VAV Research 353-8MH614.pdf

PDF 158 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System
Solicitation number
Not on record
Issued by

About this file

This document package includes drawings and schedules for an HVAC system rebalance project. The project involves rebalancing air handling terminals, valves, fan coil units, and computer room AC units on the fifth and fifth mezzanine floors of Building 8MH614 at the New Orleans VA Medical Center. Key details include specifications for over 25 exhaust air valves, 20 supply air valves, 4 supply terminal units, over 30 fan coil units, and 5 units on the fifth mezzanine floor. Control types and sequences are defined. The related federal contract opportunity is solicitation number REBALANCE for rebalancing the HVAC system at the facility. The purpose is to attach 91 additional documents to the solicitation. The agency is the Department of Veterans Affairs Veterans Health Administration VISN 16.

View the file

Other files

File Type Posted
VAV DNT 02305-2MH630.pdf PDF
ICRA ILSM for CFM - Rebalance HVAC System.xlsx XLSX spreadsheet
CEP L01.pdf PDF
AMS Research 340-8MH601.pdf PDF
RESEARCH 3 5 mech plan.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
03503-6EP103-M3.pdf PDF
VAV Research 351-8MH612.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
PANAM 104.pdf PDF
RESEARCH 5 dixie penthouse.pdf PDF
010000 General Requirements.pdf PDF
P07-General Decision.pdf PDF
S02-XHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE v2.pdf PDF
390-8EP105-P.pdf PDF
VAV DNT 02304-2MH629.pdf PDF
AMS OP 03027-3MH604.pdf PDF
P15-M-1 Typical Existing Service Bay layout.pdf PDF
OUT L07.pdf PDF
S02-EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.pdf PDF
INP L03.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
VAV Research 352-8MH613.pdf PDF
OUT L04.pdf PDF
OUT L05.pdf PDF
03491-6EL103-M3.pdf PDF
PANAM 105.pdf PDF
230593 Testing Adjusting and Balancing for HVAC.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
M-3 DNT Building Existing DOAS sequence.pdf PDF
P12-ROOMS NUMBERS LIST WITH OLD AND NEW ROOM NUMBERS.xlsx XLSX spreadsheet
RESEARCH 2nd mech plan.pdf PDF
VAV DNT 02306-2MH631.pdf PDF
DNT L02i F-G.pdf PDF
RESEARCH 4th mech plan.pdf PDF
AMS TLR 03470-6MH604.pdf PDF
P12-000110 Table of Contents 4-7-20.pdf PDF
013526 Safety Requirements.pdf PDF
VAV DNT 02303-2MH628.pdf PDF
DNT L05 G.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
AMS Research 348-8MH609.pdf PDF
CEP L03.pdf PDF
VAV DNT 02302-2MH627.pdf PDF
P12-230923 DDC Control System for HVAC 4-7-20.pdf PDF
DNT L01i D-E.pdf PDF
PANAM 103.pdf PDF
CEP L04.pdf PDF
VAV DNT 02301-2MH626.pdf PDF
Show 40 more

Latest 50 of 79 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

8MH614

BLDG 08 HVAC AIR TERMINAL/VALVES AND FAN

COIL UNIT SCHEDULE

BE RPBJuly 16, 2012

8629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

NEW ORLEANS, LOUISIANA

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

BR+A CONSULTING ENGINEERS / LOW VOLTAGE

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_09B

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

EXHAUST AIR VALVES SCHEDULE - FIFTH FLOOR

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

Min DCV

CFM

VALVE SOUND

ATTENUATOR

IN-DUCT AIR

FILTER NO.

