ATTACHMENT 23-DRAWINGS-SAT-VOL 4 OF 4 Electrical 33 pages.pdf

PDF 10 MB Posted

Attached to
145 Airlift Wing Add/Alter Small Air Terminal Building 5
Solicitation number
W50S87-21-B-5005
Issued by

About this file

This notice is a solicitation for construction services related to the 145 Airlift Wing Add/Alter Small Air Terminal Building 5 project. The solicitation seeks bids for construction work including additions and alterations to the small air terminal building at the 145th Airlift Wing facility. Interested parties are encouraged to attend a pre-bid conference on June 2, 2021 to register and receive additional details. Bids are to be submitted in response to Solicitation Number W50S87-21-B-5005 issued by the Department of the Army North Carolina Army National Guard. The solicitation includes drawings, specifications and other attachments outlining the project scope and requirements.

View the file

Other files

File Type Posted
Questions and Answers 15 JULY 2021.pdf PDF
NC ANG SAT ADF Addendum No 4.pdf PDF
Questions and Answers 13 JULY 2021.pdf PDF
W50S87-21-B-5005-0003.pdf PDF
W50S87-21-B-5005 0002.pdf PDF
Amendment 0002 Revised Drawing and Specifications.pdf PDF
Questions and Answers 1 July 2021.docx DOCX document
ATTACHMENT 4 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 4 of 4 258 pages.pdf PDF
ATTACHMENT 21-DRAWINGS-SAT-VOL 2 OF 4 Architecture Interiors 32 pages.pdf PDF
Pre-Bid sign in sheet.pdf PDF
ATTACHMENT 22-DRAWINGS-SAT-VOL 3 OF 4 Fire Protection Plumbing Mechanical 36 pages.pdf PDF
ATTACHMENT 3 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 3 of 4 476 pages.pdf PDF
ATTACHMENT 20- DRAWINGS-SAT-VOL 1 OF 4 General Civil Landscape Structural 28 pages.pdf PDF
ATTACHMENT 18 Drawings ADF - Volume 1 of 2 General Civil Structural 24 pages.pdf PDF
ATTACHMENT 1 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 1 of 4 524 pages.pdf PDF
ATTACHMENT 19 Drawings ADF - Volume 2 of 2 Architecture FP Plumbing 58 pages.pdf PDF
Amendment 0001 Add Alter Small Air Terminal Building 5.pdf PDF
PreBidSlides_W50S87-21-B-5005 Date1 June 2021.pdf PDF
ATTACHMENT 2 SPECS SAT FJRP052994 - ADF FJRP199040 dated 4 June 2021 Vol 2 of 4 578 pages.pdf PDF
ATTACHMENT 3 SPECS SAT FJRP052994 ADF FJRP199040 Volume 3 of 4.pdf PDF
ATTACHMENT 11 Brand name justification SAT Monaco Fire alarm trasceiver_Redacted.pdf PDF
ATTACHMENT 14 Pre Bid Conference and Site Visit Bid Drop-Off Map.pdf PDF
ATTACHMENT 1 SPECS SAT FJRP052994 ADF FJRP199040 Volume 1 of 4.pdf PDF
ATTACHMENT 10 Brand name justification SAT Interior and exterior finishes_Redacted.pdf PDF
ATTACHMENT 8 Brand name justification SAT Alerton - Direct Digital Controls_Redacted.pdf PDF
ATTACHMENT 12 Brand name justification SAT Sika Sarnafil PVC roof membrane_Redacted.pdf PDF
ATTACHMENT 7 STATEMENT OF WORK - Add-Alter Small Air Terminal.pdf PDF
W50S87-21-B-5005.pdf PDF
ATTACHMENT 2 SPECS SAT FJRP052994 ADF FJRP199040 Volume 2 of 4.pdf PDF
ATTACHMENT 16 145 AW Contractor Security Guide.pdf PDF
ATTACHMENT 15 145 AW Contractor Safety Guide.pdf PDF
ATTACHMENT 5 DRAWINGS 145 AW Air Drop Facility Vol 1 of 2.pdf PDF
ATTACHMENT 4 SPECS SAT FJRP052994 ADF FJRP199040 Volume 4 of 4.pdf PDF
ATTACHMENT 9 Brand name justification SAT Best Door hardware_Redacted.pdf PDF
ATTACHMENT 6 DRAWINGS 145 AW Air Drop Facility Vol 2 of 2.pdf PDF
ATTACHMENT 13 Visitor Request Worksheet.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C- 17A Globe m aster I II

C-17A Globemaster III

C-1 7A

Globe m as ter I

II

C-17A Globe m aster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III C- 17A Globe m aster I II

C-17A Globemaster III

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II rwall rwall walltank rwall

A I R P O R T D R I V E

HE

RC

UL

ES

Av e rwall rw al l rwall wall tank tank wall

PRIVATE ROAD

SABER DRIVE

BRICK SCR EEN WALL

C O N C.

RE

T AI N

I N G W A

L L

Payne Blvd

Hercules Ave

E n l i st e d

Dr i v e

H e r c ul es A v e

Stair s wall tank tank

Payne Avenue

MORRIS FIELD DRIVE

T

SOUTH ECP

S A

BE

R

DR

IV

E

PROJECT LOCATION

AIR DROP AND BUILDING 5

North Carolina Air National Guard

COMBINED PACKAGE

Charlotte, North Carolina

ISSUE FOR BIDS - MARCH 3, 2021

2000 East Lamar Boulevard, Suite 600 Arlington, Texas 76006

Telephone: 817.588.3010 www.fsb-ae.com

Frankfurt Short Bruza / Texas Architecture Engineering Planning Interior Design

C-17 Conversion: Air Drop Facility Project Number FJRP199040

C-17 Conversion: Small Terminal Project Number FJRP052994

C

-1

AD

AL

A ir

D ro p Fa c

SCALE: 1" = 30'-0"

PROJECT LOCATION1

N

0 30' 60'

THE TWO PROJECTS ISSUED FOR BID UNDER

THIS COVER SHALL BE PRICED INDEPENDENTLY

AS INDICATED ON THE BID SHEETS ISSUED BY

THE NORTH CAROLINA AIR NATIONAL GUARD.

THAT SHALL INCLUDE ANY CHANGES ISSUED

SUBSEQUENTLY DURING THE BIDDING OR

CONSTRUCTION PHASES.

THE LIMITS OF THE WORK FOR PRICING

PURPOSES IS INDICATED WITH EACH PROJECT

SET OF DRAWINGS. HOWEVER, THE WORK SHALL

BE SCHEDULED, PERFORMED AND

COORDINATED AS THOUGH IT WERE A SINGLE

SET OF CONSTRUCTION DOCUMENTS.

050024

C- 17A Globe m aster I II

C-17A Globemaster III

C-1 7A

Globe m as ter I

II

C-17A Globe m aster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-

A Globe m as ter

III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III C- 17A Globe m aster I II

C-17A Globemaster III

C-17A Globemaster III

C- 17A Globe m aster I II

C-17A Globemaster III

C- 17A Globe m aster I II rwall rwall walltank rwall

A I R P O R T D R I V E

HE

RC

UL

ES

Av e rwall rw al l rwall wall tank tank wall

PRIVATE ROAD

SABER DRIVE

BRICK SCR EEN WALL

C O N C.

RE

T AI N

I N G W A

L L

Payne Blvd

Hercules Ave

E n l i st e d

Dr i v e

H e r c ul es A v e

Stair s wall tank tank

Payne Avenue

MORRIS FIELD DRIVE

T

SOUTH ECP

S A

BE

R

DR

IV

E

PROJECT LOCATION

North Carolina Air National Guard C-17 Conversion Add/Alter Small Air Terminal - Building 5

Charlotte, North Carolina Project Number: FJRP 052994

ISSUE FOR BIDS - MARCH 03, 2021

2000 East Lamar Boulevard, Suite 600 Arlington, Texas 76006

Telephone: 817.588.3010 www.fsb-ae.com

Frankfurt Short Bruza / Texas Architecture Engineering Planning Interior Design

NORTH CAROLINA CERTIFICATE

OF AUTHORIZATION

ARCHITECTURE: # 53655

EXP: 12/31/2021

NORTH CAROLINA CERTIFICATE

OF AUTHORIZATION

PE: # C-4735

EXP: 06/30/2021

SCALE 1" = 30'-0"

