VAV DNT 02305-2MH630.pdf
PDF 395 KB Posted
- Attached to
- Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
- Solicitation number
- Not on record
About this file
This document contains an HVAC air terminal unit and fan coil unit schedule for the fourth floor of a building. It provides specifications for 31 supply terminal units, 33 return terminal units, 11 exhaust terminal units, and 5 fan coil units or computer room air conditioners on the fourth floor. Unit locations, sizes, flow rates, and control types are specified. The schedule also notes that additional capacity information can be found in other drawings. A related federal contract opportunity involves rebalancing the HVAC system for the building. The solicitation number provided is for a rebalance of the HVAC system and seeks to attach 91 additional documents to the solicitation. The agency listed is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H A L
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
E E T
(1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
X T
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2MH630
BLDG 02 HVAC AIR TERMINAL UNIT AND FAN
COIL UNIT SCHEDULE
KJS DCDFebruary 29, 2012
02629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING/ PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 02�4D1 D1 850 CFM 850 1.5 CV DETAIL 2/MH821 NOTE (1)
S�2 02�4D1 B1 275 CFM 275 0.5 CV DETAIL 2/MH821 NOTE (1)
S�3 4D227 02�4D1 E1 1350 CFM 1350 NO COIL CV DETAIL 2/MH821 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 02�4D2 C2 575 CFM 575 1 CV DETAIL 2/MH821 NOTE (1)
S�2 02�4D2 D2 920 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�3 02�4D2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�4 02�4D2 B2 350 CFM 350 0.75 CV DETAIL 2/MH821 NOTE (1)
S�5 02�4D2 C3 500 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�6 02�4D2 A3 120 CFM 120 0.5 CV DETAIL 2/MH821 NOTE (1)
S�7 02�4D2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�8 02�4D2 A3 235 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�9 02�4D2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�10 02�4D2 B3 340 CFM 150 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�11 02�4D2 A2 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�12 02�4D2 G2 1785 CFM 1785 3 CV DETAIL 2/MH821 NOTE (1)
S�13 02�4D2 E2 1380 CFM 1380 2.5 CV DETAIL 2/MH821 NOTE (1)
S�14 02�4D2 C2 550 CFM 275 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�15 02�4D2 E2 950 CFM 950 1.75 CV DETAIL 2/MH821 NOTE (1)
S�16 02�4D2 A2 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)
S�17 02�4D2 D2 800 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�18 02�4D2 B2 350 CFM 175 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�19 02�4D2 A2 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�20 02�4D2 C2 600 CFM 600 1 CV DETAIL 2/MH821 NOTE (1)
S�21 02�4D2 B1 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)
S�22 02�4D2 E1 1000 CFM 1000 1.75 CV DETAIL 2/MH821 NOTE (1)
S�23 02�4D2 A1 150 CFM 150 0.5 CV DETAIL 2/MH821 NOTE (1)
S�24 02�4D2 D2 750 CFM 750 1.25 CV DETAIL 2/MH821 NOTE (1)
S�25 02�4D2 E1 1075 CFM 1075 2 CV DETAIL 2/MH821 NOTE (1)
S�26 02�4D2 C1 600 CFM 600 1.25 CV DETAIL 2/MH821 NOTE (1)
S�27 02�4D2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�28 02�4D2 E2 1000 CFM 1000 1.75 CV DETAIL 2/MH821 NOTE (1)
