO BE

RELOCATED, RE: ARCH.

4. DEMO EXISTING 4" VERTICAL SD.

N

0 4' 8' 16'

1/8" = 1'-0"

SCALE 1/8" = 1'-0"

SECOND FLOOR PLUMBING - DEMOLITION1

SCALE 1/8" = 1'-0"

ROOF PLUMBING - DEMOLITION2

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

B. EXISTING SANITARY & VENT PIPING ABOVE

GRADE TO BE DEMOLISHED.

C. EXISTING STORM DRAIN PIPING TO REMAIN

UNLESS NOTED OTHERWISE.

D. EXISTING DOMESTIC WATER PIPING TO BE

DEMOLISHED.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 F

SEAL

2 1/2"

4"

4"

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

FIRE

C O

M M

C O

R R

ID

O

R

ELEC

UNISEX

RAMP 111

CARGO

FLEET

STOR

JOINT

INSPECTION

LOCKERS

PPE

TRAINING

BAG

FLEET

OFFICE

COFFEE

JAN

ELEV

BAGGAGE

SCAN

CORRIDOR

FLEET

WORK

MEN

WOMEN

STAIR

#1

PALLET

BUILD-UP

LAV

TRUCK

CIRCULATION

BAGGAGE

CHECK-IN

PASSENGER

HOLDING

PASSENGER

HOLDING

STERILE

3 47

4 3

3"

11 5

3"

2"

4" 4"

2"

2"

2"

2"

2"

SS

SS

SS

SS

SS

SS

3" SS UP

15 158" SD

CONNECT TO

EXISTING 8" SD

UP

SD

6"

EXISTING 8" SD

TO REMAIN

16 16 16

17 ESP, REFER

TO 11/P-501

IE = 96'-11"

4" SS UP

SS

4"

IE = 96'-1"

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec tN o.

:F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

,N C

N or th C ar ol in a

A ir

N at io na lG ua rd C

-1

C on ve rs io n:

A dd

/A lte rS m al lT er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

5/27/2020 8:59: 47

AM

UNDERFLOOR PLUMBING

P-101

LLP

WBB

WBB

SHEET KEYNOTES

GENERAL NOTES

1. REFER TO CIVIL SHEET C110 FOR

CONTINUATION.

2. NEW 2 1/2" DOMESTIC WATER SERVICE FROM

BELOW.

3. 2" VENT UP.

4. 2" SS UP FROM 2" TRAP.

5. 3" SS UP FROM 3" TRAP.

6. APPROXIMATE LOCATION OF EXISTING WASTE

PIPING SYSTEM TO BE ABANDONED, SHOWN

THIS PLAN FOR REFERENCE ONLY.

7. 4" SS UP FROM 4" TRAP.

8. 6" SD UP.

9. 4" SS FROM FLOOR ABOVE.

10. 3" SS FROM FLOOR ABOVE.

11. 2" SS UP.

12. 6" SD @ 1/8" PER FOOT SLOPE MINIMUM.

13. 4" SS UP.

14. 2" SS DOWN, 2" VENT UP.

15. 1/2" TRAP PRIMER LINE UP.

16. EXISTING STORM DRAIN TO BE ABANDONED.

17. 2" FROM SUMP PUMP UP TO ABOVE FLOOR.

18. COORDINATE LOCATION OF SUMP PUMP WITH

REQUIREMENTS OF ELEVATOR SUPPLIER.

N

0 4' 8' 16'

1/8" = 1'-0"

SCALE 1/8" = 1'-0"

UNDERFLOOR PLUMBING PLAN1

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

B. EXISTING BUILDING SLAB TO REMAIN

UNDISTURBED EXCEPT FOR NEW WORK AREAS

& AS APPROVED OR REQUIRED BY ARCHITECT.

C. UPON COMPLETION OF PIPING BELOW GRADE

REPAIR CONCRETE FLOOR, WHERE SAW CUT,

TO MATCH EXSISTING.