PROJECT LOCATION1

SHEET INDEX

NUMBER TITLE

PLUMBING

P-001 LEGEND & ABBREVIATIONS

PD101 PLUMBING DEMOLITION - UNDERFLOOR & FIRST

FLOOR

PD102 PLUMBING DEMOLITION - SECOND FLOOR &

ROOF

P-101 UNDERFLOOR PLUMBING

P-102 GROUND FLOOR PLUMBING

P-103 SECOND FLOOR PLUMBING

P-104 ROOF PLUMBING

P-501 PLUMBING DETAILS

P-601 DOMESTIC WATER RISER

P-602 WASTE AND VENT RISER

P-701 PLUMBING SCHEDULES

MECHANICAL

M-001 LEGEND & ABBREVIATIONS

MD101 GROUND FLOOR MECHANICAL DEMOLITION

PLAN

MD102 SECOND FLOOR MECHANICAL DEMOLITION

PLAN

MD103 ROOF MECHANICAL DEMOLITION PLAN

MH101 GROUND FLOOR MECHANICAL HVAC PLAN

MH102 SECOND FLOOR MECHANICAL HVAC PLAN

MH103 ROOF MECHANICAL HVAC PLAN

MP101 GROUND FLOOR MECHANICAL PIPING PLAN

MP102 SECOND FLOOR MECHANICAL PIPING PLAN

M-301 SECTIONS

M-401 ENLARGED PLANS

M-501 DETAILS

M-601 FLOW DIAGRAMS

M-701 MECHANICAL SCHEDULES

M-702 MECHANICAL SCHEDULES

M-801 MECHANICAL CONTROLS

M-802 MECHANICAL CONTROLS

ELECTRICAL

E-001 LEGEND, ABBREVIATIONS & MOUNTING HEIGHT

DETAIL

ES101 ELECTRICAL SITE LIGHTING PLAN

ES102 ELECTRICAL SITE PLAN

ED101 GROUND FLOOR ELECTRICAL DEMOLITION

PLAN

ED102 SECOND FLOOR ELECTRICAL DEMOLITION

PLAN

EG101 GROUNDING PLAN & GROUNDING SYSTEM

DIAGRAM

EG102 LIGHTNING PROTECTION PLAN

EG500 GROUNDING & LIGHTNING PROTECTION

DETAILS

EG501 GROUNDING & LIGHTNING PROTECTION

DETAILS

EP101 GROUND FLOOR POWER PLAN

EP102 SECOND FLOOR POWER PLAN

EP103 ROOF POWER PLAN

EP104 GROUND FLOOR MECHANICAL POWER PLAN

EP105 SECOND FLOOR MECHANICAL POWER PLAN

EP600 ONE-LINE DIAGRAM, FEEDER SCHEDULE &

MECHANICAL EQUIPMENT SCHEDULE

EP700 PANEL SCHEDULES

EP701 PANEL SCHEDULES

EL101 GROUND FLOOR LIGHTING PLAN

EL102 SECOND FLOOR LIGHTING PLAN

EL501 LIGHTING DETAILS

EL700 LIGHTING SCHEDULES

EY101 ELECTRICAL INTERIOR AUXILIARY SYSTEMS

EY101-PA ELECTRICAL SPECIAL SYSTEMS PUBLIC

ADDRESS

EY102 SECOND FLOOR SPECIAL SYSTEMS PLAN

EY501 SPECIAL SYSTEMS DETAILS

EY601 SPECIAL SYSTEMS RISER DIAGRAMS

ET101 GROUND FLOOR TELECOMMUNICATION PLAN

ET102 SECOND FLOOR TELECOMMUNICATION PLAN

ET501 TELECOM DETAILS

ET601 DIGITAL CLOCK RISER DIAGRAM

ET602 TELECOM RISER DIAGRAM

SHEET INDEX

NUMBER TITLE

GENERAL

G-001 COVER SHEET, SHEET INDEX & VICINITY PLAN

G-101 CODE AND LIFE SAFETY PLAN

G-102 APPENDIX B CODE SHEETS

CIVIL

C100 EXISTING CONDITIONS PLAN

C101 DEMOLITION PLAN

C102 SITE PLAN

C110 UTILITY PLAN

C111 TEMPORARY UTILITY PLAN

C112 EXTERIOR STAIRWAY PLAN

C501 CONSTRUCTION DETAILS

C502 CONSTRUCTION DETAILS

LANDSCAPE

LS100 LANDSCAPE SITE PLAN

LS400 ENLARGED LAYOUT PLANS

LP100 LANDSCAPE PLANTING PLAN

LP500 PLANTING DETAILS / PLANTING SCHEDULE

STRUCTURAL

S-001 GENERAL NOTES

S-002 TYPICAL DETAILS

SB101 FOUNDATION PLAN

SB301 FOUNDATION DETAILS

SB501 FOUNDATION DETAILS

SF101 SECOND FLOOR FRAMING PLAN

SF102 HIGH ROOF FRAMING PLAN

SF201 FRAMING ELEVATIONS

SF202 FRAMING ELEVATIONS

SF501 FRAMING DETAILS

SF502 FRAMING DETAILS

ARCHITECTURE

A-001 ABBREVIATIONS, ACCESSIBILITY, PARTITIONS &

SYMBOLS

AD101 DEMOLITION PLANS

AD102 DEMOLITION ROOF PLAN

AE101 GROUND FLOOR PLAN

AE102 SECOND FLOOR PLAN

AE103 REFLECTED CEILING PLANS

AE104 REFLECTED CEILING DETAILS

AE105 ROOF PLAN

AE201 BUILDING ELEVATIONS

AE301 BUILDING SECTIONS

AE310 WALL SECTIONS

AE311 WALL SECTIONS

AE401 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE402 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE403 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE404 INTERIOR ELEVATIONS

AE405 ENLARGED STAIR PLANS & SECTION

AE406 ENLARGED STAIR PLANS & ELEVATIONS

AE407 ENLARGED ELEVATOR PLANS & DETAILS

AE408 ENLARGED EXTERIOR STAIRS

AE501 PLAN DETAILS

AE601 DOOR SCHEDULE AND DETAILS

AE602 DOOR DETAILS

AE603 GLAZING DETAILS

AE604 ROOM FINISH SCHEDULE

AG101 GROUND FLOOR SIGNAGE PLAN

AG102 SECOND FLOOR SIGNAGE PLAN

AG103 SIGNAGE DETAILS

AG104 SIGNAGE DETAILS & SCHEDULE

INTERIORS

IF101 GROUND FLOOR FURNITURE PLAN

IF102 SECOND FLOOR FURNITURE PLAN

FIRE PROTECTION

FP001 FIRE PROTECTION, LEGEND, ABBREVIATIONS,

AND PIPING SCHEMATIC

FP101 GROUND FLOOR FIRE PROTECTION PLAN

FP102 SECOND FLOOR FIRE PROTECTION PLAN

FP401 FIRE PROTECTION ENLARGED PLANS AND

SECTIONS

FP501 FIRE ALARM & MASS NOTIFICATION RISER

DIAGRAM

FP601 FIRE ALARM & MASS NOTIFICATION

INPUT/OUTPUT MATRIX

SEAL

050568

ENGINEE

R

Frankfurt-Short-Bruza Architects Engineers Planners

11949

VOLUME 4 OF 4

TWO POLE SWITCH

THREE WAY SWITCH

FOUR WAY SWITCH

DIMMER SWITCH

MOTION DETECTOR - WALL

MOUNTED SWITCH

WEATHER PROOF SWITCH

OCCUPANCY SENSOR MOTION DETECTOR -

CEILING MOUNTED

MANUAL MOTOR STARTER

PILOT LIGHT SWITCH

KEY OPERATED SWITCH

LOW VOLTAGE SWITCH

DUAL RELAY PIR OCCUPANCY

SENSOR

OCCUPANCY SENSOR MOTION DETECTOR -

POWER PACK / CONTROL RELAY

LIGHTING DEVICES

SINGLE POLE SWITCH

JUNCTION BOX

JUNCTION BOX - DATA

FLOOR JUNCTION BOX

RELAY

POWER POLE

TELECOMMUNICATIONS POWER

POLE

ACCESS CONTROL SYSTEM

PUSH BUTTON - SWITCH

2 PUSH BUTTON - SWITCH

3 PUSH BUTTON - SWITCH

VARIABLE FREQUENCY DRIVE

PHOTOCELL

METER AND SOCKET BASE

DATA DEVICES

TELEPHONE

PUBLIC TELEPHONE

WALL TELEPHONE

TELEPHONE / DATA OUTLET

DATA OUTLET

TELEPHONE OUTLET FLOOR

TELEPHONE/DATA OUTLET FLOOR

DATA OUTLET FLOOR

SPEAKER - SURFACE MOUNTED

OR SUSPENDED

SPEAKER - RECESSED

WALL SPEAKER

MICROPHONE

BUZZER

AMPLIFIER

INTERCOM PUSH BUTTON FOR

2-WAY COMMUNICATION

KEY PAD WITH ARM / DISARM

DOOR LOCK

INFRARED MOTION SENSOR

CARD READER

MAGNETIC SWITCH

PASSIVE INFERRED SENSOR

EXIT PUSH BUTTON

BREAK GLASS SENSOR

SECURITY CONTROL CONSOLE

BALANCED MAGNETIC SWITCH

ANTENNA

TV ANTENNA

TIME CLOCK

CLOSED CIRCUIT TV CAMERA

TV OUTLET

SINGLE SIDED CLOCK

DOUBLE SIDED CLOCK

CIRCUITING

CONDUIT CONCEALED IN WALL OR

ABOVE CEILING

CONDUIT RUN EXPOSED

CONDUIT CONCEALED IN SLAB OR

UNDERGROUND

BRANCH CIRCUIT, SLASHES

DENOTE NUMBER OF

CONDUCTORS, ( ) DENOTES

GROUND WIRE NO SLASHES

DENOTE NO LESS THAN

2-#12, 1-#12 GND.

