VAV DNT 02306-2MH631.pdf

PDF 262 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains an HVAC terminal unit and fan coil unit schedule for a medical center replacement project. The schedule provides specifications for 91 supply terminal units, 37 return terminal units, and 41 fan coil units or computer room air conditioners across multiple floors. It lists the location, size, control type, and remarks for each unit. The related federal contract opportunity is a solicitation to rebalance the HVAC system for the project, with 91 attachments provided in the amendment.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
VAV DNT 02303-2MH628.pdf PDF
P12-AMS CEP 115-7MH608.pdf PDF
S02-XHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE v2.pdf PDF
VAV DNT 02305-2MH630.pdf PDF
DNT L05 G.pdf PDF
RESEARCH 4th mech plan.pdf PDF
CEP L03.pdf PDF
P12-000110 Table of Contents 4-7-20.pdf PDF
AMS TLR 03470-6MH604.pdf PDF
ICRA ILSM for CFM - Rebalance HVAC System.xlsx XLSX spreadsheet
013526 Safety Requirements.pdf PDF
VAV DNT 02302-2MH627.pdf PDF
PANAM 103.pdf PDF
230593 Testing Adjusting and Balancing for HVAC.pdf PDF
VAV DNT 02301-2MH626.pdf PDF
M-3 DNT Building Existing DOAS sequence.pdf PDF
OUT L07.pdf PDF
P13-INP L04.pdf PDF
DNT L01i D-E.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
RESEARCH 2nd mech plan.pdf PDF
OUT L05.pdf PDF
390-8EP105-P.pdf PDF
S02-EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.pdf PDF
PANAM 105.pdf PDF
P07-General Decision.pdf PDF
CEP L04.pdf PDF
230800 Commissioning of HVAC Systems.pdf PDF
RESEARCH 1st mech plan.pdf PDF
P15-M-1 Typical Existing Service Bay layout.pdf PDF
AMS PANAM 0243-9MH601.pdf PDF
AMS OP 03027-3MH604.pdf PDF
010000 General Requirements.pdf PDF
013323 Shop Drawings Product Data and Samples.pdf PDF
P12-230923 DDC Control System for HVAC 4-7-20.pdf PDF
VAV DNT 02304-2MH629.pdf PDF
P12-ROOMS NUMBERS LIST WITH OLD AND NEW ROOM NUMBERS.xlsx XLSX spreadsheet
03491-6EL103-M3.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
PANAM 104.pdf PDF
03503-6EP103-M3.pdf PDF
OUT L06.pdf PDF
OUT L04.pdf PDF
OUT L03.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
AMS Research 348-8MH609.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
P15-M-5 OP Building Existing DOAS sequence.pdf PDF
Show all 50

Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

2MH631

BLDG 02 HVAC AIR TERMINAL UNIT AND FAN

COIL UNIT SCHEDULE

KJS DCDFebruary 29, 2012

02629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE - FOURTH FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 4G227 02-4G1 E1 1250 CFM 1250 NO COIL CV DETAIL 2/MH821 NOTE (1)

S-2 02-4G1 B2 400 CFM 200 1.5 CV DETAIL 2/MH817 NOTE (1)

S-3 02-4G1 B3 200 CFM 100 1.5 CV DETAIL 2/MH817 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE - FOURTH FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-4G2 C2 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S-2 02-4G2 G3 2000 CFM 1000 1.75 VCV DETAIL 4/MH821 NOTE (1)

S-3 02-4G2 D1 800 CFM 800 1.5 CV DETAIL 2/MH821 NOTE (1)

S-4 02-4G2 A2 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-5 02-4G2 C2 450 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-6 02-4G2 G3 2000 CFM 1000 1.75 VCV DETAIL 4/MH821 NOTE (1)

S-7 02-4G2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-8 02-4G2 E2 1050 CFM 500 1.0 VCV DETAIL 4/MH821 NOTE (1)

S-9 02-4G2 D2 675 CFM 325 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-10 02-4G2 D2 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-11 02-4G2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-12 02-4G2 C3 650 CFM 325 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-13 02-4G2 C1 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)

S-14 02-4G2 C2 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)

S-15 02-4G2 C1 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)

S-16 02-4G2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-17 02-4G2 B2 330 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-18 02-4G2 G2 2120 CFM 425 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-19 02-4G2 G2 2120 CFM 425 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-20 02-4G2 G2 2010 CFM 425 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-21 02-4G2 A2 240 CFM 240 0.5 CV DETAIL 2/MH821 NOTE (1)

S-22 02-4G2 B2 350 CFM 175 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-23 02-4G2 G2 2010 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-25 02-4G2 G2 2200 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-26 02-4G2 G2 2010 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-27 02-4G2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-28 02-4G2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-29 02-4G2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-30 02-4G2 G2 2010 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-31 02-4G2 E2 1050 CFM 1050 1.75 CV DETAIL 2/MH821 NOTE (1)

S-32 02-4G2 E2 1125 CFM 1125 2.0 CV DETAIL 2/MH821 NOTE (1)