D. ANY ABANDONED IN PLACE PIPING MAY BE CUT

OR REMOVED FOR INSTALLATION OF NEW

PIPING TO COMPLETE WORK.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 F

SEAL

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

SD

6"

1/8" PER FOOT

SLOPE MIN

V

6" SD DN

SS

25 25

2" VENT UP

3/4"

V

2"

1 1/2" 1 1/2"

3/4"

HIGH AS

POSSIBLE1"

P-

P-

P-

P-

P-

P-

P-

P-7

P-6 P-9

2 1/2"

4" FS

2"

P-

P-4 P-8

1 1/2" 2 1/2"

P-1 P-2

P-5 P-5P-

P-10

FIRE

1"

4" FS

4" FS

3"

COMM

C O

R R

ID

O

R

ELEC

UNISEX

RAMP

CARGO

FLEET

STOR

JOINT

INSPECTION

LOCKERS

PPE

TRAINING

BAG

FLEET

OFFICE

COFFEE

JAN

ELEV

BAGGAGE

SCAN

CORRIDOR

FLEET

WORK

MEN

WOMEN

STAIR

#1

PALLET

BUILD-UP

LAV

TRUCK

CIRCULATION

BAGGAGE

CHECK-IN

PASSENGER

HOLDING

PASSENGER

HOLDING

STERILE

28 28

WATER

FILTERS

3/4" CW UP

8" SD FROM

ABOVE

EXISTING 4"

SD DOWN

P-

2"

4" FCO

FCO

DBP

FCO

2 1/2"

PUMP

ROOM

BFP2

356" SD FROM

ABOVE

6" SD

DOWN

3/4"

WH

WH

WH

3 WH

3 WH

3/4"

3/4" CW FROM

ABOVE THRU

BALL VALVE

3/4" CW FROM

ABOVE THRU

BALL VALVE

HB

2" SUMP PUMP LINE FROM

BELOW. DISCHARGE TO

MOP SINK AS SHOWN

THRU AIR GAP.

FCO WITH

DUCTILE

IRON TOP 4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

2/23/2021 12:44 :36 PM

GROUND FLOOR PLUMBING

P-102

LLP

WBB

WBB

SHEET KEYNOTES

GENERAL NOTES

1. 2 1/2" DOMESTIC WATER SERVICE UP FROM

BELOW GRADE. STAY BELOW FIRE

PROTECTION WALL PANELS.

2. 2" BACKFLOW PREVENTER. MOUNT BELOW FIRE

PROTECTION WALL PANELS.

3. HOSE BIBB OR WALL HYDRANT, 18" AFF OR ABV

FINISHED GRADE.

4. 2" FD.

5. LOCATION OF WATER HEATER INTAKE & FLUE

THRU-WALL TERMINAL, REFER TO MECH.

6. DOMESTIC WATER HEATER DWH, 199,000 BTU.

7. THERMOSTATIC MIXING VALVE (TMV) MOUNTED

ON WALL.

8. HOT WATER CIRCULATOR PUMP (CP1),

MOUNTED ON WALL.

9. EXPANSION TANK FOR DOMESTIC HOT WATER

SYSTEM, SUSPENDED UP HIGH.

10. 3/4" COLD WATER UP.

11. 3" VENT UP THRU ROOF.

12. 2" VENT UP TO FLOOR ABOVE.

13. 4" SS FROM FLOOR ABOVE.

14. 4" SS DOWN TO BELOW FLOOR.

15. 3" SS FROM MECH RM FLOOR DRAINS TO

BELOW FLOOR.

16. 3/4" HW AND 1/2" CW TO DISHWASHER.

17. OWNER FURNISHED ICE MAKER.

18. PROVIDE ACCESS AT BALL VALVE(S).

19. 6" SD FROM SRD ABOVE.

20. DOWNSPOUT NOZZLE, 18" ABV FINISHED

GRADE.

21. 2" VENT UP.

22. FLOOR CLEANOUT.

23. 2" SS DOWN TO FLOOR BELOW.

24. 3" FLOOR DRAIN.

25. 3" SS UP FROM 3" TRAP.

26. 2" VENT FROM BELOW.

27. 3/4" CW DOWN TO FILTERS.

28. EXISTING 4" SD TO REMAIN.

29. 4" SS FROM BELOW, 4" WCO ABOVE FLOOR,

THEN 2" VENT UP.

30. 3/4" TO P-11 MOUNTED ON WALL.

31. 3/4" TO ICE MAKER.

32. WCO ABOVE FLOOR, 4" SS DOWN, 1 1/2" VENT

UP, CONNECT TO 2" VENT, 2" VENT UP.