CONDUIT HOME RUN TO PANEL

BOARD ARROWHEADS DENOTE

NUMBER OF CIRCUITS

PC PART CIRCUIT

LV

CONDUIT TURNING UP

CONDUIT TURNING DOWN

ELEVATION CHANGE IN CONDUIT

CONDUIT SEAL

LOW VOLTAGE WIRING

FLEXIBLE CONDUIT

GROUNDING / LIGHTNING PROTECTION

GROUND ROD, 3/4" X 10' LONG

COPPERWELD

GROUND ROD, EXOTHERMIC

COUNTERPOISE CONNECTION

GROUND WELL ACCESSIBLE

CONNECTION

AIR TERMINAL

CONDUCTOR CONNECTION

STATIC GROUND RECEPTACLE

LIGHTNING PROTECTION MAIN

CONDUCTOR

BURIED GROUND CONDUCTOR

SINGLE LINE DIAGRAM

FUSED SWITCH

NON - FUSED SWITCH

CIRCUIT BREAKER, 600 VOLTS

AND BELOW

DRAWOUT CIRCUIT BREAKER, 600

VOLTS AND BELOW

DRAWOUT CIRCUIT BREAKER,

MEDIUM VOLTAGE

800AT

800AF

BREAKER TRIP SETTING

BREAKER FRAME SIZE

OR

FUSE SIZE

FRAME SIZE

POWER TRANSFORMER

AUTO TRANSFORMER

STRESS CONE

KILOWATT HOUR DEMAND METER

GENERATOR

CONTROL POWER TRANSFORMER

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

DELTA - WYE

DIGITAL METER

TRANSIENT VOLTAGE SURGE

SUPPRESSOR

CPT

PT

CT

SCHEMATIC

CONTACT, NORMALLY CLOSED

CONTACT, NORMALLY OPEN

FS

OL

SD

TC

PC

FIRE ALARM SYSTEM SHUT DOWN

CONTACT

FREEZE STAT - SHUT DOWN

CONTACT

THERMAL OVERLOAD CONTACT

SMOKE DETECTOR - SHUT DOWN

CONTACT

TIME CLOCK CONTACT

PHOTOCELL CONTACT

CONTACT OR CONTACT - COIL

LIGHTING FIXTURE OR

INDICATING LAMP

MOTOR CONTACT COIL

HAND / OFF / AUTO SWITCH

TIME CLOCK MOTOR

OVERLOAD RELAY

BATTERY

LIMIT SWITCH NORMALLY OPEN

LIMIT SWITCH NORMALLY CLOSED

SOLENOID

FUSE

PHOTOCELL

RELAY

SOLENOID COIL

ON OFF

ON / OFF SWITCH

NORMALLY OPEN PUSH - BUTTON

NORMALLY CLOSED PUSH -

BUTTON

WIRELESS ROUTER

MOTOR CONNECTION

UNFUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

DISCONNECT SWITCH FURNISHED

WITH EQUIPMENT

COMBINATION MOTOR STARTER

MOTOR STARTER

120 / 208 VOLT PANEL BOARD

277 / 480 VOLT PANEL BOARD

LIGHTING CONTACTOR

DURESS ALARM PUSH BUTTON

CLOSED CIRCUIT TV MONITOR

CABLE TRAY

TRANSFORMER

DATA OUTLET CEILING

REQUEST EXIT

SG

FA

OR

ELECTRICAL LEGEND

DESCRIPTIONSYMBOL DESCRIPTIONABBREVIATIONS

LIGHT FIXTURES

RECESSED LIGHT FIXTURE

STRIP LIGHT FIXTURE

WALL WASHER

RECESSED DOWN LIGHT

SUSPENDED LIGHT FIXTURE

SURFACE MOUNTED LIGHT

FIXTURE

SUSPENDED

SURFACE

SURFACE EMERGENCY

WALL MOUNTED EMERGENCY

WALL MOUNTED LIGHT

INCANDESCENT TRACK LIGHT

TRACK LIGHT WITH INTEGRAL

BALLAST

WALL MOUNTED LIGHT - ROUND

WALL MOUNTED SINGLE SIDE EXIT

LIGHT

WALL MOUNTED DOUBLE SIDE

EXIT LIGHT

CEILING MOUNTED SINGLE SIDE

EXIT LIGHT

CEILING MOUNTED DOUBLE SIDE

EXIT LIGHT

COMBINATION FAN - LIGHT

BATTERY POWERED EMERGENCY

LIGHT

BATTERY POWER FOR REMOTE

HEAD

REMOTE HEAD

FLOOD LIGHT

SITE LIGHTING FIXTURE

AFFF

AFF

AFG

AIC

AL

BCT

BKR

BOF

BSC

CB

CCT

CFCI

CLG

CM

CNTRL

CONC

CONN

CR

CU

D

EG

EMCS

EMGB

EP

EWC

EXIST

FA

FACP

FO

FVNR

GB

GFCI

GFGI

GFI

GND

HH

HC

IG

LC

LSIG

MAG

MC

MCB

MCC

MCP

MH

MLO

MM

MT'D

NA

NEC

NEUT

NF

NFPA

NL

NIC

NIPRNET

NTS

OSP

PC

PF

PIR

PIV

PNL

PR

PTT

PVC

RE:

RECEPT

RGSC

SCH

SIPRNET

SM

SPECS

SP

SPD

SS

TBB

TGB

TDB

THERM

TMGB

TR

TSP

TVSS

TYP

UNO

UTP

VFD

WP

Ø

XFMR

2S2W

AQUEOUS FILM FORMING FOAM

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AMPERE INTERRUPTING CAPACITY

ALUMINUM

BONDING CONDUCTOR FOR TELECOMMUNICATIONS

BREAKER

BOTTOM OF FIXTURE

BARE STRANDED CONDUCTOR

CIRCUIT BREAKER

CIRCUIT

CONTRACTOR FURNISHED / CONTRACTOR INSTALLED

CEILING

CIRCUIT MONITOR

CONTROL

CONCRETE

CONNECTION

CONTROL RELAY

COPPER

DEDICATED

EQUIPMENT GROUND

ENERGY MANAGEMENT CONTROL SYSTEM

EQUIPMENT MAIN GROUNDING BUSBAR

EXPLOSION PROOF

ELECTRIC WATER COOLER

EXISTING

FIRE ALARM

FIRE ALARM CONTROL PANEL

FIBER OPTIC

FULL VOLTAGE NON REVERSING

GROUND BUSBAR

GOVERNMENT FURNISHED / CONTRACTOR INSTALLED

GOVERNMENT FURNISHED / GOVERNMENT INSTALLED

GROUND FAULT INTERRUPTER

GROUND

HANDHOLE

HORIZONTAL CROSS - CONNECTION

ISOLATED GROUND

LIGHTING CONTACTOR

LONG TIME, SHORT TIME, INSTANTANEOUS AND

GROUND FAULT PICKUPS

MAGNETIC

MAIN CROSS - CONNECTION

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MANHOLE

MAIN LUGS ONLY

MULTI MODE

MOUNTED

NOT APPLICABLE

NATIONAL ELECTRICAL CODE

NEUTRAL

NON FUSED

NATIONAL FIRE PROTECTION ASSOCIATION

NIGHT LIGHT

NOT IN CONTRACT

NON - CLASSIFIED INTERNET PROTOCOL ROUTER

NETWORK

NOT TO SCALE

OUTSIDE PLANT

PART CIRCUIT

POWER FACTOR

PASSIVE INFRARED

POST INDICATOR VALVE

PANELBOARD

PAIR

PUSH TO TEST

POLYVINYL CHLORIDE

REFERENCE

RECEPTACLE

RIGID GALVANIZED STEEL CONDUIT

SCHEDULE

SECRET INTERNET PROTOCOL ROUTER NETWORK

SINGLE MODE

SPECIFICATIONS

SURGE PROTECTED

SURGE PROTECTION DEVICE

STAINLESS STEEL

TELECOMMUNICATION BONDING BACKBONE

TELECOMMUNICATIONS GROUNDING BUSBAR

TOP OF DUCT BANK

THERMAL

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TELECOMMUNICATIONS ROOM

TWISTED SHIELDED PAIR

TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYPICAL

UNLESS NOTED OTHERWISE

UNSHIELDED TWISTED PAIR

VARIABLE FREQUENCY DRIVE

WEATHER PROOF

PHASE

TRANSFORMER

TWO SPEED, TWO WINDING

STRIP LIGHT FIXTURE W/

EMERGENCY BATTERY PACK

RECESSED LIGHT FIXTURE

EMERGENCY

SUSPENDED LIGHT FIXTURE

EMERGENCY

SURFACE MOUNTED LIGHT

FIXTURE EMERGENCY

RECESSED DOWN LIGHT

EMERGENCY

WALL WASHER EMERGENCY

WALL MOUNTED LIGHT - ROUND

EMERGENCY

WALL MOUNTED LIGHT - SQUARE

WALL MOUNTED LIGHT - SQUARE

EMERGENCY

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

BOLLARD

ELECTRICAL FIXTURES

SIMPLEX RECEPTACLE

RECEPTACLE DUPLEX

QUADRUPLEX

RECEPTACLES - SPECIAL PURPOSE

(SEE KEYNOTES FOR TYPE)

RECEPTACLE DUPLEX -

CEILING MOUNTED

FLOOR BOX

RECEPTACLE DUPLEX -

FLOOR MOUNTED

RECEPTACLE DUPLEX -

HALF SWITCHED

RECEPTACLE DUPLEX -

HIGH VOLTAGE

SIMPLEX RECEPTACLE - FLOOR

QUADRUPLEX - CEILING

QUADRUPLEX - FLOOR

RECEPTACLE - COUNTER TOP

RECEPTACLE - GROUND FAULT

INTERRUPTER

RECEPTACLE - COUNTER TOP/

GROUND FAULT INTERRUPTER

RECEPTACLE - WEATHERPROOF

GROUND FAULT INTERRUPTER

RECEPTACLE - ISOLATED GROUND

RECEPTACLE -

SURGE PROTECTOR

RECEPTACLE - WEATHERPROOF

ELECTRICAL EQUIPMENT

TV OUTLET

TELEPHONE/DATA OUTLET

CEILING

CONTROL MODULE

DIGITAL METER

FLOOR BOX

NURSE CALL

NURSE STATION

NURSE CALL DOME LIGHT

ELECTRICAL FIXTURES

LIGHTING DEVICES

RECEPTACLES - SPECIAL PURPOSE

(SEE KEYNOTES FOR TYPE)

DATA DEVICES

JUNCTION BOX

PIT LIGHT

PUBLIC TELEPHONE

PP

TP

LC

DM

MD

WP

2MD

K

V

FL

EB

EB

FB

GFI

GFI

C

GFI

WP

IG

SP

WP

C

P

MD

MD

J

J D

J

J

P

W

MP

IR

R

PC

ACS

VFD

T

S

S R

P

M

TV

S

S

A

IC

K

CR

DL

EP

PIR

BG

BMS

S

TC

TV

W

DA

REX

CCTV

DM

C

CM

CC

FB

SCC

N

N

E

C

L

M

H O A

TC

PC

R

S

KWH

D

G

DM

TVSS

GENERAL NOTES

A. ANY DIMENSIONS SHOWN ON THESE DRAWINGS

ARE INTENDED TO PROVIDE A GENERAL

LOCATION AS REQUESTED BY THE OWNER. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR

CONFIRMING ALL DIMENSIONS PRIOR TO

ROUGH-IN AND IMMEDIATELY REPORT ANY

CONFLICTS WITH THE OUTLET PLACEMENT TO

THE GENERAL CONTRACTOR.

B. ALL CABLE BUNDLES WILL BE SUPPORTED

EVERY48"-60" OC WITH A J-HOOK OR OTHER

APPROVED PATHWAY DEVICE. REFERENCE

SPECIFICATIONS AND DETAILS FOR ADDITIONAL

CABLING PATHWAY INSTALLATION

REQUIREMENTS. CONTRACTOR WHO VIOLATES

THESE REQUIREMENTS WILL BE REQUIRED TO

REPLACE THE AFFECTED CABLE PLANT AT

THEIR EXPENSE.

C. PLASTIC TIE WRAPS ARE NOT PERMITTED AT

ANY TIME ON THIS INSTALLATION. ALL CABLE

ROUGH-IN AND DRESS-OUT WILL BE WITH

VELCRO ONLY. ALL CABLES BUNDLED WITH

PLASTIC TIE WRAPS SHALL BE IMMEDIATELY

REPLACED AT THE CONTRACTOR'S EXPENSE.

D. DO NOT INSTALL ANY CABLES IN ANY CONDUIT

SLEEVE, STUB UP, OR WALL CAP WITHOUT A

PROTECTIVE BUSHING. CABLES PULLED INTO

UNPROTECTED CONDUITS WILL BE REPLACED

AT THE CONTRACTOR'S EXPENSE. DO NOT

INSTALL ANY CABLING INTO ANY CONDUIT THAT

HAS NOT BEEN CONFIRMED TO BE BLOWN

CLEAR. COORDINATE WITH ELECTRICAL PRIOR

TO ROUGH IN OF ANY CABLING.

