P12-230923 DDC Control System for HVAC 4-7-20.pdf

PDF 195 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains specifications for direct digital control system modifications and rebalancing of the HVAC system at a Department of Veterans Affairs medical campus. The scope of work involves modifying the existing Johnson Controls DDC software programming to accomplish updated control sequences for AHU supply and return fans, return air fans, and DOAS units. It also requires rebalancing VAV terminal units and setting new static pressure setpoints. The Temperature Controls Contractor will work with the Commissioning Agent and TAB Contractor to coordinate activities and complete the work during scheduled weekend shutdowns.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
PANAM 101.pdf PDF
DNT L06 D.pdf PDF
P12-230593 Testing Adjusting and Balancing for HVAC 4-7-20.pdf PDF
DNT L01i F-G.pdf PDF
VAV Research 353-8MH614.pdf PDF
AMS DNT 02288-2MH613.pdf PDF
014219 Reference Standards.pdf PDF
RESEARCH 3rd mech plan.pdf PDF
AMS DNT 02289-2MH614.pdf PDF
PANAM 102.pdf PDF
INP L04.pdf PDF
S05- AMENDMENT- 0001.pdf PDF
S02-EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT v2.pdf PDF
CEP L02.pdf PDF
DNT L02i D-E.pdf PDF
AMS IP 01414-1MH604.pdf PDF
P12-VAV PANAM 0252-9MH610.pdf PDF
INP L05.pdf PDF
VAV CON -00MH602.pdf PDF
CEP L01.pdf PDF
382-8EL105-P.pdf PDF
VAV Research 351-8MH612.pdf PDF
AMS Research 340-8MH601.pdf PDF
RESEARCH 3 5 mech plan.pdf PDF
OUT L08.pdf PDF
S02-EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.pdf PDF
PANAM 104.pdf PDF
03503-6EP103-M3.pdf PDF
OUT L06.pdf PDF
OUT L04.pdf PDF
OUT L03.pdf PDF
S02-EXHIBIT E SURETY FORM.pdf PDF
P15-M-2 DNT Building Existing AHU sequence.pdf PDF
AMS Research 348-8MH609.pdf PDF
P14-M-4 OP Building Existing AHU sequence.pdf PDF
P15-M-5 OP Building Existing DOAS sequence.pdf PDF
OUT L02.pdf PDF
VAV Research 352-8MH613.pdf PDF
RESEARCH 5 dixie penthouse.pdf PDF
INP L03.pdf PDF
DNT L02i F-G.pdf PDF
PANAM 103.pdf PDF
230593 Testing Adjusting and Balancing for HVAC.pdf PDF
VAV DNT 02301-2MH626.pdf PDF
M-3 DNT Building Existing DOAS sequence.pdf PDF
OUT L07.pdf PDF
P13-INP L04.pdf PDF
DNT L01i D-E.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
RESEARCH 2nd mech plan.pdf PDF
Show all 50

Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09-11

23 09 23 - 1

SECTION 23 09 23

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

PART 1 - GENERAL

1.1 DESCRIPTION

A. The VA Campus has an existing Johnson Controls DDC System for automation of existing HVAC systems. The front end is located at

Level 3.5 of the CEP building. The scope of work for this project is to provide as required modifications to the existing Johnson

Controls software programming to accomplish the control sequences noted in this specification. In addition, provide setpoint modifications as required when directed in field as part of the ongoing TAB work to accomplish optimum operating conditions.

B. The Temperature Controls Contractor shall arrange to visit the VA site to become familiar with the content of the existing Johnson

Controls software programming, existing points and existing control sequences. Existing sequences that are currently working and acceptable shall be reused or modified to the new requirements where possible. Other control sequences not mentioned in this specification are to remain as existing. Any new or modified control sequence programming may be done or troubleshooted offsite before uploading to the VA front end (CCT) during actual day of TAB work.

C. The actual TAB, Commissioning and DDC controls work of Air Handling

Systems shall be planned to occur on a weekend after hours when a equipment shutdown is scheduled.

D. Refer to Johnson Controls flow diagrams and sequence of operation for typical existing DNT and OP Building Air Handling Units and DOAS

Units controls.

E. The Temperature Controls Contractor shall be work together with the

Commissioning Agent and TAB contractor to coordinate all activities to complete the project.

F. The Temperature Controls Contractor shall be a subcontractor of the

General Contractor and shall report to and be paid by the General

Contractor.

23 09 23 - 2

PART 2 - PRODUCTS

2.1 NONE

PART 3 - EXECUTION

3.1 SEQUENCE OF OPERATION

A. Provide this sequence for all VAV Air Handling Unit supply air fan (20) and return air fan (5) systems that have connected space supply and return air terminal VAV boxes. Return VAV terminals are utilized in DNT Building only.

DUCT STATIC PRESSURE RESET OPTIMIZATION

The building automation system (BAS) shall continuously monitor the damper position of all VAV terminal units. The existing duct static pressure shall be sensed directly at the ductwork near the fans.

When any VAV damper is more than 95% (adj.) open, the fans duct static pressure setpoint shall be reset upward by 0.1 in W.C. (adj.), at a frequency of 1 minute (adj.), until no damper is more than 95% open or the static pressure setpoint has reset upward to the system maximum duct static pressure setpoint or the variable-frequency drive is at the maximum speed setting.

When all VAV dampers are less than 85% (adj.) open, the fans duct static pressure setpoint shall be reset downward by 0.1 in W.C.(adj.), at a frequency of 1 minute (adj.), until at least one damper is more than 85% open or the static pressure setpoint has reset downward to the system minimum duct static pressure setpoint or the variable-frequency drive is at the minimum speed setting.

B. Provide this sequence for all VAV Air Handling Unit return air fan systems that do not have space terminal VAV boxes and are ducted directly from ceiling grilles to duct mains. This occurs in IP, OP, TLR, PanAm and CEP Buildings, 26 total AHU’s.

Existing Air Handling Units (12) not modified with this sequence shall remain as currently controlled, maintaining fixed static pressure set point.

RETURN AIR FAN CONTROL

The return air fan shall track the supply air fan and outside air intake to always maintain the required total offset differential (RA = SA-OA). The return air fan shall modulate speeds to maintain an offset based on either reading the supply duct, return duct and outside air duct air measuring stations or reading the supply, return and outside air fan VFD Hertz. The differential offset of either CFM or Hertz shall be for the entire operating range of the Air Handling Units.

C. Provide this sequence for (9) DOAS or Air Handling Units in buildings outside of DNT that have existing CO2 sensors in the return air ductwork.

The DNT building shall maintain the existing DOAS sequence of operation. This is to keep the outside air supply fixed at design

23 09 23 - 3 values, non-modulating, due to maintaining continuous building pressure requirements.

CO2 OUTSIDE AIR DEMAND CONTROL VENTILATION

The DOAS outside air fan or damper shall modulate based on maintaining a CO2 setpoint (adj.) of 700 ppm as sensed in the main return air ductwork. When the CO2 rises above setpoint, outside air shall increase upward by 5%, by either fan speed or damper position, as required and not exceed the VA specified maximum (adj.) air volume (cfm). When the CO2 drops below setpoint, outside air shall decrease downward by 5%, by either fan speed or damper position, as required and not exceed the VA specified minimum (adj.) air volume (cfm).

----- END -----

File details come from the government source that posted it. Updated .