33. 1/2" CW DOWN THRU TRAP PRIMER VALVE,

ROUTE LINE TO DISCHARGE TO FLOOR

SINK/DRAIN THRU AIR GAP.

34. 2" SS UP FROM 2" TRAP AND 1/2" TRAP PRIMER

LINE UP, TYP OF 2 @ 2ND FLOOR RESTROOMS.

35. PROVIDE LAV DRAIN TRAP PRIMER.

36. 1/2" COMPRESSED AIR FROM ABOVE WITH DRIP

LEG.

37. NOT USED

38. POWDER COATED HOSE REEL WITH 1/4" ID, 40

FT, 300 PSI HOSE WITH 1/4" QUICK DISCONNECT.

39. ELECTRIC VENTLESS DOOR-STYLE

DISHWASHING MACHINE COMPLETE WITH THE

FOLLOWING OPTIONS, PRESSURE REGULATING

VALVE, WATER HAMMER ARRESTOR KIT,

SINGLE POINT ELECTRIC KIT (FIELD INSTALLED)

AND DRAIN WATER TEMPERING KIT.

40. WH ABOVE DOWNSPOUT NOZZLE (APPROX 2' 6"

AFF)

N

0 4' 8' 16'

1/8" = 1'-0"

SCALE 1/8" = 1'-0"

GROUND FLOOR PLUMBING PLAN1

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

1 ADDENDUM #1 03/03/2021

SEAL

050568

Tectonic Copyright 2007

LOW ROOF

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

SD

SD

3/4" CW UP

TO RH

3" FD

3" FD

PRDPRD

SRDSRD

2" F

D P-

P-

P-

P- 4P-6 2" F

D

3" VTR

MECH.

CORR

DCC

ADMIN

IDO

SIPR

ATOC

UNISEX

UNISEX

CONF

CORR

SUPERVISOR

MANAGER

CORR

TO

LIBRARY

HOTEL

/ QC

BREAKRM

LOAD

PLANNING

CORR

CORRIDOR

ADMIN

LAV

TRUCK

STAIR

#1

ELEV

SD

WH8" SLOPED @

1/4" PER FOOT

MINIMUM

8" SLOPED @

1/8" PER FOOT

MINIMUM

8" SLOPED @

1/8" PER FOOT

MINIMUM

6" SLOPED @

1/8" PER FOOT

MINIMUM

UB

12 3

SD

16 17 151515

SD SD

6" SD DOWN

A

A

1/2"

10' MIN BETWEEN

PLUMBING VENTS

AND AIR INTAKES

3/4" CW

DOWN

3/4" CW

DOWN

3/4" CW

FROM

BELOW

3/4" CW APPROX 22'

ABOVE FINISHED

FLOOR

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

2/23/2021 12:44 :39 PM

SECOND FLOOR PLUMBING

P-103

LLP

WBB

WBB

SHEET KEYNOTES

GENERAL NOTES

1. 1 1/2" COLD WATER FROM BELOW.

2. 3" VENT FROM BELOW, 3" VTR.

3. 3/4" COLD WATER FROM BELOW UP THRU BALL

VALVE WITH HB IN VERTICAL.

4. 3/4" CW FROM BELOW.

5. 3/4" BACKFLOW PREVENTER (BFP2).

6. 3/4" NPW FOR MAKEUP WATER CONNECTION

FOR HEATING WATER SYSTEM. REF MECH.

7. 2" VENT FROM BELOW, OFFSET IN WALL AND

CONNECT TO 2" VENT FROM BELOW.

8. 4" SS DOWN.

9. 2" VENT FROM BELOW, 2" VENT UP, 3" VTR.

10. 6" SD FROM SECONDARY ROOF DRAIN ABOVE.

11. 8" SECONDARY SD DOWN.

12. 1/2" CW DOWN THRU TRAP PRIMER VALVE,

DISCHARGE TO FLOOR DRAIN THRU AIR GAP.

13. 7' MIN ABOVE FINISHED FLOOR.

14. 1/2" CW TO 2 TRAP PRIMER VALVES.

15. 4" SD FROM PRD.

16. 4" SD @ 1/4" PER FOOT SLOPE MINIMUM.

17. 6" SD @ 1/8" PER FOOT SLOPE MINIMUM.

18. 1/2" COMPRESSED AIR DOWN TO HOSE REEL.