E. ANY CABLING FOUND PAINTED DURING THE

CONSTRUCTION PROCESS WILL BE REPLACED

AT CONTRACTOR'S EXPENSE. CONTRACTOR

SHALL COORDINATE WITH THE GENERAL

CONTRACTOR AND PAINTER TO AVOID

CONFLICTS.

F. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO REFERENCE BOTH THE

PROJECT DRAWINGS AND THE PROJECT

SPECIFICATIONS. TOGETHER THEY FORM THE

COMPLETE CONTRACT DOCUMENTS. PLEASE

REFERENCE THE PROJECT SPECIFICATIONS

FOR ALL MATERIALS, EQUIPMENT AND

COMPONENTS NOT INDICATED ON THE

DRAWING SET.

G. CONTRACTOR SHALL COORDINATE ALL FINAL

CAMERA LOCATIONS, HEIGHTS AND CAMERA

VIEWING ANGLES WITH OWNER/OWNER'S

REPRESENTATIVE. FAILURE TO COORDINATE

ALL FINAL CAMERA LOCATIONS, HEIGHTS AND

VIEW ANGLES MAY REQUIRE RELOCATION OF

CONDUITS, CABLE AND CAMERA LOCATIONS AT

CONTRACTOR'S EXPENSE.

H. CONTRACTOR SHALL COORDINATE

TECHNOLOGY, TELECOM, SECURITY AND AUDIO

VISUAL LOCATIONS SO THAT DATA AND POWER

ARE AT THE SAME HEIGHT AND SPACED 18"-24"

APART UNLESS SPECIFIED OTHERWISE.

REFERENCE TECHNOLOGY AND MEP SHEETS

FOR COORDINATION.

I. ALL CABLING INSTALLED IN AREAS WITH

EXPOSED CEILINGS SHALL BE INSTALLED IN A

PROPERLY SIZED CONDUIT PATHWAY. CONDUIT

PATHWAYS SHALL BE PROVIDED AND

INSTALLED BY THE CONTRACTOR. THE CONDUIT

MAY BE PAINTED TO MATCH CEILING COLOR AS

DIRECTED BY THE CONTRACT DOCUMENTS.

J. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO REVIEW THE ARCHITECTURAL

DEMOLITION DRAWINGS FOR ALL DEMOLITION

AREAS.

K. CONTRACTOR SHALL DOCUMENT ALL EXISTING

TECHNOLOGY, TELECOM, SECURITY AND AUDIO

VISUAL DEVICES AND LOCATIONS PRIOR TO

DEMOLITION OF CEILINGS AND SPACES.

PROVIDE TEMPORARY SUPPORT IN ALL

DEMOLITION AREAS FOR DEVICES, RE-INSTALL

ALL EXISTING DEVICES IN NEW CEILINGS.

L. CONTRACTOR SHALL DOCUMENT ALL EXISTING

CEILING TECHNOLOGY, TELECOM, SECURITY

AND AUDIO VISUAL LABELING ON EXISTING

CEILING GRID. PROVIDE NEW LABELING PER

SPECIFICATIONS.

M. CONTRACTOR SHALL BE RESPONSIBLE FOR

STOPPING ALL TECHNOLOGY, TELECOM,

SECURITY AND AUDIO VISUAL CONDUIT

PENETRATIONS FROM WATER OR RODENT

INGRESS IN ALL BUILDINGS UPON COMPLETION

OF THE PROJECT.

PULL DOWN

FIRE ALARM

" 48

" 48

WALL

MOUNTED

TELEPHONE

MANUAL

PULL

STATION

TOP OF

PULL

STATION

HANDLE

FINISHED

FLOOR

RECEPTACLE

COUNTER HT.

RECEPTACLE

ELEVATOR

CALL

BUTTON

TELE/DATA

ELEVATOR

POSITION

INDICATOR

LIGHT

SWITCHTHERMOSTAT

NOTES:

A. VERIFY EXACT MOUNTING HEIGHTS WITH PROJECT REQUIREMENTS. DEVICES MAY OR MAY

NOT APPLY TO THIS PROJECT. REFER TO PLANS.

B. ALL NEW DEVICES SHALL BE INSTALLED ACCORDING TO THE MOUNTING

HEIGHTS INDICATED ABOVE U.N.O.

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:47: 24 PM

LEGEND, ABBREVIATIONS &

MOUNTING HEIGHT DETAIL

E-001

WCM

TLP

HFM

SCALE NTS

MOUNTING HEIGHT DETAIL1

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

035238

ENG INEER

LA - 10

Q Q

Q

Q

Q

Q

Q

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ 1

TYPICAL

Q

Q

Q3

Q3

Q3

Q

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

ZZ

2"

2' -0

REINFORCEMENT

6X6 WIRE MESH

3/4" CHAMFER

1/2"-13x18" GALVANIZED STEEL ANCHOR BOLT FURNISHED

WITH BOLLARD (TYP OF 4). J-BOLT TOPS MIN 1-1/4" ABOVE

CONCRETE SURFACE.

CONCRETE SHALL

BE 3000 PSI

FINISHED GRADE

PVC CONDUIT

BOLLARD. REFER TO FIXTURE SCHEDULE.

13" DIAMETER MIN

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:49: 44 PM

ELECTRICAL SITE LIGHTING

PLAN

ES101

WCM

TLP

HFM

SHEET KEYNOTES

1. 2-#10 AWG, 1-#10 AWG GND, 3/4" PVC SCHEDULE

40 CONDUIT, DIRECT BURIED 24" BELOW FINISHED

GRADE.

2. CONTROLLED BY "RP, RELAY 19. RELAY PANEL

"RP" AND BRANCH CIRCUIT PANELBOARD "LA" ARE

LOCATED IN ELECTRICAL ROOM 104.

3. PROVIDE A POURED CONCRETE FOOTER FOR THE

BOLLARD. REFER TO DETAIL 3 ON THIS SHEET.

ARRANGE J-BOLTS ACCORDING TO THE

MANUFACTURER'S BASE PLATE DETAIL. DRIVE A

3/4" x 10' COPPER-CLAD GROUND ROD BELOW

GRADE. EXOTHERMICALLY WELD A #6 AWG

COPPER CONDUCTOR AND GROUND THE

LIGHTING FIXTURE.

4. THE STAIR SECTION IS FOR REFERENCE ONLY.

REFER TO SHEET C112 FOR EXACT DIMENSIONS

AND CONSTRUCTION DETAILS. EXACT

PLACEMENT OF THE STAIR LIGHTING IS

APPROXIMATE.

5. CONDUIT MAY RUN EXPOSED ALONG THE

OUTSIDE OF THE CONCRETE CURB.

0 2' 4' 8'

1/4" = 1'-0"

N

SCALE 1/4" = 1'-0"

ELECTRICAL SITE LIGHTING PLAN1

SCALE NTS

LIGHTING SECTION2

SCALE NTS

BOLLARD BASE DETAIL3

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

J

J

2%

2%

2%

732.32

728.82

728.74

724.24 asphalt asphalt asphalt asphalt asphalt asphalt

BRICK

WALL

BRICK

WALL

BRICK

WALL

H V A C

Jersey Barrier

WV

Vault

WV

SSMH

RIM:723.03'

INV. OUT:717.98'

concrete concrete c o n c re te concrete concrete concrete concrete concrete c o n c re te c o n c re te asphalt asphalt

Transformer

GV

GV

GV

Overhang

C ur bi ng

C ur bi ng

C u r b i n g

C u rb in g MW

MW

MW

BFP

MW

J

2 1

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/28/2020 3:08: 50 PM

ELECTRICAL SITE PLAN

ES102

WCM

TLP

HFM

SHEET KEYNOTES

1. (1) 1” AND (1) 2” SCHEDULE 40 PVC CONDUITS

DIRECT BURIED 24” BELOW FINISHED GRADE.

FILL, COMPACT AND RETURN SURFACE TO

ORIGINAL GRADE UNLESS THIS CONFLICTS WITH

CIVIL PLANS. ROUTING IS APPROXIMATE.

2. STUB UP AND CAP THE 2” CONDUIT. PROVIDE A 4”

x 4” NEMA 4X ENCLOSURE FOR THE 1” CONDUIT

CONTAINING POWER CONDUCTORS. MOUNT THE

JUNCTION BOX ON A UNISTRUT SUPPORT

ENCASED IN CONCRETE 24” BELOW GRADE. MAKE

FINAL CONNECTIONS TO THE GATE ACCESS

CONTROLS. COORDINATE THE EXACT LOCATIONS

OF BOTH STUB-UPS WITH THE GATE SECURITY

ACCESS CONTROL INSTALLATION.

3. STUB UP BOTH CONDUITS AT COMMUNICATION

ROOM 102 USING 90 DEGREE PVC COATED RGS

SWEEPS. ENTER THE BUILDING WITH THREADED

RIGID CAST IRON CONDUIT BODIES. SEAL

PENETRATIONS.

4. CONNECT POWER TO CIRCUIT TR-9.

5. CONCRETE-ENCASED DUCTBANK. PROVIDE (2) 5

INCH TYPE EB CONDUITS WITH PULL WIRES FOR

FUTURE CABLE INSTALLATION. USE

INTERLOCKING PLASTIC SPACERS EVERY 8 FEET.

MINIMUM 3" CONCRETE ENCASEMENT. MINIMUM

DEPTH IS 36" FROM TOP OF CONCRETE TO

FINISHED GRADE. MINIMUM BEND RADIUS IS 36".

INSTALL DETECTABLE MARKING TAPE.

COORDINATE WITH CIVIL PLANS.

6. EXTEND CONDUITS 12" BEYOND ENCASEMENT

AND CAP. MARK THIS LOCATION WITH A ROUND,

FLUSH, CONCRETE MARKER POST.

7. CONVERT ONE 5" EB CONDUIT TO SCHEDULE 40

AND TURN UP INTO THE HIGH VOLTAGE

COMPARTMENT UNDER THE TRANSFORMER AND

CAP. EXTEND THE OTHER 5" CONDUIT 12" BEYOND

ENCASEMENT AND CAP.

N

SCALE NTS

ELECTRICAL SITE PLAN1

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

JJJJ

J

G

FI

W P

G

FI

W P

GFI

WP

AA

B B

C C

D D

E E

F F

6 7

9 7 4

2 1 2

4 12

REMOVE ONE CONDUIT RUNNING

UP AND OVER THE ROOF.

REMOVE 5 CONDUITS RUNNING

TO TEMPORARY TRAILERS.

