VAV DNT 02302-2MH627.pdf

PDF 268 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document package includes a technical drawing set and specifications for rebalancing the HVAC system in a federal medical facility, as well as details of a related federal contract opportunity.

The technical drawings depict the layout of the existing HVAC system and provide schedules with equipment details, sizes, control types and sequences. General notes reference related drawings for capacity information and control interlocks for emergency operation. The opportunity notice is a modification to rebalance the HVAC system depicted in the technical drawings, as issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16. The purpose is to attach ninety-one additional documents to the solicitation. No further information is provided on product or service requirements, pricing terms, response dates or other solicitation details.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
PANAM 103.pdf PDF
230593 Testing Adjusting and Balancing for HVAC.pdf PDF
VAV DNT 02301-2MH626.pdf PDF
M-3 DNT Building Existing DOAS sequence.pdf PDF
OUT L07.pdf PDF
P13-INP L04.pdf PDF
DNT L01i D-E.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
RESEARCH 2nd mech plan.pdf PDF
OUT L05.pdf PDF
390-8EP105-P.pdf PDF
S02-EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.pdf PDF
PANAM 105.pdf PDF
P07-General Decision.pdf PDF
CEP L04.pdf PDF
230800 Commissioning of HVAC Systems.pdf PDF
RESEARCH 1st mech plan.pdf PDF
P15-M-1 Typical Existing Service Bay layout.pdf PDF
AMS PANAM 0243-9MH601.pdf PDF
AMS OP 03027-3MH604.pdf PDF
010000 General Requirements.pdf PDF
013323 Shop Drawings Product Data and Samples.pdf PDF
P12-230923 DDC Control System for HVAC 4-7-20.pdf PDF
VAV DNT 02306-2MH631.pdf PDF
VAV DNT 02304-2MH629.pdf PDF
P12-ROOMS NUMBERS LIST WITH OLD AND NEW ROOM NUMBERS.xlsx XLSX spreadsheet
03491-6EL103-M3.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
PANAM 104.pdf PDF
03503-6EP103-M3.pdf PDF
OUT L06.pdf PDF
OUT L04.pdf PDF
OUT L03.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
AMS Research 348-8MH609.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
P15-M-5 OP Building Existing DOAS sequence.pdf PDF
OUT L02.pdf PDF
VAV Research 352-8MH613.pdf PDF
RESEARCH 5 dixie penthouse.pdf PDF
INP L03.pdf PDF
DNT L02i F-G.pdf PDF
VAV DNT 02303-2MH628.pdf PDF
P12-AMS CEP 115-7MH608.pdf PDF
S02-XHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE v2.pdf PDF
VAV DNT 02305-2MH630.pdf PDF
DNT L05 G.pdf PDF
RESEARCH 4th mech plan.pdf PDF
Show all 50

Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

2MH627

BLDG 02 HVAC AIR TERMINAL UNIT AND FAN

COIL UNIT SCHEDULE

KJS DCDFebruary 29, 2012

02629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE - FIRST FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-1G2 C1 640 CFM 320 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-2 02-1G2 C2 550 CFM 550 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S-3 02-1G2 C2 425 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-4 02-1G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-5 02-1G2 B2 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-6 02-1G2 B2 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S-7 02-1G2 C3 540 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-8 02-1G2 C3 645 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-9 02-1G2 E2 1100 CFM 550 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S-10 02-1G2 A2 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-11 02-1G2 C2 600 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-12 02-1G2 A3 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-13 02-1G2 C2 600 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-14 02-1G2 D3 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-15 02-1G2 B2 400 CFM 180 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-16 02-1G2 A3 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-17 02-1G2 A2 150 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-18 02-1G2 B3 200 CFM 100CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-19 02-1G2 C1 475 CFM 475 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)

S-20 02-1G2 E3 1100 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-21 02-1G2 E3 1100 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-22 02-1G2 C2 600 CFM 600 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)

S-23 02-1G2 C2 550 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-24 02-1G2 D3 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-25 02-1G2 D1 725 CFM 725 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)

S-26 02-1G2 C1 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-27 02-1G2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-28 02-1G2 D2 825 CFM 400 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-29 02-1G2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-30 02-1G2 D2 925 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-31 02-1G2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-32 02-1G2 D2 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-33 02-1G2 C3 475 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-34 02-1G2 E2 1375 CFM 1375 CFM 2.25 CV DETAIL 2/MH821 NOTE (1)

S-35 02-1G2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-36 02-1G2 E3 1200 CFM 360 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-37 02-1G2 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)

S-38 02-1G2 E2 1000 CFM 500 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)

