VAV DNT 02302-2MH627.pdf
PDF 268 KB Posted
- Attached to
- Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
- Solicitation number
- Not on record
About this file
This document package includes a technical drawing set and specifications for rebalancing the HVAC system in a federal medical facility, as well as details of a related federal contract opportunity.
The technical drawings depict the layout of the existing HVAC system and provide schedules with equipment details, sizes, control types and sequences. General notes reference related drawings for capacity information and control interlocks for emergency operation. The opportunity notice is a modification to rebalance the HVAC system depicted in the technical drawings, as issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16. The purpose is to attach ninety-one additional documents to the solicitation. No further information is provided on product or service requirements, pricing terms, response dates or other solicitation details.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H A L
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
E E T
(1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
X T
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2MH627
BLDG 02 HVAC AIR TERMINAL UNIT AND FAN
COIL UNIT SCHEDULE
KJS DCDFebruary 29, 2012
02629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING/ PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
SUPPLY TERMINAL UNIT SCHEDULE - FIRST FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-1G2 C1 640 CFM 320 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-2 02-1G2 C2 550 CFM 550 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-3 02-1G2 C2 425 CFM 225 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-4 02-1G2 B3 300 CFM 150 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-5 02-1G2 B2 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-6 02-1G2 B2 400 CFM 400 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-7 02-1G2 C3 540 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-8 02-1G2 C3 645 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-9 02-1G2 E2 1100 CFM 550 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)
S-10 02-1G2 A2 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-11 02-1G2 C2 600 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-12 02-1G2 A3 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-13 02-1G2 C2 600 CFM 270 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-14 02-1G2 D3 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-15 02-1G2 B2 400 CFM 180 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-16 02-1G2 A3 225 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-17 02-1G2 A2 150 CFM 75 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-18 02-1G2 B3 200 CFM 100CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-19 02-1G2 C1 475 CFM 475 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-20 02-1G2 E3 1100 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-21 02-1G2 E3 1100 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-22 02-1G2 C2 600 CFM 600 CFM 1.0 CV DETAIL 2/MH821 NOTE (1)
S-23 02-1G2 C2 550 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-24 02-1G2 D3 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-25 02-1G2 D1 725 CFM 725 CFM 1.25 CV DETAIL 2/MH821 NOTE (1)
S-26 02-1G2 C1 650 CFM 325 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-27 02-1G2 C3 600 CFM 300 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-28 02-1G2 D2 825 CFM 400 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-29 02-1G2 B3 400 CFM 200 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-30 02-1G2 D2 925 CFM 450 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-31 02-1G2 A3 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-32 02-1G2 D2 675 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-33 02-1G2 C3 475 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-34 02-1G2 E2 1375 CFM 1375 CFM 2.25 CV DETAIL 2/MH821 NOTE (1)
S-35 02-1G2 A3 250 CFM 125 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-36 02-1G2 E3 1200 CFM 360 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-37 02-1G2 B2 375 CFM 375 CFM 0.75 CV DETAIL 2/MH821 NOTE (1)
