VAV DNT 02303-2MH628.pdf
PDF 171 KB Posted
- Attached to
- Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
- Solicitation number
- Not on record
About this file
This document package includes an HVAC system rebalance solicitation and related drawings. The solicitation is to rebalance the HVAC system at a Department of Veterans Affairs medical center to provide (91) ninety-one attachments including schedules for air terminal units, fan coil units, return terminal units, and supply terminal units on various floors of the building. The drawings contain details for control sequences and provide equipment specifications including sizes, flow rates, and control types. The solicitation is for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 to ensure the HVAC system is properly balanced and operating as designed.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H A L
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
E E T
(1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
X T
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
2MH628
BLDG 02 HVAC AIR TERMINAL UNIT AND FAN
COIL UNIT SCHEDULE
KJS DCDFebruary 29, 2012
02629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
NEW ORLEANS, LOUISIANA
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING/ PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2F2 B3 400 CFM 100 CFM - S-7 NOTE (1)
R-2 02-2F2 E3 1175 CFM 850 CFM - S-5,S-8,S-47 NOTE (1)
R-3 02-2F2 E3 1000 CFM 350 CFM - S-9,S-11 NOTE (1)
R-4 02-2F2 E3 1100 CFM 450 CFM - S-10,S-12 NOTE (1)
R-5 02-2F2 E3 1100 CFM 450 CFM - S-13,S-14 NOTE (1)
R-6 02-2F2 E2 1175 CFM 1175 CFM - S-24 NOTE (1)
R-7 02-2F2 D2 700 CFM 700 CFM - S-1,S-2 NOTE (1)
R-8 02-2F2 D3 900 CFM 325 CFM - S-3,S-18 NOTE (1)
R-9 02-2F2 C3 550 CFM 150 CFM - S-15,S-17 NOTE (1)
R-10 02-2F2 A3 250 CFM 125 CFM - S-19 NOTE (1)
R-11 02-2F2 E2 1050 CFM 275 CFM - S-21 NOTE (1)
R-12 02-2F2 C3 550 CFM 150 CFM - S-20 NOTE (1)
R-13 02-2F2 C2 400 CFM 450 CFM - S-16,S-24 NOTE (1)
R-14 02-2F2 A3 225 CFM 225 CFM - S-31 NOTE (1)
R-15 02-2F2 D3 775 CFM 350 CFM - S-46 NOTE (1)
R-16 02-2F2 C3 500 CFM 250 CFM - S-40 NOTE (1)
R-17 02-2F2 B3 300 CFM 150 CFM - S-44 NOTE (1)
R-18 02-2F2 D3 680 CFM 340 CFM - S-26,S-28 NOTE (1)
R-19 02-2F2 E3 1080 CFM 540 CFM - S-29,S-30 NOTE (1)
R-20 02-2F2 D3 800 CFM 400 CFM - S-32,S-35 NOTE (1)
R-21 02-2F2 D3 900 CFM 450 CFM - S-39 NOTE (1)
R-22 02-2F2 E2 950 CFM 475 CFM - S-27 NOTE (1)
R-23 02-2F2 C3 500 CFM 250 CFM - S-43 NOTE (1)
R-24 02-2F2 C3 500 CFM 250 CFM - S-45 NOTE (1)
R-25 02-2F2 D3 850 CFM 425 CFM - S-33,S-34 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 2F-CO1 02-2F1 F - - NOTE (2)(3)
FCU-2 2F-CO1 02-2F1 2F4 - DETAIL 1/MH820 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU-1 STF-04 02-2F2 4C1 - DETAIL 2/MH820 NOTE (2)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR F2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2F2 C2 525 CFM 525 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-2 02-2F2 D2 800 CFM 400 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-3 02-2F2 C3 500 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-4 02-2F2 D2 750 CFM 750 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-5 02-2F2 C2 500 CFM 500 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-6 02-2F2 C3 450 CFM 450 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-7 02-2F2 C3 600 CFM 300 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-8 02-2F2 A3 150 CFM 75 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-9 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-10 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-11 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-12 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-13 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-14 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-15 02-2F2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-16 02-2F2 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-17 02-2F2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-18 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-19 02-2F2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-20 02-2F2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-21 02-2F2 E2 1050 CFM 400 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-22 02-2F2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-23 02-2F2 A3 200 CFM 100 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-24 02-2F2 D2 700 CFM 700 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-25 02-2F2 B2 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-26 02-2F2 B3 275 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-27 02-2F2 E2 1000 CFM 500 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)