16 14

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\fhm \D o cum ents\M y R evit\80720_Elec_F M cN utt.rvt

3/5/2021 11:38: 44 AM

GROUND FLOOR ELECTRICAL

DEMOLITION PLAN

ED101

WCM

TLP

HFM

SCALE 1/8" = 1'-0"

GROUND FLOOR ELECTRICAL DEMOLITION PLAN1

0 4' 8' 16'

1/8" = 1'-0"

N

GENERAL NOTES

SHEET KEYNOTES

A. DEMOLISH WIRE, CONDUIT, JUNCTION BOXES,

ELECTRICAL EQUIPMENT, AND DEVICES FOR ALL

CIRCUITS IN THE BUILDING, UNO.

B. DISCONNECT ELECTRICAL SERVICE TO EXISTING

EQUIPMENT THAT IS PART OF THE RENOVATION

PER RULES AND REGULATIONS OF AUTHORITY

HAVING JURISDICTION.

C. WHERE AN ITEM IS CALLED OUT TO BE

SALVAGED, REMOVE IT UNDAMAGED, STORE AS

REQUIRED BY OWNER, AND REINSTALL IT IN ITS

NEW LOCATION, INCLUDING ANY REQUIRED

SUPPORTS, HARDWARE, UTILITIES, AND

REFINISHING.

D. WHERE ELECTRICAL WIRING IS TO BE REMOVED

FROM WALLS AND CEILINGS TO REMAIN, PATCH

EXISTING HOLES AS REQUIRED TO MATCH

ADJACENT SURFACE AND FINISH. FOR CONDUITS

TO BE DEMOLISHED, REMOVE ACCESSIBLE

CONDUITS STUBBED UP IN THE FLOOR 1” BELOW

THE SURFACE. GROUT AND REFINISH THE

SURFACE TO MATCH THE SURROUNDING

SURFACE.

E. RECEPTACLES AND OTHER EQUIPMENT SHOWN

TO BE DEMOLISHED ARE BASED ON PLANS

FURNISHED BY OTHERS AND DO NOT

REPRESENT THE FULL EXTENT OF THE WORK

REQUIRED BY THIS CONTRACT. FIELD VERIFY

EXISTING CONDITIONS PRIOR TO BIDDING ON

THIS WORK.

F. DEMOLISH ALL EXISTING LUMINARIES, CONDUIT,

WIRING, AND CONTROLS, UNO. SALVAGE THE

EXISTING FLUORESCENT FIXTURES IN THE HIGH

BAY AREA. REFER TO ID TYPE "E" IN THE

LIGHTING FIXTURE SCHEDULE. STORE PER

OWNERS INSTRUCTIONS

G. DEMOLISH ALL COMMUNICATIONS EQUIPMENT,

OUTLETS, PATHWAYS, AND CABLING, UNO.

H. SALVAGE SECURITY AND ACCESS CONTROL

EQUIPMENT AND RETURN TO OWNER FOR

REINSTALLATION BY OTHERS. COORDINATE WITH

THE OWNER’S SECURITY-PROVIDER BEFORE

REMOVING SECURITY EQUIPMENT, DEVICES OR

CAMERAS.

I. REMOVE AND SALVAGE CAMERAS AND

SUPPORTS ON THE EXTERIOR OF THE BUILDING.

REMOVE AND SALVAGE ANTENNAS AND OTHER

COMMUNICATIONS EQUIPMENT ON THE

EXTERIOR OF THE BUILDING. RETURN

EQUIPMENT TO THE OWNER, UNO. DEMOLISH

ASSOCIATED CABLING.

J. RELOCATE 2 ANTENNAS OUTSIDE THE

MECHANICAL ROOM TO OUTSIDE COMM ROOM

102 OR FIRE ROOM 101. COORDINATE WITH THE

OWNER FOR THE EXACT LOCATION.

K. SALVAGE THE EXTERIOR SECURITY LIGHTING ON

THE BUILDING FOR REINSTALLATION BY

CONTRACTOR PER OWNER’S INSTRUCTIONS.

L. REMOVE ROOF-MOUNTED ANTENNA AND

RETURN TO OWNER.

1. EXISTING PANELBOARD “MDP”. DEMOLISH AND

REMOVE WIRING BACK TO THE EXISTING 300 kVA

TRANSFORMER.

2. REMOVE EXISTING PANELS, CONDUIT AND

WIRING.

3. REMOVE EXISTING DISCONNECT

4. REMOVE EXISTING MECHANICAL EQUIPMENT

DISCONNECTS, CONDUIT AND WIRING.

5. EXISTING 300 kVA TRANSFORMER TO REMAIN.

6. EXISTING OVERHEAD DOOR CONTROLS TO

REMAIN. REMOVE EXISTING WIRING. REUSE

EXISTING CONDUIT TO THE EXTENT POSSIBLE.

EXTEND CONDUIT TO THE NEW POWER SOURCE.

PROVIDE WIRING PER SHEET EP101.

7. REPLACE EXISTING RECEPTACLE AND REFEED

PER SHEET EP101. REUSE EXISTING CONDUIT TO

THE EXTENT POSSIBLE.

8. DISCONNECT WIRING AND CONDUIT ON EXISTING

COVERED STORAGE TO BE RELOCATED.

DEMOLISH CONDUIT AND WIRING. PROVIDE NEW

WIRING PER SHEET EP101.

9. SALVAGE FOUR DISCONNECTS PREVIOUSLY USED

FOR TEMPORARY TRAILERS. DEMOLISH EXISTING

CONDUITS AND WIRING. DEMOLISH FOUR

EXISTING 2” CONDUITS.

10. DEMOLISH EXISTING BOXES AND THEIR FOUR 2”

CONDUITS AND WIRING. CONDUITS RUN

OVERHEAD AND ON THE ROOF TO CABINET IN

NOTE 11 BELOW.

11. SALVAGE EXISTING CABINET. DEMOLISH FOUR 2”

CONDUITS COURSED OVER THE ROOF TO THE

LOCATION IN NOTE 10.

12. SALVAGE THE COMMUNICATIONS EQUIPMENT IN

THIS ROOM. RELOCATE TO COMM ROOM 102 PER

OWNER’S INSTRUCTIONS.

13. REMOVE CONDUIT, EQUIPMENT AND HARDWARE

ABOVE THE MECHANICAL ROOM DOOR.

14. (2) EXISTING SECURITY LIGHTS @ 22’ AFG;

SALVAGE.

15. (2) EXISTING CAMERAS AND A COMMUNICATIONS

APPLIANCE @ 20’ AFG; SALVAGE.

16. EXISTING COMMUNICATIONS DOME AT 22’ AFG;

SALVAGE.

17. EXISTING WALL MT’D LUMINAIRE @ 17’ AFG;

DEMOLISH.

18. EXISTING COMMUNICATIONS APPLIANCE @ 20’

AFG; SALVAGE.

19. EXISTING CAMERA @ 23’ AFG; SALVAGE.

20. 2) EXISTING WALL MT’D LUMINARIES @ 8’ AFG AND

20’ AFG; DEMOLISH.

21. EXISTING WALL MT’D LUMINAIRE @ 8’ AFG;

DEMOLISH. 1 ADDENDUM #1 3/3/2021

SEAL

050568

ENGINEE

R

AA

B B

C C

D D

E E

F F

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\fhm \D o cum ents\M y R evit\80720_Elec_F M cN utt.rvt

3/5/2021 11:39: 24 AM

SECOND FLOOR ELECTRICAL

DEMOLITION PLAN

ED102

WCM

TLP

HFM

SCALE 1/8" = 1'-0"

SECOND FLOOR ELECTRICAL DEMOLITION PLAN1

0 4' 8' 16'

1/8" = 1'-0"

N

GENERAL NOTES

A. DEMOLISH WIRE, CONDUIT, JUNCTION BOXES,

ELECTRICAL EQUIPMENT, AND DEVICES FOR ALL

CIRCUITS IN THE BUILDING, UNO.

B. WHERE ELECTRICAL WIRING IS TO BE REMOVED

FROM WALLS AND CEILINGS TO REMAIN, PATCH

EXISTING HOLES AS REQUIRED TO MATCH

ADJACENT SURFACE AND FINISH. FOR CONDUITS

TO BE DEMOLISHED, REMOVE ACCESSIBLE

CONDUITS STUBBED UP IN THE FLOOR 1” BELOW

THE SURFACE. GROUT AND REFINISH THE

SURFACE TO MATCH THE SURROUNDING

SURFACE.

C. RECEPTACLES AND OTHER EQUIPMENT SHOWN

TO BE DEMOLISHED ARE BASED ON PLANS

FURNISHED BY OTHERS AND DO NOT REPRESENT

THE FULL EXTENT OF THE WORK REQUIRED BY

THIS CONTRACT. FIELD VERIFY EXISTING

CONDITIONS PRIOR TO BIDDING ON THIS WORK.

D. DEMOLISH DISCONNECTS AND WIRING FOR

MECHANICAL EQUIPMENT ON THE ROOF.

E. DEMOLISH ALL EXISTING LUMINARIES, CONDUIT,

WIRING, AND CONTROLS, UNO. SALVAGE THE

EXISTING FLUORESCENT FIXTURES IN THE HIGH

BAY AREA. REFER TO ID TYPE "E" IN THE LIGHTING

FIXTURE SCHEDULE. STORE PER OWNERS

INSTRUCTIONS

F. DEMOLISH ALL COMMUNICATIONS EQUIPMENT,

OUTLETS, PATHWAYS, AND CABLING, UNO.

G. SALVAGE SECURITY AND ACCESS CONTROL

EQUIPMENT AND RETURN TO OWNER FOR

REINSTALLATION BY OTHERS. COORDINATE WITH

THE OWNER’S SECURITY-PROVIDER BEFORE

REMOVING SECURITY EQUIPMENT, DEVICES OR

CAMERAS.