S-39 02-1G2 B3 400 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE - FIRST FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-1G2 A2 225 CFM 225 CFM - S-2 NOTE (1)

R-2 02-1G2 A2 125 CFM 125 CFM - S-6 NOTE (1)

R-3 02-1G2 C3 540 CFM 270 CFM - S-7 NOTE (1)

R-4 02-1G2 C3 645 CFM 325 CFM - S-8 NOTE (1)

R-5 02-1G2 F3 1650 CFM 600 CFM - S-21,S-23 NOTE (1)

R-6 02-1G2 C3 575 CFM 300 CFM - S-3,S-17 NOTE (1)

R-7 02-1G2 D3 900 CFM 450 CFM - S-12,S-14 NOTE (1)

R-8 02-1G2 A3 225 CFM 125 CFM - S-16 NOTE (1)

R-9 02-1G2 C3 600 CFM 250 CFM - S-18 NOTE (1)

R-10 02-1G2 E3 1100 CFM 300 CFM - S-20 NOTE (1)

R-11 02-1G2 A2 200 CFM 200 CFM - S-22 NOTE (1)

R-12 02-1G2 C3 625 CFM 275 CFM - S-4,S-5 NOTE (1)

R-13 02-1G2 D3 675 CFM 350 CFM - S-24 NOTE (1)

R-14 02-1G2 E2 1400 CFM 600 CFM - S-11,S-13,S-15 NOTE (1)

R-15 02-1G2 C1 650 CFM 325 CFM - S-26 NOTE (1)

R-16 02-1G2 F2 1575 CFM 725 CFM - S-28,S-30 NOTE (1)

R-17 02-1G2 D3 675 CFM 350 CFM - S-31,S-33 NOTE (1)

R-18 02-1G2 B2 375 CFM 375 CFM - S-34 NOTE (1)

R-19 02-1G2 D2 675 CFM 350 CFM - S-32 NOTE (1)

R-20 02-1G2 C3 600 CFM 300 CFM - S-27 NOTE (1)

R-21 02-1G2 B3 400 CFM 200 CFM - S-29 NOTE (1)

R-22 02-1G2 B2 375 CFM 375 CFM - S-34 NOTE (1)

R-23 1G197 02-1G2 E3 1200 CFM 360 CFM - S-26 NOTE (1)

R-24 1G197 02-1G2 E2 1000 CFM 500 CFM - S-38 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIRST FLOOR G2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU-1 02-1G2 4C1 - DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-2D1 E2 1250 CFM 1250 2.25 CV DETAIL 2/MH821 NOTE (1)(4)

S-2 02-2D1 C2 500 CFM 250 1.0 CV DETAIL 2/MH821 NOTE (1)(4)

RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-2D1 E1 1250 CFM 1250 - S-1 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR D1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 02-2D1 E - NOTE (2)(3)

FCU-1 02-2D1 2F4 - DETAIL 2/MH820 NOTE (2)

RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-2D2 C2 500 CFM 500 - S-2 NOTE (1)(4)

R-2 02-2D2 B3 300 CFM 300 - S-1,S-11,S-23 NOTE (1)(4)

R-3 02-2D2 A3 200 CFM 200 - S-5,S-20 NOTE (1)(4)

R-4 02-2D2 C2 525 CFM 300 - S-26 NOTE (1)(4)

R-5 02-2D2 C3 525 CFM 525 - S-6,S-8,S-27 NOTE (1)(4)

R-6 02-2D2 D3 900 CFM 250 - S-15 NOTE (1)(4)

R-7 02-2D2 A3 100 CFM 50 - S-10 NOTE (1)(4)

R-8 02-2D2 B3 375 CFM 175 - S-12,S-16 NOTE (1)(4)

R-9 02-2D2 E3 1075 CFM 500 - S-2.S-25 NOTE (1)(4)

R-10 02-2D2 A3 200 CFM 200 - S-4,S-19 NOTE (1)(4)

R-11 02-2D2 B3 300 CFM 200 - S-21,S-22 NOTE (1)(4)

R-12 02-2D2 A3 250 CFM 125 - S-24 NOTE (1)(4)

R-13 02-2D2 E2 1050 CFM 425 - S-13,S-14,S-17 NOTE (1)(4)

R-14 02-2D2 C3 525 CFM 300 - S-29,S-35,S-36 NOTE (1)(4)

R-15 02-2D2 A2 200 CFM 100 - S-30 NOTE (1)(4)

R-16 02-2D2 A3 200 CFM 100 - S-47 NOTE (1)(4)

R-17 02-2D2 B3 300 CFM 150 - S-49 NOTE (1)(4)