S�29 02�4D2 D2 720 CFM 720 1.25 CV DETAIL 2/MH821 NOTE (1)
S�30 02�4D2 E1 1075 CFM 1075 2 CV DETAIL 2/MH821 NOTE (1)
S�31 02�4D2 E1 1000 CFM 1000 1.75 CV DETAIL 2/MH821 NOTE (1)
S�32 02�4D2 E1 1000 CFM 1000 1.75 CV DETAIL 2/MH821 NOTE (1)
S�33 02�4D2 B3 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R�1 02�4D2 A2 250 CFM 125 � S�11 NOTE (1)
R�2 02�4D2 C2 575 CFM 575 � S�1 NOTE (1)
R�3 02�4D2 D2 700 CFM 425 � S�14 NOTE (1)
R�4 02�4D2 D2 920 CFM 450 � S�2 NOTE (1)
R�5 02�4D2 C2 600 CFM 600 � S�20 NOTE (1)
R�6 02�4D2 A3 125 CFM 75 � S�3 NOTE (1)
R�7 02�4D2 B3 400 CFM 150 � S�5 NOTE (1)
R�8 02�4D2 A3 100 CFM 50 � S�7 NOTE (1)
R�9 02�4D2 A3 235 CFM 125 � S�8 NOTE (1)
R�10 02�4D2 B3 300 CFM 150 � S�9 NOTE (1)
R�11 02�4D2 B3 340 CFM 150 � S�10 NOTE (1)
R�12 02�4D2 D2 800 CFM 400 � S�17 NOTE (1)
R�13 02�4D2 B2 350 CFM 175 � S�18 NOTE (1)
R�14 02�4D2 A2 250 CFM 125 � S�19 NOTE (1)
R�15 02�4D2 B3 400 CFM 200 � S�33 NOTE (1)
R�16 02�4D2 C2 470 CFM 470 � S�29 NOTE (1)
R�17 02�4D2 B3 300 CFM 150 � S�27 NOTE (1)
R�18 02�4D2 E2 1000 CFM 1000 � S�28 NOTE (1)
R�19 02�4D2 C2 640 CFM 640 � S�24 NOTE (1)
EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
E�1 02�4D2 B4 670 CFM 670 CFM � S�13 NOTE (4)
E�2 02�4D2 B4 670 CFM 670 CFM � S�13 NOTE (4)
E�3 02�4D2 B4 830 CFM 830 CFM � S�12 NOTE (4)
E�4 02�4D2 B4 830 CFM 830 CFM � S�12 NOTE (4)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FOURTH FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC�1 02�4D1 E � � NOTE (2)(3)
FCU�1 4D227 02�4D1 2F4 � DETAIL 1/MH820 NOTE (2)
FCU�2 STD�01 02�4D1 4C3 � DETAIL 2/MH820 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FOURTH FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU�1 02�4D2 4C1 � DETAIL 2/MH820 NOTE (2)
RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R�1 4E227 02�4E1 E1 1080 CFM 500 � S�6,S�7,S�11 NOTE (1)
R�2 02�4E1 F2 1625 CFM 1625 � S�1 NOTE (1)
R�3 02�4E1 D2 770 CFM 375 � S�6,S�7,S�11 NOTE (1)
R�4 02�4E1 D2 730 CFM 350 � S�4 NOTE (1)
R�5 02�4E1 B2 400 CFM 200 � S�1 NOTE (1)
R�6 02�4E1 A2 125 CFM 75 � S�2 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R�1 02�4E2 D1 750 CFM 375 � S�12 NOTE (1)
R�2 02�4E2 A3 175 CFM 100 � S�23 NOTE (1)
R�3 02�4E2 B1 400 CFM 200 � S�25 NOTE (1)
R�4 02�4E2 E3 940 CFM 450 � S�27 NOTE (1)
R�5 02�4E2 A3 100 CFM 50 � S�22 NOTE (1)
R�6 02�4E2 A3 100 CFM 50 � S�14 NOTE (1)
R�7 02�4E2 E2 990 CFM 450 � S�21 NOTE (1)
R�8 02�4E2 D2 860 CFM 860 � S�19,S�26 NOTE (1)
R�9 02�4E2 B2 360 CFM 175 � S�20 NOTE (1)
EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
E�1 02�4E2 B4 520 CFM 520 CFM � S�9 NOTE (4)
E�2 02�4E2 C4 1200 CFM 1200 CFM � S�10 NOTE (4)
E�3 02�4E2 B4 730 CFM 730 CFM � S�10 NOTE (4)
E�4 02�4E2 G3 1950 CFM 1050 CFM � S�8 NOTE (1)
E�5 02�4E2 G3 1950 CFM 1050 CFM � S�5 NOTE (1)
E�6 02�4E2 E3 1280 CFM 530 CFM � S�9 NOTE (1)
E�7 02�4E2 G3 1950 CFM 1050 CFM � S�13 NOTE (1)
E�8 02�4E2 G3 1800 CFM 900 CFM � S�16 NOTE (1)
E�9 02�4E2 G3 1950 CFM 1050 CFM � S�18 NOTE (1)
E�10 02�4E2 B3 360 CFM 360 CFM � S�24 NOTE (1)
E�11 02�4E2 B4 730 CFM 730 CFM � S�24 NOTE (4)