1 ADDENDUM #1 3/3/2021

SEAL

050568

AA

B B

C C

D D

E E

F F

LA

PB1PA

MDP

EM

2 2

EMGB

TMGB

ROOM 221

BUS BAR

LOCATED IN

MECH

MEZZANINE

EXISTING

300KVA

TRANSFORMER

208Y/120V

MTS

TR

PB2

EXISTING

PAD MOUNTED

TRANSFORMER

NEUTRAL

BUSHING

PRIMARY TRANSFORMER

GROUNDING

LIGHTNING PROTECTION

DOWN CONDUCTOR AND

GROUNDING ROD AT COLUMN B, 8

208/120V SERVICE

ENTRANCE PANEL

"MDP"

NEUTRAL

GROUND

N

LP

G

G

G

G

#4 /0

C U

G R

O U

N D

#4/0 CU

BUILDING

STEEL

NO. 4/0 GROUND

G

G G

G G

EQUIPMENT MAIN GROUNDING

BUSBAR (EMGB)

PIPE CLAMP (TYPICAL)

HOT WATER PIPING

COLD WATER PIPING

SPRINKLER PIPING

GAS PIPING

ROOM 102

ENTRANCE

TELECOMMUNICATIONS

GROUND BUS "TMGB"

G

#4/0 CU

G

#4/0 CU MAIN

BONDING JUMPER

BOND

TO BUILDING

JOISTS

ROOM 221 BUSBAR "EGB"

#4 /0

C U

ROOM 101

BUSBAR "EGB"

#4 /0

C

UNEUTRAL

GROUND

N

ROOM 101

FIRE PUMP

DISCONNECT

NEUTRAL

GROUND

ROOM 104

MANUAL TRANSFER

SWITCH "MTS"

#4/0 CU MAIN

BONDING JUMPER

#4/0 CU MAIN

BONDING JUMPER

G

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:47: 29 PM

GROUNDING PLAN &

GROUNDING SYSTEM DIAGRAM

EG101

WCM

TLP

HFM

0 4' 8' 16'

1/8" = 1'-0"

N

SCALE 1/8" = 1'-0"

GROUNDING PLAN1

GENERAL NOTES

SHEET KEYNOTES

SCALE NTS

GROUNDING SYSTEM DIAGRAM2

A. DO NOT INSTALL CONDUIT NOR CONDUCTORS ON

THE BUILDING’S EXTERIOR SURFACE.

B. RUN LPS DOWN CONDUCTORS FOR THE NEW

ENTRY CANOPY AND COVERED STORAGE AREA

ON THEIR COLUMNS IN 1” PVC CONDUIT.

CONCEAL FROM VIEW AS MUCH AS POSSIBLE.

PAINT TO MATCH COLUMNS’ FINISHES. RE: SHEET

AE101 FOR DIMENSIONED AREAS.

C. INSTALL CONDUIT AND CONDUCTORS SUCH THAT

NO TRIP HAZARDS ARE PRESENT DUE TO THE

LPS INSTALLATION.

D. SEAL PENETRATIONS IN THE BUILDING DUE TO

THE LPS INSTALLATION WITH APPROVED

SEALANT. REPAIR AND REFINISH TO MATCH THE

SURFACE BEING DISTURBED.

1. SAW-CUT CONCRETE SIDEWALKS AND PAVING TO

INSTALL LIGHTNING PROTECTION SYSTEM (LPS)

CONDUCTORS AND GROUND RODS. CONNECT TO

THE DOWN CONDUCTORS WITH 4/0 AWG COPPER

CONDUCTOR. RUN THE CONDUCTOR 36” BELOW

GRADE AND CONNECT TO THE LPS GROUND

RODS FOR THE LPS DOWN CONDUCTORS. USE

EXOTHERMIC WELD. REPAIR CONCRETE AND

ASPHALT SURFACES TO MATCH EXISTING.

2. GROUND ROD FOR THE LPS DOWN CONDUCTOR.

RE: DETAIL 3 ON SHEET EG500.

3. CONNECT THE ENTRY CANOPY (SEE SHEET

AE201) LPS DOWN CONDUCTOR UNDERGROUND

TO THE 4/0 AWG CONDUCTOR. USE EXOTHERMIC

WELD.

4. CONNECT THE COVERED STORAGE AREA LPS

DOWN CONDUCTOR UNDERGROUND TO THE 4/0

AWG CONDUCTOR. USE EXOTHERMIC WELD.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

AA

B B

C C

D D

E E

F F

VH-1

10 TYPICAL

11 TYPICAL

12 1212

12 12

4 9

2 2

3 3

EF-1

MAU-1

CU-3

CU-1CU-2

EF-2

CVK-1

VH-3

VH-4

(SIMILAR)

VH-2

1414141414

ELEVATOR

ROOF

SEE 2/AE407

1 1

(SIMILAR)

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:48: 01 PM

LIGHTNING PROTECTION PLAN

EG102

WCM

TLP

HFM

GENERAL NOTES

N 0 4' 8' 16'

1/8" = 1'-0"

SHEET KEYNOTES

SCALE 1/8" = 1'-0"

LIGHTNING PROTECTION PLAN1

A. LIGHTNING PROTECTION SYSTEM (LPS) SHALL BE

IN ACCORDANCE WITH NFPA 780, UFC 3-575-01

AND AFI 32-1065 GROUNDING SYSTEMS, ALL

LATEST EDITIONS.

B. LIGHTNING PROTECTION SYSTEM COMPONENTS

SHALL BE CLASS I UL LABELED MATERIALS.

COMBINATIONS OF MATERIALS THAT FORM

ELECTROLYTIC COUPLES OF SUCH A NATURE

THAT, IN THE PRESENCE OF MOISTURE,

CORROSION IS ACCELERATED, SHALL NOT BE

USED.

C. LOCATION OF MAIN CONDUCTORS AND DOWN

CONDUCTORS ARE APPROXIMATE.

D. BENDS IN CONDUCTORS SHALL BE NOT LESS

THAN 8" RADIUS FOR A 90 DEGREE BEND.

E. DOWN CONDUCTORS SHALL RUN INSIDE THE

BUILDING. REFER TO DETAIL 3 ON SHEET EG500.

F. COORDINATE DOWN CONDUCTORS WITH

COLUMNS.

G. PER UFC 3-575-01 SECTION 3, THE CONTRACT FOR

A LIGHTNING PROTECTION SYSTEM PROJECT, OR

FOR ANY PROJECT ON A FACILITY CONTAINING A

LIGHTNING PROTECTION SYSTEM, SHALL

REQUIRE A LIGHTNING PROTECTION INSPECTION

PRIOR TO ACCEPTANCE. THE LIGHTNING

PROTECTION SYSTEM SHALL BE INSPECTED BY A

COMMERCIAL, THIRD PARTY INSPECTOR WHOSE

SOLE WORK IS LIGHTNING PROTECTION, AND

SHALL BE CERTIFIED BY THIS THIRD-PARTY

INSPECTOR AS COMPLIANT WITH AFI 32-1065 AND

NFPA 780, IN THAT PRIORITY ORDER.

H. ROOF PENETRATIONS SHALL BE MADE IN A

MANNER THAT DOES NOT VOID OR ALTER ROOF

WARRANTY.

I. DO NOT PLACE CABLE SPLICE HARDWARE BOLTS

WITH PROTRUDING BOLT DOWN TOWARDS

MEMBRANE BECAUSE THE BOLT END WILL POKE

A HOLE IN THE MEMBRANE.

J. ADD A WEAR PAD UNDER ALL HARDWARE

SPLICES/BOLT HEADS TO PROVIDE ADDED LIFE

TO THE WEARING AWAY OF THE MEMBRANE DUE

TO WIND INDUCED MOVEMENT OF CABLE

HARDWARE.

K. ADD WEAR PADS UNDER ALL SECUREMENT TABS

FOR CONDUCTOR CABLES. WIND MOVEMENT

CAN PULL THE SECUREMENT TABS AND RIP THE

ROOF MEMBRANE. WEAR PADS CAN DISTRIBUTE

THE STRESS LOAD OVER A LARGER AREA.

L. ADD CABLE ANCHORS NEAR ALL CABLE SPLICES

TO MINIMIZE WIND INDUCED CABLE HARDWARE

MOVEMENT.

M. ENSURE ALL WIRE CABLE ENDS CURL UPWARDS

AWAY FROM THE ROOF MEMBRANE. DOWNWARD

CURLS PUSH INTO THE MEMBRANE AND CAUSE A

WEAR PATTERN AND EVENTUALLY A HOLE.

N. ENDS OF CABLES HAVE STRANDS THAT FRAY

FROM CABLES AND CAN POKE A HOLE IN THE

MEMBRANE. SECURE CABLE ENDS TO PREVENT

STRANDS FROM FRAYING

1. EXHAUST FAN. BOND WITH LIGHTNING

PROTECTION SYSTEM. RE: DETAIL 1 ON SHEET

EG501.

2. 4" OVERFLOW ROOF DRAIN. BOND WITH

LIGHTNING PROTECTION SYSTEM. RE: DETAIL 5

ON SHEET EG500.

3. 4" ROOF DRAIN. BOND WITH LIGHTNING

PROTECTION SYSTEM. RE: DETAIL 5 ON SHEET

EG500.

4. ROOF HOOD. BOND WITH LIGHTNING

PROTECTION SYSTEM. RE: DETAIL 2 ON SHEET

EG501.

5. EXISTING POLE APPROXIMATELY 30’ AFG.

PROVIDE TERMINAL AND CONNECT TO THE LPS.

COORDINATE WITH THE OWNER BEFORE

PROCEEDING WITH THIS WORK.

6. ROOF HYDRANT.

7. NEW ROOF HATCH AND GUARDRAIL SYSTEM.

BOND WITH LIGHTNING PROTECTION SYSTEM.

REFERENCE ARCHITECTURAL

8. ROOF CAP OVER EXISTING PENETRATION. RE:

MECHANICAL.

9. PIPE VENT. BOND WITH LIGHTNING PROTECTION

SYSTEM. RE: DETAIL 4 ON SHEET EG500.

10. AIR TERMINAL. RE: DETAIL 1 ON SHEET EG500.

11. LIGHTNING PROTECTION MAIN CONDUCTOR.

PROVIDE CLASS I CONDUCTOR.

12. LIGHTNING PROTECTION DOWN CONDUCTOR TO

GROUND ROD. BOND TO BUILDING STEEL. RE:

DETAILS 2 AND 3 ON SHEET EG500.

13. PROVIDE LPS AIR TERMINALS, MAIN CONDUCTOR

AND 2 DOWN CONDUCTORS ON THE NEW

COVERED STORAGE AREA. RE: SHEET AE101 FOR

DIMENSIONED AREA.

14. CONNECT TO #4/0 CABLE CONNECTED TO TWO

DOWN CONDUCTORS. RE: PLAN 1 ON SHEET

EG101.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

24" HIGH AIR

TERMINAL

LIGHTNING PROTECTION

CROSS RUN CONDUCTOR

ADHESIVE POINT

BASE FOR FLAT ROOF

ADHESIVE CABLE

HOLDER FOR FLAT

ROOF EVERY 3'-0"

INSTALL PER ROOFING

MANUFACTURER'S RECOMMENDATIONS

SO THAT ROOF WARRANTY WILL NOT

BE AFFECTED

TOP OF ROOF

LIGHTNING PROTECTION CONDUCTOR

TO THE NEAREST MAIN CONDUCTOR.