R-18 02-2D2 A3 230 CFM 100 - S-31 NOTE (1)(4)

R-19 02-2D2 B3 350 CFM 350 - S-32,S-52 NOTE (1)(4)

R-20 02-2D2 C2 450 CFM 200 - S-33 NOTE (1)(4)

R-21 02-2D2 B3 375 CFM 200 - S-39,S-40 NOTE (1)(4)

R-22 02-2D2 C3 475 CFM 250 - S-34,S-38 NOTE (1)(4)

R-23 02-2D2 A2 250 CFM 250 - S-44 NOTE (1)(4)

R-24 02-2D2 B3 400 CFM 150 - S-46 NOTE (1)(4)

R-25 02-2D2 B3 375 CFM 275 - S-41,S-42 NOTE (1)(4)

R-26 02-2D2 A3 100 CFM 50 - S-43 NOTE (1)(4)

SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR D2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-2 02-2D2 C2 450 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-3 02-2D2 D1 750 CFM 750 1.25 CV DETAIL 2/MH821 NOTE (1)(4)

S-4 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-5 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-6 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-7 02-2D2 A1 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-8 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-9 02-2D2 B2 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-10 02-2D2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-11 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-12 02-2D2 A3 150 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-13 02-2D2 C2 450 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-14 02-2D2 C2 550 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-15 02-2D2 E3 1300 CFM 650 1.0 VCV DETAIL 4/MH821 NOTE (1)(4)

S-16 02-2D2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-17 02-2D2 B2 350 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-18 02-2D2 A2 100 CFM 100 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-19 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-20 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-21 02-2D2 A3 150 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-22 02-2D2 A3 150 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-23 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-24 02-2D2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-25 02-2D2 C2 700 CFM 400 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-26 02-2D2 D2 825 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-27 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-28 02-2D2 C2 600 CFM 300 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-29 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-30 02-2D2 A2 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-31 02-2D2 A3 230 CFM 115 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-32 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-33 02-2D2 D2 850 CFM 650 1.0 VCV DETAIL 4/MH821 NOTE (1)(4)

S-34 02-2D2 B3 350 CFM 175 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-35 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-36 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-37 02-2D2 C2 450 CFM 450 0.75 CV DETAIL 2/MH821 NOTE (1)(4)

S-38 02-2D2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-39 02-2D2 A2 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-40 02-2D2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-41 02-2D2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-42 02-2D2 B3 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-43 02-2D2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-44 02-2D2 B2 350 CFM 350 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-45 02-2D2 E2 1275 CFM 1275 2.25 CV DETAIL 2/MH821 NOTE (1)(4)

S-46 02-2D2 C3 500 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-47 02-2D2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-48 02-2D2 G2 2200 CFM 2200 3.75 CV DETAIL 2/MH821 NOTE (1)(4)

S-49 02-2D2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-50 02-2D2 B2 325 CFM 325 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-51 02-2D2 A2 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-52 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-2E1 E1 1250 CFM 1250 - CV DETAIL 2/MH821 NOTE (1)

S-2 02-2E1 D2 700 CFM 700 1.25 CV DETAIL 2/MH821 NOTE (1)

S-3 02-2E1 A2 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-4 02-2E1 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-2E1 D1 925 CFM 925 - S-1 NOTE (1)

R-2 02-2E1 C3 425 CFM 275 - S-3,S-4 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR E1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 02-2E1 F - - NOTE (2)(3)

FCU-1 02-2E1 2F4 - DETAIL 1/MH820 NOTE (2)

RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR E2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-2E2 A2 100 CFM 100 - S-5 NOTE (1)

R-2 02-2E2 E3 1400 CFM 700 - S-3,S-10 NOTE (1)

R-3 02-2E2 B2 400 CFM 400 - S-8 NOTE (1)

R-4 02-2E2 F3 1425 CFM 600 - S-9,S-11 NOTE (1)

R-5 02-2E2 E2 1200 CFM 600 - S-12 NOTE (1)

R-6 02-2E2 E3 1200 CFM 600 - S-2,S-4 NOTE (1)

R-7 02-2E2 F3 1425 CFM 600 - S-6,S-7 NOTE (1)

R-9 02-2E2 B2 400 CFM 400 - S-13 NOTE (1)

R-10 02-2E2 C3 640 CFM 325 - S-20,S-22,S-24,S-25 NOTE (1)(4)

R-11 02-2E2 D3 900 CFM 450 - S-27 NOTE (1)(4)

R-12 02-2E2 A3 150 CFM 75 - S-31 NOTE (1)(4)