S-33 02-4G2 B2 375 CFM 375 0.75 CV DETAIL 2/MH821 NOTE (1)

S-34 02-4G2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-35 02-4G2 D2 875 CFM 875 1.5 CV DETAIL 2/MH821 NOTE (1)

S-36 02-4G2 A2 100 CFM 100 0.5 CV DETAIL 2/MH821 NOTE (1)

S-37 02-4G2 A2 800 CFM 100 0.5 CV DETAIL 2/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE - FOURTH FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 4G227 02-4G1 E-1 1250 CFM 1250 - S-1 NOTE (1)

R-2 02-4G1 C2 600 CFM 300 VCV S-2, S-3 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE - FOURTH FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-4G2 E2 1130 CFM 600 - S-4,S-8,S-9,S-10 NOTE (1)

R-2 02-4G2 G3 2000 CFM 1000 - S-6 NOTE (1)

R-3 02-4G2 G3 2000 CFM 1000 - S-2 NOTE (1)

R-4 02-4G2 C2 650 CFM 650 - S-1 NOTE (1)

R-5 02-4G2 B3 400 CFM 200 - S-7,S-11 NOTE (1)

R-6 02-4G2 C2 450 CFM 225 - S-5 NOTE (1)

R-7 02-4G2 G2 1755 CFM 800 - S-4,S-8,S-9,S-10 NOTE (1)

R-8 02-4G2 B3 300 CFM 150 - S-16 NOTE (1)

R-9 02-4G2 B3 300 CFM 150 - S-27 NOTE (1)

R-10 02-4G2 B2 330 CFM 150 - S-17 NOTE (1)

R-11 02-4G2 C1 500 CFM 500 - S-13 NOTE (1)

R-12 02-4G2 B2 350 CFM 175 - S-22 NOTE (1)

R-13 02-4G2 C3 650 CFM 325 - S-12 NOTE (1)

R-15 02-4G2 B3 300 CFM 150 - S-28 NOTE (1)

R-16 02-4G2 A3 200 CFM 100 - S-34 NOTE (1)

R-17 02-4G2 A3 200 CFM 100 - S-29 NOTE (1)

R-18 02-4G2 C2 475 CFM 475 - S-35 NOTE (1)

R-19 02-4G2 A3 200 CFM 100 - S-34 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FOURTH FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 3E-C778 02-4G1 E - - NOTE (2)(3)

FCU-1 4G227 02-4G1 2F4 - DETAIL 1/MH820 NOTE (2)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FOURTH FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 4G228 02-4G2 2F4 DETAIL 2/MH820 NOTE (2)

FCU-2 STG-03-1 02-4G2 4C1 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE - FIFTH FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 5D143 02-5D1 A2 200 CFM 100 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-2 5D145A 02-5D1 A1 125 CFM 125 CFM 0.5 CV DETAIL 1/MH821 NOTE (1)

S-3 5D143 02-5D1 A3 200 CFM 100 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-4 5D143 02-5D1 B1 300 CFM 300 CFM NO COIL CV DETAIL 1/MH821 NOTE (1)

S-5 5D141 02-5D1 A1 250 CFM 250 CFM 0.5 CV DETAIL 1/MH821 NOTE (1)

S-6 5D132 02-5D1 A1 175 CFM 175 CFM NO COIL CV DETAIL 1/MH821 NOTE (1)

S-7 5D124 02-5D1 C2 425 CFM 250 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-8 5D221 02-5D1 C1 500 CFM 500 CFM 1.0 CV DETAIL 1/MH821 NOTE (1)

S-9 5D128 02-5D1 D3 850 CFM 425 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-10 5D121 02-5D1 A2 150 CFM 75 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-11 5D-C03 02-5D1 D3 675 CFM 375 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-12 5D121 02-5D1 A1 250 CFM 250 CFM 0.5 CV DETAIL 1/MH821 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE - FIFTH FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 5D-C11 02-5D2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-2 5D-C11 02-5D2 C2 700 CFM 700 CFM 1.25 CV DETAIL 1/MH821 NOTE (1)

S-3 5D-C10 02-5D2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-4 5D-C10 02-5D2 D3 750 CFM 400 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-5 5D-C10 02-5D2 C3 600 CFM 300 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-6 5D-C10 02-5D2 E3 1225 CFM 1225 CFM 2.25 CV DETAIL 1/MH821 NOTE (1)

S-7 5D-C10 02-5D2 C3 600 CFM 300 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-8 5D-C10 02-5D2 C3 600 CFM 300 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-9 5D167 02-5D2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-10 5D167 02-5D2 C3 875 CFM 625 CFM 1.25 CV DETAIL 1/MH821 NOTE (1)

S-11 5D-C10 02-5D2 C3 600 CFM 300 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-12 5D-C15 02-5D2 C2 500 CFM 250 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-13 5D-C07 02-5D2 A2 175 CFM 175 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-14 5D-C15 02-5D2 C2 575 CFM 575 CFM 1.0 CV DETAIL 1/MH821 NOTE (1)