GPM

(Flow)

CONTROL

TYPE CONTROL SEQUENCE Remarks

EV-1 08-5P CEAV-2 400 CFM 400 CFM N/A SAD-52 F-1 N/A CV TRACKS SV-1 NOTE (4)

EV-2 08-5P EAV-2 500 CFM 500 CFM N/A SAD-52 - N/A CV TRACKS SV-1 NOTE (4)

EV-3 08-5P CEAV-2 400 CFM 400 CFM N/A SAD-52 F-1 N/A CV TRACKS SV-2 NOTE (4)

EV-4 08-5P EAV-2 500 CFM 500 CFM N/A SAD-52 - N/A CV TRACKS SV-2 NOTE (4)

EV-5 08-5P HV-3 725 CFM 725 CFM N/A SAD-63 - N/A CV TRACKS SV-4 NOTE (4)

EV-6 08-5P HV-2 450 CFM 450 CFM N/A SAD-62 - N/A CV TRACKS SV-4 NOTE (4)

EV-7 08-5P HV-2 450 CFM 450 CFM N/A SAD-62 - N/A CV TRACKS SV-3 NOTE (4)

EV-8 08-5P HV-3 725 CFM 725 CFM N/A SAD-63 - N/A CV TRACKS SV-3 NOTE (4)

EV-9 08-5P HV-2 450 CFM 450 CFM N/A SAD-62 - N/A CV TRACKS SV-6 NOTE (4)

EV-10 08-5P HV-3 725 CFM 725 CFM N/A SAD-63 - N/A CV TRACKS SV-6 NOTE (4)

EV-11 08-5P EAV-2 400 CFM 400 CFM N/A SAD-52 - N/A CV TRACKS SV-8 NOTE (4)

EV-12 08-5P EAV-2 500 CFM 500 CFM N/A SAD-52 - N/A CV TRACKS SV-7 NOTE (4)

EV-13 08-5P CEAV-2 400 CFM 400 CFM N/A SAD-52 F-1 N/A CV TRACKS SV-7 NOTE (4)

EV-14 08-5P HV-3 725 CFM 725 CFM N/A SAD-63 N/A CV TRACKS SV-16 NOTE (4)

EV-15 08-5P EAV-2 400 CFM 400 CFM N/A SAD-52 - N/A CV TRACKS SV-9 NOTE (4)

EV-16 08-5P HV-2 450 CFM 450 CFM N/A SAD-62 - N/A CV TRACKS SV-16 NOTE (4)

EV-17 08-5P HV-2 450 CFM 450 CFM N/A SAD-62 N/A CV TRACKS SV-9 ON LEVEL 4 NOTE (4)

EV-18 08-5P EAV-2 500 CFM 500 CFM N/A SAD-52 - N/A CV TRACKS SV-10 NOTE (4)

EV-19 08-5P EAV-2 400 CFM 400 CFM N/A SAD-52 - N/A CV TRACKS SV-11 NOTE (4)

EV-20 08-5P EAV-3 525 CFM 525 CFM N/A SAD-53 - N/A CV TRACKS SV-13 NOTE (4)

EV-21 08-5P EAV-2 400 CFM 400 CFM N/A SAD-52 - N/A CV TRACKS SV-12 NOTE (4)

EV-22 08-5P EAV-1 200 CFM 200 CFM N/A SAD-51 - N/A CV TRACKS SV-14 NOTE (4)

EV-23 08-5P CEAV-1 200 CFM 200 CFM N/A SAD-51 F-1 N/A CV TRACKS SV-14 NOTE (4)

EV-24 08-5P EAV-2 500 CFM 500 CFM N/A SAD-52 - N/A CV TRACKS SV-17 NOTE (4)

EV-25 08-5P EAV-5 1700 CFM 1700CFM N/A SAD-55 - N/A CV TRACKS SV-5 NOTE (4)

EV-26 08-5P CEAV-2 400 CFM 400 CFM N/A SAD-52 F-1 N/A CV TRACKS SV-17 NOTE (4)

SUPPLY AIR VALVES SCHEDULE - FIFTH FLOOR

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

Min DCV

CFM

VALVE SOUND

ATTENUATOR

AIR VALVE

REHEAT NO.