S-28 02-2F2 C2 405 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-29 02-2F2 C3 540 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-30 02-2F2 C3 540 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-31 02-2F2 C2 500 CFM 500 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-32 02-2F2 A3 150 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-33 02-2F2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-34 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-35 02-2F2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-36 02-2F2 B3 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-37 02-2F2 C2 575 CFM 575 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-38 02-2F2 A2 225 CFM 225 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-39 02-2F2 D3 900 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-40 02-2F2 C3 500 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-41 02-2F2 B3 300 CFM 300 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-42 02-2F2 C1 550 CFM 500CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-43 02-2F2 C3 500 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-44 02-2F2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-45 02-2F2 C3 500 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-46 02-2F2 D3 875 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-47 02-2F2 C2 525 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 1G227 02-2G1 D1 925 CFM 925 CFM - CV DETAIL 2/MH821 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2G2 C2 600 CFM 310 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-2 02-2G2 B3 380 CFM 190 CFM .5 VCV DETAIL 4/MH821 NOTE (1)
S-3 02-2G2 D1 700 CFM 700 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-5 02-2G2 B2 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-6 02-2G2 C2 625 CFM 625 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-7 02-2G2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-8 02-2G2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-9 02-2G2 B2 350 CFM 350 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-10 02-2G2 C2 675 CFM 675 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-11 02-2G2 A3 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-12 02-2G2 B3 280 CFM 140 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-13 02-2G2 B3 280 CFM 140 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-14 02-2G2 B3 280 CFM 140 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-15 02-2G2 E3 1000 CFM 400 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-16 02-2G2 B3 280 CFM 140 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-17 02-2G2 C2 500 CFM 500 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-18 02-2G2 C2 500 CFM 500 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-19 02-2G2 E3 1000 CFM 400 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-20 02-2G2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-21 02-2G2 E2 1200 CFM 1200 CFM 2.0 CV DETAIL 2/MH821 NOTE (1)
S-22 02-2G2 C2 500 CFM 500 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-23 02-2G2 C3 450 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-24 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-25 02-2G2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-26 02-2G2 D3 700 CFM 700 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-27 02-2G2 E2 1000 CFM 405 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-28 02-2G2 C3 750 CFM 750 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-29 02-2G2 C3 425 CFM 225 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-30 02-2G2 B3 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-31 02-2G2 B3 325 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-32 02-2G2 H3 2400 CFM 1200 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)