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 4E227E 02�4E1 F1 1625 CFM 1625 NO COIL CV DETAIL 2/MH821 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 02�4E2 B3 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�2 02�4E2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�3 02�4E2 D2 750 CFM 750 1.25 CV DETAIL 2/MH821 NOTE (1)
S�4 02�4E2 D2 730 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�5 02�4E2 G3 1800 CFM 900 1.5 VCV DETAIL 4/MH821 NOTE (1)
S�6 02�4E2 D2 770 CFM 770 1.5 CV DETAIL 2/MH821 NOTE (1)
S�7 02�4E2 C2 600 CFM 600 1.0 CV DETAIL 2/MH821 NOTE (1)
S�8 02�4E2 G3 1800 CFM 900 1.5 VCV DETAIL 4/MH821 NOTE (1)
S�9 02�4E2 F3 1500 CFM 750 1.25 VCV DETAIL 4/MH821 NOTE (1)
S�10 02�4E2 G3 1800 CFM 1800 3.0 CV DETAIL 2/MH821 NOTE (1)
S�11 02�4E2 C2 480 CFM 480 1.0 CV DETAIL 2/MH821 NOTE (1)
S�12 02�4E2 D1 750 CFM 375 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�13 02�4E2 G3 1800 CFM 900 1.5 VCV DETAIL 4/MH821 NOTE (1)
S�14 02�4E2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�15 02�4E2 C2 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)
S�16 02�4E2 G3 1800 CFM 900 1.5 VCV DETAIL 4/MH821 NOTE (1)
S�17 02�4E2 A1 100 CFM 100 0.5 CV DETAIL 2/MH821 NOTE (1)
S�18 02�4E2 G3 1800 CFM 900 1.5 VCV DETAIL 4/MH821 NOTE (1)
S�19 02�4E2 C2 440 CFM 450 0.75 CV DETAIL 2/MH821 NOTE (1)
S�20 02�4E2 B2 360 CFM 180 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�21 02�4E2 E2 990 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�22 02�4E2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�23 02�4E2 A3 175 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�24 02�4E2 E3 990 CFM 990 1.75 CV DETAIL 2/MH821 NOTE (1)
S�25 02�4E2 B1 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�26 02�4E2 C2 530 CFM 530 1.0 CV DETAIL 2/MH821 NOTE (1)
S�27 02�4E2 E3 940 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FOURTH FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC�1 4E227 02�4E1 E � � NOTE (2)(3)
FCU�1 4E227 02�4E1 2F4 � DETAIL 1/MH820 NOTE (1)
FCU�2 4E227E 02�4E1 2F4 � DETAIL 1/MH820 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FOURTH FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC�1 4F227 02�4F1 E � � NOTE (2)(3)
FCU�2 4F227 02�4F1 2F4 � DETAIL 1/MH820 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE � FOURTH FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU�1 STF�04 02�4F2 4C1 � DETAIL 2/MH820 NOTE (2)
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 02�4F2 D3 830 CFM 830 1.5 CV DETAIL 2/MH821 NOTE (1)
S�2 02�4F2 E2 1140 CFM 1140 2.0 CV DETAIL 2/MH821 NOTE (1)
S�3 02�4F2 C3 470 CFM 470 1.0 CV DETAIL 2/MH821 NOTE (1)
S�4 02�4F2 D1 725 CFM 725 1.5 CV DETAIL 2/MH821 NOTE (1)
S�5 02�4F2 A3 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)
S�6 02�4F2 A3 125 CFM 125 0.5 CV DETAIL 2/MH821 NOTE (1)
S�7 02�4F2 D2 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�8 02�4F2 E2 1000 CFM 1000 1.75 CV DETAIL 2/MH821 NOTE (1)
S�9 02�4F2 D2 800 CFM 800 1.5 CV DETAIL 2/MH821 NOTE (1)
S�10 02�4F2 F3 1530 CFM 1530 2.5 CV DETAIL 2/MH821 NOTE (1)
S�11 02�4F2 E3 1300 CFM 1300 2.25 CV DETAIL 2/MH821 NOTE (1)
S�12 02�4F2 C2 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)
S�13 02�4F2 D2 760 CFM 760 1.25 CV DETAIL 2/MH821 NOTE (1)
S�14 02�4F2 E3 1330 CFM 1330 2.25 CV DETAIL 2/MH821 NOTE (1)
S�15 02�4F2 E3 1330 CFM 1330 2.25 CV DETAIL 2/MH821 NOTE (1)
S�16 02�4F2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)