S-38 02-1G2 E2 1000 CFM 500 CFM 1.0 VCV DETAIL 4/MH821 NOTE (1)
S-39 02-1G2 B3 400 CFM 250 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - FIRST FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-1G2 A2 225 CFM 225 CFM - S-2 NOTE (1)
R-2 02-1G2 A2 125 CFM 125 CFM - S-6 NOTE (1)
R-3 02-1G2 C3 540 CFM 270 CFM - S-7 NOTE (1)
R-4 02-1G2 C3 645 CFM 325 CFM - S-8 NOTE (1)
R-5 02-1G2 F3 1650 CFM 600 CFM - S-21,S-23 NOTE (1)
R-6 02-1G2 C3 575 CFM 300 CFM - S-3,S-17 NOTE (1)
R-7 02-1G2 D3 900 CFM 450 CFM - S-12,S-14 NOTE (1)
R-8 02-1G2 A3 225 CFM 125 CFM - S-16 NOTE (1)
R-9 02-1G2 C3 600 CFM 250 CFM - S-18 NOTE (1)
R-10 02-1G2 E3 1100 CFM 300 CFM - S-20 NOTE (1)
R-11 02-1G2 A2 200 CFM 200 CFM - S-22 NOTE (1)
R-12 02-1G2 C3 625 CFM 275 CFM - S-4,S-5 NOTE (1)
R-13 02-1G2 D3 675 CFM 350 CFM - S-24 NOTE (1)
R-14 02-1G2 E2 1400 CFM 600 CFM - S-11,S-13,S-15 NOTE (1)
R-15 02-1G2 C1 650 CFM 325 CFM - S-26 NOTE (1)
R-16 02-1G2 F2 1575 CFM 725 CFM - S-28,S-30 NOTE (1)
R-17 02-1G2 D3 675 CFM 350 CFM - S-31,S-33 NOTE (1)
R-18 02-1G2 B2 375 CFM 375 CFM - S-34 NOTE (1)
R-19 02-1G2 D2 675 CFM 350 CFM - S-32 NOTE (1)
R-20 02-1G2 C3 600 CFM 300 CFM - S-27 NOTE (1)
R-21 02-1G2 B3 400 CFM 200 CFM - S-29 NOTE (1)
R-22 02-1G2 B2 375 CFM 375 CFM - S-34 NOTE (1)
R-23 1G197 02-1G2 E3 1200 CFM 360 CFM - S-26 NOTE (1)
R-24 1G197 02-1G2 E2 1000 CFM 500 CFM - S-38 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIRST FLOOR G2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU-1 02-1G2 4C1 - DETAIL 2/MH820 NOTE (2)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2D1 E2 1250 CFM 1250 2.25 CV DETAIL 2/MH821 NOTE (1)(4)
S-2 02-2D1 C2 500 CFM 250 1.0 CV DETAIL 2/MH821 NOTE (1)(4)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2D1 E1 1250 CFM 1250 - S-1 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR D1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 02-2D1 E - NOTE (2)(3)
FCU-1 02-2D1 2F4 - DETAIL 2/MH820 NOTE (2)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2D2 C2 500 CFM 500 - S-2 NOTE (1)(4)
R-2 02-2D2 B3 300 CFM 300 - S-1,S-11,S-23 NOTE (1)(4)
R-3 02-2D2 A3 200 CFM 200 - S-5,S-20 NOTE (1)(4)
R-4 02-2D2 C2 525 CFM 300 - S-26 NOTE (1)(4)
R-5 02-2D2 C3 525 CFM 525 - S-6,S-8,S-27 NOTE (1)(4)
R-6 02-2D2 D3 900 CFM 250 - S-15 NOTE (1)(4)
R-7 02-2D2 A3 100 CFM 50 - S-10 NOTE (1)(4)
R-8 02-2D2 B3 375 CFM 175 - S-12,S-16 NOTE (1)(4)
R-9 02-2D2 E3 1075 CFM 500 - S-2.S-25 NOTE (1)(4)
R-10 02-2D2 A3 200 CFM 200 - S-4,S-19 NOTE (1)(4)
R-11 02-2D2 B3 300 CFM 200 - S-21,S-22 NOTE (1)(4)
R-12 02-2D2 A3 250 CFM 125 - S-24 NOTE (1)(4)
R-13 02-2D2 E2 1050 CFM 425 - S-13,S-14,S-17 NOTE (1)(4)
R-14 02-2D2 C3 525 CFM 300 - S-29,S-35,S-36 NOTE (1)(4)
R-15 02-2D2 A2 200 CFM 100 - S-30 NOTE (1)(4)
R-16 02-2D2 A3 200 CFM 100 - S-47 NOTE (1)(4)
R-17 02-2D2 B3 300 CFM 150 - S-49 NOTE (1)(4)
R-18 02-2D2 A3 230 CFM 100 - S-31 NOTE (1)(4)
R-19 02-2D2 B3 350 CFM 350 - S-32,S-52 NOTE (1)(4)
R-20 02-2D2 C2 450 CFM 200 - S-33 NOTE (1)(4)
R-21 02-2D2 B3 375 CFM 200 - S-39,S-40 NOTE (1)(4)
R-22 02-2D2 C3 475 CFM 250 - S-34,S-38 NOTE (1)(4)
R-23 02-2D2 A2 250 CFM 250 - S-44 NOTE (1)(4)
R-24 02-2D2 B3 400 CFM 150 - S-46 NOTE (1)(4)
R-25 02-2D2 B3 375 CFM 275 - S-41,S-42 NOTE (1)(4)
R-26 02-2D2 A3 100 CFM 50 - S-43 NOTE (1)(4)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR D2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-2 02-2D2 C2 450 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-3 02-2D2 D1 750 CFM 750 1.25 CV DETAIL 2/MH821 NOTE (1)(4)
S-4 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-5 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-6 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-7 02-2D2 A1 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-8 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-9 02-2D2 B2 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-10 02-2D2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-11 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-12 02-2D2 A3 150 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-13 02-2D2 C2 450 CFM 225 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-14 02-2D2 C2 550 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-15 02-2D2 E3 1300 CFM 650 1.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-16 02-2D2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-17 02-2D2 B2 350 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)