S-33 02-2G2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-34 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-35 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-36 02-2G2 C3 450 CFM 450 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-37 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-38 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-39 02-2G2 E2 950 CFM 950 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)
S-40 02-2G2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-41 02-2G2 D3 900 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-42 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-43 02-2G2 H3 2400 CFM 1200 CFM 2.0 CV DETAIL 2/MH821 NOTE (1)
S-44 02-2G2 E3 1000 CFM 1000 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)
S-45 02-2G2 E3 1000 CFM 1000 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)
S-46 02-2G2 C3 500 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-47 02-2G2 A2 225 CFM 110 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-48 02-2G2 A3 220 CFM 110 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-49 02-2G2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-50 02-2G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-51 02-2G2 A2 175 CFM 175 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 1G227 02-2G1 D2 925 CFM 925 CFM - S-1 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2G2 B3 400 CFM 200 CFM - S-5,S-11 NOTE (1)
R-2 02-2G2 E3 1125 CFM 625 CFM - S-15 NOTE (1)
R-3 02-2G2 C3 500 CFM 250 CFM - S-7,S-20 NOTE (1)
R-4 02-2G2 C2 550 CFM 550 CFM - S-10,S-21 NOTE (1)
R-5 02-2G2 E3 980 CFM 450 CFM - S-1,S-2 NOTE (1)
R-6 02-2G2 C3 560 CFM 280 CFM - S-12,S-13 NOTE (1)
R-7 02-2G2 C3 560 CFM 280 CFM - S-14,S-16 NOTE (1)
R-8 02-2G2 B2 300 CFM 300 CFM - S-17 NOTE (1)
R-9 02-2G2 E3 1125 CFM 625 CFM - S-19 NOTE (1)
R-10 02-2G2 C3 600 CFM 300 CFM - S-8,S-9 NOTE (1)
R-11 02-2G2 B2 300 CFM 300 CFM - S-18,S-21 NOTE (1)
R-12 02-2G2 C3 550 CFM 300 CFM - S-29,S-31 NOTE (1)
R-13 02-2G2 A3 200 CFM 100 CFM - S-33 NOTE (1)
R-14 02-2G2 H2 2500 CFM 1300 CFM - S-32 NOTE (1)
R-15 02-2G2 C3 600 CFM 300 CFM - S-25 NOTE (1)
R-17 02-2G2 D3 750 CFM 475 CFM - S-27,S-39,S-42 NOTE (1)
R-18 02-2G2 C3 750 CFM 225 CFM - S-23 NOTE (1)
R-19 02-2G2 C2 500 CFM 500 CFM - S-22 NOTE (1)
R-20 02-2G2 C3 600 CFM 300 CFM - S-34,S-35,S-37 NOTE (1)
R-21 02-2G2 C3 550 CFM 275 CFM - S-24,S-40 NOTE (1)
R-22 02-2G2 D3 900 CFM 450 CFM - S-41 NOTE (1)
R-23 02-2G2 C3 500 CFM 250 CFM - S-46 NOTE (1)
R-24 02-2G2 C3 600 CFM 300 CFM - S-42,S-50 NOTE (1)
R-25 02-2G2 D3 675 CFM 350 CFM - S-36,S-47 NOTE (1)
R-26 02-2G2 C3 520 CFM 260 CFM - S-38,S-48 NOTE (1)
R-27 02-2G2 B3 375 CFM 375 CFM - S-49 NOTE (1)
R-28 02-2G2 A2 175 CFM 175 CFM - S-51 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 3E-C538 02-2G1 F - - NOTE (2)(3)
FCU-1 1G227 02-2G1 2F4 - DETAIL 1/MH820 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks Count
CAC-1 02-2G2 F - - NOTE (2) 1
CAC-2 02-2G2 G - - NOTE (2) 1
CAC-3 1G167A 02-2G2 E - - NOTE (2) 1
FCU-1 1G197 02-2G2 4F4 - DETAIL 2/MH820 NOTE (2) 1
FCU-2 STG-03-3 02-2G2 4C1 - DETAIL 2/MH820 NOTE (2) 1
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - THIRD FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 3D-CO1 02-3D1 F - - NOTE (2)(3)
FCU-1 02-3D1 2F4 - DETAIL 1/MH820 NOTE (2)
FCU-2 STD-01 02-3D1 4C3 - DETAIL 2/MH820 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - THIRD FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU-1 02-3D2 4C1 - DETAIL 4/MH817 NOTE (2)
FCU-2 3D141 02-3D2 2D4 - DETAIL 1/MH817 NOTE (2)
FCU-3 02-3D2 2D4 - DETAIL 1/MH817 NOTE (2)
RETURN TERMINAL UNIT SCHEDULE - THIRD FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-3D2 B3 400 CFM 250 CFM - S-6 NOTE (1)
R-2 02-3D2 C3 600 CFM 300 CFM - S-35 NOTE (1)
R-3 02-3D2 B3 375 CFM 190 CFM - S-8 NOTE (1)
R-4 02-3D2 G3 1800 CFM 1000 CFM - S-1,S-2,S-12 NOTE (1)
R-5 02-3D2 D3 925 CFM 450 CFM - S-10,S-14 NOTE (1)
R-6 02-3D2 C3 625 CFM 295 CFM - S-13,S-17 NOTE (1)
R-7 02-3D2 E2 1000 CFM 500 CFM - S-11 NOTE (1)
R-8 02-3D2 D2 725 CFM 725 CFM - S-18,S-19 NOTE (1)
R-9 02-3D2 D3 925 CFM 480 CFM - S-9,S-15 NOTE (1)
R-10 02-3D2 C3 450 CFM 205 CFM - S-16 NOTE (1)
R-11 02-3D2 E3 1115 CFM 685 CFM - S-24,S-27 NOTE (1)