S�17 02�4F2 C2 450 CFM 450 0.75 CV DETAIL 2/MH821 NOTE (1)
S�18 02�4F2 D2 750 CFM 750 1.25 CV DETAIL 2/MH821 NOTE (1)
S�19 02�4F2 G3 2200 CFM 2200 3.5 CV DETAIL 2/MH821 NOTE (1)
S�20 02�4F2 C2 450 CFM 450 0.75 CV DETAIL 2/MH821 NOTE (1)
S�21 02�4F2 A2 250 CFM 125 0.5 CV DETAIL 2/MH821 NOTE (1)
S�22 02�4F2 D2 900 CFM 900 1.5 CV DETAIL 2/MH821 NOTE (1)
S�23 02�4F2 A1 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)
S�24 02�4F2 C1 600 CFM 600 1.0 CV DETAIL 2/MH821 NOTE (1)
S�25 02�4F2 B1 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�26 02�4F2 B2 400 CFM 400 0.75 CV DETAIL 2/MH821 NOTE (1)
S�27 02�4F2 D3 830 CFM 830 1.5 CV DETAIL 2/MH821 NOTE (1)
S�28 02�4F2 C3 510 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�29 02�4F2 B2 400 CFM 400 0.75 CV DETAIL 2/MH821 NOTE (1)
S�30 02�4F2 B3 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�31 02�4F2 H3 2925 CFM 2925 5.0 CV DETAIL 2/MH821 NOTE (1)
S�32 02�4F2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�33 02�4F2 C3 600 CFM 300 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�34 02�4F2 D2 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S�35 02�4F2 C2 525 CFM 525 1.0 CV DETAIL 2/MH821 NOTE (1)
S�36 02�4F2 B1 400 CFM 400 0.75 CV DETAIL 2/MH821 NOTE (1)
S�37 02�4F2 B3 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�38 02�4F2 B3 400 CFM 200 0.5 VCV DETAIL 4/MH821 NOTE (1)
S�39 02�4F2 C3 460 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R�1 02�4F2 F2 1640 CFM 1640 � S�2,S�4,S�9 NOTE (1)
R�2 02�4F2 F2 1510 CFM 1510 � S�13,S�18 NOTE (1)
R�3 02�4F2 G2 1800 CFM 1350 � S�7,S�8 NOTE (1)
R�4 02�4F2 B3 400 CFM 200 � S�30 NOTE (1)
R�5 02�4F2 D2 900 CFM 450 � S�34 NOTE (1)
R�6 02�4F2 B3 400 CFM 200 � S�37 NOTE (1)
R�7 02�4F2 D2 900 CFM 900 � S�22 NOTE (1)
R�8 02�4F2 A1 200 CFM 100 � S�23 NOTE (1)
R�9 02�4F2 B1 400 CFM 200 � S�25 NOTE (1)
R�10 02�4F2 C3 510 CFM 250 � S�28 NOTE (1)
R�11 02�4F2 A3 100 CFM 50 � S�32 NOTE (1)
R�12 02�4F2 B3 360 CFM 125 � S�39 NOTE (1)
R�13 02�4F2 C3 600 CFM 300 � S�33 NOTE (1)
R�14 02�4F2 A2 200 CFM 200 � S�26 NOTE (1)
R�15 02�4F2 C2 525 CFM 525 � S�35 NOTE (1)
R�16 02�4F2 B3 400 CFM 200 � S�38 NOTE (1)
EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
E�1 02�4F2 C2 520 CFM 520 CFM � S�3 NOTE (4)
E�2 02�4F2 D2 830 CFM 830 CFM � S�10 NOTE (4)
E�3 02�4F2 D2 830 CFM 830 CFM � S�1 NOTE (4)
E�4 02�4F2 D2 830 CFM 830 CFM � S�10 NOTE (4)
E�5 02�4F2 D2 830 CFM 830 CFM � S�14,S�15 NOTE (4)
E�6 02�4F2 E2 1150 CFM 1150 CFM � S�14,S�15 NOTE (4)
E�7 02�4F2 D2 830 CFM 830 CFM � S�14,S�15 NOTE (4)
E�8 02�4F2 D2 830 CFM 830 CFM � S�27 NOTE (4)
E�9 02�4F2 E2 1300 CFM 1300 CFM � S�11 NOTE (1)
E�10 02�4F2 B2 375 CFM 375 CFM � S�5,S�6 NOTE (1)
GENERAL NOTES:
1. REFER TO DRAWINGS MH603 AND MH604 FOR
SCHEDULE CAPACITES
2. REFER TO DRAWINGS MH607 AND MH608 FOR
SCHEDULE CAPACITIES
3. REQUIRES EMERGENCY POWER
4.REFER TO DRAWING 2MH609 FOR SCHEDULE
CAPACITIES
SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S�1 4F227 02�4F1 F1 1425 CFM 1425 NO COIL CV DETAIL 2/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE � FOURTH FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R�1 4F227 02�4F1 F2 1425 CFM 1425 � S�1 NOTE (1)
REFER TO SKETCH:
SK-8-1-NJ-2-MH-630-1
B4 B4
B4 B4
B4
B4 B4
C4
Size changes per RFI 3077