R-13 02-2E2 A3 125 CFM 75 - S-23,S-33 NOTE (1)(4)

R-14 02-2E2 D3 700 CFM 350 - S-14,S-15,S-16 NOTE (1)(4)

R-15 02-2E2 D3 700 CFM 300 - S-21,S-25 NOTE (1)(4)

R-16 02-2E2 B3 300 CFM 150 - S-30 NOTE (1)(4)

R-17 02-2E2 B2 300 CFM 300 - S-34 NOTE (1)(4)

R-18 02-2E2 B3 700 CFM 300 - S-21,S-35 NOTE (1)(4)

R-19 02-2E2 B3 700 CFM 350 - S-17,S-18,S-37 NOTE (1)(4)

SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR E2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 02-2E2 A1 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)

S-2 02-2E2 A3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-3 02-2E2 D3 700 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-4 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-5 02-2E2 D2 825 CFM 825 1.5 CV DETAIL 2/MH821 NOTE (1)

S-6 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-7 02-2E2 C3 525 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-8 02-2E2 E2 1050 CFM 1050 2.0 CV DETAIL 2/MH821 NOTE (1)

S-9 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-10 02-2E2 D3 700 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-11 02-2E2 B3 525 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-12 02-2E2 E2 1200 CFM 600 1.0 VCV DETAIL 4/MH821 NOTE (1)

S-13 02-2E2 B2 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)

S-14 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-15 02-2E2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-16 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-17 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-18 02-2E2 B3 275 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-19 02-2E2 B3 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-20 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-21 02-2E2 D3 800 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-22 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-23 02-2E2 A3 225 CFM 225 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-24 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-25 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-26 02-2E2 D2 725 CFM 725 1.25 CV DETAIL 2/MH821 NOTE (1)(4)

S-27 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-28 02-2E2 B3 325 CFM 325 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-29 02-2E2 A3 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-30 02-2E2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-31 02-2E2 A3 150 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-32 02-2E2 A1 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)

S-33 02-2E2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

S-34 02-2E2 E2 950 CFM 950 1.75 CV DETAIL 2/MH821 NOTE (1)(4)

S-35 02-2E2 D2 800 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)

S-36 02-2E2 A1 200 CFM 200 0.75 CV DETAIL 2/MH821 NOTE (1)(4)

S-37 02-2E2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)

SUPPLY TERMINAL UNIT SCHEDULE - FIRST FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S-1 1G227 02-1G1 D1 925 CFM 925 CFM NO COIL CV DETAIL 2/MH821 NOTE (1)

S-2 02-1G1 D1 800 CFM 800 CFM 1.5 VCV DETAIL 4/MH821 NOTE (1)

S-3 02-1G1 C2 480 CFM 240 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)

S-4 02-1G1 D3 700 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)

S-5 02-1G1 A2 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

S-6 02-1G1 C2 525 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)

RETURN TERMINAL UNIT SCHEDULE - FIRST FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

R-1 02-1G1 C1 640 CFM 320 CFM - S-1 NOTE (1)

R-2 02-1G1 D1 925 CFM 925 CFM - S-1 NOTE (1)

R-3 02-1G1 C2 480 CFM 240 CFM - S-3 NOTE (1)

R-4 02-1G1 D2 700 CFM 350 CFM - S-4 NOTE (1)

R-5 02-1G1 E2 1100 CFM 550 CFM - S-9 NOTE (1)

R-6 02-1G1 C2 525 CFM 275 CFM - S-6 NOTE (1)

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIRST FLOOR G1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 3E-C359 02-1G1 F - - NOTE (2)(3)

FCU-1 1G227 02-1G1 2F4 - DETAIL 1/MH820 NOTE (2)

GENERAL NOTES:

1. REFER TO DRAWINGS MH603 AND MH604

FOR SCHEDULE CAPACITES

2. REFER TO DRAWINGS MH607 AND MH608

FOR SCHEDULE CAPACITIES

3. REQUIRES EMERGENCY POWER

4. INTERLOCK SUPPLY TERMINAL AND

ASSOCIATED RETURN TERMINAL WITH

EMERGENCY DEPARTMENT PURGE MODE

SEQUENCE PER DRAWING MH812A

FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR E2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC-1 2E-C04 02-2E2 E - - NOTE (2)

CAC-2 02-2E2 H - - NOTE (2)

RFI:01800 - S-18 to be size C3 to provide 600 CFM as indicated on dwg

2MH101-G2.

RFI:02099 - VAV Does Not Require a Reheat Coil - Detail 5 on 0MH821 Should be Followed.

RFI:02619 - 02-2E2 R-1

should be 300 CFM.