GPM

(Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

SV-1 08-5P SAV-3 1000 CFM 1000 CFM N/A SAD-43 RHC-3 1.75 CV 2/8MH813 NOTE (4)

SV-2 08-5P SAV-3 1000 CFM 1000 CFM N/A SAD-43 RHC-3 1.75 CV 2/8MH813 NOTE (4)

SV-3 08-5P SAV-4 1075 CFM 1075 CFM N/A SAD-44 RHC-4 1.75 CV 4/8MH814 NOTE (4)

SV-4 08-5P SAV-4 1075 CFM 1075 CFM N/A SAD-44 RHC-4 1.75 CV 4/8MH814 NOTE (4)

SV-5 08-5P SAV-3 950 CFM 950 CFM N/A SAD-43 RHC-3 1.75 CV 3/8MH814 NOTE (4)

SV-6 08-5P SAV-4 1075 CFM 1075 CFM N/A SAD-44 RHC-4 1.75 CV 4/8MH814 NOTE (4)

SV-7 08-5P SAV-3 1000 CFM 1000 CFM N/A SAD-43 RHC-3 1.75 CV 2/8MH813 NOTE (4)

SV-8 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 3/8MH814 NOTE (4)

SV-9 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 3/8MH814 NOTE (4)

SV-10 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 3/8MH814 NOTE (4)

SV-11 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 3/8MH814 NOTE (4)

SV-12 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 3/8MH814 NOTE (4)

SV-13 08-5P SAV-2 425 CFM 425 CFM N/A SAD-42 RHC-2 0.75 CV 3/8MH814 NOTE (4)

SV-14 08-5P SAV-2 500 CFM 500 CFM N/A SAD-42 RHC-2 1.00 CV 1/8MH813 NOTE (4)

SV-15 08-5P SAV-3 750 CFM 750 CFM N/A SAD-43 RHC-3 1.25 CV 3/8MH814 NOTE (4)

SV-16 08-5P SAV-4 1075 CFM 1075 CFM N/A SAD-44 RHC-4 1.75 CV 4/8MH814 NOTE (4)

SV-17 08-5P SAV-3 1000 CFM 1000 CFM N/A SAD-43 RHC-3 1.75 CV 2/8MH813 NOTE (4)

SUPPLY TERMINAL UNIT SCHEDULE - FIFTH FLOOR DIXIE

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 08-5P E2 1150 CFM 575 CFM 1.0 VCV 3/8MH806 NOTE (1)

S-2 08-5P C2 450 CFM 450 CFM 1.0 CV 1/8MH806 NOTE (1)

S-3 08-5P C3 550 CFM 275 CFM 0.5 VCV 3/8MH806 NOTE (1)

S-4 08-5P B2 375 CFM 200 CFM 0.5 VCV 3/8MH806 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH FLOOR

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-2 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-3 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-4 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-5 08-5P 4B5 - 2/8MH805 NOTE (3)

FCU-6 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-7 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-8 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-9 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-10 08-5P 4B5 - 2/8MH805 NOTE (3)

FCU-11 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-12 08-5P 4B5 - 2/8MH805 NOTE (3)

FCU-13 08-5P 4B5 - 2/8MH805 NOTE (3)

FCU-14 08-5P 4B5 - 2/8MH805 NOTE (3)

FCU-15 08-5P 4F6 - 2/8MH805 NOTE (3)

FCU-16 08-5P 4F6 - 2/8MH805 NOTE (3)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH MEZZANINE FLOOR

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 08-5.5P 4B3 - 2/8MH805 NOTE (3)

FCU-2 08-5.5P 2H6 - 1/8MH805 NOTE (2, 5)

FCU-3 08-5.5P 2H7 - 1/8MH805 NOTE (2, 5)

FCU-4 08-5.5P 2H7 - 1/8MH805 NOTE (2, 5)

FCU-5 08-5.5P 2H7 - 1/8MH805 NOTE (2, 5)

GENERAL NOTES:

1. REFER TO DRAWINGS 8MH610 AND 8MH611 FOR

SUPPLY AND RETURN TERMINAL UNIT SCHEDULES.

2. REFER TO DRAWING 8MH611 FOR CAC UNIT

SCHEDULE.

3. REFER TO DRAWINGS 8MH605 AND 8MH606 FOR FCU

SCHEDULE.

4. REFER TO DRAWING 8MH607 FOR SUPPLY AND EXAHUST

AIR VALVES SCHEDULES.

5. ON EMERGENCY POWER.

1 Addendum 1 9/21/12

6 RFI-4199 9/16/14

File details come from the government source that posted it. Updated .