S-18 02-2D2 A2 100 CFM 100 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-19 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-20 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-21 02-2D2 A3 150 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-22 02-2D2 A3 150 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-23 02-2D2 A3 175 CFM 175 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-24 02-2D2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-25 02-2D2 C2 700 CFM 400 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-26 02-2D2 D2 825 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)
S-27 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-28 02-2D2 C2 600 CFM 300 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-29 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-30 02-2D2 A2 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-31 02-2D2 A3 230 CFM 115 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-32 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-33 02-2D2 D2 850 CFM 650 1.0 VCV DETAIL 4/MH821 NOTE (1)(4)
S-34 02-2D2 B3 350 CFM 175 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-35 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-36 02-2D2 A3 175 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-37 02-2D2 C2 450 CFM 450 0.75 CV DETAIL 2/MH821 NOTE (1)(4)
S-38 02-2D2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-39 02-2D2 A2 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-40 02-2D2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-41 02-2D2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-42 02-2D2 B3 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-43 02-2D2 A3 100 CFM 50 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-44 02-2D2 B2 350 CFM 350 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-45 02-2D2 E2 1275 CFM 1275 2.25 CV DETAIL 2/MH821 NOTE (1)(4)
S-46 02-2D2 C3 500 CFM 250 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-47 02-2D2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-48 02-2D2 G2 2200 CFM 2200 3.75 CV DETAIL 2/MH821 NOTE (1)(4)
S-49 02-2D2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-50 02-2D2 B2 325 CFM 325 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-51 02-2D2 A2 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-52 02-2D2 A3 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2E1 E1 1250 CFM 1250 - CV DETAIL 2/MH821 NOTE (1)
S-2 02-2E1 D2 700 CFM 700 1.25 CV DETAIL 2/MH821 NOTE (1)
S-3 02-2E1 A2 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-4 02-2E1 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2E1 D1 925 CFM 925 - S-1 NOTE (1)
R-2 02-2E1 C3 425 CFM 275 - S-3,S-4 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR E1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 02-2E1 F - - NOTE (2)(3)
FCU-1 02-2E1 2F4 - DETAIL 1/MH820 NOTE (2)
RETURN TERMINAL UNIT SCHEDULE - SECOND FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-2E2 A2 100 CFM 100 - S-5 NOTE (1)
R-2 02-2E2 E3 1400 CFM 700 - S-3,S-10 NOTE (1)
R-3 02-2E2 B2 400 CFM 400 - S-8 NOTE (1)
R-4 02-2E2 F3 1425 CFM 600 - S-9,S-11 NOTE (1)
R-5 02-2E2 E2 1200 CFM 600 - S-12 NOTE (1)
R-6 02-2E2 E3 1200 CFM 600 - S-2,S-4 NOTE (1)
R-7 02-2E2 F3 1425 CFM 600 - S-6,S-7 NOTE (1)
R-9 02-2E2 B2 400 CFM 400 - S-13 NOTE (1)
R-10 02-2E2 C3 640 CFM 325 - S-20,S-22,S-24,S-25 NOTE (1)(4)
R-11 02-2E2 D3 900 CFM 450 - S-27 NOTE (1)(4)
R-12 02-2E2 A3 150 CFM 75 - S-31 NOTE (1)(4)
R-13 02-2E2 A3 125 CFM 75 - S-23,S-33 NOTE (1)(4)
R-14 02-2E2 D3 700 CFM 350 - S-14,S-15,S-16 NOTE (1)(4)
R-15 02-2E2 D3 700 CFM 300 - S-21,S-25 NOTE (1)(4)
R-16 02-2E2 B3 300 CFM 150 - S-30 NOTE (1)(4)
R-17 02-2E2 B2 300 CFM 300 - S-34 NOTE (1)(4)
R-18 02-2E2 B3 700 CFM 300 - S-21,S-35 NOTE (1)(4)
R-19 02-2E2 B3 700 CFM 350 - S-17,S-18,S-37 NOTE (1)(4)
SUPPLY TERMINAL UNIT SCHEDULE - SECOND FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 02-2E2 A1 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)