19. AIR COMPRESSOR AC-1. SINGLE STAGE BELT

DRIVE, 60 GALLON VERTICAL ASME TANK, 3 HP,

208V, SINGLE PHASE, 135 PSI MAX, 11.3 CFM @

90 PSI.

N

0 4' 8' 16'

1/8" = 1'-0"

SCALE 1/8" = 1'-0"

SECOND FLOOR PLUMBING PLAN1

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

1 ADDENDUM #1 03/03/2021

SEAL

050568

MECH EQUIP SHOWN FOR REF

ONLY, REFER MECH PLANS

1 2 3 4 5 6 7 8 9 10 11

A

B

C

D

E

F

RH

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec tN o.

:F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

,N C

N or th C ar ol in a

A ir

N at io na lG ua rd C

-1

C on ve rs io n:

A dd

/A lte rS m al lT er m in al

B ld g

H :\P

R J\2018072 0\03-B

IM

\06-Plbg\80720_Plbg.rv t

5/27/2020 9:00: 15

AM

ROOF PLUMBING

P-104

LLP

WBB

WBB

SHEET KEYNOTES

GENERAL NOTES

1. INSTALL NEW PRIMARY ROOF DRAIN (PRD) TO

ATTACH TO EXISTING ROOF DRAIN LEADER

BELOW. FIELD-VERIFY LOCATION OF EXISTING

ROOF PENETRATION & COORDINATE WITH

EXISTING ROOFING WHICH IS TO REMAIN

(RECENTLY REPLACED).

2. INSTALL NEW SECONDARY ROOF DRAIN (SRD)

ADJACENT TO EACH EXISTING ROOF DRAIN.

COORDINATE WITH EXISTING ROOFING WHICH

IS TO REMAIN (RECENTLY REPLACED).

3. 3" VTR.

N

0 4' 8' 16'

1/8" = 1'-0"

SCALE 1/8" = 1'-0"

ROOF PLUMBING PLAN1

A. REFER TO P-001 FOR LEGEND, ABBREVIATIONS,

& GENERAL NOTES.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 F

SEAL

1/2" TRAP PRIMER

SUPPLY, TOP

CONNECTION

DOMESTIC COLD WATER LINE (1 1/2" OR

SMALLER)

TRAP PRIMER VALVE. MUST BE ACCESSIBLE.

1/2" TRAP PRIMER LINE (TYP)

FLOOR DRAIN OR

FLOOR SINK

INSTALL MIN 1'-0" AFF

BALL VALVE. MUST BE ACCESSIBLE.

UNION

1. REFER TO PLANS FOR TRAP PRIMER LINES THAT DISCHARGE TO FLOOR

DRAIN THRU AIR GAP.

FLOOR SLAB

DEEP SEAL P-TRAP

TO TRAP PRIMER

CONNECTION ON FLOOR

DRAIN/FLOOR SINK

NOTES:1

VARIES; PROVIDE

EXTENSION PIECE

AS REQUIRED

FINISHED FLOOR

CLEANOUT COVER

COUNTER SUNK SCREW

CONCRETE SURFACE

OR FLOOR COVERING

AS REQUIRED

CAULKING

FERRULE

CLEANOUT PLUG

CLEANOUT

TEE

VARIES

STAINLESS STEEL

CLEANOUT COVER

COUNTER SUNK SCREW

COUNTER SUNK

BRASS PLUG

FINISHED WALL

HWR

HW

G TMV

NC

A

3/4"

1 1/2"

120°F

1 1/2"

3/4"

1 1/4"

PLUG VALVE

DRIP LEG

(LINE SIZE)

6" CONCRETE PAD

UNION

(TYP)

1 1/2"

BALANCING VALVE

BALANCING VALVE

FOR CIRCULATOR

AQUASTAT,

ON @ 105°F,

OFF @ 110°F

1 1/2"

140°F

CP1

FINISHED FLOOR

DWH

TO FLOOR DRAIN

P&T RELIEF VALVE

CW 1 1/2"

CHECK VALVE

120°F

3/4"

HB

THERMAL EXPANSION TANK, 5 GALLON VOLUME,

3.3 GALLON ACCEPTANCE, ASME SECTION VIII

CONSTRUCTION, BUTYL…

This is the start of the file's text. The full file is on GovTribe.