R-12 02-3D2 H3 2950 CFM 1475 CFM - S-25 NOTE (1)(4)
R-13 02-3D2 H3 2950 CFM 1475 CFM - S-26 NOTE (1)(4)
R-14 02-3D2 D3 675 CFM 425 CFM - S-20,S-21,S-22 NOTE (1)
R-15 02-3D2 H3 2950 CFM 1475 CFM - S-29 NOTE (1)(4)
R-16 02-3D2 H3 2950 CFM 1475 CFM - S-32 NOTE (1)(4)
R-17 02-3D2 B3 300 CFM 150 CFM - S-30 NOTE (1)
R-18 02-3D2 A3 150 CFM 75 CFM - S-33 NOTE (1)
R-19 02-3D2 E3 1225 CFM 1225 CFM - S-28 NOTE (1)
R-20 02-3D2 E3 1125 CFM 975 CFM - S-34 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE - THIRD FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-3D1 D1 750 CFM 750 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-2 02-3D1 D3 925 CFM 925 CFM 1.5 CV DETAIL 2/MH821 NOTE (1)
S-3 02-3D1 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-4 STD-14 02-3D1 E1 1425 CFM 1425 CFM 2.5 CV DETAIL 2/MH821 NOTE (1)
S-5 02-3D1 C2 600 CFM 600 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE - THIRD FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-3D2 A3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-2 02-3D2 A3 100 CFM 50 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-3 02-3D2 C2 600 CFM 300 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-4 02-3D2 E2 950 CFM 950 CFM 1.75 CV DETAIL 2/MH821 NOTE (1)
S-5 02-3D2 E2 1150 CFM 1150 CFM 2.0 CV DETAIL 2/MH821 NOTE (1)
S-6 02-3D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-7 02-3D2 A2 200 CFM 200 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-8 02-3D2 B3 375 CFM 190 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-9 02-3D2 C3 475 CFM 240 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-10 02-3D2 C3 475 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-11 02-3D2 E2 1000 CFM 500 CFM 0.9 VCV DETAIL 4/MH821 NOTE (1)
S-12 02-3D2 F2 1450 CFM 800 CFM 1.3 VCV DETAIL 4/MH821 NOTE (1)
S-13 02-3D2 B3 375 CFM 175 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-14 02-3D2 C3 450 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-15 02-3D2 C3 450 CFM 240 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-16 02-3D2 C3 450 CFM 205 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-17 02-3D2 A3 250 CFM 115 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-18 02-3D2 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-19 02-3D2 B2 300 CFM 300 CFM 0.75 CV DETAIL 2/MH821 NOTE(1)
S-20 02-3D2 B3 300 CFM 300 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-21 02-3D2 A3 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-22 02-3D2 B3 275 CFM 140 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-23 02-3D2 C2 450 CFM 450 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-24 02-3D2 C2 465 CFM 465 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-25 02-3D2 H3 3200 CFM 1600 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-26 02-3D2 H3 3200 CFM 1600 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-27 02-3D2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-28 02-3D2 D3 825 CFM 825 CFM 1.5 CV DETAIL 2/MH821 NOTE (1)
S-29 02-3D2 H3 3200 CFM 1600 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-30 02-3D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-31 02-3D2 A3 150 CFM 70 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-32 02-3D2 H3 3200 CFM 1600 CFM 2.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-33 02-3D2 A3 150 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-34 02-3D2 C3 450 CFM 450 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-35 02-3D2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2F1 D2 1250 CFM 1250 CFM - S-1 NOTE (1)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR F1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 2F-CO1 02-2F1 D1 925 CFM 925 CFM NO COIL VCV DETAIL 6/MH817 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - THIRD FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-3D1 C2 0 CFM 255 CFM CV DETAIL 2/MH821 NOTE (1)
R-3 STD-14 02-3D1 1425 CFM 1425 CFM VCV DETAIL 4/MH821 NOTE (1)
R-4 02-3D1 A2 600 CFM 90 CFM VCV DETAIL 4/MH821 NOTE (1)
GENERAL NOTES:
1. REFER TO DRAWINGS MH603 AND
MH604 FOR SCHEDULE CAPACITES
2. REFER TO DRAWINGS MH607 AND
MH608 FOR SCHEDULE CAPACITIES
3. REQUIRES EMERGENCY POWER
4. INTERLOCK BOXES PER CONTROL
DIAGRAM MH812B
30 BULL 029C - IMAGING 7/23/2014