CONNECT THIS CONDUCTOR TO THE

MAIN CONDUCTOR.

THRU-ROOF CABLE CONNECTING ASSEMBLY,

FURNISHED WITH PIPE FLASHING, FLASHING

ADAPTER AND 1/2" DIA. X 18" ALL THREAD ROD.

INSTALL BOOT PER ROOFING CONTRACTOR'S

RECOMMENDATIONS SO THAT ROOF WARRANTY

WILL NOT BE AFFECTED.

LIGHTNING PROTECTION

TOP ROOF

THRU-ROOF CABLE CONNECTION

3'-0" MIN

EXTERIOR WALL

STEEL COLUMN

STEEL COLUMN

DOWN CONDUCTOR

EXOTHERMICALLY

CONNECT DOWN

CONDUCTOR TO

GROUND ROD

#4/0 COPPER

GROUND

CONDUCTOR

3/4" ∅ X

10' COPPER

CLAD

GROUND ROD

LIGHTNING PROTECTION

LOWER ROOF

THRU-ROOF CABLE CONNECTION

STEEL COLUMN

1" EMT BOND TO STEEL COLUMN

LIGHTNING PROTECTION

1" EMT BOND TO STEEL COLUMN

1" EMT BOND TO STEEL COLUMN

EXOTHERMICALLY WELD STEEL

COLUMN TO DOWN CONDUCTOR

ROUND ADJUSTABLE TYPE PIPE

BONDING STRAP WITH BOLT AND

CABLE CONNECTOR.

CONTRACTOR TO FIELD ADJUST

AND INSURE A SECURE BOND.

LIGHTNING PROTECTION

BONDING CONDUCTOR.

CONNECT THIS CONDUCTOR TO

THE NEAREST MAIN OR CROSS

RUN CONDUCTOR.

CAST BRONZE TERMINAL BONDING LUG.

SECURE WITH A ~6" X ~W" STAINLESS

STEEL MACHINE BOLT WITH STAINLESS

STEEL LOCKWASHER AND NUT.

ROOF DRAIN DOME

LIGHTNING PROTECTION BONDING

CONDUCTOR. CONNECT THIS

CONDUCTOR TO THE NEAREST MAIN OR

CROSS RUN CONDUCTOR WITH A BOLTED

TYPE CONNECTION.

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:47: 46 PM

GROUNDING & LIGHTNING

PROTECTION DETAILS

EG500

WCM

TLP

HFM

GENERAL NOTES

A. INSTALLATION OF ASSEMBLIES/SYSTEMS WILL

COMPLY WITH UFC 4-010-05.

SCALE NTS

TYPICAL AIR TERMINAL TYPE "B"1 SCALE NTS

TYPICAL THRU-ROOF CABLE CONNECTION DETAIL2

SCALE NTS

THROUGH ROOF LIGHTNING PROTECTION3 SCALE NTS

TYPICAL ROOF VENT CONNECTION4 SCALE NTS

TYPICAL ROOF DRAIN CABLE CONNECTION DETAIL5

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

1/4" x 4" COPPER BAR STOCK

9/16 DIA. HOLE (TYPICAL)

TYPICAL GROUND CABLE.

(INDIVIDUAL CABLES AND

CONNECTIONS ARE NOT SHOWN)

TERMINATE CONDUIT ABOVE OR BELOW

PLATE WITH BONDING WEDGE OR

GROUNDING BUSHING

SIDE

3/8-16 x 1" LONG

MOUNTING BOLT (TYPICAL)

COPPER BAR STOCK

WALL

SUPPORT BRACKET

TYPICAL

ANCHOR BRACKET TO WALL

WITH 5/8" x 1-1/2" BOLTS

AND SLEEVE ANCHORS.

MODIFY BRACKET SUPPORT

BASED ON ACTUAL WALL TYPE

INSULATOR

4"

2" 2"

**-LENGTH AS REQUIRED

EQUAL SPACES AT 2"1"

3'

TO

F

LO

O

R

ELEVATION

PVC CONDUIT

SLEEVE

2" 1"

1/2" X 1" LONG BOLT WITH

FLAT WASHER, LOCKWASHER

AND NUT.

10" TYPICAL SPACING

FLOOR

1/

2"

1/ 2"

1"

LIGHTNING PROTECTION

SYSTEM CABLE

SELF-DRILLING AND TAPPING SCREW

AIR TERMINAL

NARROW WALL POINT

BASE WITH METAL

SCREW

AND SEALING WASHER 4

PER LOCATION

NOTE - ALL ROOF PENETRATIONS TO BE

SEALED BY THE ROOFING

CONTRACTOR

LIGHTNING PROTECTION

BONDING CONDUCTOR.

CONNECT THIS CONDUCTOR TO

THE NEAREST MAIN OR CROSS

RUN CONDUCTOR.

CROSS RUN CONNECTOR PARALLEL CONNECTOR

BONDING CONNECTOR PARALLEL CONNECTOR

BI-METAL CONNECTOR

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\fhm \D o cum ents\M y R evit\80720_Elec_F M cN utt.rvt

3/5/2021 11:39: 25 AM

GROUNDING & LIGHTNING

PROTECTION DETAILS

EG501

WCM

TLP

HFM

SCALE NTS

ELECTRICAL MAIN GROUND BUS (EMGB) DETAIL, TELECOMMUNICATIONS GROUND BUS (TMGB) AND

ELECTRICAL GROUND BUS (EGB) DETAILS4

SCALE NTS

TYPICAL EXHAUST FAN/MECHANICAL AIR TERMINAL1

SCALE NTS

LIGHTNING PROTECTION SYSTEM ABOVE GRADE TYPICAL CABLE CONNECTOR DETAIL3

NOTES: ADD A ROOF MEMBRANE PROTECTIVE PAD UNDER EACH CABLE CONNECTOR AND AT EACH CABLE END.

1 ADDENDUM #1 3/3/2021

SEAL

050568

G

FI

CG

FI

C

G

FI

GFI

WP

GFI

WP

G

FI

W P

G

FI

G

FI

GFI

G

FI

GFI

G

FI

W P

GFI

G

FI

C

GFI

C

GFI

GFI

WP

GFI

WP

G

FI

W P

G

FI

W P

G

FI

W P

GFI

WP

G

FI C

GFI

WP

G

FI

W P

G

FI

W P

GFI

WP

GFI

WP

GFI

WP

J

J

JJ

GFI

J

J

G

FI

C

GFI

C

J

J

GFI

J

J

GFI

WP

J

J

G

FI

W P

M

LAV TRUCK

FLEET OFFICE

PPE TRAINING

BAG

COFFEE

JAN

ELEV 121

LOCKERS

BAGGAGE /

PALLET

FLEET WORK

MEN

FLEET STOR

JOINT

INSPECTION

PALLET BUILD-UP

CORRIDOR

FIRE

COMM

CORR

ELEC

TOILET

PASSENGER

HOLDING STERILE

WOMEN

RAMP

CARGO

STAIRS

PASSENGER

HOLDING

BAGGAGE

CHECK-IN

AA

B B

C C

D D

E E

F F

MDP

L5-30R

EP101

+66"

EXISTING

300KVA

TRANSFORMER

208Y/120V

+66"

+66"

TR

+76"

+66"

PB1 - 1

PA - 14

PA - 11

PA - 9

PA - 12

PA - 16

PA - 20

PA - 18

PA - 15

PA - 2

PC2 - 2

PB1 - 27

PB1 - 28

PB1 - 21

TR - 2

PA - 5

PB1 - 19

PB2 - 9

PB1 - 15

PB1 - 22

TR - 5 TR - 4

PA - 1

PB1 - 9

PB1 - 18

+66"

PB1 - 25

PC2 - 10,12,14

PC2 - 5,7,9

PC2 - 4,6,8

10PA - 13

TR - 6

TMGB

PC2 - 16,18,20

3-#6 & 1-#10 EG, 1"C

+66"

PB2 - 30

PB2 - 13

+66"

PA - 3

TV

TV

TV

TV

TVTV

TV

PB2 - 8

PB2 - 11PB2 - 12

PA - 29

PA - 28

PB2 - 18

PA - 8

PA - 27

PB2 - 17

PA - 30

EM - 4

PA - 31

PB2 - 19

PB1 - 30 PB1 - 17

PB1 - 29

PB1 - 20

PB1 - 32

HP-1

HP-2

PB2 - 24,26,28

TV

+66"

TV

+66"

TV

+66"

PB2 - 30

PB2 - 30

PB2 - 30

PB2 - 30

PB2 - 30

PB2 - 30

PB2 - 10

PC

PC

PC

PC

PC

PC

PC

PC

PC

PB2 - 30

PB2 - 30

PC

PB1 - 31

PB1 - 33

+48" +48"

PB2 - 35

PB2 - 36

+36"

+36"

23 23

COMM

PUMP

ROOM

PARACHUTE

DRYING

TOWER

BAGGAGE SCAN

BAGGAGE SCAN

CORRIDOR

PB1 - 34

EM

LA

PB1PA

MDP

ELEC

MTS

EMGB

PB2

RP

5 3/4"

2 1/8"

DOWNWARD

FACING

ACTIVATIONS

SURFACE METAL RACEWAY SECTION.

ALUMINUM,

SILVER COLOR

NOTE: DIMENSIONS VARY BY

MANUFACTURER.

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\fhm \D o cum ents\M y R evit\80720_Elec_F M cN utt.rvt

3/5/2021 11:38: 54 AM

GROUND FLOOR POWER PLAN

EP101

WCM

TLP

HFM

SCALE 1/8" = 1'-0"

GROUND FLOOR POWER PLAN1

0 4' 8' 16'

1/8" = 1'-0"

N

SCALE 1/4" = 1'-0"

ENLARGED ELECTRICAL ROOM 1042

0 2' 4' 8'

1/4" = 1'-0"

GENERAL NOTES

SHEET KEYNOTES

A. RECEPTACLES SHOWN MOUNTED +66” AFF ARE

FOR TELEVISION OR OTHER TYPE MONITORS.

B. ALL WORK SHALL MEET THE REQUIREMENTS OF

THE NEC AND ALL STATE AND LOCAL CODES.

C. REFER TO SHEET EP600 FOR FEEDER SCHEDULE.

1. RACEWAY. RE: DETAIL 3, THIS SHEET.

RECEPTACLES ARE TAMPER-RESISTANT 15A

DUPLEX WITH USB CHARGING CAPABILITIES.