S-2 02-2E2 A3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-3 02-2E2 D3 700 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-4 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-5 02-2E2 D2 825 CFM 825 1.5 CV DETAIL 2/MH821 NOTE (1)
S-6 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-7 02-2E2 C3 525 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-8 02-2E2 E2 1050 CFM 1050 2.0 CV DETAIL 2/MH821 NOTE (1)
S-9 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-10 02-2E2 D3 700 CFM 350 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-11 02-2E2 B3 525 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-12 02-2E2 E2 1200 CFM 600 1.0 VCV DETAIL 4/MH821 NOTE (1)
S-13 02-2E2 B2 500 CFM 500 1.0 CV DETAIL 2/MH821 NOTE (1)
S-14 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-15 02-2E2 A3 250 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-16 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-17 02-2E2 A3 225 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-18 02-2E2 B3 275 CFM 125 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-19 02-2E2 B3 300 CFM 300 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-20 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-21 02-2E2 D3 800 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)
S-22 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-23 02-2E2 A3 225 CFM 225 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-24 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-25 02-2E2 A3 160 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-26 02-2E2 D2 725 CFM 725 1.25 CV DETAIL 2/MH821 NOTE (1)(4)
S-27 02-2E2 D3 900 CFM 450 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)
S-28 02-2E2 B3 325 CFM 325 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-29 02-2E2 A3 200 CFM 200 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-30 02-2E2 B3 300 CFM 150 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-31 02-2E2 A3 150 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-32 02-2E2 A1 250 CFM 250 0.5 CV DETAIL 2/MH821 NOTE (1)(4)
S-33 02-2E2 A3 125 CFM 75 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
S-34 02-2E2 E2 950 CFM 950 1.75 CV DETAIL 2/MH821 NOTE (1)(4)
S-35 02-2E2 D2 800 CFM 400 0.75 VCV DETAIL 4/MH821 NOTE (1)(4)
S-36 02-2E2 A1 200 CFM 200 0.75 CV DETAIL 2/MH821 NOTE (1)(4)
S-37 02-2E2 A3 200 CFM 100 0.5 VCV DETAIL 4/MH821 NOTE (1)(4)
SUPPLY TERMINAL UNIT SCHEDULE - FIRST FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 1G227 02-1G1 D1 925 CFM 925 CFM NO COIL CV DETAIL 2/MH821 NOTE (1)
S-2 02-1G1 D1 800 CFM 800 CFM 1.5 VCV DETAIL 4/MH821 NOTE (1)
S-3 02-1G1 C2 480 CFM 240 CFM 0.5 CV DETAIL 2/MH821 NOTE (1)
S-4 02-1G1 D3 700 CFM 350 CFM 0.75 VCV DETAIL 4/MH821 NOTE (1)
S-5 02-1G1 A2 200 CFM 100 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
S-6 02-1G1 C2 525 CFM 275 CFM 0.5 VCV DETAIL 4/MH821 NOTE (1)
RETURN TERMINAL UNIT SCHEDULE - FIRST FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
R-1 02-1G1 C1 640 CFM 320 CFM - S-1 NOTE (1)
R-2 02-1G1 D1 925 CFM 925 CFM - S-1 NOTE (1)
R-3 02-1G1 C2 480 CFM 240 CFM - S-3 NOTE (1)
R-4 02-1G1 D2 700 CFM 350 CFM - S-4 NOTE (1)
R-5 02-1G1 E2 1100 CFM 550 CFM - S-9 NOTE (1)
R-6 02-1G1 C2 525 CFM 275 CFM - S-6 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - FIRST FLOOR G1
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 3E-C359 02-1G1 F - - NOTE (2)(3)
FCU-1 1G227 02-1G1 2F4 - DETAIL 1/MH820 NOTE (2)
GENERAL NOTES:
1. REFER TO DRAWINGS MH603 AND MH604
FOR SCHEDULE CAPACITES
2. REFER TO DRAWINGS MH607 AND MH608
FOR SCHEDULE CAPACITIES
3. REQUIRES EMERGENCY POWER
4. INTERLOCK SUPPLY TERMINAL AND
ASSOCIATED RETURN TERMINAL WITH
EMERGENCY DEPARTMENT PURGE MODE
SEQUENCE PER DRAWING MH812A
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE - SECOND FLOOR E2
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 2E-C04 02-2E2 E - - NOTE (2)
CAC-2 02-2E2 H - - NOTE (2)
RFI:01800 - S-18 to be size C3 to provide 600 CFM as indicated on dwg
2MH101-G2.
RFI:02099 - VAV Does Not Require a Reheat Coil - Detail 5 on 0MH821 Should be Followed.
RFI:02619 - 02-2E2 R-1
should be 300 CFM.