S-15 5D151C 02-5D2 A3 250 CFM 250 CFM 0.5 CV DETAIL 1/MH821 NOTE (1)

S-16 5D151C 02-5D2 A3 225 CFM 225 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-17 5D166 02-5D2 C3 525 CFM 475 CFM 1.0 VCV DETAIL 3/MH821 NOTE (1)

S-18 5D-C07 02-5D2 B3 350 CFM 175 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-19 5D-C07 02-5D2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-20 5D-C07 02-5D2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-21 5D-C07 02-5D2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-22 5D-C07 02-5D2 C3 650 CFM 325 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-23 5D166 02-5D2 D3 700 CFM 700 CFM 1.25 CV DETAIL 1/MH821 NOTE (1)

S-24 3E-C277 02-5D2 B3 275 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-25 3E-C277 02-5D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-26 3E-C277 02-5D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-27 5D166 02-5D2 E3 950 CFM 950 CFM 1.75 CV DETAIL 1/MH821 NOTE (1)

S-28 3E-C277 02-5D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-29 3E-C277 02-5D2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-30 3E-C277 02-5D2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-31 3E-C277 02-5D2 D3 700 CFM 700 CFM 1.25 VCV DETAIL 3/MH821 NOTE (1)

S-32 3E-C277 02-5D2 A3 225 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-33 5D-C03 02-5D2 B3 275 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-34 5D-C05 02-5D2 C3 600 CFM 600 CFM 1.25 CV DETAIL 1/MH821 NOTE (1)

S-35 5D-C05 02-5D2 A3 250 CFM 150 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-36 5D-C03 02-5D2 D3 675 CFM 375 CFM 0.75 VCV DETAIL 3/MH821 NOTE (1)

S-37 5D116 02-5D2 A2 250 CFM 250 CFM 0.5 CV DETAIL 1/MH821 NOTE (1)

S-38 5D106 02-5D2 A2 125 CFM 75 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-39 5D-C04 02-5D2 A2 150 CFM 75 CFM 0.5 VCV DETAIL 3/MH821 NOTE (1)

S-40 5D-C12 02-5D2 E2 1100 CFM 550 CFM 1.0 VCV DETAIL 3/MH821 NOTE (1)

S-41 5D-C12 02-5D2 D2 700 CFM 700 CFM 1.25 CV DETAIL 1/MH821 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH FLOOR D

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 5D-C03 02-5D1 E - - NOTE (2)(3)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH FLOOR E

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 02-5E 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-2 02-5E 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-3 02-5E 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-4 02-5E 4F4 - DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH FLOOR F

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 4F227 02-5F 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-2 4F227 02-5F 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-3 02-5F 4F4 - DETAIL 2/MH820 NOTE (2)

FCU-4 02-5F 4D4 - DETAIL 2/MH820 NOTE (2)(3)

FCU-5 02-5F 4B1 - DETAIL 2/MH820 NOTE (2)

FCU-6 02-5F 4H7 - DETAIL 2/MH820 NOTE (2)(3)

FCU-7 02-5F 4H7 - DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIFTH FLOOR G

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 02-5G 4F2 DETAIL 2/MH820 NOTE (2)

FCU-2 02-5G 4F2 DETAIL 2/MH820 NOTE (2)

FCU-3 02-5G 4F2 DETAIL 2/MH820 NOTE (2)

FCU-4 5G226 02-5G 4F2 DETAIL 2/MH820 NOTE (2)

FCU-5 02-5G 4F2 DETAIL 2/MH820 NOTE (2)

FCU-6 02-5G 4F3 DETAIL 2/MH820 NOTE (2)

FCU-7 5G228B 02-5G 4F8 DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SIXTH FLOOR D

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 02-6D 4F3 - DETAIL 2/MH820 NOTE (2)

FCU-2 02-6D 4F3 - DETAIL 2/MH820 NOTE (2)

FCU-3 02-6D 4F3 - DETAIL 2/MH820 NOTE (2)

FCU-4 02-6D 4F3 - DETAIL 2/MH820 NOTE (2)

FCU-5 02-6D 4F3 - DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SIXTH FLOOR F

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SEVENTH FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 02-7D1 4H6 - DETAIL 2/MH820 NOTE (2)(3)

GENERAL NOTES:

1. REFER TO DRAWINGS MH603 AND MH604 FOR

SCHEDULE CAPACITES

2. REFER TO DRAWINGS MH607 AND MH608 FOR

SCHEDULE CAPACITIES

3. REQUIRES EMERGENCY POWER

4. INTERLOCK WITH KITCHEN HOOD VAV

EXHAUST PER DRAWING 2MH802.

FAN EF- 29: S-18,S-19,S-20

FAN EF- 27: S-23,S-25,S-26,S-30

REFER TO SKETCH:

SK-8-1-NJ-2-MH-631-1

File details come from the government source that posted it. Updated .