SPACE RECEPTACLES 4’ OC. MOUNT RACEWAY

ON CENTER AT 36” AFF.

2. REFER TO SHEET KEYNOTE 1 ON EP600. SAW-CUT

SIDEWALK AND PAVING. TRENCH AND BURY

CONDUITS 24” BELOW GRADE. PROVIDE

UNDERGROUND PULL BOX WHERE TOTAL BENDS

EXCEED 270 DEGREES. STUB UP AT THE PANEL

MDS LOCATION WITH A 90 DEGREE PVC COATED

RGS SWEEP. ENTER THE BUILDING WITH

THREADED RIGID CAST IRON CONDUIT BODIES.

COMPACT FILL AND RESTORE SURFACE TO

MATCH EXISTING SURFACE, UNLESS DIRECTED

OTHERWISE.

3. RELOCATE GENERATOR RECEPTACLE AND

CONNECT TO THE “MTS” IN ELEC ROOM 104.

4. CONNECT TO THE RECESSED PROJECTION

SCREEN ABOVE CEILING. COORDINATE THE

LOCATION OF THE CONTROL AND INSTALL.

5. NOT USED.

6. MOUNT THIS RECEPTACLE IN THE TRANSACTION

COUNTER PER DETAIL 11 SHEET AE403.

7. MOUNT RECEPTACLES ON CABLE TRAY.

8. TAP POWER TO THE FIRE PUMP FROM EXISTING

TRANSFORMER. SAW-CUT SIDEWALK AND

PAVING. TRENCH AND BURY (4) #1 AWG CU IN 2”

CONDUIT 24” BELOW GRADE. PROVIDE

UNDERGROUND PULL BOX WHERE TOTAL BENDS

EXCEED 270 DEGREES. STUB UP AT THE

CONTROLLER LOCATION WITH A 90 DEGREE PVC

COATED RGS SWEEP. ENTER THE BUILDING WITH

A THREADED RIGID CAST IRON CONDUIT BODY.

CONNECT TO THE FIRE PUMP DISCONNECT AT

THE CONTROLLER. COMPACT FILL AND RESTORE

SURFACE TO MATCH EXISTING SURFACE, UNLESS

DIRECTED OTHERWISE.

9. PROVIDE POWER TO THE 5 TON BRIDGE CRANE.

10. MAGNETOMETER.

11. CONNECT TO THE ICE MACHINE.

12. CONNECT TO THE HIGH-PRESSURE DISHWASHER

PER MANUFACTURER'S INSTRUCTIONS. CIRCUIT

BREAKER MUST BE LOCKABLE PER NEC 110.25.

13. OPERABLE PARTITION. CONNECT TO MOTOR AND

KEY SWITCH. COORDINATE WITH PARTITION

INSTALLATION.

14. RECONNECT DISCONNECT AND CONTROLLER

FOR EXISTING OVERHEAD DOOR.

15. LOCKABLE PER NEC 110.25.

16. MOUNT ON WALL NEAR BACK OF BAGGAGE

SCANNER.

17. 240V, 60A,3-POLE, FUSED. CONNECT TO THE

BRIDGE CRANE ELECTRIFICATION SYSTEM.

COORDINATE WITH THE CRANE INSTALLATION.

ADJUST FEEDER, FUSES, AND CIRCUIT BREAKER

SIZES PER REQUIREMENTS IN THE BRIDGE CRANE

SHOP DRAWINGS.

18. ELECTRIC WATER COOLER WITH BOTTLE FILLER.

LOCATE RECEPTACLES PER MANUFACTURER'S

INSTRUCTIONS.

19. PROJECTOR.

20. RELAY PANEL "RP". REFER TO THE LIGHTING

CONTROL SCHEDULE ON SHEET EL700. PROVIDE

CONTROL POWER FROM CIRCUIT EL-18.

21. PROVIDE POWER TO THE DOOR OPERATORS AND

CONTROLS. ONE CONTROL IS ON THE WALL

INSIDE THE BUILDING; THE OTHER IS ON A

PEDESTAL OUTSIDE NEAR THE DOOR. RUN 3/4"

PVC CONDUIT 18" UNDERGROUND UP THROUGH

THE PEDESTAL TO THE CONTROL. COORDINATE

WITH ARCHITECTURAL AND THE INSTALLER.

22. SUMP PUMP RECEPTACLE. MOUNT AT 60" ABOVE

PIT. LED INDICATOR TO VERIFY CIRCUIT IS

ENERGIZED. SUPPLY POWER FROM SUMP PUMP

DISCONNECT IN ROOM 221.

23. AIRPORT SCALE RECEPTACLE. MOUNT AT 6-5/8"

AFF IN THE TRANSACTION COUNTER. PROVIDE

GROMMETS IN THE MILLWORK AS REQUIRED FOR

PLUG CONNECTION FROM THE SCALE.

1 ADDENDUM #1 3/3/2021

SCALE NTS

RACEWAY DETAIL3

SEAL

050568

C

G

FI

G

FI

G

FI

G

FI C

G

FI C

C

G

FI

C

GFI

WP

G

FI

W P

M

ADMIN

ELEV

SUPERVISOR /

MANAGER

CORR

CONF

TO LIBRARY /

HOTEL / QC213

COFFEE /

BREAKRM

LOAD PLANNING

TOILET

TOILET

IDO 210

SIPR

CORRIDOR

ATOC

CORR

STAIRS

DCC

ADMIN

AA

B B

C C

D D

E E

F F

EP102

AHU-1

PA - 10 PA - 7

PA - 6

PA - 25

PA - 22

PA - 17

PA - 23

PA - 26

PA - 21

PA - 19

PA - 24

PC1 - 28

PB2 - 6

PB2 - 3

PB2 - 4

PB2 - 5

PB2 - 7

+66"

PC2 - 3

+66"

+66"

+66"

+66" +66" +66"

+66"

EGB

TV

TV

TV

TV

TV

TV

TV

TV

PB1 - 24

PB1 - 23

PB2 - 1

PB2 - 2

PB2 - 14PB2 - 15

PB2 - 16

PA - 4

C

C

C

+66"

TV

+66"

TV

+66"

TV

+66"

TV

PB2 - 29

LA - 15

PC1 - 31

VAV-1611 11

MECH.

c

+60"

PB2 - 32

E E

F F

PC1

AHU-1

B-1

PC1 - 30

PC1 - 19,21,23

PC1 - 20

PC2

AC-1

PC1 - 27,29

3 3

#10

PC

PC

MECH.

PC1 - 2,4

PC1 - 2,4

HWP-1

HWP-2

#10

8#10

#10

#10

PC1 - 33

HWP-3

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/28/2020 12:42 :51 PM

SECOND FLOOR POWER PLAN

EP102

WCM

TLP

HFM

SCALE 1/8" = 1'-0"

SECOND FLOOR POWER PLAN1

0 4' 8' 16'

1/8" = 1'-0"

N

SCALE 1/4" = 1'-0"

MEZZANINE LEVEL ENLARGED PLAN2

0 2' 4' 8'

1/4" = 1'-0"

SHEET KEYNOTES

1. CONNECT TO BOILER B-1. PROVIDE POWER TO

THE BOILER CIRCULATION PUMP THROUGH B-1.

2. FOR RECEPTACLE IN AHU-1.

3. PROJECTOR.

4. COFFEE MAKER.

5. GFCI RECEPTACLE FOR MICROWAVE.

6. REFRIGERATOR.

7. INSURE COMPLIANCE WITH NEC 110.26.

COORDINATE WITH OTHER TRADES.

8. 240V, 30A, 2 POLE, NF

9. 240V, 30A, 3 POLE, NF

10. MOUNT NEXT TO COMMUNICATIONS OUTLET FOR

WAP POWER @ 20' ABOVE GROUND LEVEL.

11. THIS PARTITION IS STC 60 SOUND-RATED.

SURFACE-MOUNT DEVICES AND EQUIPMENT ON

THIS PARTITION. SEAL PENETRATIONS WITH AN

APPROVED ACOUSTICAL SEALANT, BUT AVOID

PENETRATIONS AS MUCH AS POSSIBLE.

12. COMBINATION MOTOR STARTER, SIZE 0, NEMA 1

ENCLOSURE, 9 AMPS CONTINUOUS AT 120V,

1P15A MCP. COORDINATE COIL VOTAGE WITH

MECHANICAL.

GENERAL NOTES

A. RECEPTACLES SHOWN MOUNTED +66” AFF ARE

FOR TELEVISION OR OTHER TYPE MONITORS.

B. ALL WORK SHALL MEET THE REQUIREMENTS OF

THE NEC AND ALL STATE AND LOCAL CODES.

C. REFER TO SHEET EP600 FOR FEEDER SCHEDULE.

Frankfurt-Short-B document1 5801 Broadway Extension, S

Telephone (405) 840-2931 Fa

SEAL

GFI

WP

G

FI

W P

G

FI

W P

GFI

WP

GFI

WP

G

FI

W P

GFI

WP

GFI

WP

AA

B B

C C

D D

E E

F F

VH-4

VH-2

F-3

PB1 - 3,5

EF-1

CU-3

MAU-1

CU-1

CU-2

110V FROM RTH-1

110V FROM VF-2

110V FROM VF-3

PC1 - 22,24,26

VH-1

110V FROM VF-1 TR - 1,3

PB1 - 6,8

VH-3

EF-2

FROM VFD

RE: SHEET EP104

PB1 - 14

PC1 - 25

PB1 - 4

PC

4930 MINUTEMAN WAY

CHARLOTTE, NC 28208

2000 East Lamar Blvd, Suite 600 Arlington, TX 76006 fsb-ae.com

Architecture Engineering Planning Frankfurt Short Bruza / Texas

817.588.3010

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

MAY 29, 2020

20180720

LLP

Pr oj ec t N o.

: F

JR

P

C ha rlo tte A

N G

B as e, C

D

IA

, N C

N or th C ar ol in a

A ir

N at io na l G ua rd C

-1

C on ve rs io n:

A dd

/A lte r S m al l T er m in al

B ld g

C :\U sers\tlp\D oc um ents\M y R evit\80720_Elec_TL P .rvt

5/27/2020 1:50: 19 PM

ROOF POWER PLAN

EP103

WCM

TLP

HFM

SCALE 1/8" = 1'-0"

ROOF POWER PLAN1

0 4' 8' 16'

1/8" = 1'-0"

N

SHEET KEYNOTES

1. CONNECT TO ASSOCIATED INDOOR UNIT.

PROVIDE DISCONNECT 240V, 30A, 2 POLE, NEMA

3…